Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Product Usage
Eaton Power Xpert Solar 1500/1670 kW Inverter is intended for conversion of
photovoltaic-module energy into alternating-current for grid-tie applications. Usage
other than as intended is prohibited, voiding the warranty and certification.
Support Services
The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our
products. We are dedicated to providing fast, friendly, and accurate assistance. That is why
we offer you so many ways to get the support you need. Whether it’s by phone, fax, or email,
you can access Eaton’s support information 24 hours a day, seven days a week. Our wide
range of services is listed below.
Please contact your local distributor or sales representative for product specification,
availability pricing, and ordering. Product-application assistance is available through these
channels.
Website
Use the Eaton website to find product information, directly. You can also find information on
local distributors or Eaton’s sales offices.
Product Website
www.eaton.com/powerxpertsolar
● Photovoltaic Inverters
www.eaton.com/solar
● Photovoltaic Balance of System Products
Table of Contents
DEFINITIONS, SAFETY, AND LIMITATIONS
Read these Instructions FIRST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Save These Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Definitions and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION INSTRUCTIONS
Delivery Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unloading and Moving Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Anchoring Requirements—Concrete Pad and Seismic . . . . . . . . . . . . . . . . . . . 16
DC Input Fuse Options—Re-Combiner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ELECTRICAL CONNECTIONS
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
DC Circuit Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Inverter AC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Neutral and Equipment Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Phase Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Grounding Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Grounding Electrode Terminal and Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Positive-Ground Photovoltaic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
INVERTER OPERATION
Pre-Commission Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Energize and Operation Procedure: Automatic Operation . . . . . . . . . . . . . . . . . 30
De-Energize Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Interactive Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Operational States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
MAINTENANCE
Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
TROUBLESHOOTING
Identifying Inverter Faults and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Inverter Response to Faults and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Troubleshooting Ground-Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
APPENDIX A
Power Xpert Solar Electrical, Mechanical and Equipment Specifications . . . . . 65
APPENDIX B
Flex Bus Kit: Throat Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
APPENDIX C
Step-Up Transformer Sensor Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
APPENDIX D
Torque Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
APPENDIX E
Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
APPENDIX F
Enclosure Lifting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
APPENDIX G
Customer External Load-Power Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . 76
APPENDIX H
Maintenance Schedule Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
APPENDIX J
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
List of Figures
Figure 1. Symbols and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 2. DANGER—WARNING—CAUTION—NOTICE . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 3. Power Xpert Solar Inverter Rating Label (Typical) . . . . . . . . . . . . . . . . . . . . . . 5
Figure 4. Power Xpert Solar 1500/1670 kW Inverter Diagram . . . . . . . . . . . . . . . . . . . . 6
Figure 5. Major Components Diagram: Inverter and Step-Up Transformer . . . . . . . . . . 8
Figure 6. Power Xpert Solar Inverter with Step-Up Transformer . . . . . . . . . . . . . . . . . . 8
Figure 7. Power Xpert Solar: Inverter Power Module and Power Stacks . . . . . . . . . . . . 11
Figure 8. Schematic of the Ventilation-Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 9. Mounting of Lifting Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 10. Mounting of Cover Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 11. Inverter Transport by Lift Truck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 12. Inverter Transport by Crane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 13. Inverter Cabinet Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 14. Anchoring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 15. Inverter Conductor Entry-Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 16. Inverter and Transformer Conductor Entry Locations . . . . . . . . . . . . . . . . . . 18
Figure 17. Electrical Connections, Power Xpert Solar 1500/1670 kW Inverter . . . . . . . . 20
Figure 18. PV Conductor Terminations (Typical)—Positive and Negative Connections . 21
Figure 19. Typical Mounting with MV Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 20. Phase Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21. AC Output Phase Connections: Throat Connection Details . . . . . . . . . . . . . 24
Figure 22. DC Section: 24 Input-Circuit options, Illustrated PV Input Connections . . . . 26
Figure 23. DC Section Grounding Bus and Grounding Electrode Terminal . . . . . . . . . . 26
Figure 24. AC Section Equipment Grounding Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 25. Accessory Power Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 26. Inverter AC Cabinet Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 27. HMI Menu Display Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 28. Power Xpert Solar Machine-State Transition Diagram . . . . . . . . . . . . . . . . . 46
Figure 29. The GFDI Connection Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 30. Flex Bus Kit: 84-37413-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 31. Example of Available Step-Up Transformer Monitoring . . . . . . . . . . . . . . . . . 70
Figure 32. Enclosure Lifting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Figure 33. Location of CB4 in the Electrical Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
List of Tables
Table 1. Word Meanings: “shall,” “may,” “must,” and “should” . . . . . . . . . . . . . . . . . . 1
Table 2. Standard Inverter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 3. DC Input Fuse Re-Combiner Options:
Power Xpert Solar 1500/1670 kW Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 4. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 5. Inverter Minimum and Required Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 6. Re-Combiner Input Options: Power Xpert Solar 1500/1670 kW Inverter . . . . . 17
Table 7. Fasteners and Sequence for Conductor Termination . . . . . . . . . . . . . . . . . . . . . 21
Table 8. 3-Wire Connection—Inverter Point-of-Common Coupling Interface . . . . . . . . . 24
Table 9. 30-Day, 6-Month and Annual Inspection and Maintenance . . . . . . . . . . . . . . . 40
Table 10. Fault and Warning Types: Actions and Resolution . . . . . . . . . . . . . . . . . . . . . . 44
Table 11. Critical Faults: CRITICAL FAULTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 12. Non-Critical Faults: FAULT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 13. Warnings That Become Faults: WARNING R FAULT . . . . . . . . . . . . . . . . . . . 49
Table 14. Warnings That Cannot Become Faults: FAULT R . . . . . . . . . . . . . . . . . . . . . 54
Table 16. Inverter Inhibit Status: INHIBIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 15. Alerts That Signal Inverter Service Is Required: NOTIFY . . . . . . . . . . . . . . . . 55
Table 17. Power Xpert Solar Electrical,
Mechanical and Equipment Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Table 18. Grid-Tie Settings: Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 19. Step-Up Transformer Sensor Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Table 20. DC Section Electrical Connection Torque Values . . . . . . . . . . . . . . . . . . . . . . 71
Table 21. AC Section Electrical Connection Torque Values . . . . . . . . . . . . . . . . . . . . . . . 71
Table 22. Ground Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Table 23. Inverter Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Table 24. Maintenance Schedule Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
WARNING!
Save These Instructions WARNING indicates a hazardous situation that,
SAVE THESE INSTRUCTIONS—This manual contains if not avoided, could result in death or serious
important instructions for the Power Xpert Solar 1500/ injury.
1670 kW Inverters that shall be followed during all aspects When this symbol appears in this document or
of planning, designing-in, ordering, receiving, installing, is posted in/on the inverter equipment, read
operating, and maintaining the inverter. and follow the instructions carefully.
Photovoltaic Ground-Fault
The inverter is designed for grounded PV systems only. It
is furnished with photovoltaic Ground-Fault Detection and
Interruption (GFDI). If the inverter detects a PV Ground Fault,
it will interrupt the fault-current within the inverter, set a
ground-fault alarm error message visual on the HMI (LCD)
and Modbus, stop exporting power (turn-off) and open CB1,
DS1, DS2, and DS3. Additional corrective and protective
actions will be required when this alarm is active. Refer to
“Troubleshooting Ground Faults” on Page 43 for a detailed
description of the ground fault detection and interruption
circuit: operation and servicing requirements.
By Code, the PV system must be labeled as illustrated,
below. Look for such labeling.
Figure 2. DANGER—WARNING—CAUTION—NOTICE
Limitations
The Power Xpert Solar 1500/1670 kW Inverter is designed
and tested to the UL508C and UL 1741 standards. As with all
electrical/electronic equipment, this document cannot
possibility anticipate all site, installation, or operation
variances. It is the system engineer’s, installer’s, operator’s
and owner’s responsibility to follow these instructions and
ensure any deviation from this document first establishes
that neither personnel (persons) safety nor the inverter’s and
photovoltaic (PV) system’s balance of system (BOS)
components are compromised.
Professional engineering and construction standards must
always be followed. Incorrect installation and maintenance
will adversely affect any warranty. Contact Eaton for any
questions.
Eaton Corporation
Electrical Sector
877-ETN-CARE (877-386-2273)
4003986
PHOTOVOLTAIC UTIILITY INTERACTIVE INVERTER
30-46871-02
K11
K1
INVERTER 3-PHASE- 60Hz
RE-COMBINER BOX K2 690V, 1800A
1000V FUSE
CONFIGURABLE
MCCB
CB2
INVERTER
+
CONTROL POWER
DS2 MAGNUM
K9 CB1
POSITIVE BUS F25/F26/F27
3
3
1000VDC/3100A
K12
K3
K4 690V, 1800A
A-B-C 30A
PHASE F31/F32/F33
ROTATION
SEQUENCE
SS2 /4
C
A
NEGATIVE BUS
-
DS3 B
K10 F28/F29/F30 OUTPUT-CIRCUITS
3 SURGE
K13
K1 SUPPRESSOR
CS1
K2 690V, 1800A
F3/5A
F2/20A RG1-4
CB3
SS1
+
}
-
Table 3. DC Input Fuse Re-Combiner Options: Power Xpert Solar 1500/1670 kW Inverter
Number of Inputs Fuse Ampacity Compression Lug Compression Lugs
Recommendations Typical Usage 2-Hole: 1/2 inch dia. at 1.75 inch spacing —
(24 maximum) (DC Amperes) Lugs not supplied with the inverter Tin-Plated-Bar: 1/4 inch
24 x 1000 Vdc Fuse 160, 200, 250 As specific to solar site or design: Al/Cu
22 x 1000 Vdc Fuse 200, 250, 315 350 kcmil example lugs
20 x 1000 Vdc Fuse 250, 315, 350 Burndy p/n YA31A3
Ilsco p/n 21ACL-350
18 x 1000 Vdc Fuse 315, 350, 355
600 kcmil example lugs
16 x 1000 Vdc Fuse 315, 350, 355
Burndy p/n YA36A3
14 x 1000 Vdc Fuse 315, 350, 355 Ilsco p/n 21ACL-600
1
Other, larger fuses 400–630 Amp 1
Note
1 Consult Eaton.
Inverter Power-Modules and Stacks The power-stacks feature the latest IBGT-module technology
and are liquid cooled. The IGBT module-technology allows
The power stacks are the heart of the inverter, inverting the true 1000 Vdc switching. Once the minimum PV voltage and
variable direct voltage and current from the photovoltaic energy are available, the inverter’s control algorithms will
modules into a grid-matching quasi-sinusoidal waveform and synchronize its output-AC waveform and frequency with the
frequency. Operating 1 power-module per phase, the 9 utility’s, controlling the exported power as current. The
power-modules form the 3 power-stacks and are identical. inverter is grid-tie, therefore its actual (versus nominal)
Each liquid cooled power-module assembly weighs less than output voltage and frequency is established by the utility grid,
23 kg (50 lbs) and is individually replaceable. Figure 7 via feedback based upon the MV transformer’s step-up ratio.
illustrates the power-module and power-stacks.
The capacitors within the power stack store the energy for
The Power Xpert Solar’s power-stacks are nominally rated continuous millisecond operation during photovoltaic
500 kW with a minimum of 500 Vdc input (Vmp). Operation fluctuations (e.g., momentary irradiance fluctuations).
to 555 kW is available whenever factory-configured for Furthermore, they are sized to enable the inverter to meet
operation with a minimum 555 Vdc input (Vmp). Combining Low Voltage Ride Through (LVRT) and Frequency Ride
the power-stacks outputs in a parallel fashion results in the Through (FRT) required for utility-scale photovoltaic systems,
inverter’s overall 1500/1670 kW rating. The actual power is as well as significant VAR support.
defined within the software, corresponding to the minimum
DC input voltage and AC output voltage.
Figure 7. Power Xpert Solar: Inverter Power Module and Power Stacks
Power Stacks
Inverter Output Circuit As shown in Figure 8, cool air also passes through the AC
cabinet, exiting directly into the exhaust duct.
Inductors and capacitors, working as LC filters on the output
stage of the power-stacks, removes (filters) the carrier The cooling-loop is self-contained within the inverter and
frequency and smooth’s the voltage waveform, resulting in a sealed. Pressure and flow sensors constantly monitor the
nominal 320 AC (357 for the 1670 kW inverter) sinusoidal AC health of the cooling system.The standard coolant is an
waveform, ready to be transmitted to the step-up medium environmentally friendly 30/70 mix of propylene-glyco/
voltage transformer. distilled-water.
The final components of the individual power-stacks and No on-site coolant and plumbing installation is required.
LC-filter are the isolation contactors, K8, K9, and K10, The inverter is delivered with the cooling system complete.
illustrated in Figure 4. Each isolates the power-stack Serviceable air-filters are fitted to both the air-inlet and outlet
and LC-filter from the utility-AC before the power-stack vents, as well as immediately before the coolant radiator
outputs are combined in a parallel-output manner prior to located in the cooling/blower cabinet.
the main circuit breaker CB1. Located on the inverter side
of CB1, these contactors are opened to isolate the inverter Figure 8. Schematic of the Ventilation-Principle
stacks and LC-filters during sleep-mode, faults, and when
turned off.
A 3-phase AC surge suppressor (transient voltage
suppression) protects the inverter from voltage spikes
Cool Air
stemming from the utility-side connection. In areas prone to Inlet
lightning, utility-side medium voltage suppression is
Hot Air
recommended, as is the typical practice for utility-scale Exhaust
projects.
The main AC disconnect is an Eaton Magnum® circuit
breaker, noted as CB1 in Figure 4. The circuit breaker CB2,
connected on the utility side of CB1, supplies the inverter’s
control power. It must be closed prior to inverter operation.
When CB2 is off (open/tripped), the inverter will not operate,
regardless of whether utility voltage is connected to the
medium voltage transformer.
AC Section
Air Inlet
Cooling-System Blower
Installation Instructions
Connect the Power Xpert Solar 1500/1670 kW Inverter to the Unloading and Moving Procedure
photovoltaic array and utility per the NEC, ANSI/NFPA70
requirements. Additional utility and local codes may also The inverter can be transported locally by crane or forklift.
apply. Following the inverter-specific instructions will ensure Direct Crane from the delivery-truck to inverter pad is highly
optimum performance, longevity, and warranty retention. recommended and efficient. Typical unloading, in this
Contact Eaton if there are any questions. manner, is under an hour. Note: The transformer is similar,
yet cannot be transported by forklift without a pallet. The
inverter is delivered with 4 lifting-brackets per (delivery) site.
DANGER of Electric Shock Hazard
Re-use these brackets when multiple inverters are delivered
to any one location.
If additional brackets are required, please consult your sales
WARNING! representative.
● Rigging must attach to the 4 lifting-brackets on the front
and back of the inverter.
NOTICE! ● Select appropriate spreading bar and straps to prevent
damage
1
2 1
3 2 3
4 4
Table 4. Mounting
Lifting Brackets Cover Plates
1 Lift Tab Opening Cover Plate
2 5/8 Flat Plain Washer 5/8 Flat Plain Washer
3 5/8 Spring-Lock Washer 5/8 Spring-Lock Washer
4 5/8-11 x 2.5 Hex Cap Head Grade 5 Machine Screw 5/8-11 x 1.5 Hex Cap Head Grade 5 Machine Screw
(Back of Unit)
DC Section
(Left Side)
(Front)
Clearance Requirements
Installation shall comply with the minimum clearances for When planning the inverter installation, include the step-up
electrical conductors, door openings, and adjacent energized transformer dimensions and requirements. The step-up
equipment according to the National Electrical Code. When transformer specifications are not covered in the scope of
planning the inverter placement, maintain at least the this Manual.
minimum clearances and guidance listed in Table 5.
1.25
.00
.00 1.75 40.38 44.38 86.38 90.38 129.01
DC Input Fuse Options—Re-Combiner Use Table 6 to select the inverter’s re-combiner option.
The Power Xpert Solar 1500/1670 kW Inverter offers Note: When ordering, the fuse quantity and ampere rating
maximum flexibility for matching photovoltaic arrays must be specified, as the option number simply
following NEC 690.8 guidelines. Five standard options cover specifies the number of fuse-holders to install in the
the most common quantity of the inverter’s input-fuses, inverter’s re-combiner. Consult Eaton for Option-4 and
easily matching available solar-modules technologies rated further assistance when considering a mix of input
for 1000 V. All OCPD (Over Current Protection Device) fuses fuses to ensure the configuration meets the UL 1741
are rated for 1000 Vdc. certification, as some limitations will apply as noted in
The Power Xpert Solar inverters are UL 1741 approved Inverter DC Section on Page 9.
for mixed-fuse quantity –and– ratings at the re-combiner.
Any quantity 160–355 A 2XL fuses can be utilized up to
the physical limit of 24 devices and electrical limit of 5600
amperes (reference Inverter DC Section on Page 9 for more
information).
Electrical Connections
Utilize wiring methods when installing the Power Xpert Solar
1500/1670 kW Inverter in accordance with the ANSI/NFPA
70: National Electrical Code. In addition, determine and
follow applicable local, state, and utility regulations. Use only
high-quality aluminum (Al) or copper (Cu) conductors with an
insulation rating of 90 °C (minimum). Select the DC, AC and
Ground circuit conductor’s wire-type and voltage-ratings as
appropriate per Code, and directed by the inverter’s UL 1741
certification and power rating.
Electrical Connections
All the inverter’s photovoltaic input and AC output
connection points are tin-plated copper busbars. Use only
high quality compression lugs for the PV conductor
terminations. The throat-coupled AC connection to the
transformer is provided as a kit, including specific
instructions. The basic electrical connections locations are
illustrated in Figure 17. The PV-conductor securing methods
are illustrated in Figure 18 and Table 7.
Throat
Connection
Controls Inverter AC
Section Section
DC
Connections
Back-Side of Inverter
AC
Connection
Cooling Inductor DC
Section Section Section
DC Circuit Connection
The DC inputs to the Power Xpert Solar are designed for
grounded PV systems. The photovoltaic system’s positive,
negative, and equipment-ground conductors terminate in the
inverter’s DC section as illustrated in Figure 18. The NEC
defines these as the inverter’s input circuits. DC and PV are
often used interchangeably, referring to the photovoltaic DC
voltage and amperage. This is a central inverter, requiring
external source combiners and disconnects.
6
4
2
3
Inverter AC Connection The AC output connections are located on the side of the AC
enclosure (the individual 3-phase busbars from CB1) as
The connection to the medium voltage transformer utilizes a illustrated in Figure 19 and Figure 21. The 3 terminals are
throat-enclosure between the inverter and transformer, as labeled A, B, C, left to right, when facing the inverter. When
illustrated in Figure 19 example. Both the inverter and facing the transformer, it will be just the opposite.
transformer are designed (aligned) for this connection,
forming an enclosed-connection of the three phases. A
flex-bus is provided to make this field-connection to the
busbars, along with the enclosure.
C
B
A
AC Circuit Breaker
Access Detail Transformer Lifting Feature
Bushing
Centerline
to Base
40.0
Appendix B references the contents of the flex-bus kit and Figure 21. AC Output Phase Connections: Throat
the instructions which accompany the inverter. No provisions Connection Details
for a cabled connection is provided, or allowed.
12.00
As illustrated in Figure 21:
12.80
● Prepare each mating bus face with Penetrox “E” or
suitable equivalent for copper connections
● DO NOT use Penetrox “A” or similar compounds made
6.75
for Al to Al or Al to Cu connections
● Apply a tamper-proof torque-marking paint, once the
hardware is properly torqued
6.33 12.00
DETAIL A
Figure 20. Phase Locations THROAT, SIDE VIEW
DETAIL B
Phase C THROAT, TOP VIEW
Phase B
Phase A
Grounded Conductors
The grounded-conductor busbar has provisions for up to 24
circuits using 2-hole compression lugs. Bolt size is 1/2-inch;
bar material is 1/4-inch thick. Minimum hardware is grade-5
and UL-approved crimp-on type ring terminal lugs. Aluminum
hardware kits can be utilized, if they are Listed for use with
the specific compression lugs. Select lugs to match the
busbar’s 2-hole: 1/2-inch dia. at 1.75-inch spacing as noted
in Table 3 and Table 6. Figure 22 and Figure 23 illustrate
the connection points.
When planning for cable-routing, the grounded-conductor
bus terminals will match the number of OCPD (fuse) inputs
utilized on the non-grounded bus.
1
● Inverter’s AC output Current: 2700–2707 amperes
PV panels are available in grounded negative or grounded positive
configurations, depending upon the manufacturer and technology. (nominal rating)
The Power Xpert Solar Inverter can accommodate either. However, the
configuration must be ordered and factory tested. Changing the inverter
● Inverter’s AC branch circuit over-current: 3200 amperes
polarity once the inverter has left the factory requires additional expense (maximum rating)
and removal of the UL 1741 certification. Therefore, verify the photovoltaic
modules that will be used to ensure the proper inverter, before ordering. Additionally, the ground-busbar has two 2-Hole 1/2-inch dia.
Consult Eaton for application assistance. at 1.75-inch spacing, four 3/8-inch spaced at 1.25-inch, and
Negative Grounded PV: The PV-negative are the grounded conductors. an additional two 1/2-inch diameter holes for single-hole
See cabinet label: NEGATIVE GROUND SYSTEM compression lugs. Use this DC Ground bus as the PV’s GET.
Positive Grounded PV: The PV-positive are the grounded conductors.
Bond the GEC to the GET bus by use of irreversible bonding
See cabinet label: POSITIVE GROUND SYSTEM connectors, such as an irreversible busbar connector (e.g.,
Hubbell p/n HYG14BTC28) or approved compression lug
Equipment Grounding Conductors secured to the GET with an appropriate (star) lock washer
with bolted hardware.
The PV system’s equipment-grounding conductors (EGC)
from the array’s modules, racking, source-combiners, Do not exothermally-weld the GEC inside the inverter (i.e., to
conduit, and external PV-disconnecting means terminate to a an exposed ground-rod or the GET bus).
ground-bus common (bonded) to the inverter cabinet and AC
ground bus. Up to 24 circuits using 1-hole compression lugs
are possible. Bolt size is 5/16-inch on a 1/4-inch thick
tin-plated bar. Minimum hardware is grade-5 and
UL-approved crimp-on type ring terminal lugs. Figure 23
illustrates the ground-busbar for 24 input-circuit option.
When planning for cable-routing, the EGCs conductors will
match the quantity of the grounded and non-grounded PV
circuits at the inverter’s re-combiner, coming from each
source-combiner, array sub-combiners, or external
PV-disconnects.
AC
GROUND
BUS
AC GROUND
& COMM(S)
CONDUIT
FLOOR-PLATE
OPENING: 6” x 8”
GEC Connection
The GEC is the Grounding Electrode Conductor. The
Grounding Electrode Conductor shall be attached to the
ground terminal labeled Grounding Electrode Terminal (GET)
that is located in the DC section of the unit. The minimum
wire size is 3/0 for copper (Cu) and 250 kcmil for aluminum
(Al) conductor material. This is based upon inverter’s input
DC amperage. Connecting the inverter Install as per
2011 NEC 690 and the permitting authority and utility.
Auxiliary Power
Electrical power for custom loads can be supplied from the
low voltage 320/357 Vac bus via a 60 ampere circuit breaker
inside the inverter (CB4, see Figure 26). Use of 8-AWG
ferrules recommended.
SEL
PROTECTION CB1
RELAY
CB2
CB4
TBC1
CONTROL
POWER
CAPACITORS
Inverter Operation
The inverter’s installation, operation, and maintenance is Pre-Commission Check
intended for qualified personnel who are trained for
electrical-power systems used within the inverter, the Prior to energizing the inverter for the first time, complete a
medium-voltage transformer, and 1,000-volt photovoltaic thorough inspection. Verify that incoming and outgoing wires
systems. The inverter can connect to medium voltage up to and conductors are properly terminated and
35 k, with the appropriate transformer. The installation is securing-fasteners torqued. Check that the inlet and outlet air
intended for licensed electrical contractors, employing ducts are not blocked and the filter material is clean and in
qualified master and journeymen electrical technicians place. Verify that all tools used in the installation are
familiar with 1000 V PV systems. removed, any protective and safety covers that were
removed during non-energized installation tasks are properly
re-installed, and any debris from the installation process is
DANGER of Electric Shock Hazard
removed from within and around the inverter. The immediate
area shall be clear from obstructions. Maintain the
equipment-clearance requirements as per Code and Table 5
on Page 15, utilizing whichever is the maximum distance.
WARNING! Never use compressed air to remove debris from inside or
outside the inverter.
To prevent damage to inverter-controllers, circuit-boards, and
electronic components, use only ESD-free Vacuum
CAUTION! equipment to clean inside the inverter and the air-filters.
Notice: Damage to components due to Electrostatic
Discharge (ESD) is not covered by warranty.
Never use water to clean or allow water or fluids to enter the
NOTICE! inverter cabinets.
Working from the solar modules, ensure all strings and
source-combiners are properly wired. Verify no PV-positive
Operation of the inverter, energizing both the PV and AC and PV-negative conductors are reversed. Continue this
circuits, switching circuit breakers and interacting with the polarity-check procedure for all array re-or-sub combiners and
inverter, its control power, the transformer and its utility external PV-disconnects. Leave the PV-source combiners or
connection, and all connected PV equipment requires final/last photovoltaic-disconnecting-means (external to the
adherence to electrical safety guidelines, as set forth in the inverter) OFF (open circuit) prior to commissioning and
NEC, NFPA70E, OSHIA, and all local, regional, utility, and operating the inverter.
company(s) policies.
At the inverter, verify the PV-positive and PV-negative
Photovoltaic inverters utilize both DC and AC voltages and conductors are properly wired for polarity and securely
are subject to external backfeed-voltage and energy sources terminated. Ensure all equipment ground circuits are installed
from the PV array, transformer, other inverters, and AC and the PV system is properly bonded to the GET and
switchboards and switchgear at the site. Understand the establishes the required PV grounding electrode system as
disconnecting means available at the site, both PV (DC) and per Code. Only when the PV circuits are verified, shall the
AC is paramount to safe work practices. inverter be energized.
Pay attention to all AC and DC arc-flash and electric-shock Prior to scheduling inverter commissioning services, obtain
equipment labels, their indicated working and boundary from Eaton and complete the:
distances, and all posted safety notices and labels.
Non-labeled equipment must be evaluated prior to work. Power Xpert Solar 1500/1670 kW Inverters
Damaged or missing arc-flash and electric-shock labeling Pre-Commissioning Installation Checklist
shall and must be replaced.
Have this completed form available, or return this completed
Do not proceed to the install, energize or operate the inverter form to Eaton, to ensure efficient on-site inverter
unless authorized. commissioning service. Allow at least 2 weeks for
commissioning services after completing the
pre-commissioning installation checklist and scheduling the
service.
Note: Due to the nature of PV systems, inverter
commissioning is only conducted during dry weather.
6. Under Real Power Limit verify or enter the desired 8. On the Operation page select Charge Request. The
power output limit, if different. In this case 1500 is Inverter will now be in the CHARGING state. The DC
selected (i.e., the Power Xpert Solar 1500 kW Inverter). buses will begin to charge. DS1, DS2, DS3 need to be
closed manually within 30 seconds of the icon-button’s
illumination to avoid a charge timeout fault.
The image shown below is the Charge Request page.
WARNING!
CAUTION!
NOTICE!
● The inverter does not provide a means to isolate utility Interactive Menu
voltage on the transformer-side of circuit breaker CB4 or
any additional control-power disconnect(s) which are The HMI’s LCD touch-screen provides information pertaining
located inside the inverter AC cabinet (section) to the inverter’s present and historical operating status and
provides access to user adjustable parameters. Navigation
● The inverter does not provide a means to isolate input through the menus is achieved through a combination of
circuits from the PV-array (system) side of disconnects menu screens icons, each with subsequent touch screen
DS1, DS2, and DS3, which are located inside the inverter sub-menus. After the duration of 15 minutes the display will
DC cabinet (section). Unless the PV-array is fully always return to the default screen of the current menu.
disconnected externally from the inverter, the inverter
re-combiner will be energized Five main menus are available for operating the inverter,
obtaining information from the inverter, and
troubling-shooting. Figure 27 illustrates the menu structure
De-Energized Inverter and available screens
1. Verify the inverter is in the OFF state Screen Notes:
2. The inverter will de-energize stored capacitive-energy ● Menus ICONS are located along the bottom of the screen
when in the OFF state.
● The icons are similar to a Footer on a printed page
a. and CB1, CB2, CB4, DS1, DS2, and DS3 and are
verified opened. ● Operational status is located in the top-left corner, for
example;
b. Notice: the inverter will remain energized unless the
transformer is also disconnected or isolated form the ● OFF
utility grid and completely de-energized. The inverter’s ● Sleep
throat-connection is a direct feed from the
transformer. ● Wake-up
c. Notice: the inverter will remain energized unless the ● Export
external PV-disconnects are fully open. Disconnects ● Fault
DS1 DS2 and DS2 do not isolate the inverter
re-combiner from the PV array system. ● Based upon the menu, selective information is displayed
through the screen between the top and bottom sections
● Pressing the emergency stop switch will also shut-off the
inverter, forcing open CB1, DS1, DS2, and DS3, but not
CB2 or CB4.
a. Notice: the inverter control power and transformer will
remain live.
b. Notice: the inverter re-combiner will remain energized
from the PV.
● Wait at least 5 minutes to allow the stored capacitive
energy to dissipate before opening the cabinet doors and
access panels.
● Always VERIFY no-voltage is present using calibrated
instruments appropriate to the voltage.
● Always follow applicable safety requirements and
equipment labeling when verifying voltage
● Follow defined LOTO procedures prior to servicing the
inverter
● PV Systems: Understand and verify all sources of external
power connected to the inverter, including backfeed from
the photovoltaic system, other inverters, loop-feed
transformers and their common points of utility
connection.
Any Screen
Settings Page 2
Voltages Configuration • Ramp Up
• Vab, Vbc, Vcb • Local/Remote Sel Hardware Alarm • System Power Limit
• Output Frequency • Auto/Maunal Inputs 2 • Auto Retry/Grid
• Real/Reactive Power • PF Control Enable • E-Stop/Door Open • Reconnect Timers
• Fuse Faults
• Blower
Line Currents Application Settings Page 3
• Ia, Ib, Ic Custom
• Modbus/TCP Enable
• DC Power • Customer Specific Hardware I/O • Inverter IP Address
• Real/Reactive Power • Application Specific Status 1
• DC Inputs/
• Commands per
• Stack Settings Page 4
DC Monitors
• Inverter Subnet
• Primary DC Voltage • Mask
• Secondary DC Voltages • Inverter Gateway
• Secondary DC Currents • Address
Hardware I/O
Status 2
• Breaker/Contactors
Temperatures 1 • Pump/Blower Settings Page 5
• Inlet/Outlet Temp • Optional I/O PLC
• Inlet/Outlet Pressure • Enable
• I/O PLC IP Address
• Return Flow
Application
Custom
• Customer Specific
Temperatures 2 • Application Specific
• IGBT Module Temps
Standard version displays
• Total MWh
general purpose MF I/O status
• Real/Reactive Power
Operational States Whenever the inverter is in sleep mode and is inhibited from
exiting and progressing to the standard power-export state,
pressing the information “i” on the touch-screen will open
Sleep State the illustrated screen (on the right) indicating the reason why
the inverter is inhibited. In the example, there is an active
During the SLEEP state the following is the status of the
warning with the 60-second retry timer at 45 seconds. The
inverter and PV-system:
inverter will attempt to clear all non-critical faults and
● The inverter stacks are disconnected from the AC grid warnings using the 60-second retry timer. Pressing the Fault!
or Diagnostic Menu will provide further information.
● Power-stack contactors K8 K9 K10 are OPEN
● The DC voltage is below the Wake-up level
● The AC line voltage and frequency are within the grid-tie
specified limits
Whenever the PV voltage drops below the inverter’s
minimum, the inverter will enter the sleep state. When the
AC grid is first applied (or returns after a loss of grid-tie
tolerance event), there is a 300 seconds (5 minutes) period to
transition from the sleep state before grid synchronization
can begin. The HMI will display this count-down the seconds.
Should the solar array be unable to supply either enough
power to support power-export (typically 7500 W), or the
voltage drops below the minimum (500/555), the inverter will
display a “low array” fault and re-enter the sleep state. The
low-array and entry into the sleep state is typical in the
evening as irradiance diminishes, and often at first light in the
morning, when minimal irradiance may rise the array’s
open-circuit voltage (Vac), yet not have enough irradiance to
support either the minimum voltage or export-power
wattage. These are “normal” solar-system conditions and
events.
Faults
The HMI display will alert any active faults in the upper-left
section of the display (header).
To access the fault, navigate to the fault! menu, where the
date, fault code and a short description is displayed.
● Troubleshooting, beginning on Page 43, covers the
troubling-shooting aspects of the inverter.
Maintenance
The Power Xpert Solar 1500/1670 kW Inverter is easy to
maintain. No periodic adjustments are required. Only basic
field-wiring, systems checks and inspections are required.
The monitoring system is designed to alert to operator of a
case requiring non-periodic maintenance. Only qualified
personnel shall maintain the inverter. Please consult your
local sales person for support.
CAUTION!
NOTICE!
Maintenance Schedule
Following the inverter’s commissioning, the inverter must be
maintained on an appropriate schedule, fitting to the
installation. To establish the correct periodic maintenance
schedule, an initial check-list is provided in the table below.
❑ Phases A/B/C
minimum.
❑ Field wiring (PV and AC connection points)
❑ Neutral (4-wire)
❑ Inverter
❑ Ground
❑ internal wiring and components
■ Inverter bolt-down fasteners
❑ Filter-Capacitor inspection
❑ Temperatures
– Modules
❑ Lose Cables
– Shading
❑ Evidence of “hot spots” at
– Soiling
❑ Note for future maintenance
Connections
❑ AC Grid Connections
❑ Vandalism /Damage
❑ Other as Specified
❑ Power meter
❑ Monitoring Systems
❑ HMI Display
❑ Bolt-Downs
❑ Other as Specified
Cooling System Inspection ✔ ✔ ✔ Inspection of liquid cooling system for any sign of leakage, liquid
accumulation, discoloration, loss of pressure and/or flow, and operating
pressure higher than normal.
Cooling Hoses Inspection — — ✔ Inspect the cooling system hoses for any sign of cracks, leakage,
deformation, discoloration, chocking, and any other abnormality.
■ Replace if necessary
blockage
❑ Clean as necessary
abrasion
Perform manual operation of blower observing for;
■ Abnormal noise
■ Vibration
■ With the inverter off, operate the motor and observe for
❑ noise, vibration
■ Harness
❑ Chafing
■ Moisture egress
❑ Door seals
Cooling flush and Clean-up — — When pump Cooling flush (renew) and clean-up
is serviced
Inspect the Solar Array and Cables ✔ ✔ ✔ See PV System Details
■ Panel Condition
■ PV Disconnects
■ Labels
The maintenance-schedule log shown in Appendix H (or 3. Immerse the filter in a solution of warm soapy water,
similar) should have entries made to document when and using a mild detergent. Rinse with clear water and let
what maintenance is performed by the qualified personnel. completely dry.
The maintenance log should include air filter cleaning or
replacement, inspection of the air inlets and air outlets for 4. Discard the filter, replace with new filter (material).
the absence of foreign debris that could impede air-flow on
the outside of the inverter, internal and external component Component Inspection
and connection inspection inside and externally associated
with the inverter. An annual inspection should be made on all components.
Components, including bus-bars and connections should be
inspected for the any sign of overheating and an
Air Filters accumulation of foreign material on the component or inside
The frequency of air filter maintenance will depend on the the inverter. To prevent damage to the inverter circuit-boards
local environment in which the inverter is located. and electronic components, use only ESD-free Vacuum
Dust-prone environments will require more frequent air-filter equipment to clean inside the inverter, the air-filters if
maintenance. The following procedure may be used to in-place, and the radiator. Notice: Damage to components
access and perform maintenance on the air filter. due to Electrostatic Discharge (ESD) is not covered by
warranty.
One of the following procedures may be used to clean or
service the filters, after removal from the inverter.
Connection Inspection
1. Vacuum the filter (material)
An annual inspection should be made on all electrical
2. Rinse the filter with a stream of water, and let the filter connections and wiring. The rated torque values for bolted
completely dry. connections are provided in Appendix D.
Troubleshooting
Reasons for troubleshooting the inverter include annunciated Identifying Inverter Faults and Warnings
faults, reduced-exported power, and physical damage to the
inverter from external events. Understanding the basis of any Detected events or situations that prevent power export are
troubles characterized as either array-based, inverter-based annunciated via the HMI and Modbus as either faults or
or grid-based forms the analysis process of troubleshooting warnings. In addition, a history log is stored on-board the
the inverter. inverter.
● The inverter will indicate specific faults and warnings via
Array-Input the HMI display.
The inverter’s input-power window is the specified minimum ● Active and historical data is stored under the fault! menu
and maximum DC voltage while supplying enough current to and can be accessed via the HMI display.
overcome approximately 0.5% of the inverter’s AC power
rating. The minimum DC voltage is defined as the lower
MPPT voltage. The inverter will not synchronize to the utility
and export power when the PV array is below its minimum Inverter Response to Faults and Warnings
voltage. The maximum DC voltage is defined as 1000 V, FAULT and WARNING are divided in 4 categories which
typically corresponding to the photovoltaic array’s Vac during provide the basis of the inverter’s behavior whenever these
non-operation. The PV array (input power) must always are detected or present. The FAULT category takes
remain slightly greater than the export power (barring precedence over the WARNING category. Detection takes
momentary LVRT events if the inverter is so equipped or place in any state, however;
operated). While detected and annunciated as a FAULT or
WARNING, loss of the appropriate photovoltaic input-power ● For instance … if already in the fault state and a critical
may not be considered an inverter-centric troubleshooting fault occurs, the inverter transitions appropriately.
event. For example, when operating near the inverter’s lower
voltage window, large arrays can lose enough power due to
● When in the critical fault state, the inverter will still detect
sudden shading that the inverter will shut-off as its natural most warnings and faults, yet they will not be acted upon.
power processing will collapse the array’s voltage. While
Fault location:
such events are outside the scope of this manual and normal
inverter operation, understanding the available faults and ● Power-Stack 1 indicates the fault occurred in the 1st
warnings will give rise to determining if an external event inverter (left-side stack).
adversely affected the inverter’s INPUT.
● Power-Stack 2 indicates the fault occurred in the 2nd
inverter (middle stack).
AC-Output
The inverter’s sinusoidal output waveform must match the ● Power-Stack 3 indicates the fault occurred in the 3rd
utility’s across the step-up transformer’s 3-phases, inverter (right-side stack).
accounting for voltage magnitude, frequency, phase-angle,
and power-factor. The UL1741 grid-tie IEEE 1547 settings Inverter system (Inv sys):
are the default-basis for the grid specification and continued ● Indicates the fault occurred outside of the inverter, and
inverter operation. While detected and annunciated as a within the separate diagnostic circuits from the modules or
FAULT or WARNING, loss of the appropriate grid may not be stacks.
considered an inverter-centric troubleshooting event. While
such events are outside the scope of this manual and normal Fault text on HMI:
inverter operation, understanding the available faults and
warnings will give rise to determining if an external event ● Displays the fault code followed by the fault text
adversely affected the AC-OUTPUT.
DESCRIPTION is a basic statement about the fault
Inverter RESOLUTION is the basic recommendation for gathering
Multiple fault-tolerant control algorithms will always try to information, addressing the issue and resuming inverter
reset the inverter whenever the PV-array or AC-Grid fall operation.
outside of the operating specifications, automatically
resuming operation once both the input (array) and output
(grid) are within specification. While complex
engineering-level diagnostic steps are outside the scope of
this manual, understanding the available faults and warnings
will give rise to determining if an internal event adversely
affected the INVERTER.
A CRITICAL FAULT will not automatically retry and can only be re-set by the following manual
intervention methods. From the HMI;
■ Disable the inverter via the first screen of the Operation menu: Press Disable .
■ Re-close the Disconnects DS1-2-3 via the Charge Request on the menu.
❑ Note that the underlying condition(s) originally causing the CRITICAL FAULT must be remedied.
❑ For the signals having both open and closed feedback, the intent is to detect wiring errors or
loose wires. These are classified as CRITICAL, as a solution cannot be fixed without physical
presence at the inverter.
FAULT A FAULT will stop the inverter and isolate it from the AC.
■ Opens the Stack’s Output contactors (K8, K9, K10)
Fault will not be automatically retry and can only be re-started by the following manual intervention
methods. From the HMI;
■ Attempt to clear the fault by the Fault Reset function of the HMI
❑ If the fault does not re-set (clear), re-check the underlying cause
Alternatively;
■ Disable the inverter via the first screen of the Operation menu: Press Disable .
■ Enable the inverter following the completion of the pre-charge procedure.
❑ The inverter’s control power, CB2, does not have to be cycled
❑ Note that the underlying condition(s) originally causing the fault must be remedied.
■ A non-critical fault may be reset locally or via SCADA controller (if the unit is being controlled via
seconds.
❑ Output contactors open (K8, K9, K10)
Alternatively;
■ Re-Enabling the inverter issues a “Clear Warning” condition to the inverter.
❑ Note that the underlying condition(s) originally causing the fault must be remedied.
Table 10. Fault and Warning Types: Actions and Resolution, continued
Fault Type/Category Actions and Resolutions
WR∞ A WARNING with an infinite retry.
Warning cannot become a fault ■ The inverter will automatically attempt to clear the warnings and resume operation.
❑ Output contactors open (K8, K9, K10)
Alternatively;
■ Re-Enabling the inverter issues a “Clear Warning” condition to the inverter.
❑ Note that the underlying condition(s) originally causing the fault must be remedied.
W ■ If a Schweitzer FAULT occurs (grid disturbance), the “Reconnect” time dictates the minimum delay
Warning before attempt. (default is 5 minutes, typical to UL1741)
Schweitzer Protection Relay Notes ■ The AC breaker CB1 will open in this case due to wiring between Schweitzer and Magnum shunt
trip.
NOTIFY Items that address servicing the inverter
FUF2 Fuse Fault 2 Filter Capacitor Fuse Fault Check the 400 A LC filter fuses in Stack 2 (continuity check)
Indicates one of the filter-capacitor fuses ■ F16 –FSW4 | F17 –FSW5 | F18 –FSW6
GF Ground Fault Photovoltaic Ground Fault Detection and Reference the GFDI troubleshooting section
Interruption (GFDI). 5 A FU3 cleared and/or
CB3 has tripped
PS3 Logic 3.3 V Power Fail Logic 3.3 V Power Fail Contact Eaton
PS5 Logic 5 V Power Fail Main Communication board PIB 5 V power Check for 5 V on the power supply PS9
supply failure ■ COMMC board J1(+) to J1(-) shall be 5 Vdc
PS15 Logic 15 V Power Fail Main control board PIB ±15 V power supply 1. Check for +15 V on the power supply PS2 (from TB4-1)
failure – TB3-1 to PIB-J20-1 shall be +15 Vdc (to TB3-5 / PIB-J20-2)
2. Check for -15 V on the power supply PS3 (from TB4-2)
– TB3-9 to PIB-J20 shall be –15 Vdc (to TB3-5 / PIB-J20-2)
PS24 Aux 24 V Power Fail Main control board PIB 24 V auxiliary power Check for 24 V on the aux. power supply
supply failure ■ PS4 (CAN)
SEQ1 Pre-Charge Timeout Pre-charge operation not completed within 1. Verify PV voltage, allow DC-bus voltage to diminish
30 seconds (bleed-down). Reset fault on HMI, then re-start the pre-charge,
PV Voltage must be >0 Vdc close DS1 DS2 DS3 closing disconnects within 30-seconds of the HMI “charging”
PV-voltage relative to existing DC-Bus (stack) state icon-buttons illumination.
voltage must be <20 Vdc to perform pre-charge 2. Check the DC disconnect / pre-charge aux-switch (ST) wiring.
(close DS1-2-3).
SF0–SF5 Internal Fault 00–05 Internal non-recoverable fault in main controller 1. Reset Fault on HMI operation menu
(DSP uP) or the Control Board. 2. Disable Inverter completely), then cycle the control-power.
SF0: Reserved ! Warning of AC Arc-flash if/when CB2 is cycled!
SF1: Invalid State Fault 3. Contact Eaton
SF2: Reserved
SF3: Software Incompatible
SF4: NVRAM Fault
SF5: Reserved
XI0 Door Open Protected Cabinet Door Open 1. Close all cabinet doors
2. Check cabinet door switches
XI1–XI4 External Fault(s) 1–4 External Interlock Fault Four optional provisions allowing external-event or
(optional, for customer equipment / usage) equipment-interfaced critical faults. Loss of signal-voltage
(open-circuit) type of action.
❑ External Fault 1 – TB9-1 – PIB J14-3 (+24 Vdc)
XCF1–XCF4 Definable Faults User Defined Fault Future provision. Definable Faults.
■ Consult Eaton
Usages examples:
■ Medium Voltage Transformer
SEL Protection Relay Schweitzer Protection Relay fault Check the SEL Protection relay for proper operation
■ SEL monitors utility over/under voltage and frequency, as per its
settings
SEQ2 Wakeup Timeout Magnitude and phase voltage synchronization 1. Check for collapsing PV array voltage when inverter is entering
failed to be achieved within the time threshold. power-export mode
The grid-sync feedback via CAUX4 unable to 2. Check Sync transformers TR5 TR6 TR7 in LC cabinet:
sustain waveform for 30 sec. ■ Fuses F78 -83 1-Amp
THM16 Inlet Water Temp Stacks’ Inlet Water Temperature sensor Coolant is not sufficiently cooled exiting the radiator
exceeds over-temp threshold (70 °C) for 1. Verify Inlet Temp reading on HMI: Monitor menu
10 seconds. 2. Check for coolant leaks
3. Check for: blower operation | air-filter blockage or reduction of
air-flow thru radiator
4. Check coolant Temperature Sensor/Transducer TT1 in LC
cabinet section: wiring
■ TB11-6 | TB11-13 | CANUX2 J7-8/3/(7-shield drain-wire)
THM17 Outlet Pressure Indicates that the stacks’ outlet pressure is less Pressure entering the coolant pump: pump inlet
than or equal to the minimum outlet pressure 1. Verify Outlet Pressure reading on HMI: Monitor-menu
(20 PSI) for 3 seconds while the pump is 2. Check for coolant leaks
running. 3. Check coolant Pressure Sensor/Transducer PT2 in LC Cabinet
section: wiring
■ TB11-5 | TB11-12 | CANUX2 J6-8/3/(7-shield drain-wire)
THM18 Outlet Water Temp Stacks’ Outlet Water Temperature sensor Coolant is exceeding allowed temperature-rise thru IBGT stacks, prior to
exceeds over-temperature threshold (72 °C) radiator
for 10 seconds. 1. Verify Outlet Temp reading on HMI compared to IGBT temps:
Monitor menu
■ Temperature 2 menu: M1A/B/C | M2A/B/C | M3A/B/C
cooled)
2. Check coolant Temperature Sensor/Transducer TT2 in LC
cabinet section: wiring
■ TB11-7 | TB11-14 | CANUX2 J7-10/5/(4-shield drain-wire)
THM19 Choke Over Temp Indicates that one of the chokes has exceeded 1. Check choke temperature switch: TSW LO1 | LO2 | LO3
safe operating threshold 2. Check choke series-connected wiring
3. Check choke temperature switches wiring at: TB11-6 and
CANUX2-J6
4. Check for: blower operation | air-filter blockage or reduction of
air-flow thru radiator
And exiting into LC Cabinet section and then exiting rear of
inverter (air exit vents)
UF Under-Frequency Grid under-frequency alarm SEL set for UL1741 grid-tie parameters: incompatible with
Frequency <95% Rated Frequency [57 Hz] for low-frequency ride-thru
1.2 sec ■ Check for/if SCADA control seeking low-frequency ride-thru
power-export
Abnormal Operation (typically when solar irradiance > 200 W/m2)
■ Verify solar array modules for damage and source and output
connections
XW1–XW8 User-Defined User defined Warnings as part of the Consult Eaton prior to Inverter order/factory build
Multi-Function IO Feature set. 1. See equipment delivery documents
Examples: Typical to the medium-voltage
transformer;
1. Liquid Level Alarm; Activates low level
alarm circuit.
2. Liquid Temperature Alarm 1.
Low set-point
3. Liquid Temperature Alarm 2.
High set-point
4. Pressure Switch Alarm; Activates at
+6.0 PSIG falling
5. Vacuum Switch Alarm; Activates at
–2.5 PSIG falling
SG2 AC Surge 2 AC Surge Protector Failure Replace AC Surge protector SS3 in the AC Cabinet Section
AC Surge device on TR2 X1/X2/X3 ■ Verify 30 A fuses F46 | F47 | F48
SG3 DC Surge DC Surge Protector Failure Replace DC Surge protector SS1 in the lower DC Cabinet section
DC Surge device DC (PV) input circuits ■ Verify 20 A fuses F1 and F2
XN1 – XN8 User-Defined User defined Notify messages as part of Consult Eaton prior to Inverter order/factory build
the Multi-Function IO Feature set. 1. See equipment delivery documents
During normal operation while exporting power (current) to Ground Fault Troubleshooting Checks
the grid, should a PV ground fault occur, either CB3 will trip
(open) or the fuse clear (based upon actual fault). In either Figure 29 shows the GFDI connections. The circuit is
case, the inverter will stop, opening contactors K8/K9/K10, comprised of 3 components:
CB1, and disconnects DS1-3. This will isolate the inverter 1. Ground Fault Device (sensor) GFD1 set to 5 A.
stacks from the fault and annunciate the required Ground
Fault Error Message, DC Ground on the HMI and Modbus. 2. Fuse—opens the ground path during a ground fault.
Once fuse F3 and/or CB3 is tripped, the GFDI circuit ● Fuse has a trip-indicator, evoking the holder’s
continues to maintain system safety through the 4000 Ohm microswitch change-state.
RG1-4 resistors. With either/both CB3-open or F3-cleared, ● Operates even when AC power is removed from the
the resulting single-point-ground’s open-circuit will allow a
inverter
small electric current (Voc/4000 = X mA | 1000/4000 =
250 mA) to trickle through resistors RG1-4 to the PV-negative 3. Circuit-breaker—shunt tripped by the CS1 or fuse-holder
conductors grounded bus at the inverter’s re-combiner. microswitch during a fault.
Understanding Kirchhoff’s Voltage Law (KVL), each RG1
resistor will drop (X mA x 1000 = XV | 250 mA x 1000 = ● Operates when the inverter is ON (control power
250 V) volts, in essence the entire Voc potential (disregarding must be present).
PV-system conductor resistance). This will minimize the The fault-interrupter design is a redundancy system, as either
shock-potential between equipment ground and CB3 or F3 (both are in series connection) can react to open/
grounded-PV conductors. Note: When diagnosing a PV operate/function during a ground fault event.
ground fault, if voltage measured across RG1-4 is lower than
the expected string-voltage (Voc), expect a ground-fault along Step 1: Verify the GFDI tripped CB3 or cleared 5 A F3
the string(s) at the relative voltage corresponding to the
If tripped or cleared; determine if the fault is a positive or
number of modules (Voc). Furthermore, individual Module Isc
negative ground fault.
is equal to the “string Isc” due to the series-connection of
the modules per string. Only at the source-combiner, post Measure the DC voltage across resistors RG1-4, looking for a
string fuses, is the module or string Isc additive (increased). “negative” value if the DMM ground-lead is placed on GET.
Critical to an effective GFDI is the PV grounding electrode ● GET Bus-1 to Grounded-PV-Conductor bus
system, and its bonding to the inverter GET (i.e., GET bus-1).
The PV system must always be built with a PV Grounding If voltage is present, there is a faulted PV positive conductor
Electrode System, bonded to the inverter’s GET. The in the PV-array system. Typical damage is found in
minimum bonding conductor size is 3/0 as per UL1741 for non-protected module string-conductors in-route to the
the 1500/1670 kW inverters. source-combiners, or source-combiner output circuits faulted
inside conduit in-route to the PV-Disconnects or inverter.
DANGER of Electric Shock Hazard ● Once the fault is repaired, install a new 5 A F3 fuse if
When a Ground-Fault is present. damaged
● (check fuse for an open circuit: ∞ Ohms)
WARNING! ● Re-set (close) CB3
When a Ground-Fault is present. ● Re-cycle inverter power
● Turn-on the inverter
NOTICE!
If voltage is NOT present across resistors RG1-4, suspect
IF A GROUND FAULT IS INDICATED, a negative PV ground fault. Typical damage is found in
NORMALLY GROUNDED CONDUCTORS non-protected module string-conductors in-route to the
MAY BE UNGROUNDED AND ENERGIZED. source-combiners, or source-combiner output circuits faulted
inside conduit in-route to the PV-Disconnects or inverter …
circumventing the fundamental single-point-ground of a
grounded PV system.
● Once the fault is repaired, install a new 5 A F3 fuse if
damaged
● (check fuse for an open circuit: ∞ Ohms)
● Re-set (close) CB3
● Re-cycle inverter power
● Turn-on the inverter
Gnd +24V
Glossary
Term Abbreviation / Definition
AC . . . . . . . . . . . . . . . . . . Alternating Current
Typically a sinusoidal waveform (i.e., pure, quasi, or stepped)
CB . . . . . . . . . . . . . . . . . . Circuit Breaker
An automatically operated electrical switch designed to protect an electrical circuit and
equipment from damage caused by overload or short circuit. When used in solar
applications they shall be designed for backfeed or bidirectional operation, without reference
to Line or Load.
DC . . . . . . . . . . . . . . . . . . Direct Current
A non-sinusoidal waveform
Eaton . . . . . . . . . . . . . . . . Manufacturer of the Power Xpert Solar 1500 kW Grid Tie Inverter Series Grid Tie Inverter.
Described herein is the Power Xpert Solar 1500 kW Grid Tie Inverter 250 kW Solar Grid Tie
Inverter.
The grounding electrode conductor(s) forms the continuous, unbroken, ground reference of all
non-energized metal components compromising the PV array, the S-Max inverter, and the
B.O.S components up-to and including the point of common coupling (electrical panel / utility).
Inverter Input Circuit . . . . Conductors between the inverter and the photovoltaic output circuits for electrical
production and distribution network. 1
e.g., Inverter’s DC circuits connected to the PV Array
Inverter Output Circuit . . . The conductors between the utility interactive inverter and the service equipment or
another electrical power production source, such as a utility, for electrical production and
distribution network. 1
3-phase AC circuits connecting to the point of common coupling (PCC)
IR . . . . . . . . . . . . . . . . . . . Infrared
Infrared light is electromagnetic radiation with wavelengths longer than visible light. Uses
include remote temperature sensing.
Neutral Conductor . . . . . . The conductor connected to the neutral point of a system that is intended to carry current
under normal conditions. 1
Note: A neutral conductor is a current-carrying conductor, regardless of the fact it is grounded.
Power Factor . . . . . . . . . . Defined as the ratio of the real power flowing to the load or facility (kW) to the apparent
power (kVA) in the facility’s circuits.
Typically expressed as a percentage, where 100% is perfect power (unity) where the kW
equals the kVA and reactive power is supplied by the utility.
PV Module . . . . . . . . . . . . An electro-mechanical assembly of solar cells forming a single sealed unit positive and
negative lead outputs.
PV arrays (solar systems) are comprised of PV Modules.
SI . . . . . . . . . . . . . . . . . . . Standard for the Use of the International System of Units (SI) The Modern Metric System.
Units of measure used in this Installation and Operations Manual are provided in the SI
system [meter, Newton, kilogram] along with the U.S. engineering units, e.g., ft | in m | mm /
lb-in Nm / lb kg
Vars may be considered as either the imaginary part of apparent power, or the power flowing
into a reactive load (e.g., inductive loads such as motors or capacitive loads such as switching
power supplies), where voltage and current are specified in volts and amperes. The two
definitions are equivalent.
For utility AC distribution sinusoid-currents and voltages at the same frequency, reactive power
in vars is the product of the RMS voltage and current, or the apparent power, multiplied by the
sine of the phase angle between the voltage and the current. The reactive power Q (measured
in units of volt-amperes reactive or var), is given by:
where f is the phase angle between the voltage and the current.
Only effective power, the actual power delivered to or consumed by the load, is expressed in
watts. Imaginary power is properly expressed in volt-amperes reactive and does not
accumulate Watts on a utility-billing power meter.
WYE . . . . . . . . . . . . . . . . . Star-connection.
Line-to-Line and Line-to-Neutral Connections
A type of 3-phase transformer with a central neutral connection. The neutral is equally
referenced to the 3-phases (i.e., Line-to-Neutral).
Note:
1 Reference citation: NAPF 70: National Electric Code 2011.
Appendix A
Table 17. Power Xpert Solar Electrical, Mechanical and Equipment Specifications
Description 1500 kW Inverter 1670 kW Inverter
AC Output Specifications (–20 °C to +50 °C)
Rated Output Power AC 1500 kW 1667 kW
Nominal Apparent Power AC 1650 kVA 1850 kVA
Nominal Output Current AC 2700 A 2707 A
Maximum Branch Circuit Output Protection AC 3200 A 3200 A
Maximum Continuous Output Current at 50 °C 3000 A 3000 A
Nominal Operating Voltage (L-L) 320 Vac 357 Vac
Operating Grid-Tie Voltage Range (88%–110% L-L) 282 to 352 Vac 313 to 392 Vac
CEC Efficiency (inverter only, no options or MV transformer) 98.0 98.5
Nominal Operating Frequency 60 Hz 60 Hz
Operating Frequency Range 57– 63 Hz 57– 63 Hz
(UL1741 Grid-Tie Range) (57.0 – 60.5 Hz) (57.0 – 60.5 Hz)
Total Harmonic Distortion at rated power Per IEEE 1547, < 5% TDD Per IEEE 1547, < 5% TDD
Power factor at rated power ± 0.91 adjustable power factor ± 0.91 adjustable power factor
(UL1741 Grid-Tie Range) ± 0.99 (leading/lagging) ± 0.99 (leading/lagging)
AC Configuration Delta 3-Wire / WYE 3-Wire (non-grounded neutral)
AC Output breaker Eaton Magnum MDS (w/Optional trip units: Digitrip 520 LSI, default unit)
DC Input Specifications (–20 °C to +50 °C)
Maximum Input Voltage, PV VOC 1000 Vdc 1000 Vdc
Nominal DC Operating Current 3100 A 3100 A
Maximum PV-Array Short-Circuit Current 5600 A 5600 A
(Total array short-circuit current connected to the [4,480 A with the application [4,480 A with the application
inverter re-combiner) of NEC 690.8 (A)] of NEC 690.8 (A)]
PV Input Voltage Operating Range 500 to 1000 Vdc 550 to 1000 Vdc
Maximum Power Point Tracking (MPPT) Range (CEC) 500–800 Vdc 550–800 Vdc
DC Input Connections PV-Circuit Conductors:
■ Grounded PV systems, only To 1/4-inch thick, tin-plated copper bus prepared for compression lugs
Al/Cu Compression Lug type: dual 1/2-inch holes: holes spaced at 1-3/4 inch
PV Equipment Ground Conductors:
To 1/4-inch thick, tin-plated copper bus prepared for compression lugs
Al/Cu Compression Lug type: single 5/16 -inch hole
Optional Configurations:
■ Prepared Bus only (no fuses): 24 locations each for non-grounded / grounded PV conductors,
and PV EGCs
■ Prepared Bus for 24 (max.) non-grounded PV circuit conductors mating to each individual OCPD
1000 V fuse
Standard prepared bus for Grounded-PV and EGC conductors {as in option (1)}
Inverter Re-Combiner Fuses 160 / 200 / 250 / 315 / 350 / 355 / 400 A 1000 Vdc
■ For non-grounded PV circuit conductor, only
Table 17. Power Xpert Solar Electrical, Mechanical and Equipment Specifications, continued
Description 1500 kW Inverter 1670 kW Inverter
Protection
AC Disconnect AC Circuit Breaker with LOTO AC Circuit Breaker with LOTO
AC Surge Suppression Yes, monitored by Inverter SCADA Yes, monitored by Inverter SCADA
DC Disconnect Switch disconnect with LOTO Switch disconnect with LOTO
DC Surge suppression Yes, monitored by Inverter SCADA Yes, monitored by Inverter SCADA
PV Ground Fault Monitoring Yes, monitored by Inverter SCADA Yes, monitored by Inverter SCADA
AC Grid-Tie Yes, SEL 751A Protection Relay Yes, SEL 751A Protection Relay
Communications and Controls
Communications with plant central controller Modbus TCP; Optional Fiber optics connection Modbus TCP; Optional Fiber optics connection
HMI Yes Yes
Convenience Power
120 Vac Outlet (service) 15 A-fused 1x Control Cabinet / 1x LC Cabinet
120 Vac Customer Power 3 A (5 A fused) 14-AWG Terminal Silos: 3x Line / 3x Neutral / 3x AC-Ground
Mechanical Specifications
Operating Temperature Range Full Power –20 °C to +50 °C –20 °C to +50 °C
Optional extended temperature range (cold weather package) –40 °C to +50 °C –40 °C to +50 °C
Storage Temperature Range –30 °C to +70 °C –30 °C to +70 °C
Enclosure Protection Outdoor Rated
NEMA 4 for power electronics and controls equipment
NEMA 3R for magnetics and switchgear
Relative Humidity 0 to 100% Non-Condensing
Inverter Mounting (including transformer) Pad [Skid Mount, consult Eaton]
Cooling Self-contained: closed-loop pressurized liquid cooling and forced-air convection
Maximum operating altitude 3300 ft (1000 m) [higher altitudes possible with de-rating]
Appendix B
Contents
Each 84-37413-1 kit will contain the following;
1. Top cover (has lifting handles), 1 pc.
2. Bottom cover, 1 pc.
3. 3/8 inch hardware (SS bolts, nuts, flat and lock washers)
for cover assembly, 32 pcs.
4. Flex-bus jumpers, 6 pcs.
5. 1/2 inch hardware (Gr5 bolts, lock-nuts, flat and Belleville
washers) for Bus assembly, 288 pcs.
6. This document
Instructions
Assemble as follows;
1. Prepare each mating bus face with Penetrox “E” or
suitable equivalent for copper connections. DO NOT use
Penetrox “A” or similar compounds made for Al to Al or
Al to Cu connections.
2. Place two Flex-bus bars on each side of one phase
(3 places) of the unit output/ transformer LV input
bus stubs.
3. Bolt assembly direction: 1/2 inch Bolt, 2 Belleville
washers (in parallel), flat washer, bus assembly, flat
washer, 1/2 inch lock nut.
4. Torque 1/2 inch bolt assemblies to 50–60 ft/lbs
(68–81 Nm). DO NOT OVER-TIGHTEN!
5. Place top cover over throat assembly, attach bottom
cover with 3/8-16 x 3/4 inch lg. SS bolts and washers
(4 places, each side) and torque to 6 ft/lbs (8 Nm).
DO NOT OVER-TIGHTEN!
6. Secure cover assembly to unit and transformer throat
apertures with 3/8-16 x 2 inch lg. SS bolts and washers
(4 places, underneath each end) and torque to 6 ft/lbs (8
Nm). Tighten jam nut at each location to secure
assembly. DO NOT OVER-TIGHTEN!
Appendix C
3365E
3365C
3365B
3365A
TBC1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Analog Inputs
Multi-Funcion
MFAI 3.1
MFD 3.1
MFD 3.2
Multi-Funcion
Digital inputs
MFD 3.3
MFD 3.4
MFD 3.5
MFD 3.6
Appendix D
Torque Values
The tables below list the torque for all of the electrical
connections by enclosure section. These tables may be used
to verifying that the electrical and mechanical connections.
Appendix E
Fuse Replacement
The following table summarizes the fuses that are used in
the inverter. Use only fuses that are the same part number
and value.
Appendix F
Enclosure Lifting Instructions
Appendix G
Appendix H
Appendix J
Notes
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2014 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. MN141001EN / Z15242 All other trademarks are property
October 2014 of their respective owners.