Sei sulla pagina 1di 5

Zeus energy SAC Pressure Relief Valve Sizing & Selection Report

jorge.rodriguez@zeusol.com.pe 16-sep-2019

Peru
+51949827888
jorge.rodriguez@zeusol.com.pe
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 Valve ID 41 SIZING DATA
2 Tag No. QuickCalc001 42 Design Code ASME Section VIII Sizing Std. API 520
3 Service 43 Sizing Basis Fire Case
4 PID No. 44 Fluid State at Inlet Gas / Vapor
5 Line No. Quantity 45 Relieving Case Pressure Relief
6 1 46 Fluid Properties
7 GENERAL 47 Fluid Name
8 Valve Type Conventional, Direct Spring-Op 48 Molecular Weight, M 16.5
9 Safety / Relief Safety Relief Balanced No 49 Compressibility, Z 0.98
10 Nozzle Full Bonnet Closed 50 Ratio of Sp. Heats, k (Cp / Cv) 1.4
11 CONNECTIONS 51 Gas Constant, C 356.1
12 Inlet 3/4" Thrd. MNPT Standard 52
13 Outlet 1" Thrd. FNPT ASME B1.20.1 53
14 MATERIALS OF CONSTRUCTION 54
15 Body Cylinder CS SA216-WCB 55
16 Body Base 316 SST 56
17 Connections N/A 57
18 Disc 316 SST 58
19 Seat Buna-N (70) 59 Sizing Coefficients Unit -
20 Seals N/A 60 K, Gas Kd, Gas 0.878 0.975
21 Spindle 416 SST 61 Kb Kc 1 1
22 Guide 316 SST 62
23 Spring 17-7 PH SST 63
24 64 Required Capacity Unit lb/hr
25 Cap Type Screwed 65 Total 1656.125
26 NACE MR0175 / ISO 15156:2015 No 66
27 67 Pressures Unit psig
Accessories

28 68 MAWP Operating 1100


29 69 Set CDTP 1240 1240.00
30 70 Over Pressure 260.4 21%
31 SIZING / SELECTION SUMMARY 71 Constant Superimposed 0
32 Valve Model No. 951201MFA 72 Back Variable Superimposed 0
33 Brand Crosby® 73 Pressure Built-Up 0
34 Area Calculated Selected 0.023 0.084 74 Total 0
35 (in²) Data Set Orifice ASME 5 75 Inlet Loss 0 0%
36 Unit Required lb/hr 1656.125 76 Atmospheric (Barometric) 14.696 psia
37 Flow Rated Actual 6004.871 6672.079 77 Temperatures Unit °F
38 78 Normal System
39 Reaction Force, Open Discharge 68.5 daN 79 Operating Relieving 90 287.442
40 Noise Level (db), Open Discharge 115.3 at 100-ft 80 Design Min Design Max
A
3
Valve Dimensions

B
Tag Notes

in

1.75
C
10.38
Weight
lb

Printed On: 16-sep-2019 PRV²SIZE Software Version pr7_20190226.1 Page : 1


Emerson Automation Solutions and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2019 Emerson Electric Co.
Zeus energy SAC Pressure Relief Valve Calculation Report
jorge.rodriguez@zeusol.com.pe 16-sep-2019

Peru
+51949827888
jorge.rodriguez@zeusol.com.pe
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 VALVE ID 11 CALCULATION NOTES
2 Tag No. QuickCalc001 12
3 Valve Model No. 951201MFA Qty. 1 13
4 SIZING DATA 14
5 Design Code ASME Section VIII Sizing Std. API 520 15
6 Fluid State at Inlet Gas / Vapor 16
7 CALCULATION SUMMARY
8 Required 1656.125 lb/hr 18 Required 0.023 in²
Flow Area
9 Rated 6004.871 lb/hr 19 Selected 0.084 in²
10 Reaction Force, Open Discharge 68.5 daN 20 Noise Level (db), Open Discharge 115.3 at 100 ft
Variable Type Variable Name Symbol Input Value Equation Value
Fluid Properties Molecular Weight M 16.5 16.5
Ratio of Specific Heats k 1.4 1.4
Compressibility Z 0.98 0.98
Process Cond. Required Mass Flow Wreq 1656.125 lb/hr 1656.125 lb/hr
Set Pressure Pset 1240 psig 1240 psig
Over Pressure Pover 260.4 psig 260.4 psig
Inlet Line Loss Ploss 0 psig 0 psig
Back Pressure Pback 0 psig 0 psig
Atmospheric Pressure Patm 14.696 psia 14.696 psia
Relieving Temperature T 287.442 °F 747.112 °R
Distance from Valve (noise) r 100 ft 100 ft
Rupture Disc CCF Kc 1 1
Valve Data Discharge Coefficient (actual) Kd 0.975 0.975
Discharge Coefficient (derated) K 0.878 0.878
Orifice Area A 0.084 in² 0.084 in²
Back Press. Correction Factor Kb 1 1
Outlet Diameter Do 1.05 in 1.05 in
Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio
P1 = Pset + Pover - Ploss + Patm P1 1515.096 psia
P2 = Pback + Patm P2 14.696 psia
PR = P2 / P1 PR 0.01

Calculate Gas Constant C 356.1


C = 520 * {k * [2 / (k + 1)]^[(k + 1) / (k - 1)] }^0.5

Calculate Mass Critical Flow W 6004.871 lb/hr 6004.871 lb/hr


W = A * C * K * P1 * Kb * Kc * [M / (T * Z)]^0.5

Calculate Required Orifice Area Areq 0.023 in² 0.023 in²


Areq = A * Wreq / W

Printed On: 16-sep-2019 PRV²SIZE Software Version pr7_20190226.1 Page : 2


Emerson Automation Solutions and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2019 Emerson Electric Co.
Zeus energy SAC Pressure Relief Valve Calculation Report
jorge.rodriguez@zeusol.com.pe 16-sep-2019

Peru
+51949827888
jorge.rodriguez@zeusol.com.pe
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 VALVE ID 11 CALCULATION NOTES
2 Tag No. QuickCalc001 12
3 Valve Model No. 951201MFA Qty. 1 13
4 SIZING DATA 14
5 Design Code ASME Section VIII Sizing Std. API 520 15
6 Fluid State at Inlet Gas / Vapor 16
7 CALCULATION SUMMARY
8 Required 1656.125 lb/hr 18 Required 0.023 in²
Flow Area
9 Rated 6004.871 lb/hr 19 Selected 0.084 in²
10 Reaction Force, Open Discharge 68.5 daN 20 Noise Level (db), Open Discharge 115.3 at 100 ft
Calculate Mass Critical Flow (for Noise Calc) W 6672.079 lb/hr
W = A * C * Kd * P1 * Kb * Kc * [M / (T * Z)]^0.5

Calculate Noise Level at 100-ft (30-m) L100 115.3 db


L100 = [6.5 * log( 1/PR ) + 51.28] + [10 * log(0.29354 * W * k * T / M)]

Calculate Noise Level at Distance, r Lp 115.3 db


Lp = L100 - 20 * log(r / 100)

Calculate Outlet Static Pressure Po 69.786 psig


Po = [(0.00245 * A * C * Kd * P1 * Kc) / (Do^2 * (k * Z)^0.5)] - Patm

Calculate Reaction Force for Open Discharge Fr 68.5 daN 154 lbf
Ao = (π * Do^2) / 4
Fr = (A * C * Kd * P1 * Kc / 366) * {k / [(k + 1) * Z]}^0.5 + (Ao * Po)

Printed On: 16-sep-2019 PRV²SIZE Software Version pr7_20190226.1 Page : 3


Emerson Automation Solutions and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2019 Emerson Electric Co.
Zeus energy SAC Pressure Relief Valve Dimensional Drawing
jorge.rodriguez@zeusol.com.pe 16-sep-2019

Peru
+51949827888
jorge.rodriguez@zeusol.com.pe
Quote Number: No Prpd. Chk. Appr. Date Revision
Client:
Location: End-User Ref. No.:
Project: Project Ref. No.:
1 Valve ID 7 SELECTION SUMMARY
2 Tag No. QuickCalc001 8 Valve Model No. 951201MFA
3 Service 9 Brand Crosby®
4 PID No. 10 CONNECTIONS
5 Line No. Quantity 11 Inlet 3/4" Thrd. MNPT Standard
6 1 12 Outlet 1" Thrd. FNPT ASME B1.20.1

Wt.= 7 lb = 3.18 kg

A= 3 in = 76.20 mm

B= 1.75 in = 44.45 mm

C= 10.38 in = 263.53 mm

D= =

E= =

F= =

G= =

H= =
Dimension Notes

• Accessories not shown.


• Actual valve may vary from.
Tag Notes

image.

Printed On: 16-sep-2019 PRV²SIZE Software Version pr7_20190226.1 Page : 4


Emerson Automation Solutions and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2019 Emerson Electric Co.
PRV²SIZE Software

Summary Report
Project Information
Company: Project:
Location: Project Ref. No.:

Tag Information
Tag Number: QuickCalc001
Revision: Last Modified: 16/09/2019 11:08:35
Prepared By: Checked By: Approved By:

Specific Tank Data


Sized Using User Defined Flow
Pressure Set Point: 1240 psig
Allowed Over Pressure: 260.4 psig

Valve Sizing Information


Valve Type: 900, 5
Part Number: 951201MFA Quantity to Order: 1
Max Pressure Flow Capacity: 6004.871 lb/hr

Selected Valve Description


Code Category Description
951 Model 951 Fixed Blowdown Relief Valve (-5) 1500 psig Maximum
8 ASME Code Section ASME Section VIII
3STD Valve Service Gas other than "Air"
PR9 Pressure Ranges 500.1 to 1500 PSIG
TR2 Temperature Ranges -20 to 400 Deg. F
1 Body Material Carbon Steel
1 Connection Size 0.75x1
1 Connection Materials Threaded (either MNPT or FNPT)
M Valve Inlet x Outlet Conn. MNPT x FNPT
N Flange Face N/A (NPT or Welded Ends)
T Outlet Port Type NPT or Welded Ends
0 Body/Trim/Spring Matl CS Body / 316 SST Trim / 17-7 PH Spring
3 Seat Material Buna-N Seat 70
A Cap Type Std. Screwed Cap
SGPR1 Soft Good Pressure Range >= 50 psig
N NACE Standard (without NACE)
1 Nameplate Units STANDARD NAME PLATE
1 Code Case No Code Case
BLN Block Body No Block Body
900 Group - MD 900
H Group - SM - 1 H
C Group - SM - 2 C

Printed On: 16-sep-2019 PRV²SIZE Software Version pr7_20190226.1 Page : 5


Emerson Automation Solutions and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license

agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2019 Emerson Electric Co.

Potrebbero piacerti anche