Sei sulla pagina 1di 5

Shangri-La Lift Lobby Ventilation

Total Pressue Loss Calculation 7-Jul-13


Duct Total Section
Friction Velocity Duct
AirFlow Duct Size Velocity Summary of Pressure Pressure Pressure
Duct Fitting Duct Element ASHRAE factor Pressure, Length,
Fitting Loss Los/100ft, Loss, Loss,
Section No and Fitting Fitting No.
Coefficients
Eq
m3/h ʄ W H m/s Pa m Pa/m Pa Pa
Round Ø
1 - Duct 5100 0.005 600 250 414 10.5 - 0.6 - 3.2 1.9
1 Entry 700 600 0.81
- Fittings - 5100 10.5 66.7 0.81 54.1 56.0
2 - Duct - 5100 0.005 600 250 414 10.5 - 0.6 - 3.2 1.9
2 Elbow 90° CR3-1 r/W = 1 H/W = 0.42 θ = 90° K=1 0.25
- Fittings - 5100 10.5 66.7 0.25 16.7 18.6
3 - Duct - 5100 0.005 600 250 414 10.5 - 1.2 - 3.2 3.9
3 Fire Damper 0.86
4 Elbow 90° CR3-15 0.25
- Fittings 5100 10.5 66.7 1.11 74.1 78.0
4 - Duct 5100 0.005 600 250 414 10.5 - 3.7 - 3.2 11.9
5 Tee Main SR5-5 Qs/Qc = 0.95 Cs 0.01
- Fittings - 5100 10.5 66.7 0.01 0.7 12.6
5 - Duct - 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
8 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
10 Diffuser - 122 150 150 0.092
- Fittings - 122 1.6 1.55 0.392 0.6 1.0
6 - Duct - 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
5 Tee Branch SR5-5 Qb/Qc = 0.05 Ab/Ac = 0.2 Cb 8
6 Fire Damper 0.86
7 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
8 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
9 Diffuser - 122 150 150 0.092
- Fittings - 2.4 3.5 10.882 38.0 38.5
7 - Duct - 4857 0.005 600 250 414 10.0 - 3.7 - 2.9 10.8
5 Tee Main SR5-5 Qs/Qc = 0.95 Cs 0.01
- Fittings 4857 10.0 60.5 0.01 0.6 11.4
8 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
14 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
15 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.55 0.392 0.6 1.0
9 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
11 Tee Branch SR5-5 Qb/Qc = 0.05 Ab/Ac = 0.2 Cb 8
12 Fire Damper 0.86
13 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
14 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
16 Diffuser 122 150 150 0.092
- Fittings 2.4 3.5 10.882 38.0 38.5
10 - Duct 4614 0.005 600 250 414 9.5 - 3.7 - 2.6 9.8
11 Tee Main SR5-5 Qs/Qc = 0.95 Cs 0.01
- Fittings 4614 9.5 54.6 0.01 0.5 10.3
11 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
20 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
21 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
12 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
17 Tee Branch SR5-5 Qb/Qc = 0.05 Ab/Ac = 0.2 Cb 8
18 Fire Damper 0.86
19 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
20 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
22 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
13 - Duct 4371 0.005 600 250 414 9.0 - 3.7 - 2.4 8.8
17 Tee Main SR5-5 Qs/Qc = 0.95 Cs 0.01
- Fittings 4371 9.0 49.0 0.01 0.5 9.3
14 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
26 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
27 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
15 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
23 Tee Branch SR5-5 Qb/Qc = 0.06 Ab/Ac = 0.2 Cb 8
24 Fire Damper 0.86
25 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
26 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
28 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
16 - Duct 4129 0.005 600 250 414 8.5 - 3.7 - 2.1 7.8
23 Tee Main SR5-5 Qs/Qc = 0.94 Cs 0.01
- Fittings 4129 8.5 43.7 0.01 0.4 8.3
17 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
32 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
33 Diffuser 122 150 150 0.092
Shangri-La Lift Lobby Ventilation
Total Pressue Loss Calculation 7-Jul-13
Duct Total Section
Friction Velocity Duct
AirFlow Duct Size Velocity Summary of Pressure Pressure Pressure
Duct Fitting Duct Element ASHRAE factor Pressure, Length,
Fitting Loss Los/100ft, Loss, Loss,
Section No and Fitting Fitting No.
Coefficients
Eq
m3/h ʄ W H m/s Pa m Pa/m Pa Pa
Round Ø
- Fittings 122 1.6 1.6 0.392 0.6 1.0
18 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
29 Tee Branch SR5-5 Qb/Qc = 0.06 Ab/Ac = 0.2 Cb 8
30 Fire Damper 0.86
31 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
32 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
34 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
19 - Duct 3886 0.005 600 250 414 8.0 - 3.7 - 1.9 6.9
29 Tee Main SR5-5 Qs/Qc = 0.94 Cs 0.01
- Fittings 3886 8.0 38.7 0.01 0.4 7.3
20 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
38 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
39 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
21 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
35 Tee Branch SR5-5 Qb/Qc = 0.06 Ab/Ac = 0.2 Cb 8
36 Fire Damper 0.86
37 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
38 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
40 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
22 - Duct 3643 0.005 550 250 398 8.1 - 3.7 - 2.0 7.4
35 Tee Main SR5-5 Qs/Qc = 0.94 Cs 0.01
- Fittings 3643 8.1 39.9 0.01 0.4 7.8
23 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
44 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
45 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
24 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
41 Tee Branch SR5-5 Qb/Qc = 0.07 Ab/Ac = 0.2 Cb 8
42 Fire Damper 0.86
43 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
44 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
46 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
25 - Duct 3400 0.005 500 250 381 8.3 - 3.7 - 2.2 8.0
41 Tee Main SR5-5 Qs/Qc = 0.93 Cs 0.01
- Fittings 3400 8.3 41.4 0.01 0.4 8.4
26 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
50 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
51 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
27 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
47 Tee Branch SR5-5 Qb/Qc = 0.07 Ab/Ac = 0.2 Cb 8
48 Fire Damper 0.86
49 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
50 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
52 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
28 - Duct 3157 0.005 500 250 381 7.7 - 3.7 - 1.9 6.9
47 Tee Main SR5-5 Qs/Qc = 0.93 Cs 0.01
- Fittings 3157 7.7 35.7 0.01 0.4 7.3
29 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
56 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
57 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
30 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
53 Tee Branch SR5-5 Qb/Qc = 0.08 Ab/Ac = 0.2 Cb 8
54 Fire Damper 0.86
55 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
56 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
58 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
31 - Duct 2914 0.005 450 250 363 7.8 - 3.7 - 2.0 7.5
53 Tee Main SR5-5 Qs/Qc = 0.92 Cs 0.01
- Fittings 2914 7.8 36.9 0.01 0.4 7.9
32 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
62 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
63 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
33 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
Shangri-La Lift Lobby Ventilation
Total Pressue Loss Calculation 7-Jul-13
Duct Total Section
Friction Velocity Duct
AirFlow Duct Size Velocity Summary of Pressure Pressure Pressure
Duct Fitting Duct Element ASHRAE factor Pressure, Length,
Fitting Loss Los/100ft, Loss, Loss,
Section No and Fitting Fitting No.
Coefficients
Eq
m3/h ʄ W H m/s Pa m Pa/m Pa Pa
Round Ø
59 Tee Branch SR5-5 Qb/Qc = 0.08 Ab/Ac = 0.3 Cb 8
60 Fire Damper 0.86
61 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
62 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
64 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
34 - Duct 2671 0.005 450 250 363 7.2 - 3.7 - 1.7 6.3
59 Tee Main SR5-5 Qs/Qc = 0.92 Cs 0.01
- Fittings 2671 7.2 31.0 0.01 0.3 6.6
35 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
68 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
69 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
36 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
65 Tee Branch SR5-5 Qb/Qc = 0.09 Ab/Ac = 0.3 Cb 8
66 Fire Damper 0.86
67 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
68 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
70 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
37 - Duct 2429 0.005 400 250 344 7.3 - 3.7 - 1.8 6.8
65 Tee Main SR5-5 Qs/Qc = 0.91 Cs 0.01
- Fittings 2429 7.3 31.8 0.01 0.3 7.1
38 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
74 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
75 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
39 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
71 Tee Branch SR5-5 Qb/Qc = 0.10 Ab/Ac = 0.3 Cb 8
72 Fire Damper 0.86
73 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
74 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
76 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
40 - Duct 2186 0.005 400 250 344 6.5 - 3.7 - 1.5 5.5
71 Tee Main SR5-5 Qs/Qc = 0.90 Cs 0.01
- Fittings 2186 6.5 25.7 0.01 0.3 5.8
41 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
80 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
81 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
42 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
77 Tee Branch SR5-5 Qb/Qc = 0.11 Ab/Ac = 0.3 Cb 8
78 Fire Damper 0.86
79 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
80 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
82 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
43 - Duct 1943 0.005 350 250 323 6.6 - 3.7 - 1.6 6.0
77 Tee Main SR5-5 Qs/Qc = 0.89 Cs 0.01
- Fittings 1943 6.6 26.1 0.01 0.3 6.3
44 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
86 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
87 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
45 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
83 Tee Branch SR5-5 Qb/Qc = 0.13 Ab/Ac = 0.3 Cb 8
84 Fire Damper 0.86
85 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
86 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
88 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
46 - Duct 1700 0.005 350 250 323 5.8 - 3.7 - 1.2 4.6
83 Tee Main SR5-5 Qs/Qc = 0.87 Cs 0.01
- Fittings 1700 5.8 20.0 0.01 0.2 4.8
47 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
92 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
93 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
48 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
89 Tee Branch SR5-5 Qb/Qc = 0.14 Ab/Ac = 0.3 Cb 8
90 Fire Damper 0.86
Shangri-La Lift Lobby Ventilation
Total Pressue Loss Calculation 7-Jul-13
Duct Total Section
Friction Velocity Duct
AirFlow Duct Size Velocity Summary of Pressure Pressure Pressure
Duct Fitting Duct Element ASHRAE factor Pressure, Length,
Fitting Loss Los/100ft, Loss, Loss,
Section No and Fitting Fitting No.
Coefficients
Eq
m3/h ʄ W H m/s Pa m Pa/m Pa Pa
Round Ø
91 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
92 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
94 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
49 - Duct 1457 0.005 300 250 300 5.7 - 3.7 - 1.3 4.9
89 Tee Main SR5-5 Qs/Qc = 0.86 Cs 0.01
- Fittings 1457 5.7 19.8 0.01 0.2 5.1
50 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
98 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
99 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
51 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
95 Tee Branch SR5-5 Qb/Qc = 0.17 Ab/Ac = 0.4 Cb 8
96 Fire Damper 0.86
97 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
98 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
100 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
52 - Duct 1214 0.005 300 250 300 4.8 - 3.7 - 0.9 3.4
95 Tee Main SR5-5 Qs/Qc = 0.83 Cs 0.01
- Fittings 1214 4.8 13.7 0.01 0.1 3.5
53 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
104 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
105 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
54 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
101 Tee Branch SR5-5 Qb/Qc = 0.20 Ab/Ac = 0.4 Cb 8
102 Fire Damper 0.86
103 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
104 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
106 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
55 - Duct 971 0.005 300 250 300 3.8 - 3.7 - 0.6 2.2
101 Tee Main SR5-5 Qs/Qc = 0.80 Cs 0.01
- Fittings 971 3.8 8.8 0.01 0.1 2.3
56 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
110 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
111 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
57 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
107 Tee Branch SR5-5 Qb/Qc = 0.25 Ab/Ac = 0.4 Cb 8
108 Fire Damper 0.86
109 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
110 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
112 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
58 - Duct 729 0.005 300 250 300 2.9 - 3.7 - 0.3 1.2
107 Tee Main SR5-5 Qs/Qc = 0.75 Cs 0.01
- Fittings 729 2.9 4.9 0.01 0.0 1.3
59 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
116 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
117 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
60 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
113 Tee Branch SR5-5 Qb/Qc = 0.33 Ab/Ac = 0.4 Cb 8
114 Fire Damper 0.86
115 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
116 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
118 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
61 - Duct 486 0.005 250 250 274 2.3 - 3.7 - 0.2 0.9
113 Tee Main SR5-5 Qs/Qc = 0.67 Cs 0.01
- Fittings 486 2.3 3.2 0.01 0.0 0.9
62 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
122 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
123 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
63 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
119 Tee Branch SR5-5 Qb/Qc = 0.50 Ab/Ac = 0.5 Cb 8
120 Fire Damper 0.86
121 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
122 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
Shangri-La Lift Lobby Ventilation
Total Pressue Loss Calculation 7-Jul-13
Duct Total Section
Friction Velocity Duct
AirFlow Duct Size Velocity Summary of Pressure Pressure Pressure
Duct Fitting Duct Element ASHRAE factor Pressure, Length,
Fitting Loss Los/100ft, Loss, Loss,
Section No and Fitting Fitting No.
Coefficients
Eq
m3/h ʄ W H m/s Pa m Pa/m Pa Pa
Round Ø
124 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 10.882 38.0 38.5
64 - Duct 243 0.005 250 250 274 1.1 - 3.7 - 0.1 0.2
119 Tee Main SR5-5 Qs/Qc = 0.50 Cs 0.01
125 Elbow 90° CR3-15 0.25
- Fittings 243 1.1 0.8 0.26 0.2 0.4
65 - Duct 122 0.005 150 150 164 1.6 - 2.1 - 0.2 0.4
128 Tee Main SR3-13 Qs/Qc = 0.5 As/Ac = 0.75 Cs 0.3
129 Diffuser 122 150 150 0.092
- Fittings 122 1.6 1.6 0.392 0.6 1.0
66 - Duct 243 0.005 200 150 189 2.4 - 1.5 - 0.4 0.6
126 Fire Damper 0.86
127 Elbow 90° CR3-1 r/W = 1 H/W = 0.75 θ = 90° K=1 0.23
128 Tee Branch SR3-13 Qb/Qc = 0.5 Ab/Ac = 0.75 Cb 1.7
130 Diffuser 122 150 150 0.092
- Fittings 243 2.4 3.5 2.882 10.1 10.6

TOTAL PRESSURE LOSSES (PA) 1089.15