OMICRON PTL ABB REG316 XRIO Converter User Manual

OMICRON PTL

XRIO Converter

ABB REG316 6.6a

User Manual

V1.000

© OMICRON electronics GmbH 1/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

Contents
Contents........................................................................................................................................................2
1 General Information ..................................................................................................................................3
2 Quick Start Information ............................................................................................................................3
3 Using the Converter..................................................................................................................................4
4 Required Software Version ......................................................................................................................4
5 Functional Range ......................................................................................................................................4
6 Not Supported Functions .........................................................................................................................6
7 OMICRON Test Strategy ...........................................................................................................................6
8 Converter Structure ..................................................................................................................................6
8.1 REG316 Section...................................................................................................................................6
8.1.1 Relay Parameter Section................................................................................................................6
8.1.2 Additional Information.....................................................................................................................7
8.1.3 RIOPlus (Advanced view)...............................................................................................................8
8.1.3.1 NamePlate...............................................................................................................................8
8.1.3.2 PowerSystemParameters .......................................................................................................8
8.1.3.3 Frequency ...............................................................................................................................8
8.1.3.4 PhaseVoltage ..........................................................................................................................8
8.1.3.5 Power ......................................................................................................................................8
8.1.3.6 Overfluxing (VoltsPerHertz) ....................................................................................................8
8.1.3.7 Generator Differential..............................................................................................................8
8.1.3.8 Loss of Excitation ....................................................................................................................9
8.1.3.9 Stator Overload .......................................................................................................................9
8.1.3.10 Rotor Overload ......................................................................................................................9
8.1.3.11 Pole Slipping .........................................................................................................................9
8.1.3.12 Underimpedance ...................................................................................................................9
8.1.3.13 OvercurrentProtection ...........................................................................................................9
8.1.3.14 NPS OC.................................................................................................................................9
8.1.4 TemplateController (Advanced view) ...........................................................................................10
8.1.4.1 Circuit Breaker.......................................................................................................................10
8.2 RIO .....................................................................................................................................................11
8.2.1 Generator Differential ...................................................................................................................11
8.2.2 Underimpedance ..........................................................................................................................11
8.2.3 Pole Slip........................................................................................................................................11
8.2.4 Loss of Excitation .........................................................................................................................11
8.2.5 Overcurrent...................................................................................................................................12
8.2.6 NPS ..............................................................................................................................................12
8.2.7 Overtemperature Trip ...................................................................................................................12
8.2.8 Overtemperature Warn.................................................................................................................12
8.2.9 Rotor Overload .............................................................................................................................12
8.2.10 Stator Overload ..........................................................................................................................12
8.3 Activating the RIO functions ...............................................................................................................13
8.4 Specific Features................................................................................................................................13
8.4.1 Phase Overcurrent .......................................................................................................................13

© OMICRON electronics GmbH 2/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

1 General Information
The ABB REG316 converter is designed for use with the OMICRON Test Universe 2.22 software for
testing the REG316 generator protection relays. The converter provides all necessary data for testing the
generator protection functions (see chapter 2 ) of the REG316 relays.

Note: This converter is tested with the relay described above. It may work with similar relays, too.

2 Quick Start Information


To work with the ABB REG316 XRIO converter:
1. Start a new OMICRON Control Center (OCC) document or open an existing OCC document.
2. Insert a new test object or open the existing test object.
3. On the File menu, click Import.
4. Browse to the latest OMICRON REG316.xrio file.
5. Click Open.
6. Enter all necessary settings in the Relay Parameter Section, Additional Information –
General/Power System Parameters/Circuit Breaker Information/Test Parameters (see
chapter 8.1.1 and 8.1.2 ).
7. Click OK.

Figure 1: Opening and importing the ABB REG316 XRIO converter

© OMICRON electronics GmbH 3/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

3 Using the Converter


The ABB REG316 XRIO converter can be used as a stand-alone converter or in association with a relay
specific test template, for example with the OMICRON Generator Protection template for the REG316
relays.

In any way the converter is used, follow the quick start instructions and create your test using LinkToXRIO
or start using the relay specific test template (for more information, see the test template documentation).

4 Required Software Version


To use this converter, you must have a valid license for the OMICRON Test Universe 2.22 software.

5 Functional Range
The ABB REG316 XRIO converter implements the following functions:

• 81 Over/Underfrequency protection (6 stages)


• 27/59 Under/Overvoltage protection (6 stages)
• 59 Peak Value Overvoltage (3 stages)
• 24 Inverse time Overfluxing protection
• 24 Definite time Overfluxing protection (4 stages)
• 87 Generator Differential protection
• 49 Rotor Overload protection
• 49 Stator Overload protection
• 46 Inverse time Negative Phase Sequence Overcurrent
• 46 Definite time Negative Phase Sequence Overcurrent (3stages)
• 51 Inverse time Overcurrent protection
• 50 Definite time Overcurrent protection (2 stages)
• 50 Peak value Overcurrent protection
• 50-27 Voltage controlled overcurrent
• 51N Earth Fault Overcurrent
• 32 Power protection (4 stages)
• 40 Loss of Excitation protection (2 elements)
• 78 Pole Slipping protection
• 21 Underimpedance (2 elements)

© OMICRON electronics GmbH 4/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

Some of the functions listed above use the RIO interface of the Test Universe software. Consequently, the
test modules are configured automatically without using LinkToXRIO.
The following functions use the RIO interface:
• 87 Biased Differential protection
• 21 Impedance protection
• 78 Out of Step protection
• 40 Field Failure protection
• 46 Negative sequence
• 50, 50N, 50DT, 51N, 51V, 67N Instantaneous/Definite/Inverse Timed Phase/Neutral Overcurrent
protection
• 49 Thermal overload protection
• 46 NPS Thermal protection

For testing the other functions, you must use LinkToXRIO.

© OMICRON electronics GmbH 5/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

6 Not Supported Functions


The following functions are currently not supported:

• 64S 100% Stator Ground protection-low frequency injection


• Definite time over current function for high-impedance differential protection
• 81R Rate-of-frequency change
• 60 Voltage balance protection
• 87T Transformer differential protection*

* The Transformer differential protection can be tested using the OMICRON RET316 XRIO converer

7 OMICRON Test Strategy


The OMICRON test strategy is described in the OMICRON Protection Test Template (PTT) Generator
documentation. For detailed information, see the PTT Generator documentation.

8 Converter Structure
The converter is divided into two sections: the REG316 section and the RIO section. Both sections consist
of several function blocks. The converter comes up in the standard view; the RIOplus section and the
template controller section can only be seen in the advanced view.

8.1 REG316 Section


The REG316 section is divided into four groups: the Relay Parameter Section, the Additional
Information section, the RIO Plus section and the TemplateController section.

8.1.1 Relay Parameter Section


The Relay Parameter Section includes the parameters which have to be changed by the user. All relay
parameters are included in this section and have to be set to the actual relay values. The parameters are
grouped and named as in the ABB MiCOM S1 Studio software. Each parameter in this block is identified
by a Foreign ID (witch corresponds to the Address in the relay software).

© OMICRON electronics GmbH 6/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

Figure 2: Setting the parameters in the Relay Parameter Section

8.1.2 Additional Information


This block contains additional data for testing the REG316 relay functionality. The block is divided into the
following sections:
 General section – includes detailed information needed for the test report like manufacturer,
device type, substation name etc. This section includes parameters which have to be changed by
the user according to the customer relay type and substation.
 Relay Information section - This block has been added for relay specific parameters such as
tolerances which cannot be set by the user, because they are constant values. All values set in
this block can be found in the "REG316 Generator Protection Relay" manual. Typically, these
blocks do not have to be changed, as they are already set to the values given in the user manual
of the relay.
 Circuit Breaker Information section – includes information which is required for the CB test.
 Test Tolerance section – includes an additional test tolerance to calculate the start and end value
for trip and pickup tests by using the OMICRON TU Ramping module.
 Test Parameters section – includes additional test parameters for testing e.g. test points for the
Inverse Time Overfluxing protection

© OMICRON electronics GmbH 7/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

8.1.3 RIOPlus (Advanced view)


The RIO Plus section contains the interface, which provides the link between the XRIO converter and all
test modules which have no access to RIO functions. All tests using basic test modules like Ramping or
State Sequencer have to be linked to the parameters in the RIO Plus section of the converter.

8.1.3.1 NamePlate
The NamePlate block contains all necessary information to identify the protection device to be tested. This
block contains the relay vendor, serial number, model, the relay location, hardware revision, software
revision and a description.

8.1.3.2 PowerSystemParameters
The number of phases, phase rotation and the nominal frequency are stored in this block.

8.1.3.3 Frequency
This block contains all necessary data for testing the over- and under frequency protection functions. All
stages of the under frequency and over frequency protection function in the relay are modeled as sub
blocks of the FrequencyElements block. Each stage sub block stores information about the pickup value,
operating time and the pickup drop-off ratio.

8.1.3.4 PhaseVoltage
This block contains all necessary data for testing the over- and under voltage protection functions. All
stages of the voltage protection function in the relay are modeled as sub blocks of the VoltageElements
block. Each stage sub block stores information about the pickup value, operating time and the pickup
drop-off ratio.

8.1.3.5 Power
This block contains all necessary data for testing the over- and under power protection function. All stages
of the directional power protection function in the relay are modeled as sub blocks of the PowerElements
protection block. Each stage sub block stores information about the pickup value, operating time and the
pickup drop-off ratio.

8.1.3.6 Overfluxing (VoltsPerHertz)


This block contains all necessary data for testing the Volts per Hertz (Overfluxing) protection. All stages of
the VoltsPerHertz protection function in the relay are modeled as sub blocks of the VoltsPerHerzElements
block. Each stage sub block stores information about the pickup value, operating time, the pickup drop-off
ratio and the operating curve.

8.1.3.7 Generator Differential


This block contains all necessary data for testing the 87G differential and the 64 restricted earth fault
protection function. The following protection function curves are modeled as sub blocks of the
DifferentialElements block:
• biased differential curve,
• high impedance differential curve,
• interturn differential curve,
• low impedance restricted earth fault curve and
• high impedance restricted earth fault curve

Each sub block stores information about the pickup value, operating time, HarmonicRestraintElements
and the operating curve.

© OMICRON electronics GmbH 8/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

8.1.3.8 Loss of Excitation


This block contains all necessary data for testing the Field Failure protection function. The Field Failure
tripping elements are modeled as sub blocks of the UnderExcitationElements block. Each tripping element
sub block (FF1, FF2 and FFAlarm) stores information about:
• the impedances in the BorderElements and GenericShape sub blocks
• the reach and phi values and tolerances in the Reach sub block
• the operating and reset delay time values and tolerances in the OperateDelayTime sub block

8.1.3.9 Stator Overload


This block contains all necessary data for testing the stator overload protection. All stages of the stator
overload protection function in the relay are modeled as sub blocks of the StatorOverloadElements block.
Each sub block stores information about the stator overload characteristics of the relay.

8.1.3.10 Rotor Overload


This block contains all necessary data for testing the stator overload protection. All stages of the stator
overload protection function in the relay are modeled as sub blocks of the RotorOverloadElements block.
Each sub block stores information about the stator overload characteristics of the relay.

8.1.3.11 Pole Slipping


This block contains all necessary data for testing the out of step protection function. The out of step
detection element and the starting element of the out of step protection function in the relay are modeled
as sub blocks of the OutOfStepElements block. The sub block StartingElements block stores information
about voltage pickup element. The sub block ImpedanceZoneElement includes the different pole slip
detection elements and the reset delay time. Each SlipDetectionElement stores information about:
• the impedances in the BorderElements and GenericShape sub blocks
• the reach and phi values and tolerances in the Reach sub block
• the operating and reset delay time values and tolerances in the OperateDelayTime sub blocks

8.1.3.12 Underimpedance
This block contains all necessary data to test the distance protection circle. The nominal values and the
CT / VT settings used by the distance protection functions can be found here. All zones of the distance
protection function in the relay are modeled as sub blocks of the ImpedanceZoneElements block. Each
zone sub block stores information about:
• the grounding factors in the GroundingFactor sub block
• the impedances in the BorderElements and GenericShape sub blocks
• the reach and phi values and tolerances in the Reach sub block
• the operating and reset delay time values and tolerances in the OperateDelayTime sub blocks

8.1.3.13 OvercurrentProtection
This block contains all necessary data for testing the overcurrent protection elements witch use the phase
current transformers. All stages of the overcurrent protection function in the relay are modeled as sub
blocks of the OvercurrentElements block. Each stage sub block stores information about the pickup value,
operating time, pickup drop-off ratio and the curve type. The sub block Voltage Controlledt OC block
contains all necessary data for testing the voltage dependent overcurrent function.

8.1.3.14 NPS OC
This block contains all necessary data for testing the overcurrent protection elements witch use the phase
current transformers. All stages of the NPS overcurrent protection function in the relay are modeled as
sub blocks of the OvercurrentElements block. Each stage sub block stores information about the pickup
value, operating time, pickup drop-off ratio and the curve type.

© OMICRON electronics GmbH 9/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

8.1.4 TemplateController (Advanced view)


The TemplateController block contains special values needed for some tests, especially for tests using
LinkToXRIO. These are mainly calculated values which cannot be calculated in the RIOPlus. These
values are needed for using LinkToXRIO. Furthermore this block contains special functionalities like e.g.
an OC sort function. These values with its special functions are linked to the RIO section and are needed
for the use of the OMICRON test modules.

Figure 3: Structure of the Template Controller

Note: Other values needed for customer designed test can be stored in this block.

8.1.4.1 Circuit Breaker


The circuit breaker block contains all necessary data for testing protection functions together with the
circuit breaker. The modeled parameter is the trip time.

© OMICRON electronics GmbH 10/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

8.2 RIO
The RIO section of the converter contains all specialized RIO functions needed to use the more
specialized test modules (like e.g. Advanced Differential or Overcurrent) provided by the OMICRON Test
Universe software.

Warning: Do not change any values in this section. The values have been set using the relay settings of
the Relay Parameter Section.

Note: Do not activate the former test object view in the advanced mode of the XRIO test object. Changing
parameters in this view could disable formulas in the RIO section.

8.2.1 Generator Differential


The RIO Differential function provides the necessary values for testing the Biased Differential protection
function of the REG316 relay. The RIO differential function contains all values needed for using the
following OMICRON Test Universe modules:
• Diff Configuration
• Diff Characteristic
• Diff Trip Time Characteristic

8.2.2 Underimpedance
This RIO Distance function provides the necessary values for testing the distance protection functions of
the REG316 relay with the Advanced Distance test module. The protection functions supported by this
RIO function include:
• 21 Underimpedance

The following RIO function for testing these distance protection functions is available:
• Distance

8.2.3 Pole Slip


The RIO Pole Slip block provides the necessary values for testing the out of step function of the REG316
relay with the StateSequencer module with distance curve view.

8.2.4 Loss of Excitation


This RIO Field Failure function provides the necessary values for testing the trip time of the field failure
protection function of the REG316 relay with the Advanced Distance test module. The protection functions
supported by this RIO function include:
• 40 Loss of Excitation tripping zones

© OMICRON electronics GmbH 11/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

8.2.5 Overcurrent
This RIO Overcurrent block provides the necessary values for testing the trip times of the Phase
Overcurrent function in forward direction. The protection functions supported by this RIO function include:
• 50,51,Phase Overcurrent

8.2.6 NPS
This RIO NPS block provides the necessary values for testing the trip times of the NPS Overcurrent
function in forward direction. The protection functions supported by this RIO function include:
• 46 NPS definite time Overcurrent
• 46 NPS inverse time Overcurrent

8.2.7 Overtemperature Trip


The RIO Overtemperature functions for testing the trip time of the thermal overload protection function
with Test Universe are implemented in the RIO block of the REG316 XRIO converter:
• Thermal Overload (tripping element)
This module contains the stator overload characteristic curve.

8.2.8 Overtemperature Warn.


The RIO ThermalOverload functions for testing the alarm time of the thermal overload protection function
with Test Universe are implemented in the RIO block of the REG316 XRIO converter:
• Thermal Overload (warning element)

8.2.9 Rotor Overload


The RIO Rotor functions for testing the trip time of the rotor overload protection function with Test
Universe are implemented in the RIO block of the REG316 XRIO converter:

8.2.10 Stator Overload


The RIO Stator functions for testing the trip time of the stator overload protection function with Test
Universe are implemented in the RIO block of the REG316 XRIO converter:

© OMICRON electronics GmbH 12/13


OMICRON PTL ABB REG316 XRIO Converter User Manual

8.3 Activating the RIO functions


The RIO functions have to be set to active manually in each Overcurrent test module if the converter is
used in the stand-alone mode. Activate the RIO function you intend to use in the local hardware
configuration as shown below.

Figure 4: Activating a RIO function

8.4 Specific Features


This section deals with special requirements of some of the converter's functions. Functions not listed
here have no known limitations to their functionalities.

8.4.1 Phase Overcurrent


The parameter Min. Tripping Time is not supported
Not Supported Overcurrent operating curves: RXIDG, LTEF

© OMICRON electronics GmbH 13/13