PROJECT: NCSCM, CHENNAI FIRE ABSTRACT

McD Built Environment Research Laboratory Pvt Ltd

SUMMARY FOR FIRE PROTECTION WORKS FOR NCSCM, CHENNAI

PART DESCRIPTION OF WORK

A FIRE HYDRANT SYSTEM


B FIRE EXTINGUISHERS - FIRST AID
C PUMPS AND ACCESSORIES
D SPRINKLER SYSYTEM
E SIGNAGES
F FIRE DETECTION & ALARM SYSTEM
G TWO WAY TALK BACK SYSTEM

Contractor to provide details of all taxes and duties (Customs, Excsise and
others) considered.

Grand Total

ARCHITECTS: FLYING ELEPHANT STUDIO 64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE ABSTRACT

Environment Research Laboratory Pvt Ltd

R NCSCM, CHENNAI

AMOUNT

ARCHITECTS: FLYING ELEPHANT STUDIO 64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

BILL
Rev, R1
Notes:
1. This cost is inclusive of sales tax (KST &CST), VAT without 'C' form, Works contract tax, Excise duty without CT3 for
applicable taxes, duties, levies, sales tax/VAT/WCT and applicable services & indirect taxes etc
2. This cost is inclusive of all items in note 1 above except Excise duty, customs duty, service tax, sales tax/VAT/WCT f
3. This cost is inclusive of all items in note 1 above including labour charges, levies, and any statutory levies, and serv
4. This cost is inclusive of all items in note 1 above excludes Excise duty, customs duty, service tax and indirect taxes.
5. Please note that contractor needs to maintain separate record for the tax collected from APET and APFD and depos
6. All records of taxes collected from APET and APFD and submitted to the government to be audited by APET & APFD
7. Wherever the quantities are Zero it is Rate Only item. Please quote the rate accordingly

TOTAL
SL NO DESCRIPTION OF WORK QUANTITY

SECTION A - FIRE HYDRANT SYSTEM


1.0 Earth work excavation for trenches upto a maximum depth of 1.0 meters in all types
of soil (width of trench shall be as shown in the detailed drawing) including soft
rock and disintegrated rock for laying fire water supply pipes.The soil shall be
deposited on banks with all lead, lift, including necessary wooden/steel form work
where ever required. Depositing of the surplus earth after backfilling to a initial lead
of 30 meters. Refilling of the pipe line trenches and foundation with selected earth
available from the trench excavation including watering consolidation in layers of
15cm thickness complete as per specifications. The back fill soil shall be graded soil 190
free from stones, pebbles, clay lumps and vegetation etc., complete as per the
specifications, drawings and direction of the engineer.

1.1 Same as above for hard rock including blasting. R.Only


2.0 UNDERGROUND PIPING
Supplying, installing, testing and commissioning of GI 'C' class pipe line confirming
to IS 1239 malleable specials extruded type, such as Reducers, elbows, flanges.
necessary puddle flanges for tank connection, laying of pipes in excavated trenches,
proper supports at bottom. ( Excavation, Foundation & refilling as per item Nos E-01
of Civil works)The pipes shall be anti corrosive wrapping treated. Wrapping
material shall consist of three layers of high molecular high density polyethylene,
three layers of polymerized bitumen and one layer of polyesters (total seven
layers).Wrapping is applied over two coats of anti corrosive rubber modified
bituminous primer of density 0.92 gm/cu cm and viscosity of 500 to 1000 cps
applied at 150 gms per Sq.M. (under ground piping )

2.1 80 mm dia R.Only


2.2 100 mm dia R.Only
2.3 150mm dia 560

ARCHITECTS: FLYING ELEPHANT STUDIO 3+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

3.0 PIPING ABOVE GROUND


Supplying, installing, testing and commissioning of GI pipes of class 'C' to confirm IS
1239, malleable specials extruded type, such as Reducers, elbows, flanges. The pipes
shall be painted with primer & Paint using approved type, Galvanized, supports at
standard spacing, anchor fasteners, bolts, nuts, clamps, rails "U" & threaded bolt,
Including cutting, Welding, fixing in / on walls, ceiling by using the supports etc, as
per drawings. The quoted rate shall also include for chasing / chipping walls, Floors,
making bore holes in walls / floor and making them good with Non shrink filler
material (as approved by Architect )in bore holes / finished in cement mortar etc.
complete. (Above Ground )The quoted rate shall includes of Acrylic Fire stop
Sealant ( as per IS 12458:1988 ) in the opening for pipes passing through fire
compartment walls of RCC floors, masonry walls to provide up to 2 hours fire rating.

3.1 80mm dia 30


3.2 100mm dia 550
3.3 150mm dia R.Only
4.0 Supplying, Installing, testing and commissioning CI butterfly valves as per BS 5155
( PN 16) slim seal standard lever operated type with required flanges, nuts, bolts
etc. complete.
4.1 50 mm dia R.Only
4.2 65 mm dia R.Only
4.3 80 mm dia R.Only
4.4 100 mm dia R.Only
4.5 150 mm dia 9
5.0 Constructing valve chamber made of brick masonry with bricks of class designation
75 in cement mortar 1: 5 (1 cement:5 fine sand) 12 mm thick plastering on internal
face with cement mortar 1:3 (1cement : 3 fine sand) including floating coat of neat
cement and rough plaster on outer face complete with excavation in all kinds of soil,
back filling and cart away surplus earth as directed.RCC top slab with CI medium
duty manhole cover and frame to be not less than 50kg)

5.1 Size: 450 x 450 mm x 450mm(clear dimension) 3


6.0 Supplying, installing ,testing and commissioning of approved make 20mm dia.
automatic air release valve with suitable size of ball valves and unions etc. complete. 6

7.0 Supply, installation, testing & commissioning of R.C.C NP2 class Hume pipe laid to
the required level and grade with collars jointed with in CM1:3. Including encasing
the pipe around a depth of not less than 15cm thick with selected earth (fine
aggregate) availble from the excavation as per specification and direction of the
engineer. The excavated soil shall be deposited on banks with all lead, lift, including
necessary wooden/steel form work where ever required. Depositing of the surplus
earth after backfilling to a initial lead of 30 meters. Refilling of the pipe line trenches
and foundation with selected earth available from the trench excavation including
watering consolidation in layers of 15cm thickness complete as per specifications.
The back fill soil shall be graded soil free from stones, pebbles, clay lumps and
vegetation etc., complete as per the specifications, and drawings.

7.4 250 mm dia 80

ARCHITECTS: FLYING ELEPHANT STUDIO 4+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

8.0 Supply, installation, testing and commissioning of Yard Hydrants comprising of the
following:(a) 80mm dia pipe fitted with single headed 63mm dia landing valve as
per design.(b) Providing 2nos 15mts long 63mm dia CP hose with gun metal male
and emale instantaneous Coupling. (c) 63mm dia branch pipe with gun metal
hexogonal detachable nozzle made of instantaneous coupling.(d) Two keys in recess
type compartment for break glass.(e) 80 mm dia. GI bend.(f) 80 mm dia. GIDF stand
pipe (1 mtr above ground). g) Hose cabinet to accomodate two sets of controled
percolating hose of 15mt length with 1 pair of male and female coupling and 1
branch pipe with nozzle. The cabinet is made of MS sheet of 16 SWG thick, with a
double door , glass font (4mm thick) with hinged door and lock. The cabinet is
painted to scarlet red colour size 30"x10"x24" & wall mounted

The pipe portion below ground shall be treated with anti-corrosive wrapping &
coating of "Pypkote" make as per detailed specification. The quoted rate shall be
inclusive of supply and fixing of hose cabinet with hinged front door and lock made
of 16G MS sheet of suitable size to accommodate the above in MS cabinet with glass 9
door and supporting frame.

9.0 Supplying, installing and commissioning of fire brigade inlet connection conforming
to IS 5290 comprising of 4nos. 63mm dia instantaneous couplings complete, CI
butterfly valve, connected to 150mm dia Fire hydrant ring main and fire hydrant wet 1
riser pipe.

10.0 Supplying, installing and commissioning of fire brigade inlet connection conforming
to IS 5290 comprising of 2nos. 63mm dia instantaneous couplings complete, CI 1
butterfly valve, connected to 150 mm dia for tank filling.
11.0 Supplying, erecting & commissioning Fire Hose cabinet comprising of internal
hydrant.

a) 63mm dia instantaneous pattern single headed oblique hydrant valve with gun
metal cap, GI chain twist release type plug.
b) 2 lengths of 15mtrs. 63mm dia reinforced rubber lined hose with instantaneous
male and female coupling.
c) 1 no gun metal branch pipe with nozzle (63mm x 20mm) with Gunmetal gate/
ball valve (20mm)
d) Two keys in recess type compartment for break glass
e) 19mm dia. Reinforced hose reel 30m length as per IS 5132 fitted with 6.35mm 24
dia nozzle and shut off valve (IS 884 - 1969) . The hose reel shall be recessed swing
type with reel drum.The hose shall be provided with coupling as per detailed
specifications.

f) The Frame shall comprise of 800 mm wide x 150 mm deep x 1200mm high made
of 16 guage 'MS sheet to house the above accessories. The cabinet shall be firmly
fixed to the wall with expansion bolts. The cabinet shall be powder coated both
internally and externally. The door shall be provided with suitable locking
arrangement as per standards.The quote shall include fixing the cabinet to the wall
& making good to the wall

TOTAL FOR FIRE HYDRANT SYSTEM

SECTION B:- FIRE EXTINGUISHERS - FIRST AID

ARCHITECTS: FLYING ELEPHANT STUDIO 5+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Supplying, installing and commissioning of ABC Powder 6 Kg Fire Extinguisher


containing Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure
Gauge, fittted with discharge hose, wall mounting bracket etc., Discharge Time less
than 15 Secs, Controllable discharge mechanism, Range minimum 4 Meters,
applicable on Class A,B,C and electrically started Fire, A Rating- 8A, B Rating 34B,
Can Construction : Deep drawn & Co2 Mig welded, Valve Construction : Forging &
1.0 Machining, Internal Coating of Can : Epoxy Powder coating, External Coating of Can : 43
Epoxy Polyster Powder coating, Sheet metal thickness : 1.60MM, ISI approved as per
IS:15683:2006

Supplying, installing and commissioning of ABC Powder 2 Kg Fire Extinguisher


containing Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure
Gauge, fittted with discharge hose, wall mounting bracket etc., Discharge Time less
than 15 Secs, Controllable discharge mechanism, Range minimum 4 Meters,
applicable on Class A,B,C and electrically started Fire, A Rating- 8A, B Rating 34B,
Can Construction : Deep drawn & Co2 Mig welded, Valve Construction : Forging &
3.0 Machining, Internal Coating of Can : Epoxy Powder coating, External Coating of Can : 6
Epoxy Polyster Powder coating, Sheet metal thickness : 1.60MM, ISI approved as per
IS:15683:2006

Mechanical foam unit of 9 lts. Capacity with water inlet and foam water out let, foam
maker, foam branch pipe etc. complete. Unit shall be fabricated by M.S. sheet with
4.0 FRP lining inside and whole unit mounted with rubber wheels of suitable size and 2
handle for movements.

Fire buckets (FILLED WITH SAND) round bottom type enamel painted, white inside
5.0 & Red out side and Letter "FIRE" in black out side and handle with mounting 16
bracket.
TOTAL FOR FIRE EXTINGUISHERS - FIRST AID

SECTION C:- PUMPS AND ACCESSORIES


1.0 Supply, fixing, testing and commissioning of Electric Motor Driven Booster Pump
complete with Pump Set, Electric Motor, Base Frame and all accessories like
pressure switch, pressure gauges, Butterfly valves, NRV etc.as per NBC. PCC
foundation and foundation bolts as per specifications, the quoted rate inclusive of
Starter, Panel and Cable from Panel to Pump and duty conditions as
follows(1working and 1 Stand By): 5

I) Flow rate: 450 Ltrs/Min


ii) Head: 40 Meter
iii)Type: Single Head
2.0 Supply, fixing, testing and commissioning of Electric Motor Driven Fire pump
complete with pump set, electric motor, Base frame and all accessories like PCC
foundation and foundation bolts as per specifications and duty conditions as
follows:
1
I) Flow rate: 2280 Ltrs/Min
ii) Head: 60 Meter
iii)Type: Single Head
3.0 Supply, fixing, testing and commissioning of Electric Motor Driven Fire pump
complete with pump set, electric motor, Base frame and all accessories like PCC
foundation and foundation bolts as per specifications and duty conditions as
follows:
1
I) Flow rate: 2280 Ltrs/Min

ARCHITECTS: FLYING ELEPHANT STUDIO 6+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ
1

ii) Head: 60 Meter


iii) Type: Single Head
4.0 Supply, fixing, testing and commissioning of Electric Motor Driven Jockey Pump
complete with Pump Set, Electric Motor, Base Frame and all accessories like PCC
foundation and foundation bolts as per specifications and duty conditions as
follows:
1
I) Flow rate: 180 Ltrs/Min
ii) Head: 60 Meter
iii) Type: Single Head
5.0 CONTROL PANEL FOR FIRE PUMPS
Supplying, installing ,testing and commissioning of compartmentalized common
control panel for Electrical motor driven pumps and Diesel engine driven pumps. 1

INCOMING
2 Nos 250 A TPN MCCB (50 KA) with mechanical/ electrical interlocking
1 Sets of 250 Amps. TPN Al. Bus bars with color coded heat shrinkable PVC sleeves.

1 Set of RYB indicating lamps with individual RCBO


1 No 0-250 Amps. Ammeter with selector switch and suitable rated current
transformers.
1 Nos 0-415V, Voltmeter with selector switch.
OUTGOING
FEEDER FOR MAIN PUMPS - 02 Nos
01 No 100 A TP MCCB , DOL Starter with 02 Nos 0-100 Amps. Ammeter with
selector switch and suitable rated current transformers and indicating lamps with
ON / OFF push buttons.
01 No Auto manual selector switch

FEEDER FOR JOCKEY PUMPS - 01 No


01 No 16 A TP MCCB
DOL starter with 1 No 0-25 Amps. Ammeter with selector switch and suitable rated
current transformers. Starter with over load relay, single phase preventor and
indicating lamps with ON / OFF push buttons.
01 No Auto manual selector switch
DIESEL ENGINE PUMP 01 No
a) 20Amps DPMCB - 01 No
b) Battery charger with transformer with rectifier resistance DC ammeter, DC
voltmeter, Trickle / booster / off selector switch - 1 No
c) 1 set of indicating lamps for the following :
1. phase indication
2. battery charger on
3. over load relay
4. DC supply on
5. control switch on
6. Engine fails to start
7. Pump on
8. Low oil pressure
9. High water temperature
10. Auto manual selector switch
d) 1 sets of push button stations for the following :
1. Engine Start

ARCHITECTS: FLYING ELEPHANT STUDIO 7+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

2. Engine Stop
3. Engine - hooter ACK
4. Engine - fault reset
e) Selector switches (Engine control, mode selector)-1 No
f) Auxiliary relays / contactors / timer for sequence operating for starting and
stopping of the engine - 1 set.
g) Hooter for audio alarm (Industrial type) - 1 No
All the components shall be housed in a common cubical made of 16 swg. M.S. sheet
with required stiffeners ( if required). The panel shall be powder coated of approved
color both inside & out side. The panel shall have both bottom & top cable entry
provisions and panel shall be mounted on Pedestal of 300 mm height.

Also panel shall have sufficient (min. 50 Nos) NO/NC contacts for extending the
status( annunciation) of fire pumps to the Fire alarm panel.
6.0 1100 V GRADE POWER / CONTROL CABLES
Supplying, installing ,testing and commissioning of FRLS,PVC outer sheated, steel
armored, aluminum conductor, 1100v grade power cables with glands etc.The
cables shall be laid in tray / Hume pipe / in trenches/on walls/ floor etc. as
required. For cables laid out door the rate shall include earth excavation providing
brick and sand protection, refilling and compacting the earth. The rate shall
excludes tray & Hume pipes. The minimum size of the cables shall as mentioned
below.

3.5C x 50 sq.mm Aluminum cable for main pumps 30


4 C x 16 sq.mm. Aluminum cable for Jockey pumps 30
12 C x 2.5 sq.mm.Aluminum cable Diesel engines 30
4 C x 1.5 sq.mm Copper armored for Instrumentation 30
7.0 CABLE TRAY
Supplying and installing of perforated G.I.sheet cable tray with necessary angle iron
suspension supports, anchor fasteners etc. complete. Maximum height of
suspension shall Not exceed 500 mm.Size of the tray shall be suitable for laying the 30
above mentioned cables.

Supplying, installing ,testing and commissioning of G.I. Earthing strips of 25mm x


6mm thick, strip shall be run on floor / ceiling / walls, from the equipment to the
8.0 nearest Earth pit with necessary accessories as required. ( Earth pit shall be
executed by other agencies).

50mm x 6mm thick -GI strip 36


Supplying, installing ,testing and commissioning of G.I. pipes of class 'C' to confirm
IS 1239, , 6 mm thick, malleable specials extruded type, such as flanges, Butt welded
etc .The pipes shall be painted primer & one coat Paint (with needed touch up),
using approved type supports at standard spacing, anchor fasteners, Galvanized -
bolts, nuts, clamps, rails "U" & threaded bolt, Including cutting, Welding, fixing in /
on walls, ceiling by using the supports etc, as per drawings. The quoted rate shall
9.0 also include for chasing / chipping walls, making bore holes in walls / floor and
making them good with Non shrink filler material / RCC as required and finished in
cement mortar etc. complete.

9.1 200 mm dia 15


9.2 250 mm dia 15

ARCHITECTS: FLYING ELEPHANT STUDIO 8+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

10.0 Supplying, installing, testing and commissioning of GI pipes of class 'C' to confirm IS
1239, malleable specials extruded type, such as Reducers, elbows, flanges. The pipes
shall be painted with primer & Paint using approved type, Galvanized, supports at
standard spacing, anchor fasteners, bolts, nuts, clamps, rails "U" & threaded bolt,
Including cutting, Welding, fixing in / on walls, ceiling by using the supports etc, as
per drawings. The quoted rate shall also include for chasing / chipping walls, Floors,
making bore holes in walls / floor and making them good with Non shrink filler
material (as approved by Architect )in bore holes / finished in cement mortar etc.
complete. (Above Ground )The quoted rate shall includes of Acrylic Fire stop
Sealant ( as per IS 12458:1988 ) in the opening for pipes passing through fire
compartment walls of RCC floors, masonry walls to provide up to 2 hours fire rating.

10.1 80 mm dia 10
10.2 100 mm dia R.Only
10.3 150 mm dia 20
Supply, installation, testing and commissioning approved make ball valves with
11.0 screwed ends confirming to IS 1703 -1977 with unions, etc.including all the
necessary fixing materials complete.
11.1 25 mm dia 2
12.0 Supplying, Installing, testing and commissioning CI butterfly valves as per BS 5155
( PN 16) slim seal standard lever operated /gear operated type with required
flanges, nuts, bolts etc. complete.
12.1 80 mm dia 1
12.2 100 mm dia R.Only
12.3 150 mm dia 2
12.4 200 mm dia - Gear operated type 1
13.0 Supplying, installing ,testing and commissioning of precharged air vessel (size 450
mm dia & 2000 mm height) for pressurization of hydrant / sprinkler system
complete with adequate pressure switches (as per design / requirement) with
valves to operate as per operating sequences including 25 mm dia drain valve, air
release valve with stop cock on the top, 25 mm dia inlet with isolating valve duly 1
painted from inside and outside complete as required. Shall be installed at the -
Plant room

14.0 Supplying, installing and commissioning C.I.flanged "Y" type Strainer with SS mesh,
suitable flanges, nuts, bolts, gaskets etc. complete.
14.1 80mm dia 1
14.2 100mm dia R.Only
14.3 150mm dia 2
15.0 Supplying, installing, testing and commissioning of C.I. Non-return valves as per
IS:5312 (PN 16) swing check type with required flanges, nuts, bolts and gaskets etc.
complete.
15.1 80mm dia 1
15.2 100mm dia R.Only
15.3 150 mm dia 2
Supplying, installing ,testing and commissioning of Pressure switches of suitable
16.0 range for pump sets with Ball valves, Fittings like unions / colors / reducers etc. 1

ARCHITECTS: FLYING ELEPHANT STUDIO 9+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Supplying, installing ,testing and commissioning of Pressure gauges of suitable


range for pump sets and pipe lines for the respective floors near to the flow switches
17.0 with Ball valves, siphon, Fittings like unions / colors / reducers etc. Glycerine filled 1
pressure gauges to use on pump discharge lines.

Supplying, installing ,testing and commissioning of additional length of exhaust


pipes M.S. Medium grade Class B with mineral wool insulation with aluminum sheet
with long radius bend from residential silencer with necessary clamps, fixtures, civil
works and 2 coat painted with heat resistant, rust proof, bituminous paint of
approved colors to full height, in stages of following sizes including suitable rain
18.0 guard for top. Fixing shall be done with proper GI clamps, expansion bolts, support
angle of size 40X25X3 mm, also painted, fixed on the wall / inside the duct etc
.complete, as instructed by the Engineer.

150 mm dia M.S. Medium grade with mineral wool insulation with aluminum
18.1 sheeting. 21
150mm dia M.S. Medium grade shall be laid above ground with structural steel
18.2 supports. 21
Supplying, installing ,testing and commissioning of Flow meter( Electronic type) on
19.0 Test line to measure 175 % of pump flow and suitable to 150 mm dia. 1
TOTAL FOR PUMPS AND ACCESSORIES

SECTION D:- SPRINKLER SYSYTEM


1.0 Supplying, installing, testing and commissioning of GI pipes of class 'C' to confirm IS
1239, malleable specials extruded type, such as Reducers, elbows, flanges. The pipes
shall be painted with primer & Paint using approved type, Galvanized, supports at
standard spacing, anchor fasteners, bolts, nuts, clamps, rails "U" & threaded bolt,
Including cutting, Welding, fixing in / on walls, ceiling by using the supports etc, as
per drawings. The quoted rate shall also include for chasing / chipping walls, Floors,
making bore holes in walls / floor and making them good with Non shrink filler
material (as approved by Architect )in bore holes / finished in cement mortar etc.
complete. (Above Ground )The quoted rate shall includes of Acrylic Fire stop
Sealant ( as per IS 12458:1988 ) in the opening for pipes passing through fire
compartment walls of RCC floors, masonry walls to provide up to 2 hours fire rating.

1.1 25mm dia 100


1.2 32mm dia 20
1.3 40mm dia 20
1.4 50mm dia 10
1.5 65mm dia 10
1.6 80mm dia 30
1.7 100mm dia R.Only
1.8 150mm dia R.Only
1.9 200mm dia R.Only

ARCHITECTS: FLYING ELEPHANT STUDIO 10+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Supplying, installing, testing and commissioning of GI 'C' class pipe line confirming
to IS 1239 malleable specials extruded type, such as Reducers, elbows, flanges.
necessary puddle flanges for tank connection, laying of pipes in excavated trenches,
proper supports at bottom. ( Excavation, Foundation & refilling as per item Nos E-01
of Civil works)The pipes shall be anti corrosive wrapping treated. Wrapping
material shall consist of three layers of high molecular high density polyethylene,
three layers of polymerized bitumen and one layer of polyesters (total seven
2.0 layers).Wrapping is applied over two coats of anti corrosive rubber modified
bituminous primer of density 0.92 gm/cu cm and viscosity of 500 to 1000 cps
applied at 150 gms per Sq.M. (under ground piping )

2.1 150mm Nominal dia 20


3.0 Supplying, installing, testing and commissioning of Gun metal chrome finished Ball
valves with fittings of screwed end type.
3.1 25 mm dia (screwed ends) R.Only
4.0 Supplying, Installing, testing and commissioning of CI butterfly valves ( PN 16) as
per BS 5155 slim seal standard lever operated type with required flanges, nuts,
bolts etc. complete.
4.1 40mm dia R.Only
4.2 50mm dia 2
4.3 65mm dia 3
4.4 80mm dia R.Only
4.5 100mm dia R.Only
4.6 150mm dia R.Only
Supplying, installing, testing and commissioning of standard response Sprinkler
5.0 quartzoid bulb type with 15mm screwed end connection of 68 deg. C. temperature
rating,K 80 and orifice shall Not be less than 3 mm.
5.1 Pendent sprinkler 53
5.2 Side Wall sprinkler R.Only
5.3 Upright sprinkler R.Only
7.0 Supply of spare sprinklers as per the specifications mentioned in item no.5.0 above
10
9.0 Supplying, installing, testing and commissioning flow switch installed on the
sprinkler main distribution line capable of sending impulses to the Monitor Module

9.3 80mm dia 1


9.4 100mm dia 1
9.5 150mm dia R.Only
10.0 Supplying, laying, testing and commissioning approved make 2C x 2.5 Sq.mm. PVC
insulated, armoured cable PVC sheathed, confirming to IS 1554 etc., for
annunciation panel of flow switch on the sprinkler line capable of sending impulses 250
to the control room with accessories.

TOTAL FOR SPRINKLER SYSYTEM

SECTION E:- SIGNAGES

ARCHITECTS: FLYING ELEPHANT STUDIO 11+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

1.0 Supply, installation, testing and commissioning of in position the signages of "FIRE
BOARDS APPROVED BY TAMIL NADU STATE FIRE SERVICE - SIZE 2FT X 4FT MADE
OUT OF PVC RIGID SHEET 1MM THICK WITH COMPUTER CUT PVC NON-
REFLECTIVE SELF ADHESIVE IMPORTED VINYL PAINTED ON THE FRONT OF PVC
RIGID SHEET COMPLETE WITH WALL MOUNTING ARRANGEMENTS WITH MIRROR
SCREWS".

2.0 Supplying and installing of in position the following type of sign boards made out of
3mm thick "Opaque" PVC foam board with computer cut, PVC Non-reflective self
adhesive vinyle painted foam board, complete with mirror fasteners.

a. Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED
OTHERWISE" of 1.5cm height letters in red with white back ground. The size of the
board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished 28
floor near Manual call points.

b. Floor identification signage ( i.e., GROUND FLOOR …etc.) at each stair enclosure on
every floor, indicating the floor number in words, lettering size shall be 7.5 cm with
contrasting color from back ground. Size shall be 15cm x 60cm. 28

c Fire Exit signage at each stair on every floor, indicating the direction of fire exit,
lettering size shall be 7.5 cm with contrasting color from back ground. Size shall be 200
15cm x 60cm.
3.0 Supplying and installing of in position the signages " FIRE ORDER" it should contain
the following matter on 3mm thick "Opaque" PVC foam board of computerized cut,
PVC Non-reflective self adhesive vinyle painted foam board of 3' x 4'. 5

a A) alert the security at security room by actuating manual call point located at
strategic locations.
B) evacuate the occupants by using fire exits and emergency exits only and assemble
at various assembly poits.
C) if possible try to extinguish the fire by using nearest / suitable portable
extinguisher or water from nearest wet riser.
D) be calm and do not give any room from panic, walk, do not run.
E) if you encounter serious difficulty in evacuation, flat and try to attract attention of
rescue team.
b Action by security/reception upon receipt of information through fire alarm or fire
detectors or by using public address system. 5
A) alert the occupants by using public address system.
B) inform fire control through any one of the following phone numbers: 101 /(local
numbers)
C) refer evacuation plan from evacuating standard people.
D) guide the fire force, on their arrival to the seat of fire.
E) in case of the casualties, call ambulance by dialing number……..
Phone : -----------------------
Fax : ----------------------------
TOTAL FOR SIGNAGES
TOTAL FOR SIGNAGES

SECTION F: FIRE DETECTION & ALARM SYSTEM


1.0 Smoke detectors

ARCHITECTS: FLYING ELEPHANT STUDIO 12+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Supply and installation of Analog addressable optic smoke detectors(multi sensor)


suitable for detecting a wide range of smoke from slow smouldering and fast
flamming fire.The detector shall have following features and also including supply of
all fixing materials complete as required.

I. Solid state addressing arrangement in combination with a hand held progarmmer


to configure the sensor address. 332
ii. Electronics free mounting base.
iii. Twin alarm LEDs for 360 deg. Viewing and shall have blinking LED facility.
iv. Photo electric sensor shall have a removable chamber for ease of cleaning or
replacement.
v. Simple anti-tamper locking mechanism.
vi.Automatic compensation for smoke sensor contamination.
vii. Shall have a built in test facility which allows the alarm threshold levels to
compensate for contamination and shall have a maintenance alarm display when
threshold can no longer be adjusted.
viii. Operating temperature-- 10 deg C to 50 deg C and operating RH at 40deg C --
95% RH.
2.0 Duct detectors
supply and installation of optical type duct detectors same as item No.1.0 above but
inside a air sampling chamber to be located inside the AC return air duct including 2
supply of all fixing materials
3.0 Heat detectors
Supply and installation of analog addressable heat detectors.The detectors shall
have the following features: 20
4.0 Visual indicators
Supply and installation of visual type response indicators with LED indicating lamp,
housed in suitable MS enclosure with acrylic cover fixed in flush with wall to
operate in conjunction with smoke/Heat detectors operating on 24 VDC installed
above the false ceiling or below the false floor, complete with all accessories and 1
fixing materials as required and as directed by Engineer-in-charge.

5.0 Short circuit isolator


Supply and installation of short circuit isolator,analog addressable type for isolating
analog devices from short circuit,fault isolating module shall have LED that latchesto
indicate a short on the loop.This device shall automatically determining an return to
normalcondition of the loop restore the isolated segments 14

6.0 Electronic Hooters


Supplying, installing ,testing and commissioning of Hooter Cum Strobe at 85 dBA @
3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication. With
Control Module. The Hooter cum Strobe with Control Module shall be flush or
surface mountable type with all accessories etc., complete and as per technical 28
specification. The devices shall be of EN and LPCP listed

7.0 Manual call station


Supplying, installing ,testing and commissioning of break glass type Manual call
point . The Manual call point with monitor module shall be single stage type with all
accessories and suitable sinages complete., the Manual call point shall be as per 28
technical specification. and shall be of EN and LPCP listed.

ARCHITECTS: FLYING ELEPHANT STUDIO 13+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Supplying, installing ,testing and commissioning of Addressable Monitor Module


complete with all accessories. The two wire monitor module shall mount in a 101.6
mm square, 54 mm deep electrical box or with an optional surface back box. The
8.0 monitor module shall be as per technical specification and shall be of EN and LPCP 8
listed.

Supply, installing testing and commissioning of Addressable Control Module. It shall


be provided to supervise and control the operation of one conventional device of
compatible, 24 VDC powered, polarized audio/visual Notification layout. The
9.0 Addressable control module shall be as per technical specification. And shall be of 42
EN and LPCP listed.

Supplying, installing ,testing and commissioning of Control relay Module for Lift
10.0 Machines. The module shall be as per technical specification. The devices shall be of 5
EN and LPCP listed
12.0 Fire alarm control panel

Supply, installation,testing and commissioning of micro processor


based,digital,distributed processing real time,multi tasking and multi - user type 4
loops as per Analogue addressable type fire alarm control panel (FACP) and control 1
panel shall have the following features including supply of all fixing materials
interconnections earthing complete as required.

i. FACP shall be suitable for operating on 230V 50HZ AC supply and smoke detectors
shall be powered using FACP based smoke detection circuits.Devices shall receive
power and communication from the same pair of conductors.

ii. FACP shall provide for resetting smoke detectors fault isolation and sensor loop
operation.
iii. FACP shall be suitable for mixing different fire devices and beam smoke detectors
with in the same loop to optimize field wiring.
iv. FACP shall have alarm indication of individual sensors detector trouble alarm
indication for dust accumulation.The panel shall check detectors once in every 24
hours for contamination for this purpose.
v. The FACP shall regularly supervise all the sensors and devices on the loop and
initiate fire or trouble alarm whenever required.
vi.FACP shall have 2 wire circuit to connect 125 addressable devices & 125 detectors
per loop.
vii. FACP shall be with repeater interface and suitable 24V battery with built in
software and 2x40 character alphanumeric LCD display and necessary front panel
control keys.FACP shall display the date time and description for Anologue sensors
to indicate alarm and trouble situations.
viii. FACP switch shall allow authorised personal to accomplish the following:-
a) Initiate general alarm condition
b) Silence the local audible
c) Silence the alarm signals
d) Reset all zones /points
ix.FACP shall have walk-test facility
x. Shall have facility for programming from the key board or utililsing PC set up
software via lap top/desk top computer.
xi. Shall have memory data for panel configuration and operation reside in non -
volatile memory(EPROM)

xii. FACP shall have facility for speech processor (to record pre-recorded message of
20 S) and also have auto dialer facility.(Can dial upto 8 different lines)

ARCHITECTS: FLYING ELEPHANT STUDIO 14+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

xiii. All addressable units shall be connected to the FACP through the loop cards and
shall be addressed through individualized numbers.The FACP shall be able to obtain
Analogue value for all detectors in the circuit through a pulsed digitized current
data.The FACP shall be able to analyze all Analogue inputs from all addressable units
and through its own software and ambient level screening.The FACP shall be able to
identify fire,possible fire or fault conditions.The unit supervision shall be dynamic
and continuos.

xiv. The FACP shall itself have all loop cards in it.No isolated mother board or
transponder shall be considered
xv. Short / open circuit units shall also be reported at the FACP in such cases,the
system through the use of fault isolators shall be able to isolate that segment
between the two fault isolators.The missing detector /device shall also be reported
to the FACP with identification of the location.

xvi. The FACP shall have the facility to set smoke sensor sensitivity remotely to
either high sensitivity manually or on a pre - programmed sequence(ie Day/Night)
period.

xvii. When an alarm condition is sensed at the FACP from smoke or heat detector ,a
delay time /alarm verification period shall be started. If the sensor is still in alarm
after the delay time expired an alarm condition is reported.The delay time shall be
adjusted from 0 to 990 seconds.

xviii. The FACP shall have either and in-built or external printer coupler to the FACP
which shall log all events with time.The printout shall clearly indicate the event
-Fire/pre alarm fault etc.with uint address and time.

xix. The FACP shall also be able to discriminate between false alarms and fire
conditions,as well as priority selection of alarm in case alarm activates in two or
more remotely located units simultaneously.In such cases the manual call stations
shall have the highest priority.

xx. The FACP also be able to actuate switches automatically in case of fire conditions
that of AHUs and power supply or other system such as piped pressurised gas
supply.
xxi.The system shall be fail safe and adequate safe gaurds should be under taken
that in the event of a failure of a part of the system it shall not handicap the
complete system.The loop cards shall be of modular construction.

xxii. The FACP shall have its own battery backup of a minium 48 hours in normal run
and half an hour in the alarm condition.The back up time calculation shall be done
as per TAC standards.The battery shall be 2 x 12V (24V)DC and of sealed
maintenance free type,housed inside the FACP.

xxiii. It shall be able to with stand the temperature varition from 0 deg.C to 50 deg
C.and further RH (non condensing type )up to 95% shall not hamper its
performance.The voltage rating shall be from 17V DC to 31V DC though the voltage
may change depending upon the working voltage of proprietary FACP

xxivThe FACP shall be totally enclosed ,dust and vermin proof type made of
minimum 16 SWG dust inhibited sheet with oven finish.The FACP shall be
completely solid stage design
xxv.The logic circuitry shall be based on high noise immunity solid state hardware
employing modular construction. Logic cards shall be of epoxy fiber glass
construction.
xxvi. The FACP shall have EN 54/UL/FM approval.
xxvii. The panel shall have extra loop card to serve as stand by in case of burntout or
malfunctioning of any operating loop cards.

ARCHITECTS: FLYING ELEPHANT STUDIO 15+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

xxviii. The FACP shall be capable of being networked (future expansion) with other
similar FACP located at different part of the premises through single RS 485 bus.

xxix.The FACP shall have provision for interfacing with the public address system
and BMS(RS 485)
13.0 80 Character Liquid Crystal Display Repeater Panel which mimics all display
information from the host panel and control switches for System Acknowledge,
Signal Silence, Drill and Reset with enable key. The Repeater Panel shall have system
LEDs for Power, Alarm, Trouble, Supervisory and Alarm Silenced. It should display
device type identifiers, individual point alarm, trouble or supervisory, zone and
custom alpha labels. It should have time and date display field. The panel shall have 1
provision to be powered by 24 VDC from the host FACP or from remote 24 VDC
power source. It should be capable of being remotely located up to 6000 from the
host control panel.

14.0 Supply and Wiring


14.1 Supply and wiring with 4C x 1.5 sq.mm FR twisted pair shielded,1.1KV grade PVC
insulated armoured copper conductor cable, PVC overall sheathed cable in already
laid conduit with interconnections complete as required and as directed by EIC. R.Only

14.2 Supply and wiring with 2C x 1.5 sq.mm FR twisted pair shielded,1.1KV grade PVC
insulated unarmoured copper conductor cable, PVC overall sheathed cable in
already laid conduit with interconnections complete as required and as directed by 2900
EIC.(For fire detector )

15.0 Conduit
Supply and embedment of 25mm dia HGMS conduit concealed in wall / floor /
ceiling including supply and drawing of 12 SWG GIwire as fish wire including supply 2900
of all fixing materials complete as required and as directed by EIC.
TOTAL FOR FIRE ALARM SYSTEM

SECTION G: TWO WAY TALK BACK SYSTEM


1.0 Speakers
Supplying, installing, testing and commissioning 6W wall mounted type speakers
a with talk back facility(Two way), in CRCA sheet fabricated housing, complete. 28

3.0 Amplifier
Supply,fixing,testing and commissioning of 240 watt amplifier with accessories etc. 1
complete
4.0 P A Console
Supply,fixing,testing and commissioning 20 zone control console ,goose neck 1
microphone with call station keypad and other accessories. complete
5.0 Supply and Wiring
Supply and wiring with 4C x 1.5 sq.mm FR twisted pair shielded,1.1KV grade PVC
insulated unarmoured copper conductor cable, PVC overall sheathed cable in 1200
already laid conduit with interconnections complete as required and as directed by
EIC for public address system)
6.0 Conduit
Supply and embedment of 25mm dia HGMS conduit concealed in wall / floor /
ceiling including supply and drawing of 12 SWG GIwire as fish wire including supply 1200
of all fixing materials complete as required and as directed by EIC.
TOTAL FOR TWO WAY TALK BACK SYSTEM

ARCHITECTS: FLYING ELEPHANT STUDIO 16+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

BILL OF QUANTITIES FOR FIRE PROTECTION WORKS FOR PROPOSED NCS

e duty without CT3 form, Shipment charges, customs clearing & forwarding, transportation Charges, entry tax, education cess an

x, sales tax/VAT/WCT full and applicable service tax and indirect taxes.
tutory levies, and service tax component excluding Excise duty, customs duty, and sales tax/VAT/WCT full.
ax and indirect taxes.
T and APFD and deposited back to the government and tax return to be file separately to APET and APFD.
udited by APET & APFD team or appointed consultants on monthly or quarterly basis and contractor needs to submit the clearan

UNI Supply
T

Sales Customs
Basic rate Tax/VAT/WC Excise Duty Total Rate
Duty Supply
* see note 4 T full considere
considered * see note 2
considered d

Cum

Cum

Rmts
Rmts
Rmts

ARCHITECTS: FLYING ELEPHANT STUDIO 17+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Rmts
Rmts
Rmts

Nos
Nos
Nos
Nos
Nos

Each

Nos

Rmts

ARCHITECTS: FLYING ELEPHANT STUDIO 18+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Nos

Nos.

Nos.

Nos

ARCHITECTS: FLYING ELEPHANT STUDIO 19+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Nos

Nos

Nos

Nos

Nos

Set

Set

ARCHITECTS: FLYING ELEPHANT STUDIO 20+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ
Set

Set

Nos

ARCHITECTS: FLYING ELEPHANT STUDIO 21+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Rmt
Rmt
Rmt
Rmt

Rmt

Rmt

Rmts
Rmts

ARCHITECTS: FLYING ELEPHANT STUDIO 22+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Rmts
Rmts
Rmts

Nos.
Nos.
Nos.
Nos.

Nos.

Nos.
Nos.
Nos.

Nos.
Nos.
Nos.

each

ARCHITECTS: FLYING ELEPHANT STUDIO 23+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

each

Rmts

Rmts

Rmts

Rmts
Rmts
Rmts
Rmts
Rmts
Rmts
Rmts
Rmts
Rmts

ARCHITECTS: FLYING ELEPHANT STUDIO 24+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Rmts

Nos

Nos
Nos
Nos
Nos
Nos
Nos

Nos
Nos
Nos
Nos

Nos
Nos
Nos

Rmts

ARCHITECTS: FLYING ELEPHANT STUDIO 25+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

each

each

each

each

ARCHITECTS: FLYING ELEPHANT STUDIO 26+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Each

Each

Each

Each

Each

Each

Each

ARCHITECTS: FLYING ELEPHANT STUDIO 27+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Each

Each

Each

set

ARCHITECTS: FLYING ELEPHANT STUDIO 28+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 29+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

Each

Mts

Mts

Mts

each

each

each

Rmts

Rmts

ARCHITECTS: FLYING ELEPHANT STUDIO 30+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

RKS FOR PROPOSED NCSCM, CHENNAI

Charges, entry tax, education cess and other cesses, insurance, ESI, PF, Royalties, Octroi, loading & unloading charges, wastages,

/VAT/WCT full.

PET and APFD.


ontractor needs to submit the clearance certificate for compliance along with each invoices

Installation ** see note 2

Total Rate Supply &


Sales Total Rate Installation
Basic Rate Tax/VAT/W Service Tax Installatio * See Note 1
* see note CT n
considered
4 full * see note
considered 3

ARCHITECTS: FLYING ELEPHANT STUDIO 31+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 32+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 33+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 34+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 35+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 36+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 37+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 38+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 39+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 40+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 41+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 42+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 43+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 44+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ading & unloading charges, wastages, losses, damages and all other

Total Amount Supply and


Supply Installation Installation
* see note 4 * see note 4 * see note 1

ARCHITECTS: FLYING ELEPHANT STUDIO 45+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 46+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 47+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 48+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 49+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 50+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 51+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 52+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 53+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 54+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 55+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 56+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 57+64 CONSULTANTS: McD BERL


PROJECT: NCSCM, CHENNAI FIRE BOQ

ARCHITECTS: FLYING ELEPHANT STUDIO 58+64 CONSULTANTS: McD BERL

Potrebbero piacerti anche