Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
AquaStream™ Air-Cooled
Liquid Chillers
Model CGAM
20—120 Tons - Made in USA
CG-PRC017-EN 3
Features and Benefits
Reliability
• Years of laboratory testing including running the chiller at extreme operating conditions have
resulted in optimized compressor and chiller systems reliability by confirming a robust design
and verifying quality each step of the way.
• Direct-drive, low-speed scroll compressors with fewer moving parts provide maximum
efficiency, high reliability, and low maintenance requirements. Suction gas-cooled motor stays
at a uniformly low temperature for long motor life.
• The third generation microprocessor control system provides improved control capabilities
with Adaptive Control™ to keep the unit operating even in adverse conditions. Advanced
microelectronics protect both the compressor and the motor from typical electrical fault
conditions like thermal overload and phase rotation.
• Standard factory-installed water strainer helps prevent system debris from affecting unit flow
or heat transfer.
• Flow switch is factory-installed at the optimum location in the piping for reduced chiller
installation cost and superior flow sensing, reducing the potential for nuisance trips.
• Exceptionally rigid condenser coil structure is manufactured with hairpin tubes which halves
the number of braze joints significantly reducing the potential for leaks.
• Innovative condenser pressure integrated fan control algorithms and optional variable
frequency drive on circuits’ lead fans provides more reliable operation at extreme temperature
conditions.
Application Versatility
• Industrial/low temperature process cooling - Excellent operating temperature range and
precise control capabilities enable tight control.
• Ice/thermal storage - Utilities and owners benefit from reduced cooling energy cost. The
AquaStream chiller’s dual setpoint control and industry leading ice energy storage efficiency
assures reliable operation and superior system efficiency Trane’s partnership with CALMAC,
brings a proven track record of successful installations across many markets; from churches
and schools to sky scrapers and office buildings.
• Partial heat recovery - An optional factory-installed heat exchanger provides hot water for many
needs; water preheat and reheat for enhanced system humidity control are just two. This option
reduces operating costs associated with boilers/hot water heaters.
4 CG-PRC017-EN
Features and Benefits
Precision Control
• Microprocessor-based Trane CH530 controls monitor and maintain optimal operation of the
chiller and its associated sensors, actuators, relays, and switches, all of which are factory-
installed, powered up and tested prior to shipping.
• Adaptive Control maintains chiller operation under adverse conditions, when many other
chillers might simply shut down. Operating conditions that are compensated for include high
condensing pressure and low suction pressure.
• AquaStream advanced microprocessor controls enable variable primary flow applications
providing chilled water temperature control accuracy of ±2°F (1.1°C) for flow changes up to 10
percent per minute, plus handling of flow changes up to 30 percent per minute with continuous
operation.
• Easy-to-use operator interface displays all operating and safety messages, with complete
diagnostics information, on a highly readable panel with a scrolling touch-screen display.
Status and diagnostic messages are in plain language - no codes to interpret - and are available
in 20 languages.
Improved Serviceability
• All major serviceable components are close to the edge. Service shutoff valves and water
strainer are conveniently located to enable easy service.
• Water piping connections are factory piped to the edge of the unit to make installation safer and
faster.
• Electronic expansion valve designed so controls can be removed and serviced without
refrigerant handling.
• The optional pump package is designed to be serviced in place. The unit structure includes a
rigging point for pump servicing, making inspection, cleaning and pump seal changes easier
• High pressure transducer and temperature sensors mountings enable troubleshooting and
replacement without removing refrigerant charge, greatly improving serviceability over the life
of the unit.
• Dead front panel construction provides for enhanced service technician safety.
CG-PRC017-EN 5
Features and Benefits
6 CG-PRC017-EN
Application Considerations
Certain application constraints should be considered when sizing, selecting and installing Trane
AquaStream chillers. Unit and system reliability is often dependent upon proper and complete
compliance with these considerations. Where the application varies from the guidelines presented,
it should be reviewed with your local Trane account manager.
Note: The terms water and solution are used interchangeably in the following paragraphs.
Unit Sizing
Intentionally over-sizing a unit to assure adequate capacity is not recommended. Erratic system
operation and excessive compressor cycling are often a direct result of an oversized chiller. In
addition, an oversized unit is usually more expensive to purchase, install, and operate. If over sizing
is desired consider using two smaller units.
Water Treatment
The use of untreated or improperly treated water in chillers may result in scaling, erosion,
corrosion, and algae or slime buildup. This will adversely affect heat transfer between the water
and system components. Proper water treatment must be determined locally and depends on the
type of system and local water characteristics.
Neither salt nor brackish water is recommend for use in Trane air-cooled AquaStream chillers. Use
of either will lead to a shortened life. Trane encourages the employment of a qualified water
treatment specialist, familiar with local water conditions, to assist in the establishment of a proper
water treatment program.
Foreign matter in the chilled water system can also increase pressure drop and, consequently,
reduce water flow. For this reason it is important to thoroughly flush all water piping to the unit
before making the final piping connections to the unit.
Ambient Limitations
Trane AquaStream chillers are designed for year-round operation over a range of ambient
temperatures. The air-cooled model CGAM chiller will operate in ambient temperatures of 32°F to
125°F (0°C to 52°C). Selecting the wide ambient option will allow the chiller to operate down to 0°F
(-18°C). Without the wide ambient option freeze damage can occur with operation below 32°F
(52°C).
The minimum ambient temperatures are based on still conditions (winds not exceeding five mph).
Greater wind velocities will result in a drop in head pressure, therefore increasing the minimum
starting and operating ambient temperature. The Adaptive Control™ microprocessor will attempt
to keep the chiller on-line when high or low ambient conditions exist, making every effort to avoid
nuisance trip-outs and provide the maximum allowable tonnage.
CG-PRC017-EN 7
Application Considerations
50°F (10°C)
112 gpm (7 l/s)
50°F (10°C)
32 gpm (2 l/s)
57°F (14°C)
112 gpm (7 l/s)
60°F (16°C)
80 gpm (5 l/s)
Flow Proving
Trane provides a factory-installed water flow switch monitored by CH530 which protects the chiller
from operating in loss of flow conditions.
8 CG-PRC017-EN
Application Considerations
Water Temperature
Leaving Water Temperature Limits
Trane AquaStream chillers have three distinct leaving water categories:
• standard, with a leaving solution range of 42 to 65°F (5.5 to 18°C)
• low temperature process cooling, with leaving solution range of 10 to 65°F (-12.2 to 18°C)
• ice-making, with leaving solution range of 20 to 65°F (-7 to 18°C)
Since leaving solution temperature below 42°F (5.5°C) results in suction temperature at or below
the freezing point of water, a glycol solution is required for all low temperature and ice-making
machines. Ice making control includes dual setpoint controls and safeties for ice making and
standard cooling capabilities. Consult your local Trane account manager for applications or
selections involving low temperature or ice making machines.
The maximum water temperature that can be circulated through the CGAM evaporator when the
unit is not operating is 125°F (51.7°C). Evaporator damage may result above this temperature.
68°F (20°C)
178 gpm 178 gpm L
(11.2 l/s) (11.2 l/s)
238 gpm (15 l/s)
P
95°F (35°C) 95°F (35°C)
60 gpm (3.8 l/s) 238 gpm (15 l/s)
CG-PRC017-EN 9
Application Considerations
10 CG-PRC017-EN
Application Considerations
CG-PRC017-EN 11
Application Considerations
Unit Placement
Setting The Unit
A base or foundation is not required if the selected unit location is level and strong enough to
support the unit’s operating weight (see “Weights” section of this catalog).
For a detailed discussion of base and foundation construction, refer to the sound engineering
bulletin or the unit IOM. Manuals are available through the local Trane office.
HVAC equipment must be located to minimize sound and vibration transmission to the occupied
spaces of the building structure it serves. If the equipment must be located in close proximity to
a building, it should be placed next to an unoccupied space such as a storage room, mechanical
room, etc. It is not recommended to locate the equipment near occupied, sound sensitive areas of
the building or near windows. Locating the equipment away from structures will also prevent
sound reflection, which can increase sound levels at property lines or other sensitive points.
Elastomeric
isolators
Elastomeric
isolators
Flexible electrical
conduit
Concrete base
For maximum isolation effect, water lines and electrical conduit should also be isolated. Wall
sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through
water piping. To reduce the sound transmitted through electrical conduit, use flexible electrical
conduit.
Local codes on sound emissions should always be considered. Since the environment in which a
sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound
power levels for chillers are available on request.
12 CG-PRC017-EN
Application Considerations
Servicing
Adequate clearance for evaporator and compressor servicing should be provided. Recommended
minimum space envelopes for servicing are located in the dimensional data section and can serve
as a guideline for providing adequate clearance. The minimum space envelopes also allow for
control panel door swing and routine maintenance requirements. Local code requirements may
take precedence.
Unit Location
General
Unobstructed flow of condenser air is essential to maintain chiller capacity and operating
efficiency. When determining unit placement, careful consideration must be given to assure a
sufficient flow of air across the condenser heat transfer surface. Two detrimental conditions are
possible and must be avoided: warm air recirculation and coil starvation. Air recirculation occurs
when discharge air from the condenser fans is recycled back to the condenser coil inlet. Coil
starvation occurs when free airflow to the condenser is restricted.
Condenser coils and fan discharge must be kept free of snow or other obstructions to permit
adequate airflow for satisfactory unit operation. Debris, trash, supplies, etc., should not be allowed
to accumulate in the vicinity of the air-cooled chiller. Supply air movement may draw debris into
the condenser coil, blocking spaces between coil fins and causing coil starvation.
Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity
because of the higher head pressures associated with them. The air-cooled AquaStream chiller
offers an advantage over competitive equipment in these situations. Operation is minimally
affected in many restricted air flow situations due to its advanced Adaptive Control™
microprocessor which has the ability to understand the operating environment of the chiller and
adapt to it by first optimizing its performance and then staying on line through abnormal
conditions. For example, high ambient temperatures combined with a restricted air flow situation
will generally not cause the air-cooled model CGAM chiller to shut down. Other chillers would
typically shut down on a high pressure nuisance cut-out in these conditions.
Cross winds, those perpendicular to the condenser, tend to aid efficient operation in warmer
ambient conditions. However, they tend to be detrimental to operation in lower ambients due to
the accompanying loss of adequate head pressure. Special consideration should be given to low
ambient units. As a result, it is advisable to protect air-cooled chillers from continuous direct winds
exceeding 10 mph (4.5 m/s) in low ambient conditions.
The recommended lateral clearances are depicted in the close spacing engineering bulletin
available from your local office.
CG-PRC017-EN 13
Model Number Descriptions
Digit 1-4 — Chiller Model Digit 14 — Pressure Vessel Code Digit 22 — Water Connection
(Evap)
CGAM = Air-Cooled Scroll Packaged X = No Pressure Vessel Code
Chiller 1 = ASME Pressure Vessel Code and 1 = Grooved Pipe Connection
CRN
Digit 23 — Condenser Fin
Digit 5-7 — Unit Nominal Material
Tonnage Digit 15 — Unit Application
A = Lanced Aluminum Fins
020 = 20 Tons B = High Ambient (32-125F/0-52C) D = Lanced Aluminum Fins w/
026 = 26 Tons D = Wide Ambient (0 to 125F/-18 to CompleteCoat™
52C)
030 = 30 Tons
035 = 35 Tons Digit 24 — Condenser Heat
Digit 16 — Refrigerant Isolation Recovery
040 = 40 Tons
Valves
052 = 52 Tons X = No Heat Recovery
2 = Refrigerant Isolation Valves 1 = Partial Heat Recovery w/ Fan
060 = 60 Tons (Discharge Valve) Control (10-15% of cooling)
070 = 70 Tons
080 = 80 Tons Digit 17 — Seismically Rated
Unit Digit 25
090 = 90 Tons
100 = 100 Tons A = Not Seismically Rated Unit X
14 CG-PRC017-EN
Model Number Descriptions
CG-PRC017-EN 15
General Data
Table 1. General Data - 60 Hz - IP
16 CG-PRC017-EN
General Data
CG-PRC017-EN 17
General Data
18 CG-PRC017-EN
General Data
CG-PRC017-EN 19
Controls
LCD Touch-Screen Display with Multi-Language Support
The standard DynaView display provided with the Trane CH530 control panel features an LCD
touch-screen that is navigated by file tabs. This is an advanced interface that allows the user to
access any important information concerning setpoints, active temperatures, modes, electrical
data, pressure, and diagnostics. It uses full text display available in 19 languages.
20 CG-PRC017-EN
Controls
Adaptive Controls
Adaptive Controls directly sense the control variables that govern the operation of the chiller:
evaporator pressure and condenser pressure. When any one of these variables approaches a limit
condition when damage may occur to the unit or shutdown on a safety, Adaptive Controls takes
corrective action to avoid shutdown and keep the chiller operating. This happens through
combined actions of compressor and/or fan staging. Whenever possible, the chiller is allowed to
continue making chilled water. This keeps cooling capacity available unit the problem can be
solved. Overall, the safety controls help keep the building or process running and out of trouble.
Stand-Alone Controls
Single chillers installed in applications without a building management system is simple to install
and control: only a remote auto/stop for scheduling is required for unit operation. Signals from the
chilled-water pump contactor auxiliary, or a flow switch, are wired to the chilled-water flow
interlock. Signals from a time clock or some other remote device are wired to the external auto/stop
input.
Standard Features
• Auto/Stop - A job-site provided contact closure turns the unit on and off.
• External Interlock - A job-site provided contact opening wired to this input turns the unit off and
require a manual reset of the unit microcomputer. This closure is typically triggered by a job-
site provided system such as a fire alarm.
Hardwire Points
Microcomputer controls allow simple interface with other control systems, such as time clocks,
building automation systems, and ice storage systems via hardwire points. This means you have
the flexibility to meet job requirements while not having to learn a complicated control system.
Remote devices are wired from the control panel to provide auxiliary control to a building
automation system. Inputs and outputs can be communicated via a typical 4–20 mA electrical
signal, an equivalent 2–10 Vdc signal, or by utilizing contact closures.
This setup has the same stand features as a stand-alone water chiller, with the possibility of having
additional optional features:
• Ice making control
• External chilled water setpoint
• External demand limit setpoint
• Chilled water temperature reset
• Programmable relays - available outputs are: alarm-latching, alarm-auto reset, general
alarm, warning, chiller limit mode, compressor running, and Tracer control
BACnet Interface
BACnet interface capabilities are available, with communication link via single twisted-pair wiring
to a factory-installed and tested communication board.
Required features:
• BACnet Interface (selectable option with chiller)
BACnet is a data communication protocol for building automation and control networks developed
by American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
CG-PRC017-EN 21
Controls
Tracer Summit
The chiller plant control capabilities of the Trane Tracer Summit building automation system are
unequaled in the industry. Trane’s depth of experience in chillers and controls makes us a well-
qualified choice for automation of chiller plants using air-cooled AquaStream chillers. Our chiller
plant automation software is fully pre-engineered and tested.
Required features:
• LonTalk/Tracer Summit Interface (selectable option with chiller)
• Building Control Unit (external device required)
Energy Efficiency
• Sequences starting of chillers to optimize the overall chiller plant energy efficiency
– Individual chillers operate as base, peak, or swing based on capacity and efficiency
– Automatically rotates individual chiller operation to equalize runtime and wear
between chillers.
– Evaluates and selects the lowest energy consumption alternative from an overall
system perspective.
Regulatory Compliance Documentation
• Gathers information and generates the reports mandated in ASHRAE Guideline 3.
Easy Operation and Maintenance
• Remote monitoring and control
• Displays both current operation conditions and scheduled automated control actions
• Concise reports assist in planning for preventative maintenance and verifying performance
• Alarm notification and diagnostic messages aid in quick and accurate troubleshooting
When integrated with a Tracer Summit building management system the total building operation
can be optimized. With this system option, the full breadth of Trane’s HVAC and controls experience
are applied to offer solutions to many facility issues. If your project calls for an interface to other
systems, Tracer Summit can share data via BACnet, the ASHRAE open systems protocol.
22 CG-PRC017-EN
Controls
CG-PRC017-EN 23
Controls
BACnet
BCNT - Unit level BACnet interface
BACnet
1A15 - Analog input/output
J2-1, 2
Programmable Relay
PRLY - Programmable relay outputs
1A18 - Binary output
1A18 - J2-1, 3/J2-2, 3 NO/NC BMS
J2-4, 6/J2-5, 6 NO/NC
J2-7, 9/J2-8, 9 NO/NC
J2-10, 12/J2-11,12 NO/NC
Capacity Output
PCAP 2-10VDC output
1A25 Analog output BMS
J2-4, 6
24 CG-PRC017-EN
Electrical Data
Table 5. Electrical Data - 60 Hz
Unit Rated Number Qty Qty Fan Motor Cond Fan Compressor Compressor
Size Power Circuits Comp¹ Fans¹ Power (kw) FLA RLA¹ ² LRA¹ ³
200/60/3 1 2 2 1 6.7 38.8-38.8 278-278
230/60/3 1 2 2 1 5.9 33.7-33.7 278-278
20 380/60/3 1 2 2 1 3.5 23.7-23.7 177-177
460/60/3 1 2 2 1 2.9 18.6-18.6 130-130
575/60/3 1 2 2 1 2.3 15.4-15.4 104-104
200/60/3 1 2 2 1 6.7 45.7-45.7 338-338
230/60/3 1 2 2 1 5.9 44-44 338-338
26 380/60/3 1 2 2 1 3.5 26.3-26.3 196-196
460/60/3 1 2 2 1 2.9 22.4-22.4 158-158
575/60/3 1 2 2 1 2.3 18.6-18.6 126-126
200/60/3 1 2 3 1 6.7 57.8-57.8 485-485
230/60/3 1 2 3 1 5.9 50.3-50.3 485-485
30 380/60/3 1 2 3 1 3.5 32-32 210-210
460/60/3 1 2 3 1 2.9 25.8-25.8 160-160
575/60/3 1 2 3 1 2.3 20.2-20.2 135-135
200/60/3 1 2 3 1 6.7 57.8-81 485-485
230/60/3 1 2 3 1 5.9 50.3-76.5 485-485
35 380/60/3 1 2 3 1 3.5 32-41.1 210-260
460/60/3 1 2 3 1 2.9 25.8-33 160-215
575/60/3 1 2 3 1 2.3 20.2-26.3 135-175
200/60/3 2 2 2 1 6.7 38.8-38.8 278-278
230/60/3 2 2 2 1 5.9 33.7-33.7 278-278
40 380/60/3 2 2 2 1 3.5 23.7-23.7 177-177
460/60/3 2 2 2 1 2.9 18.6-18.6 130-130
575/60/3 2 2 2 1 2.3 15.4-15.4 104-104
200/60/3 2 2 2 1 6.7 45.7-45.7 338-338
230/60/3 2 2 2 1 5.9 44-44 338-338
52 380/60/3 2 2 2 1 3.5 26.3-26.3 196-196
460/60/3 2 2 2 1 2.9 22.4-22.4 158-158
575/60/3 2 2 2 1 2.3 18.6-18.6 126-126
200/60/3 2 2 3 1 6.7 57.8-57.8 485-485
230/60/3 2 2 3 1 5.9 50.3-50.3 485-485
60 380/60/3 2 2 3 1 3.5 32-32 210-210
460/60/3 2 2 3 1 2.9 25.8-25.8 160-160
575/60/3 2 2 3 1 2.3 20.2-20.2 135-135
1. Data shown for circuit one. The second circuit is always the same.
2. RLA - Rated Load Amps - Rated in accordance with UL Standard 1995.
3. LRA - Locked Rotor Amps - Based on full winding starts.
4. Units have single point power connection as standard. Optional dual point power connections are available for 40-120 ton units.
5. Voltage Utilization Range:
Rated voltage (use range): 200/60/3 (180-220), 230/60/3(208-254), 380/60/3 (342-418), 460/60/3 (414-506), 575/60/3 (516-633)
6. One separate 120/60/1, 15 amp customer provided power connection is required to power the heaters. An additional 120/60/1, 15 amp
customer provided power connection is required if the optional buffer tank is selected.
CG-PRC017-EN 25
Electrical Data
Unit Rated Number Qty Qty Fan Motor Cond Fan Compressor Compressor
Size Power Circuits Comp¹ Fans¹ Power (kw) FLA RLA¹ ² LRA¹ ³
200/60/3 2 2 3 1 6.7 57.8-81 485-485
230/60/3 2 2 3 1 5.9 50.3-76.5 485-485
70 380/60/3 2 2 3 1 3.5 32-41.1 210-260
460/60/3 2 2 3 1 2.9 25.8-33 160-215
575/60/3 2 2 3 1 2.3 20.2-26.3 135-175
200/60/3 2 2 2 1 6.7 81-81 485-485
230/60/3 2 2 2 1 5.9 76.5-76.5 485-485
80 380/60/3 2 2 2 1 3.5 41.1-41.1 260-260
460/60/3 2 2 2 1 2.9 33-33 215-215
575/60/3 2 2 2 1 2.3 26.3-26.3 175-175
200/60/3 2 2 3 1 6.7 81-94.5 485-560
230/60/3 2 2 3 1 5.9 76.5-89.1 485-560
90 380/60/3 2 2 3 1 3.5 41.1-54.5 260-310
460/60/3 2 2 3 1 2.9 33-43 215-260
575/60/3 2 2 3 1 2.3 26.3-34.4 175-210
200/60/3 2 2 4 1 6.7 94.5-94.5 560-560
230/60/3 2 2 4 1 5.9 89.1-89.1 560-560
100 380/60/3 2 2 4 1 3.5 54.5-54.5 310-310
460/60/3 2 2 4 1 2.9 43-43 260-260
575/60/3 2 2 4 1 2.3 34.4-34.4 210-210
200/60/3 2 2 4 1 6.7 94.5-110.6 560-680
230/60/3 2 2 4 1 5.9 89.1-104.4 560-680
110 380/60/3 2 2 4 1 3.5 54.5-60.3 310-360
460/60/3 2 2 4 1 2.9 43-50.6 260-320
575/60/3 2 2 4 1 2.3 34.4-38.5 210-235
200/60/3 2 2 4 1 6.7 110.6-110.6 680-680
230/60/3 2 2 4 1 5.9 104.4-104.4 680-680
120 380/60/3 2 2 4 1 3.5 60.3-60.3 360-360
460/60/3 2 2 4 1 2.9 50.6-50.6 320-320
575/60/3 2 2 4 1 2.3 38.5-38.5 235-235
1. Data shown for circuit one. The second circuit is always the same.
2. RLA - Rated Load Amps - Rated in accordance with UL Standard 1995.
3. LRA - Locked Rotor Amps - Based on full winding starts.
4. Units have single point power connection as standard. Optional dual point power connections are available for 40-120 ton units.
5. Voltage Utilization Range:
Rated voltage (use range): 200/60/3 (180-220), 230/60/3(208-254), 380/60/3 (342-418), 460/60/3 (414-506), 575/60/3 (516-633)
6. One separate 120/60/1, 15 amp customer provided power connection is required to power the heaters. An additional 120/60/1, 15 amp
customer provided power connection is required if the optional buffer tank is selected.
26 CG-PRC017-EN
Electrical Data
Unit Rated Without Pump Package Standard Head Pump Package High Head Pump Package
Size Power MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD²
200/60/3 105.1 125 111.1 125 121.1 150
230/60/3 92.3 125 98.3 125 108.3 125
20 380/60/3 61.6 80 n/a n/a
460/60/3 49.2 60 52.0 70 58.3 70
575/60/3 41.0 50 43.5 50 47.2 60
200/60/3 120.6 150 126.6 150 136.6 175
230/60/3 115.5 150 121.5 150 131.5 175
26 380/60/3 67.4 90 n/a n/a
460/60/3 57.7 80 60.5 80 66.8 80
575/60/3 48.2 60 50.7 60 54.4 70
200/60/3 154.6 200 160.6 200 170.6 225
230/60/3 135.5 175 141.5 175 151.5 200
30 380/60/3 83.8 110 n/a n/a
460/60/3 68.3 90 71.1 90 77.4 100
575/60/3 54.1 70 56.6 70 60.3 80
200/60/3 183.6 250 189.6 250 199.6 250
230/60/3 168.3 225 174.3 250 184.3 250
35 380/60/3 95.1 125 n/a n/a
460/60/3 77.3 110 80.1 110 86.4 110
575/60/3 61.7 80 64.2 90 67.9 90
1. MCA - Minimum Circuit Ampacity-125 percent of largest compressor RLA plus 100 percent of all other loads per NEC 440-33 2008.
2. Max Fuse or HACR type breaker or MOPD -225 percent of the largest compressor RLA plus all other loads per NEC 440-22 2008.
3. Local codes may take precedence.
4. n/a - means option not available with voltage.
CG-PRC017-EN 27
Electrical Data
Without Pump Package Standard Head Pump Package High Head Pump Package
Dual Point Power Dual Point Power
Single Point Dual Point Single Point Single Point
Unit Rated Power Power Power Circuit 1 Circuit 2 Power Circuit 1 Circuit 2
Size Power MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD MCA¹ MOPD MCA¹ MOPD
200/60/3 196.4 225 105.1 125 206.4 225 115.1 150 101.0 125 212.4 250 121.1 150 101.0 125
230/60/3 172.6 200 92.3 125 182.6 200 102.3 125 88.7 110 188.6 200 108.3 125 88.7 110
40 380/60/3 115.2 125 61.6 80 n/a n/a
460/60/3 91.8 110 49.1 60 97.1 110 54.4 70 47.4 60 100.9 110 58.2 70 47.4 60
575/60/3 76.6 90 40.9 50 80.6 90 44.9 60 39.5 50 82.8 90 47.1 60 39.5 50
200/60/3 225.9 250 120.7 150 235.9 250 130.7 175 116.6 150 241.9 250 136.7 175 116.6 150
230/60/3 216.3 250 115.4 150 226.3 250 125.4 150 111.8 150 232.3 250 131.4 175 111.8 150
52 380/60/3 126.0 150 67.4 90 n/a n/a
460/60/3 108.2 125 57.8 80 113.5 125 63.1 80 56.0 70 117.3 125 66.9 80 56.0 70
575/60/3 90.2 100 48.2 60 94.2 110 52.2 70 46.7 60 96.4 110 54.4 70 46.7 60
200/60/3 290.6 300 154.6 200 306.6 350 170.6 225 150.5 200 313.6 350 177.6 225 150.5 200
230/60/3 254.9 300 135.5 175 270.9 300 151.5 200 132.0 175 277.9 300 158.5 200 132.0 175
60 380/60/3 157.4 175 83.8 110 n/a n/a
460/60/3 128.4 150 68.3 90 137.5 150 77.4 100 66.5 90 140.6 150 80.5 100 66.5 90
575/60/3 101.7 110 54.1 70 107.9 125 60.3 80 52.7 70 110.9 125 63.3 80 52.7 70
200/60/3 342.9 400 183.6 250 358.9 400 199.6 250 179.5 250 365.9 400 206.6 250 179.5 250
230/60/3 313.9 350 168.3 225 329.9 400 184.3 250 164.7 225 336.9 400 191.3 250 164.7 225
70 380/60/3 177.8 200 95.1 125 n/a n/a
460/60/3 144.6 175 77.3 110 153.7 175 86.4 110 75.5 100 156.8 175 89.5 110 75.5 100
575/60/3 115.4 125 61.7 80 121.6 125 67.9 90 60.3 80 124.6 150 70.9 90 60.3 80
1. MCA - Minimum Circuit Ampacity-125 percent of largest compressor RLA plus 100 percent of all other loads per NEC 440-33 2008.
2. Max Fuse or HACR type breaker or MOPD -225 percent of the largest compressor RLA plus all other loads per NEC 440-22 2008.
3. Data shown for circuit one. The second circuit is always the same.
4. Local codes may take precedence.
5. n/a - not available
28 CG-PRC017-EN
Electrical Data
Without Pump Package Standard Head Pump Package High Head Pump Package
Dual Point Power Dual Point Power
Single Point Dual Point Single Point Single Point
Unit Rated Power Power Power Circuit 1 Circuit 2 Power Circuit 1 Circuit 2
Size Power MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD² MCA¹ MOPD MCA¹ MOPD MCA¹ MOPD
200/60/3 376.0 450 200.2 250 392.0 450 216.2 250 196.1 250 399.0 450 223.2 300 196.1 250
230/60/3 354.5 400 188.6 250 370.5 400 204.6 250 185.0 250 377.5 450 211.6 250 185.0 250
80 380/60/3 189.0 200 100.7 125 n/a n/a
460/60/3 153.1 175 81.6 110 162.2 175 90.7 110 79.8 110 165.3 175 93.8 125 79.8 110
575/60/3 122.9 125 65.5 90 129.1 150 71.7 90 64.0 90 132.1 150 74.7 100 64.0 90
200/60/3 419.6 500 223.7 300 435.6 500 239.7 300 219.6 300 442.6 500 246.7 300 219.6 300
230/60/3 394.6 450 210.2 250 410.6 450 226.2 300 206.7 250 417.6 500 233.2 300 206.7 250
90 380/60/3 226.2 250 121.0 175 n/a n/a
460/60/3 181.5 200 97.0 125 190.6 225 106.1 125 95.2 125 193.7 225 109.2 150 95.2 125
575/60/3 145.8 175 77.9 110 152.0 175 84.1 110 76.5 110 155.0 175 87.1 110 76.5 110
200/60/3 459.9 500 243.8 300 475.9 500 259.8 350 239.7 300 489.9 500 273.8 350 239.7 300
230/60/3 431.6 500 228.7 300 447.6 500 244.7 300 225.2 300 461.6 500 258.7 300 225.2 300
100 380/60/3 259.9 300 137.9 175 n/a n/a
460/60/3 207.3 250 109.9 150 216.4 250 119.0 150 108.1 150 222.3 250 124.9 150 108.1 150
575/60/3 166.6 200 88.3 110 172.8 200 94.5 125 86.9 110 177.8 200 99.5 125 86.9 110
200/60/3 496.2 600 264.0 350 519.2 600 287.0 350 259.9 350 526.2 600 294.0 400 259.9 350
230/60/3 466.1 500 247.9 350 489.1 500 270.9 350 244.3 300 496.1 600 277.9 350 244.3 300
110 380/60/3 273.0 300 145.1 200 n/a n/a
460/60/3 224.5 250 119.5 150 236.7 250 131.7 175 117.7 150 239.5 250 134.5 175 117.7 150
575/60/3 175.9 200 93.5 125 185.1 200 102.7 125 92.0 125 187.1 225 104.7 125 92.0 125
200/60/3 528.5 600 280.1 350 551.5 600 303.1 400 276.0 350 574.5 600 326.1 400 276.0 350
230/60/3 496.7 600 263.2 350 519.7 600 286.2 350 259.6 350 542.7 600 309.2 400 259.6 350
120 380/60/3 284.6 300 150.9 200 n/a n/a
460/60/3 239.8 250 127.1 175 252.0 300 139.3 175 125.3 175 263.8 300 151.1 200 125.3 175
575/60/3 184.1 200 97.6 125 193.3 200 106.8 125 96.1 125 202.1 225 115.6 150 96.1 125
1. MCA - Minimum Circuit Ampacity-125 percent of largest compressor RLA plus 100 percent of all other loads per NEC 440-33 2008.
2. Max Fuse or HACR type breaker or MOPD -225 percent of the largest compressor RLA plus all other loads per NEC 440-22 2008.
3. Data shown for circuit one. The second circuit is always the same.
4. Local codes may take precedence.
5. n/a - not available
CG-PRC017-EN 29
Electrical Data
30 CG-PRC017-EN
Electrical Data
CG-PRC017-EN 31
Electrical Data
32 CG-PRC017-EN
Electrical Data
Table 10. Lug Range Size - 60 Hz - Pump Package - High Head Pump
CG-PRC017-EN 33
Electrical Data
Unit Rated Number Qty Qty Fan Motor Cond Fan Compressor Compressor
Size Power Circuits Comp¹ Fans¹ Power (kW) FLA RLA¹ ² LRA¹ ³
20 400/50/3 1 2 2 1 2.1 18.6-18.6 130-130
26 400/50/3 1 2 2 1 2.1 22.4-22.4 158-158
30 400/50/3 1 2 3 1 2.1 26.6-26.6 160-160
35 400/50/3 1 2 3 1 2.1 26.6-33.3 160-215
40 400/50/3 2 2 2 1 2.1 18.6-18.6 130-130
52 400/50/3 2 2 2 1 2.1 22.4-22.4 158-158
60 400/50/3 2 2 2 1 2.1 26.6-26.6 160-160
70 400/50/3 2 2 3 1 2.1 26.6-33.3 160-215
80 400/50/3 2 2 2 1 2.1 33.3-33.3 175-175
90 400/50/3 2 2 3 1 2.1 33.3-43.7 175-210
100 400/50/3 2 2 3 1 2.1 43.7-43.7 210-210
110 400/50/3 2 2 4 1 2.1 43.7-50.6 210-235
120 400/50/3 2 2 4 1 2.1 50.6-50.6 235-235
1. Data shown for circuit one. The second circuit is always the same.
2. RLA - Rated Load Amps - Rated in accordance with UL Standard 1995.
3. LRA - Locked Rotor Amps - Based on full winding starts.
4. Units have single point power connection as standard. Optional dual point power connections are available for 40-120 ton units.
5. Voltage Utilization Range:
Rated voltage (use range): 400/50/3 (360-440)
6. One separate 120/50/1, 15 amp customer provided power connection is required to power the heaters. An additional 120/50/1, 15 amp
customer provided power connection is required if the optional buffer tank is selected.
34 CG-PRC017-EN
Electrical Data
CG-PRC017-EN 35
REV
36
SHEET
TRANE 5720-6004 1 OF 3
THIS DRAWING IS PROPRIETARY AND SHALL NOT BE COPIED OR ITS
A
CONTENTS DISCLOSED TO OUTSIDE PARTIES WITHOUT THE WRITTEN
WARNING AVERTISSEMENT ADVERTENCIA CONSENT OF TRANE
A B C A B C DRAWN BY: C TRANE DATE:
FIELD WIRING DIAGRAM
L1 L2 L3 L1 L2 L3 HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
REPLACES:
CGAM
1 DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS À DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y REVISION DATE:
12/5/08
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCÉDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y
VERROUILLAGE ET DES ÉTIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL SIMILIAR TO:
2 PROCEDURES BEFORE SERVICING.
INSURE THAT ALL MOTOR TOUTE INTERVENTION. VÉRIFIER QUE TOUS SERVICIO. ASEGÚRESE DE QUE TODOS
6Q2 6Q1 CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
3 STORED VOLTAGE. UNITS WITH DÉCHARGÉS. DANS LE CAS D'UNITÉS DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER COMPORTANT DES ENTRAÎNEMENTS À PARA LAS UNIDADES CON TRANSMISIÓN
TO DRIVE INSTRUCTIONS FOR VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS
4 CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
FAILURE TO DO THE ABOVE DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
12 COULD RESULT IN DEATH OR NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
5
SERIOUS INJURY. PRÉCAUTION PEUT ENTRAÎNER DES INDICADO, PODRÍA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ÊTRE O SERIAS LESIONES PERSONALES.
6 MORTELLES.
7
CONTROL PANEL
10 A B C A B C A B C A B C A B C A B C
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
11
15
Electrical Connections
19 115V 27V 42 43 44 45 1 2
OR
110V
20
1X6-1
X1 X2 X3 X4 42
HEATERS 634
21
1A18 CIRCUIT 3 1X6-2
QUAD RELAY OUTPUTS UNIT 43
STATUS PROGRAMMABLE 636
22
RELAY (OPTIONAL) 1X6-3
44
BUFFER TANK
642
23 HEATERS
1X6-4
CIRCUIT 4
45
643
24
1X7-1
3
J2 0-10VDC
831
25 12 11 10 9 8 7 6 5 4 3 2 1 CUSTOMER PUMP
1X7-2
INVERTER SPEED SIGNAL
4
832
26
1 5 6 1 7 8 1 9 10 1 11 12
27
28
29
30 6K8
5 2
1A14 1A15 1A16 1A13 1A12
31 6K9
ANALOG INPUT/OUTPUT COMMUNICATION BOARD DUAL LOW VOLTAGE DUAL LOW VOLTAGE DUAL LOW VOLTAGE
BINARY INPUT BINARY INPUT BINARY INPUT 6 2
EXTERNAL CHILLED WATER (OPTIONAL)
32 SETPOINT & DEMAND LIMIT LCI-C ICE MAKING CONTROL EMERGENY STOP/ CHILLED WATER PUMP 6K10
(OPTIONAL) (OPTIONAL) AUTO STOP FAULT INPUT
7 2
33 6K11
8 2
34 6K12
9 2
35 6K13
10 2
INPUT
INPUT
36 6K14
11 2
TO TRACER OR
OTHER TRANE
REMOTE DEVICE
TO NEXT UNIT
E-STOP
PUMP 2
PUMP 1
AUTO STOP
37 J2 J2 J2 J2 J2 6K15
5+
2+
6 GND
3 GND
4
4
4
3
2
3
2
3
2
1
1
1
1 2 3 4
12 2
38
W3
W2
39
3
812
818
817
1X5-8
1X5-7
1X5-6
1X5-5
811
40 15 16 17 18 19 20 23 24 25 26
41
PAIR LEADS
PAIR LEADS
CG-PRC017-EN
ED TWISTED
ED TWISTED
EXTERNAL CHILLED WATER (OPTIONAL) BINARY INPUT BINARY INPUT BINARY INPUT
32 SETPOINT & DEMAND LIMIT LCI-C ICE MAKING CONTROL EMERGENY STOP/ CHILLED WATER PUMP 6K10
(OPTIONAL) (OPTIONAL) AUTO STOP FAULT INPUT
7 2
33 6K11
8 2
34 6K12
9 2
35 6K13
10 2
INPUT
INPUT
36 6K14
CG-PRC017-EN
11 2
TO TRACER OR
OTHER TRANE
REMOTE DEVICE
TO NEXT UNIT
E-STOP
PUMP 2
PUMP 1
AUTO STOP
37 J2 J2 J2 J2 J2 6K15
5+
2+
6 GND
3 GND
4
4
4
3
2
3
2
3
2
1
1
1
1 2 3 4
12 2
38
W3
W2
39
3
812
818
817
1X5-8
1X5-7
1X5-6
1X5-5
811
40 15 16 17 18 19 20 23 24 25 26
41
PAIR LEADS
PAIR LEADS
42
SHIELDED TWISTED
SHIELDED TWISTED
43 34 33 32 31 30 29 28 27
16
44
6K6
15 16
45
6K5
38 39
17 18
46
6K4
PHASE 19 20
47
A B C 6F2
15 L1 L2 L3 23 24
48 1A9
DUAL RELAY OUTPUT 18 6F1
J2 EVAP WATER PUMP 25 26
RELAYS RUN SIGNAL
6 GND
49
4 2-10VDC
50 6Q1
51
17 CUSTOMER SUPPLIED PUMP
52 27
PUMP 2
PUMP 1
6M1 5
53 28
ANALOG INPUT/OUTPUT M
3
54 CAPACITY OUTPUT J2 3 29
(OPTIONAL)
3
6
1
6
1A25
55 30
3 NOTICE
540
536
535
539
1X4-32
1X4-30
1X4-29
1X4-31
56 31
TRANE PUMP CONTROL MUST BE USED TO
PROVIDE PUMP CONTROL. CHILLED WATER PUMP 7
57 MUST BE CONTROLLED BY THE CHILLER OUTPUT. 32
41 40 41 40 FAILURE TO COMPLY WITH THIS REQUIREMENT.
COULD RESULT IN DAMAGE TO THE UNIT.
58 33
PUMP STARTER COILS 8
59 34
6M2
41 40 41 40
60 M 38
3
3 9
61 39
62 6Q5
17
63 40 H
64 41 N
65
66
67
68
69
70
37
Electrical Connections
Electrical Connections
REV
TRANE 2309-1915 SHEET
A
WARNING AVERTISSEMENT ADVERTENCIA
2 OF 3
THIS DRAWING IS PROPRIETARY AND SHALL NOT BE COPIED OR ITS
CONTENTS DISCLOSED TO OUTSIDE PARTIES WITHOUT THE WRITTEN
DRAWN BY:
CONSENT OF TRANE
C TRANE DATE:
FIELD WIRING DIAGRAM
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO! CGAM
REPLACES:
73 DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS À DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y 12/5/08
REVISION DATE:
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCÉDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y
SIMILIAR TO:
74 PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ÉTIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL
INSURE THAT ALL MOTOR TOUTE INTERVENTION. VÉRIFIER QUE TOUS SERVICIO. ASEGÚRESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
75 STORED VOLTAGE. UNITS WITH DÉCHARGÉS. DANS LE CAS D'UNITÉS DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER COMPORTANT DES ENTRAÎNEMENTS À PARA LAS UNIDADES CON TRANSMISIÓN
TO DRIVE INSTRUCTIONS FOR VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS
76 CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
FAILURE TO DO THE ABOVE DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
COULD RESULT IN DEATH OR NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
77
SERIOUS INJURY. PRÉCAUTION PEUT ENTRAÎNER DES INDICADO, PODRÍA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ÊTRE O SERIAS LESIONES PERSONALES.
78 MORTELLES.
79
80
1 SINGLE SOURCE POWER IS PROVIDED AS STANDARD ON THESE PRODUCTS, DUAL
81
SOURCE POWER IS OPTIONAL. FIELD CONNECTIONS FOR SINGLE SOURCE
POWER ARE MADE TO 1X1, 1Q1, OR 1Q2. WHEN THE OPTIONAL DUAL SOURCE
82 POWER IS SELECTED THE FIELD CONNECTIONS FOR CIRCUIT #2 ARE MADE TO
1X2, 1Q3, OR 1Q4.
83
104
105
11. REFER TO CGAM ELECTRICAL SCHEMATIC FOR SPECIFIC ELECTRICAL CONNECTION
106
INFORMATION AND NOTES PERTAINING TO WIRING INSTALLATION.
107 12 ALL UNIT POWER WIRING MUST BE 600 VOLT COPPER CONDUCTORS ONLY AND
HAVE A MINIMUM TEMPERATURE INSULATION RATING OF 75 DEGREE C. REFER TO
108
UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT
109
PROTECTION DEVICE. PROVIDE AN EQUIPMENT GROUND IN ACCORDANCE WITH
APPLICABLE ELECTRIC CODES. REFER TO WIRE RANGE TABLE FOR LUG SIZES.
110
111 13. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND
LOCAL REQUIREMENTS.
112
14. ALL CUSTOMER CONTROL CIRCUIT WIRING MUST BE COPPER CONDUCTORS ONLY
113
AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS. EXCEPT AS NOTED,
114
ALL CUSTOMER WIRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED
BOX LUGS WITH A WIRE RANGE OF 14 TO 18 AWG OR DIN RAIL MOUNTED
115 SPRING FORCE TERMINALS.
116 15 UNIT PROVIDED DRY CONTACTS FOR THE CONDENSER/CHILLED WATER PUMP
CONTROL. RELAYS ARE RATED FOR 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY,
117
OR 13 HP, 7.2 FLA AT 120 VOLTS 60 HZ, CONTACTS ARE RATED FOR 5 AMPS
118 GENERAL PURPOSE DUTY 240 VOLTS.
119 16 CUSTOMER SUPPLIED CONTACTS FOR ALL LOW VOLTAGE CONNECTIONS MUST BE
COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC FOR A 12 mA RESISTIVE LOAD.
120
SILVER OR GOLD PLATED CONTACTS RECOMMENDED.
121
17 FIELD CONNECTIONS ARE ONLY MADE IN A CUSTOMER PROVIDED PUMP. THESE
122 CONNECTIONS WILL BE MADE BY THE FACTORY WHEN THE PUMP IS PROVIDED BY
THE FACTORY. CUSTOMER SUPPLIED POWER 115V, 60Hz, 1PH.
123
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
38 CG-PRC017-EN
Electrical Connections
REV
TRANE 2309-1915 SHEET
A
WARNING AVERTISSEMENT ADVERTENCIA
3 OF 3
THIS DRAWING IS PROPRIETARY AND SHALL NOT BE COPIED OR ITS
CONTENTS DISCLOSED TO OUTSIDE PARTIES WITHOUT THE WRITTEN
DRAWN BY:
CONSENT OF TRANE
C TRANE DATE:
FIELD WIRING DIAGRAM
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO! CGAM
REPLACES:
145 DISCONNECT ALL ELECTRIC POWER COUPER TOUTES LES TENSIONS ET DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUDING REMOTE DISCONNECTS OUVRIR LES SECTIONNEURS À DISTANCE, INCLUSO LAS DESCONEXIONES REMOTAS Y 12/5/08
REVISION DATE:
AND FOLLOW LOCK OUT AND TAG PUIS SUIVRE LES PROCÉDURES DE SIGA LOS PROCEDIMIENTOS DE CIERRE Y
SIMILIAR TO:
146 PROCEDURES BEFORE SERVICING. VERROUILLAGE ET DES ÉTIQUETTES AVANT ETIQUETADO ANTES DE PROCEDER AL
INSURE THAT ALL MOTOR TOUTE INTERVENTION. VÉRIFIER QUE TOUS SERVICIO. ASEGÚRESE DE QUE TODOS
CAPACITORS HAVE DISCHARGED LES CONDENSATEURS DES MOTEURS SONT LOS CAPACITORES DEL MOTOR HAYAN
147 STORED VOLTAGE. UNITS WITH DÉCHARGÉS. DANS LE CAS D'UNITÉS DESCARGADO EL VOLTAJE ALMACENADO.
VARIABLE SPEED DRIVE, REFER COMPORTANT DES ENTRAÎNEMENTS À PARA LAS UNIDADES CON TRANSMISIÓN
TO DRIVE INSTRUCTIONS FOR VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS
148 CAPACITOR DISCHARGE. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
FAILURE TO DO THE ABOVE DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
COULD RESULT IN DEATH OR NE PAS RESPECTER CES MESURES DE EL NO REALIZAR LO ANTERIORMENTE
149
SERIOUS INJURY. PRÉCAUTION PEUT ENTRAÎNER DES INDICADO, PODRÍA OCASIONAR LA MUERTE
BLESSURES GRAVES POUVANT ÊTRE O SERIAS LESIONES PERSONALES.
150 MORTELLES.
151
152
153
154
155
156
157
158
159
REPLACEABLE FUSE TABLE
160
FUSE CLASS AMPS TON V Hz
161 1F1 CC 10 All All All
162 1F2 CC 10 All All All
163
1F3 CC 10 40-130 All All
164
1F4 CC 10 40-130 All All
1F5, 1F6 CC 10 All 200 60
165
1F5, 1F6 CC 8 All 230 60
166
1F5, 1F6 CC 5 All 380 60
167
1F5, 1F6 CC 5 All 400 50
168 1F5, 1F6 CC 5 All 460 60
169 1F5, 1F6 CC 4 All 575 60
170
1F7 CC 10 20-70 200 60
1F7 CC 8 20-70 230 60
171
1F7 CC 5 20-70 380 60
1F7 CC 5 20-70 400 50
172
173
1F7 CC 5 20-70 460 60
174 1F7 CC 4 20-70 575 60
175 1F8, 1F9, 1F10 CC 10 40-70 200 60
176
1F8, 1F9, 1F10 CC 8 40-70 230 60
177
1F8, 1F9, 1F10 CC 5 40-70 380 60
1F8, 1F9, 1F10 CC 5 40-70 400 50
1F8, 1F9, 1F10 CC 5 40-70 460 60
178
179
1F8, 1F9, 1F10 CC 4 40-70 575 60
180 1F11 CC 10 All All All
181 1F12, 13 CC 6 All All All
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
NOTICE AVIS AVISO
USE COPPER CONDUCTORS ONLY! N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! ¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT LES BORNES DE L'UNITÉ NE SONT PAS CONÇUES LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
216
OTHER TYPES OF CONDUCTORS. POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS. PARA ACEPTAR OTROS TIPOS DE CONDUCTORES.
FAILURE TO DO THE ABOVE COULD RESULT IN FAIRE DÉFAUT À LA PROCÉDURE CI-DESSUS PEUT NO SEGUIR LAS INSTRUCCIONES ANTERIORES PUEDE
EQUIPMENT DAMAGE. ENTRAÎNER DES DOMMAGES À L'ÉQUIPEMENT. PROVOCAR DAÑOS EN EL EQUIPO.
CG-PRC017-EN 39
Dimensions
Figure 4. Sizes 20 and 26 ton - standard unit
Fan
Control
Panel Chilled water
84.7 in inlet
(2151 mm)
Wire Compressor
20.3 in (516 mm)
Connection
9.7 in (246 mm)
20.8 in (528 mm)
Chilled 16.8 in
50.6 in
(1285 mm) 92.4 in (2348 mm) water
outlet (428 mm)
114.0 in (2895 mm)
More clearance may be needed for airflow Total of four mounting locations.
depending on the installation.
40 CG-PRC017-EN
Dimensions
Figure 6. Sizes 20 and 26 ton - pump package, buffer tank, partial heat recovery units
Fan
Figure 7. Sizes 20 and 26 ton - pump package, buffer tank, partial heat recovery unit water connections
Chilled Chilled
Chilled water water
water inlet outlet
outlet
12.8 in
(325 mm)
22.4 in 22 in
9.7 in (569 mm) (559 mm) 15.2 in
(246 mm)
(385 mm)
Chilled (317 mm) 12.5 in 20.9 in
water 6.9 in
(531 mm) Heating 67.4 in (1712 mm)
Heating (176 mm)
inlet 39.8 in outlet
29.8 in inlet
(1011 mm) (757 mm)
Water connections are 1.3 in (33mm) Water outlet connection is 14.8 in (377 mm) Partial heat recovery connections are even with unit edge.
from unit end. and inlet is 0.3 in (7.8 mm) from unit end.
The chilled water inlet and outlet connections are the same
as the standard unit unless pump package or buffer tank
are ordered.
CG-PRC017-EN 41
Dimensions
Fan
Control
Panel Chilled water
84.7 in inlet
(2151 mm)
Compressor
Wire 20.3 in (516 mm)
Connection
9.7 in (246 mm)
21 in (534 mm)
50.6 in Chilled water 16.8 in
(1285 mm) 128.2 in (3257 mm) outlet (428 mm)
150.0 in (3809 mm)
More clearance may be needed for airflow Total of four mounting locations.
depending on the installation.
42 CG-PRC017-EN
Dimensions
Figure 10. Sizes 30 and 35 ton - pump package, buffer tank, partial heat recovery units
Control Panel
Fan
Figure 11. Sizes 30 and 35 ton - pump package, buffer tank, partial heat recovery unit water connections
Chilled Chilled
water water Chilled water
outlet outlet inlet
12.9 in
(327 mm)
22.2 in 22 in
9.7 in (564 mm) (559 mm) 15.2 in
(246 mm) (385 mm)
Chilled (313 mm) 12.3 in 20.9 in
water 7.2 in
(531 mm) Heating 67.4 in (1712 mm)
Heating (182 mm)
inlet 39.9 in outlet
29.8 in inlet
(1012 mm) (757 mm)
Water connections are 1.3 in (33 mm) Water outlet connection is 14.9 in (379 mm) Partial heat recovery connections are even with unit edge.
from unit end. and inlet is 5.3 in (135 mm) from unit end.
The chilled water connections are the same as the standard
unit unless pump package or buffer tank are ordered.
CG-PRC017-EN 43
Dimensions
Wire
Control Panel Fan Compressor
Connection
Chilled water
84.8 in inlet
(2155 mm)
Chilled water
outlet
Figure 13. Sizes 40 and 52 ton - service clearances and mounting locations
85.2 in
(2164 mm)
Door Chilled water
Swing connection side
Control
panel side
More clearance may be needed for airflow Total of four mounting locations.
depending on the installation.
44 CG-PRC017-EN
Dimensions
Figure 14. Sizes 40 and 52 ton - pump package, buffer tank or partial heat recovery unit dimensions
Control Connection
Panel Wire Compressor Pump Buffer Tank
Fan
Package
84.8 in
(2155 mm)
Pump
Package
VFD
Figure 15. Sizes 40 and 52 ton - pump package, buffer tank, partial heat recovery unit water connections
Buffer Tank
Chilled
Chilled water water inlet
inlet
Chilled water Chilled
outlet water
54.8 in
outlet
(1392 mm)
19.7 in 19.7 in 19.7 in 45.4 in
(499 mm) (500 mm) (500 mm) (1153 mm)
9.2 in
(474 mm) 18.7 in
18.7 in (474 mm)
(234 mm)
70.4 in (1788 mm)
66.8 in (1696 mm) 44.2 in
(1122 mm)
Water outlet connection is even with unit end, Water inlet connection is even with unit end, Partial heat recovery connections are even with
inlet is 6.1 in (154 mm) from unit end. outlet is 14.8 in (376 mm) from unit end. unit end.
CG-PRC017-EN 45
Dimensions
Chilled water
inlet
84.8 in
(2155 mm) Chilled water
outlet
Figure 17. Sizes 60 and 70 ton - service clearances and mounting locations
85.2 in
(2164 mm)
Door
Chilled water
Swing Control
panel side connection side
More clearance may be needed for airflow Total of six mounting locations.
depending on the installation.
46 CG-PRC017-EN
Dimensions
Figure 18. Sizes 60 and 70 ton - pump package, buffer tank or partial heat recovery unit dimensions
84.8 in
(2155 mm)
Pump
Package
VFD
Figure 19. Sizes 60 and 70 ton - pump package, buffer tank, partial heat recovery unit water connections
Buffer Tank
Chilled
Chilled water inlet water inlet
Water outlet connection even with end, Water inlet connection even with end, Partial heat recovery connections are even with
inlet 6.1 in (154 mm) from unit end. outlet 14.8 in (376 mm) from unit end. unit end.
CG-PRC017-EN 47
Dimensions
Fan Compressor
Chilled water
92.4 in inlet
Control (2347 mm)
Panel Chilled water
outlet
Wire
Connection
31.1 in (789 mm)
29.6 in (752 mm) 7.9 in (200 mm)
89.0 in
(2260 mm)
89.2 in (2265 mm)
Figure 21. Sizes 80 and 90 ton - service clearances and mounting locations
More clearance may be need for airflow Total of six mounting location.
depending on the installation.
48 CG-PRC017-EN
Dimensions
Figure 22. Sizes 100, 110 and 120 ton - standard unit
Fan Compressor
Chilled water
92.5 in inlet
Control (2349 mm)
Panel Chilled water
outlet
31.1 in
(789 mm)
29.6 in (752 mm)
89.0 in
(2260 mm) 11.4 in 7.9 in
111.7 in (2837 mm) (289 mm) (200 mm)
165.9 in (4214 mm)
Water connections are 5.7 in (145 mm)
from unit end.
Figure 23. Sizes 100, 110 and 120 ton - service clearances and mounting locations
85.2 in
Door Chilled water
(2164 mm)
Swing connection side
Control
panel side
More clearance may be needed for airflow Total of six mounting locations.
depending on the installation.
CG-PRC017-EN 49
Weights
Weights
Table 14. Weights - 60 Hz
Shipping Weight Operating Weight
Tons
pounds kilograms pounds kilograms
20 1898 861 1919 870
26 1966 892 1989 902
30 2501 1134 2527 1146
35 2557 1160 2588 1174
40 3359 1524 3377 1532
52 3492 1584 3516 1595
60 4498 2040 4526 2053
70 4574 2075 4605 2089
80 5083 2306 5120 2322
90 5441 2468 5480 2486
100 6261 2840 6304 2859
110 6303 2859 6353 2882
120 6303 2859 6353 2882
1. Weights based on aluminum fins.
2. Weights do not include pump package, buffer tank, partial heat recovery, etc.
3. All weights ±5%.
50 CG-PRC017-EN
Mechanical Specifications
General
Units are constructed of galvanized steel frame with galvanized steel panels and access doors.
Component surfaces are finished with a powder-coated paint. Each unit ships with full operating
charges of refrigerant and oil.
Unit-Mounted Starter
The control panel is designed per UL 1995 type enclosure with three-phase, overload protection.
The starter is in across-the-line configuration, factory-mounted and fully pre-wired to the
compressor motor and control panel. A factory-installed, factory-wired 820 VA control power
transformer provides all unit control power (120 Vac secondary) and Trane CH530 module power
(24 Vac secondary). Power line connection type is standard with a terminal block.
Evaporator
Braze plate evaporator is made of stainless steel with copper as the braze material. It is designed
to withstand a refrigerant side working pressure of 430 psig (29.6 bars) and a waterside working
pressure of 150 psig (10.5 bars). Evaporator is tested at 1.1 times maximum allowable refrigerant
side working pressure and 1.5 times maximum allowable water side working pressure. It has one
water pass. Immersion heaters protect the evaporator to an ambient of -20°F (-29°C).
The evaporator is covered with factory-installed 0.75 inch (19.05 mm) Armaflex II or equal (k=0.28)
insulation. Foam insulation is used on the suction line.
Condenser
Air-cooled condenser coils have aluminum fins mechanically bonded to internally-finned copper
tubing. The condenser coil has an integral subcooling circuit. The maximum allowable working
pressure of the condenser is 650 psig (44.8 bars). Condensers are factory proof and leak tested at
715 psig (49.3 bars).
Direct-drive vertical discharge condenser fans are balanced. Three-phase condenser fan motors
with permanently lubricated ball bearings and external thermal overload protection are provided.
High ambient units start and operate from 32°F to 125°F (0°C to 52°C) - standard offering.
CG-PRC017-EN 51
Mechanical Specifications
52 CG-PRC017-EN
Options
Quality Assurance
The quality management system applied by Trane has been subject to independent third-party
assessment and approval to ISO 9001. The products described in this catalog are designed,
manufactured and tested in accordance with the approved system requirements described in the
Trane Quality Manual.
Options
Application Options
Wide Ambient
A variable speed drive on the first fan of each circuit allows for ambient temperatures between 0°F
(-18°C) to 125°F (52°C).
Low-Temperature Processing
An additional temperature sensor enables leaving evaporator water temperature below 42°F
(5.5°C).
Partial Heat Recovery with Fan Control
A supplemental brazed plate heat exchanger is mounted in series to the condenser coil. Connecting
piping and inlet and outlet water sensors are included. CH530 controls display heat recovery inlet
and outlet water temperatures and controls the fans. The heat rejection to the partial heat recovery
heat exchanger is not controlled. Flow and temperature variations through the partial heat recovery
heat exchanger will vary. The partial heat recovery heat exchanger is typically used to preheat water
before it enters a boiler or other water heating process.
Pump Options
Dual Standard and High Head Pump Package
Pump package includes: two standard or high head pumps, VFD, air separators with vents,
expansion vessels, drainage valves, shut-off valves at entering and leaving connections, and
service valves to isolate each pump for repair/replacement.
The pump package is single point power integrated into the chiller unit power with a separate
factory wired control panel. The control of the pump is integrated into the chiller controller. The
CH530 displays evaporator pump starts and run-times. Freeze protection down to an ambient of -
20°F (-29°C) is included as standard. The cold parts of the pump package will also be insulated.
Designed with one redundant pump, it is controlled to operate both pumps through a lead/lag
and failure/recovery functionality. There is a variable flow option with factory-installed bypass
line.
A variable speed drive is installed in an additional panel to control the pump. The inverter is
adjusted upon start up to balance the system flow and head requirements. The purpose is to save
on wasted pump energy caused by a traditional balancing valve.
Standard head pump is offered for applications that have short water loops or are de-coupled. High
head pump is offered for applications where the integrated chiller pump serves the entire loop
volume or where there is substantial vertical rise.
CG-PRC017-EN 53
Options
Electrical Options:
Circuit Breaker
A molded case standard interrupting capacity circuit breaker, factory pre-wired with terminal block
power connections and equipped with a lockable external operator handle, is available to
disconnect the chiller from main power.
Control Options:
BACNet Interface
Allows user to easily interface with BACNet via a single twisted-pair wiring to a factory-installed
and tested communication board.
54 CG-PRC017-EN
Options
Other Options
ASME Evaporator
The evaporator will be tested and stamped in accordance with ASME.
Half Louvers
Louvered panels cover the condenser coil only. Available on the largest W coil units only.
Isolators
Molded elastomeric isolators sized to reduce vibration transmission to the supporting structure
when the unit is installed. Isolators ship with the chiller.
Nitrogen Charge
Unit is shipped with oil and a nitrogen holding charge in lieu of refrigerant.
Performance Tests
Performance tests are available to certify chiller performance before shipment.
CG-PRC017-EN 55
Literature Order Number CG-PRC017-EN
Date December 2008
Supersedes New
www.trane.com