Sei sulla pagina 1di 14

Cyclic tests of

welded headed
stud connections
Richard A. Spencer
Assistant Professor
Department of Civil Engineering
University of British Columbia
Vancouver, Canada

Donald S. Neille
Graduate Research Fellow
Department of Civil Engineering
University of British Columbia
Vancouver, Canada

Richard A. Spencer Donald S. Neille

n many precast box-type buildings, should perform adequately when sub-


I wall panels and floor and roof units jected to the dynamically induced
are connected together to act as shear earthquake forces, acting in combina-
walls and diaphragms to resist lateral tion with the live and dead loads.
loads due to earthquakes. In this type A simple equivalent static lateral
of building all loads must be trans- load analysis' shows that the connec-
ferred by the connections, and these tions must be able to transfer in-plane

70
shear forces between precast units, and
in some cases also resist pullout forces Synopsis
due to out-of-plane inertia forces on
the units themselves. Simulated earthquake
The accelerations in a severe earth- loading was applied to a
quake may be much greater than those type of welded headed stud
assumed in the equivalent static lat- connection used in precast
eral load analysis. It is generally ac-
cepted that while a building should be box-type buildings.
able to resist moderate earthquakes
Load-deflection hysteresis
with only non-structural damage, yield-
ing and associated structural damage is loops were obtained, and the
acceptable in a severe earthquake. The actual strength of each
structure should be able to undergo connection under cyclic
large deformations without collapse. loading was compared with
The connections between units in the static ultimate design
precast box-type buildings are seldom st ength.
capable of transferring loads which
would cause the precast units to yield. Although the design strength
Therefore, the connections themselves
was exceeded by up to
should be able to yield and sustain large
deflections when loaded to their design 30 percent in the initial
ultimate load and beyond in an earth- cycles, the strength began
quake. to fall as the number of load
The tests described here were made cycles increased, and was
on a commonly used welded headed generally well below the
stud connection. There have been sev-
design strength at failure.
eral static or monotonic tests on con-
nections of this type2' 3' 4 and design Deflections at failure were
data are available for calculating their from seven to twenty-four
static shear and pullout capacity.5'7
times the theoretical elastic
However, there is little or no informa-
tion on their behavior under cyclic or deflection at the design
alternating loads such as those occur- ultimate strength, but
ring during an earthquake. because the connections
lose both strength and
stiffness before failure, their
Welded Headed
Stud Connection ductility does not justify any
reduction in the lateral
The type of connection considered here forces used for earthquake-
is shown in Fig. 1. Short lengths of resistant design.
angle, each with two headed studs
welded to it by the fusion process, are If the connections are
embedded in the edges of each pre- properly designed and
cast unit.
detailed they should perform
A piece of bar or rod is site welded
between two adjacent angles to make satisfactorily in buildings
a connection. The number of connec- designed as box systems.
tions required along each edge is gov-

PCI JOURNAL/May-June 1976 71


TYPICAL PANEL
ASSEMBLY

Fig. 1. Welded headed stud connections showing typical ap-


plications in precast buildings.

erred by the design shear and pullout of the connection angle, producing a
forces. moment which is resisted by a com-
pressive force C and a pullout force P,
assumed to act through the studs as
Method of Testing shown. These forces are equal to 10
and 15 percent of F for 12 and 10-in.
The connections were loaded in the
long connection angles, respectively.
test rig shown in Fig. 2. A 2 x 4-ft
This system of forces is not identical
panel with an embedded connection
to the forces resulting from the story
angle was clamped in a vertical posi-
shears and panel inertia forces acting
tion. The cyclic shear force F was ap-
in a box-type building during a severe
plied to this connection angle as shown
earthquake. Further, when units are
in Fig. 3. connected together in a building, each
A 5 x 12 x 5/s-in, steel plate was
connection angle is restrained from ro-
welded to the angle with a Y4-in. spat-
tation as long as adjacent panel edges
er. A displacement controlled hydraulic
remain parallel. However, it is felt that
jack with its axis vertical applied the this test method is sufficiently realistic
cyclic force to the steel plate. The to provide useful data.
loading system did not prevent either
pullout of the studs or rotation of the
connection about a horizontal axis. Connections Tested
The system of forces acting on a
connection is shown in Fig. 3. The Details of the six connection angles
cyclic force F acts 7/8 in. from the face tested are shown in Fig. 4. Each angle

72
has a $/s-in. diameter, 6-in, headed p 4/3 jJ 4/8
stud welded 2-in, from each end. The
studs had a specified ultimate tensile
P uy] ± L'-
v
<1

strength, f, of 60,000 psi, and a spe- For stud capacity:


cified yield strength of 50,000 psi.
Each connection angle was cast in
a 2 x 4 ft x 8-in, concrete panel with an
[ P u^ 2 + ^Vus]2
average 28-day strength f' of 4600 psi. The design strengths shown in Table
A No. 4 grade 60 reinforcing bar was 1 were calculated from the above equa-
placed close to the studs in some of tions. It should be noted that the PCI
the panels, as shown in Fig. 4. recommends an additional load factor
As a result of a fabrication error, of 4/3 for the design of this type of
Connection B3 had studs which were connection.L $ This would be equiva-
bent and tack welded to a panel rein-
forcing bar (see Fig. 4). It is included
in the test series to draw attention to
the consequences of this kind of error.

Design strength
The static ultimate design strength of
each connection was analyzed using
the procedure recommended by the
PCI Connections Manual and PCI De-
sign Handbook.5,7
The ultimate concrete shear strength
for each stud, V'u,, based on the shear-
friction concept, was found to be 14.1
kips. The ultimate pullout strength,
calculated using the area of the
45-deg shear cone, reduced because the
full cone intersects with the surfaces
of the panel, was 29.9 kips for the
Series A connections and 17.5 kips for
the Series B. The ultimate shear ca-
pacity of a stud exclusive of the con-
crete, V', was 13.8 kips, and the ulti-
mate tension capacity exclusive of con-
crete, P'u8, was 16.6 kips.
The design strength of each connec-
tion was then calculated assuming that
the applied shear force F is divided
equally between the two studs, and
that the pullout capacity of the stud-
carrying tension is not affected by the
adjacent stud, which carries compres-
sion. Combined shear, V,,, , and tension,
on a single stud was assumed to
govern, and applied using the PCI in- Fig. 2. Test rig for cyclic loading.
teraction equations. The loading yoke applies cyclic
For concrete capacity: loads directly to the connection.

PCI JOURNAL/May-June 1976 73


lent to reducing the calculated design followed by cycles at increasing ampli-
strengths of the connection by 25 per- tude up to failure. The loading se-
cent and using normal load factors. quence for each cyclic test is shown in
Figs. 6 to 10.
Although the frequencies and the
Test Loading loading sequences in these tests are
different from those of actual earth-
Connection Al was loaded monoton- quake loading, the results obtained
ically to failure. The load was in-
from this type of test can be used for
creased in a series of small increments predicting the behavior of these con-
and the test took approximately 30 nections during an earthquake.
min to complete. The other five con-
nections were subjected to cyclic load-
ing at frequencies in the range of 0.01 Test Results
to 0.02 Hz.
Load versus deflection hysteresis The test results obtained for each con-
loops were obtained for each connec- nection are summarized in Tables 1
tion (see Figs. 5 to 10). The load was and 2. Connection B3, which is ano-
measured by a load cell on the hy- malous because of a fabrication error,
draulic jack, and the deflection was is discussed separately.
measured between the 5 -in, plate
welded to the connection angle and the Monotonic test
top of the panel. Connection Al exhibited considerable
The cyclic tests all began with a ductility under monotonic loading (see
number of cycles in the elastic range, Fig. 5). The strength of the connection

I XIS OF HYDRAULIC JACK

ro F
.0 0:^..^ b.®CS
vP
C SPACER I i

TRANSVERS E AXIS
OF LOADING YOKE
P
FACEPLATE I^

1k 5^8
^^8 5 N

Fig. 3. Forces acting on a connection during a test.

74
DETAILS OF STUDS &
CONNECTION
PANEL REINFORCEMENT

Al

4"x3'x $ Lx12' LONG

A2.A3
aao

x3z3l8 L x1 "LONG

B1 °Q ^^^

3 x3 x /Lx12 LONG
oo'o & Q
B2

3 x2^x3%8Lx10`LONG ^
-0aaao

B3 9. n.:

3x2x3/8 Lx10 LONG

Fig. 4. Details of connections tested, showing the


arrangement of the studs and the fabrication
error in Connection B3.

0
0
J

DEFLECTION (in.)
Fig. 5. Load-deflection curve (Connection Al) for
monotonic loading to failure.

PCI JOURNAL/May-June 1976 75


Fig. 6. Load-deflection loops (Connection A2) showing stable behavior after
35 cycles of loading. Groups of curves have been separated for greater
clarity.

at yield exceeded the ultimate design Cyclic loading above the


strength then began to fall as the de- stability limit
flection increased. It remained above After three cycles of loading to about
design strength and began to increase 70 percent of the expected yield
again prior to failure, which occurred strength, Connection A2 was loaded to
at a deflection of about seventeen times about 90 percent of the expected yield
the deflection at yield. strength in Cycle 4 (see Fig. 6). The
stiffness of the connection then began
Cyclic loading in the elastic range to fall, the width of the hysteresis loops
Cyclic testing of each connection be- began to increase, and there was in-
gan with several cycles of loading in creasingly marked "hardening spring"
the elastic range. In each case (except behavior.
Connection B3), these initial cycles The displacement amplitude of the
produced stable, narrow load-deflec- jack was held constant from Cycle 4
tion hysteresis loops (see Figs. 6 to 9), to Cycle 38, but the falling stiffness of
with no degradation of stiffness for the connection together with the flex-
cycles of loading up to about 80 to 85 ibility of the loading apparatus led to
percent of the expected yield strength. steadily increasing deflections and de-
The stability of the loops for loads in creasing loads, until the loops stabilized
this range (which approached the ulti- in Cycle 34 or 35.
mate design strength of the connec- The continuing gradual changes in
tion) is a significant result. the hysteresis loops during Cycles 4

76
Fig. 7. Load-deflection loops (Connection A3). Note the relatively large
deflections reached before failure.

to 34 show that the loading was just tained for cycles with constant jack
above the limit for stable behavior, un- displacement allow approximate sta-
til Cycle 35. Approximate stability limit bility Iimit curves to '' be established,
curves are shown in Fig. 6 for this similar to those for Connection A2.
connection. Using the hysteresis loops for the
Degradation of stiffness and increas- cycles when the jack displacement was
ing loop width would be expected if increased (e.g., Cycle 14, Fig. 7), ap-
the load-deflection curve crossed these proximate yield strength envelopes can
curves. Loop behavior would be stable also be constructed. These show a con-
if load reversal occurred before the tinuing loss of strength with an in-
stability limit was crossed. creasing number of cycles of load, and
are quite different from the monotonic
Cyclic loading up to yield load-deflection curve. The maximum
•Connections A3 and B2 were loaded load in each direction in the cycle
up to yield after the initial cycles in preceding failure is shown in Table 1.
the elastic range, and then subjected Connection B1 was also loaded up
to steadily increasing deflections (see to yield, but there was a much bigger
Figs. 7 and 9). After each increase, increase in deflection in each succes-
the displacement amplitude of the jack sive cycle than for Connections A3 or
was held constant for no more than B2 (see Fig. 8). The strength of this
-three or four cycles (e.g., Cycles 10, connection fell for loading in one di-
11, 12, and 13, Fig. 7). The loops ob- rection, but not the other, and it failed

PCI JOURNAL/May-June 1976 77


Table 1. Summary load data for various types of connections
(also refer to Fig. 4).
Load in cycle
Connection Design ultimate strength Maximum load before failure
Concrete Steel Up Down Up Down
(kips) (kips) (kips) (kips) (kips) (kips)

Al 27.2 27.2 35.4 -- -- --


A2 27.2 27.2 31.5 30.2 7.0 8.0
A3 27.2 27.2 29.3 27.0 11.1 12.6
B1 26.4 27.2 31.8 28.0 29.2* 25.5*
82 25.5 26.9 30.0 32.0 15.8 14.0
B3 25.5 26.9 23.4 24.0 6.0 6.5

* These values are for Cycle 4. Failure occurred in Cycle 7 after two cycles
at reduced load.

at 32 kips, a load substantially in ex- tests are now being carried out so that
cess of the ultimate design strength more precise predictions can be made.
(although the strength in the other di-
rection had fallen below the design Ductility
strength). The maximum deflection in each di-
From Figs. 7, 8, and 9 it seems clear rection in the cycle prior to failure,
that increasing the number of cycles X,,,^, is given in Table 2. It is clear
above the stability limit will cause that these connections have a consider-
an increasing reduction in the yield able capacity to deflect beyond their
strength, and that the yield strength deflection at yield, and in that sense
envelope for each connection will tend they might be called "ductile." Their
to approach the stability limit as a use would allow a box-type building
lower limit. However, the data from to sustain large, permanent deforma-
these tests are limited, and further tions without collapsing.

Table 2. Summary of deflection data and mode of failure for various types
of connections (also refer to Fig. 4).
Theoretical Maximum deflection (X µQ Mode of Cycles
max ) failure at failure
Connection deflection in cycle before failure (Ratio of
Xmax to XX)
Xt Up Down
(in.) (in.) (in.)

Al 0.014 0.5* -- 36 Concrete --


A2 0.015 0.21 0.18 12 Stud 57
A3 0.014 0.42 0.26 19 Stud 22
B1 0.013 0.1 0.1 8 Concrete 7
B2 0.014 0.21 0.23 15 Stud 19

B3 0.019 0.16 0.15 8 Stud 14

* Monotonic test. Note that Xmax is deflection at failure.

78
7
30

EFLECTION (in.)
-10

5 Fig. 8. Load-deflection loops


Z
-20
(Connection B1). Rapid increase
in the applied deflection led to
failure after relatively few cycles.

-3 0

i ii
1
1AFAPiLU
t
0.3 0.2

^/^
iUifiiiiii

■ !Ilf.hIIII
LII11(I1
.. - .
—YIELD ENVELOPE ''' '

PCI JOURNAL /May-June 1976 79


Fig. 10. Load-deflection loops (Connection B3). The
relatively poor performance resulted from a
fabrication error.

A ductility factor, S for each con-


p ,, like those tested here, which tend to
nection is given in Table 2, which is lose both strength and stiffness under
computed from: cyclic loading.
µl = X,ma./X I (3) Cracking and mode of failure
where The first observable sign of distress on
X,,,,Q, peak deflection in cycle pre-
= each connection was crushing of the
ceding failure concrete at the ends of the connection
Xl = theoretical linear deflection angle, accompanied by vertical tension
at design ultimate strength cracks in the concrete panel parallel
assuming a constant stiffness to the angle and several inches away
is equal to initial elastic stiff- from each leg. This could be seen first
ness at a load of about 70 percent of the
The ductility is found using the design strength.
smaller of the two values of . X,, As cyclic loading progressed, there
in Table 2. It should be emphasized, was continued crushing and spalling of
however, that few of the assumptions the concrete above and below the
made about the behavior of buildings angle, and growth of the tension cracks.
which are classed as "ductile" for earth- Uncrushed concrete was exposed at
quake resistance design would be valid each end of the angle as it slipped
for box-type buildings with connections up and down during each cycle.

80
There must also have been crushing
and failure of the concrete around the
studs as the test progressed. Further-
more, it is likely that some of this con-
crete simply fell out during each cycle,
allowing the studs to deform, and ex-
plaining in part both the steadily
falling stiffness and the hardening
spring behavior observed in every
cyclic test.
As the applied deflection was in-
creased, the tension cracks in the panel
increased in length and width, and the
connection began to rotate slightly as
first one stud and then the other began
to pull out. The connections in a build-
ing would probably be restrained
against this rotation, but they might
be subject to pullout forces as a result
of inertia loads on the panels.
Connections Al and B1 failed by
concrete failure when a large block of
concrete surrounding the studs broke
away (see Fig. 11). The other connec-
tions (except Connection B3) failed Fig. 11. Connection B1 failed when
when one of the studs broke close to a large block of concrete surround-
the fusion weld (see Fig. 12). ing the studs broke away.

Fig. 12. Connection A3 failed after the upper stud


broke close to the angle.

PCI JOURNAL/May-June 1976 81


This stud failure apparently occurred of the connections will fall with an in-
because each stud was eventually re- creasing number of cycles, and the
strained for only a short length, close yield strength envelope will tend to
to the head so that plastic hinges approach the stability limit.
formed close to the connection angle 4. The deflections reached before
during each half cycle of loading. The failure were from seven to twenty-four
mode of failure for each connection is times the theoretical elastic deflection
shown in Table 2. corresponding to the design ultimate
Connections A2 and A3 both had strength.
a panel reinforcing bar outside the 5. These connections, if properly de-
studs, but 4these connections did not signed and detailed, appear to be suit-
carry higher loads than the other con- able for use in earthquake-resistant
nections. Connections with the studs buildings designed as box-type systems.
parallel to the front of the panel did
seem to be able to sustain somewha
deflections than those with the Acknowledgment
studs at 45 deg to the front face. The
effect pf panel reinforcement and stud This research was financed by the Na-
arrangement is the subject of a further tional Research Council of Canada, and
study. carried out at the University of British
Columbia.
Behavior of Connection 83
Connection ` B3, as can be seen from References
Fig. 4, had the studs bent into an in-
correct position. In addition, the studs 1. PCI Design Handbook, Prestressed
were tack-welded to the panel rein- Concrete Institute, Chicago, Illinois,
forcing bar. In spite of the adverse 1971, pp. 10-3 to 10-10.
effects of the stud placement on both 2. PCI Committee on Connection De-
the strength and stiffness of this con- tails, "Summary of Basic Informa-
nection, which were noticeable even in tion on Precast Connections," PCI
the elastic range, the studs failed at JOURNAL, V. 14, No. 6, December
the tack weld. 1969, pp. 14-58.
3. Concrete Anchor Design Data, Man-
ual No. 21, Nelson Stud Welding,
Summary and Conclusions Division of Gregory Industries, Inc.,
1961.
Simulated earthquake loading of one 4. Venuti, W. J., "Diaphragm Shear
type of welded headed stud connection Connectors Between Flanges of Pre-
used in precast buildings led to the stressed Concrete T-Beams," PCI
following conclusions: JOURNAL, V. 15, No. 1, February
1. The PCI procedures for calculat- 1970, pp. 67-68.
ing the ultimate design strength of 5. PCI Manual on Design of Connec-
these connections under static loading tions for Precast Prestressed Con-
give conservative results. crete, Prestressed Concrete Institute,
2. The strength of the connections in Chicago, Illinois, 1973, pp. 37-38.
the first cycles of loading up to yield 6. ibid, pp. 21-22.
will be approximately the same as the 7. PCI Design Handbook, Prestressed
strength in monotonic loading. Concrete Institute, Chicago, Illinois,
3. If cyclic loading is continued 1971, pp. 6-18 to 6-19.
above the stability limit, the strength 8. ibid, p. 6-4.

82
V' ultimate concrete shear capac-
Notation ity of a stud
V' ultimate shear capacity of a
C = compressive force in a stud stud exclusive of concrete
subject to test load strength
F = test load applied to connec- V = ultimate shear strength of a
tions stud subject to combined ten-
P = pullout force on a stud sub- sion and shear
ject to test load XZ = theoretical deflection of con-
Pu = ultimate pullout strength of a nection at design ultimate
stud subject to combined ten- strength assuming constant
sion and shear stiffness equal to initial stiff-
P' = ultimate pullout strength of a ness
stud controlled by the concrete Xm = maximum deflection of con-
P' ultimate tension capacity of a nection in cycle preceding
stud exclusive of concrete failure
strength [LI, = ratio of Xma, to Xa

Discussion of this paper is invited.


Please forward your comments to
PCI Headquarters by October 1, 1976.

PCI JOURNAL/May-June 1976 83

Potrebbero piacerti anche