Distance between two headers is to short, Insulation will clash. pls increase.
Distance between two headers is to short, Insulation will clash. pls increase.
There are so many piping. Proper support from civil to be design, assignment to be sent if
required.
Chiller line clash with column.
CW line clash
Do not reduce size of line for such small portion.
Acid hose connection valve to be placed in side the curb wall end.
Caustic hose connection valve to be extended towards the curb wall end.
Isolation valve required.
Caustic line, chlorine line, water line compressed air, instrument air, line etc to be extended
up to chlorine shed.
Pls droop line (Acid & caustic) outside of rack & also near column to take support.
All tapping from process line as per PID 1700. Is not shown.
RO feed pump along with piping is not shown.
Also RO water line to boiler & RO reject line to flushing tank T-1101 to be show.
Condensate tank T-1702 along with is not found
Sealing water supply & return line all tapping to be shown as per PID