Wiring diagrams Compact NSX100 to 630

Fixed circuit breakers

Power Micrologic Remote operation

Upstream CB a (+) a (+)


3P or 4P NSX cord

Z1
Z2
Z3
Z4
Z5
N L1 L2 L3 SDE 81
DB115707

+ - BPO BPF
HL

82 84

D2

C2

A4

A2

B4

B2
Z1

Z2
MN MX
T1
Q T2 auto
I 0 I
ou manu
Z3
Z4

U Z5

A1
L1
D1

C1
a (-)
manu SDE

a (-)

Motor mechanism (MT)


NSX cord
3P + N
N L1 L2 L3
Z1
Z2
Z3
Z4
Z5

a (220/240 V)

+ -
Downstream CB

HL
BSCM

B4
Z1

Z2

Q I U T1

T2
Z3
Z4
Z5

ENVT auto 0 I
manu
A1

ENCT
H2 T1 a

Communicating motor
H1 T2 mechanism (MTc)

Micrologic A or E Remote operation


A/E Communication MN: undervoltage release
H(WH), L(BL): data or
- (BK), + (RD): 24 V DC power supply
MX: shunt release
A/E ZSI (Zone Selective Interlocking)
Z1: ZSI OUT SOURCE Motor mechanism (MT)
Z2: ZSI OUT A4: opening order
Z3: ZSI IN SOURCE A2: closing order
Z4: ZSI IN ST (short time)
Z5: ZSI IN GF (ground fault) B4, A1: power supply to motor mechanism
Note: Z3, Z4, Z5 for NSX400/630 only. L1: manual position (manu)
A/E ENCT: external neutral current transformer: B2: SDE interlocking (mandatory for correct operation)
- shielded cable with 1 twisted pair (T1, T2)
- shielding earthed at one end only (CT end). BPO: opening pushbutton
Connection L = 30 cm max. BPF: closing pushbutton
- maximum length of 10 metres
- cable size 0.4 to 1.5 mm2 Communicating motor mechanism (MTc)
- recommended cable: Belden 8441 or equivalent. B4, A1: motor mechanism power supply
E ENVT: external neutral voltage tap for connection to the BSCM: breaker status and control module
neutral via a 3P circuit breaker.