INSTRUCTION MANUAL
General description
The optional expert menu of the remote control type HS contains functions of the fault indicators of the
FLA3.1 product line that technically skilled users may want to change. All functions should be changed
carefully as this influences the performance of the indicator and the battery lifetime.
Commands
EF VOLTCHECK: Earth-fault voltage check
The interval tc for the voltage check after the detection of a possible fault by the
di/dt algorithm is factory-set to 1 sec. (Please refer to figure 1.) With this function this
interval can be changed.
This function is available for fault indicators type FLA3.1V and type FLA3.1VL with
firmware version 113 or higher.
When the short transmission function is enabled fault indications will be transmitted
via short transmissions similar to the transmissions used for datalogging. (Please
see the instruction manual for more details.)
Using short transmissions reduces battery power consumption of the indicators and
saves time for the remote indication procedure. The RTU will receive fault indicati-
ons within approx. 10-30sek.
INSTRUCTION MANUAL
Precondition for the usage of this function is a RIS-FS module in permanent re-
ceiving mode which implements EMG Modbus protocol Rev. 9 or later. Due to the
increased power consumption for permanent receiving mode of the RIS-FS, integra-
tion into a non-rechargable battery-powered RTU is not recommended.
Selectable values:
OFF: Standard procedure enabled. Works with all RIS interfaces.
ON: Short transmissions enabled. Works only with RIS-FS interface.
This function is available for fault indicators of the FLA3.1 product family with firm-
ware version 113 or higher.
This function is available for fault indicators of the FLA3.1 product family with firm-
ware version 109 or higher.