Sei sulla pagina 1di 88

Surge Arrester

May 21, 2019

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General 1


Surge Arrester

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General 2


Content:
1. Basics
2. Insulation coordination
3. History
4. Classification of Lightning arrester
5. Principle of operation
6. Manufacturing process
7. Common terms used
8. Designing
9. Testing
10. Field testing
11. Causes of failure
12. New developments.

3
Basics of Lightning Arrester

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General 4


Basics:

5
Definitions of Lightning Arrestor
According to most definitions, a Lightning Arrester is….

“A Device Used on Power Systems above 1000V to Protect


other Equipment from Lightning and Switching Surges”

It is not a Lightning Rod.

Although Lightning Rods are devices that divert


lightning surges to ground, they are simple
conductive terminals that are always at ground
potential and are never energized.

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


What exactly does a lightning arrester do?

• It Does not Absorb the Lightning.

• It Does not Stop the Lightning.

• It Does Divert the Lightning to Ground.

• It Does Clamp (limit) the Voltage produced by the Lightning.

• It Only protects equipment electrically in parallel with it.

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Lightning Arrester:

……..Also called as Surge Arrester or Surge Diverter

Used for protection of power systems equipment's from


surges like, Lightning, Switching, Steep Currents &
Temporary over voltages

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Insulation Coordination

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General 9


Insulation Coordination

“The process of correlating the insulation


strengths of electrical equipment with expected
over voltages and with the characteristics of
surge protective devices”

10
Insulation Coordination Principle

11
Fundamentals of Insulation Coordination

12
History of Lightning Arrester

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General 13


History of Lightning Arrester

• Lightning Arresters were first used


on Telegraph lines dating back to
the 1840’s.
– The first known patent on an arrester is
1855 and the arrester is called a
atmospheric discharge device.
US patent 13389
– The first US patent to use the term
arrester was issued on August 7, 1860.
• The first power system Arresters
appeared after the first overhead
power systems began to appear. Circa
1890

Curtsey: www.arrestersworks.com

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


History of Lightning Arrester

• The Silicon Carbide Arrester Era 1926-


1982
– Began in 1926 with the introduction of the
Crystal Valve arrester by ESSCo

Curtsey: www.arrestersworks.com

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Brief History of Lightning Arrester

• The Silicon Carbide Arrester Era 1926-1982

Curtsey: www.arrestersworks.com

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Brief History of Lightning Arrester

The SiC Arrester Issues


– High Front of Wave
Gap Section

Sparkover
– Power Follow Current
– Gap Degradation
Porcelain

– Many parts
Air Volume

SiC Block

SiC Block

Curtsey: www.arrestersworks.com

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Brief History of Lightning Arrester

Gap Section

Porcelain
Air Volume
SiC Block

SiC Block

Curtsey: www.arrestersworks.com

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Brief History of :Lightning Arrester

Degraded Gaps of
SiC Surge Arrester

Curtsey: www.arrestersworks.com

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Brief History of Lightning Arrester

•Metal Oxide Varistor Based Arrester


also called Gapless Arresters:
•First Discovered in 1967 in Japan by Dr.
Matsuoko and team.
•First applications were on low voltage
devices
•GE Developed the first High Voltage devices
and introduced the first MOV Arrester in
1977 (Tranquil)
•McGraw Edison introduced the first
Dr. Michio Matsuoka distribution MOV arrester in the US in 1981
Inventor of Zinc Oxide Varistor
(VariSTAR)
•First Produced in Polymer Housing by
Hubbell in 1987

Name : Nitin Jha Division : S-4 Lightning Arresters Category : General


Advantage of Gapless Arresters:

• Improved reliability due to simplicity of the design.


• Superior protective characteristics.
• Minimum energy absorption commensurate with the
protective levels provided.
• Superior performance on low impedance circuits(e.g
cable and capacitor application)
• Gentle operation due to absence of spark gaps
• Superior energy absorption capability
• Excellent pollution performance

21
Classification of Lightning Arresters

Name : Nitin Jha Division : S4-R&D Category : General 22


Classification of Lightning Arrester:

• Surge Arresters on the basis of their housing are


broadly Classified as:
– Polymeric Type Surge Arresters
– Porcelain Type Surge Arresters

• On the basis of energy dissipation capability:


– Distribution class
– Class 2
– Class 3
– Class4
– Class 5

Name : Nitin Jha Division : S4-R&D Category : General


Classification

• As per IEC:60099-4 the Arresters are classified


on the basis of their Standard Nominal Discharge
Current i.e.
– Station Class for 10kA & 20kA NDC.
– Intermediate or Distribution Class for 5kA NDC.
– Secondary Distribution Class for 1.5kA NDC or below.

Standard Nominal Discharge Current


20kA 10kA 5kA 2.5kA 1.5kA
Rated Voltage Ur 360kV to 3 kV to Up to Up to -
(kVr.m.s) 756kV 360kV 132kV 36kV

Name : Nitin Jha Division : S4-R&D Category : General


Principle of Operation of
Lightning Arresters

Name : Nitin Jha Division : S4-R&D Category : General 25


Principle of Operation

• Offers High Resistance during low voltage.


– Not in circuit during normal working conditions.
• Offers low Resistance during High or Over voltage
conditions.
– Diverting Surge Energy to the ground
• Non Linear Resistance.
I = K (V)α

K= Material Constant
α= Non Linear Constant.

I = Current
V = Voltage

Name : Nitin Jha Division : S4-R&D Category : General


Heart of surge Arrester-MOV

At the Heart of All


Arresters is the Metal
Oxide Varistor (MOV)

The MOV Disk is a


Semiconductor that is
sensitive to Voltage and has
its own VI Characteristic

Name : Nitin Jha Division : S4-R&D Category : General


VI Characteristics of MOV

Name : Nitin Jha Division : S4-R&D Category : General


MOV Overview

By magnifying the MOV


material 5000 times,
MOV Metal Oxide Grains and
Dopants in the
material can be
discerned

Each MOV Disk with a


35mm diameter and a
35mm height contains
about
28 Billion
MOV Grains

Name : Nitin Jha Division : S4-R&D Category : General


MOV Overview

MOV grains and their junctions are the electronics


switches that turns ON and OFF in unison to divert the
lightning around the equipment
Spinal Phase
ZnO Grain
ZnO Grain

Very
Nonlinear
Part of
Circuit

The Switches ZnO Grain

are at the ZnO Grain Doped


Junction
Between
junctions Grains
Antimony
between the ZnO Grain
Phase
10 micro meters
grains
ZnO Grain ZnO Grains
are low
impedance
linear ZnO Grain
element of
circuit

Name : Nitin Jha Division : S4-R&D Category : General


MOV Overview
A lightning arrester is essentially a collection of billions of
microscopic junctions of Metal Oxide Grains that turn on and off in
microseconds to form a current path from the top terminal to the
ground terminal of the arrester. Current
path during
Lightning

Spinal Phase
ZnO Grain
ZnO Grain

Very
Nonlinear
Part of
Circuit

ZnO Grain

ZnO Grain Doped


Junction
Between
Grains
Antimony
Phase
ZnO Grain
10 micro meters

ZnO Grain
ZnO Grains
are low
impedance ZnO Grain
linear
element of
circuit

Name : Nitin Jha Division : S4-R&D Category : General


Equivalent Circuit of ZnO Block

Name : Nitin Jha Division : S4-R&D Category : General


V-I characteristics of an MO Arrester (420 kV)

33
Voltage current waveform of MO Arrester

34
Arrester VI Characteristics

Name : Nitin Jha Division : S4-R&D Category : General


How Lightning Arrester Works?
When an Excess over voltage
Arrester is on is clipped by the
the system Arrester
insulator
flashover risk
Arrester
can be lowered

Excess over voltage


is bypassed through
Arrester in terms of
energy i.e. V x I x T

Name : Nitin Jha Division : S4-R&D Category : General


How Arrester divert the surge

The arrester diverts much of the charge to ground, but


in the process, it adsorbs energy.

Name : Nitin Jha Division : S4-R&D Category : General


Manufacturing process

Name : Nitin Jha Division : S4-R&D Category : General 38


Composition of ZnO Block

• The ZnO Block consist of :


– ZnO - 90%
– And remaining are the additives which gives the
nonlinear property to the ZnO Block. These
additives are:
– SiO2
– Cr2O3
– MnCO3
– Sb2O3
– Bi2O3

Name : Nitin Jha Division : S4-R&D Category : General


ZnO Block manufacturing

Name : Nitin Jha Division : S4-R&D Category : General 1


ZnO Block manufacturing

Name : Nitin Jha Division : S4-R&D Category : General 1


ZnO Block manufacturing

Name : Nitin Jha Division : S4-R&D Category : General 1


ZnO Block manufacturing

Name : Nitin Jha Division : S4-R&D Category : General 1


Manufacturing Process

Name : Nitin Jha Division : S4-R&D Category : General


CGL-Gapless surge Arrester from 3kV to 400kV

Name : Nitin Jha Division : S4-R&D Category : General


Construction of Surge Arrester

• Metal oxide arrester consists of a stack of


• ZnO discs mounted in a sealed porcelain
• housing.
End cups
Spring

Insulator ZnO disc

Spacer Tube

Name : Nitin Jha Division : S4-R&D Category : General


Basic component of Distribution Arrester

Name : Nitin Jha Division : S4-R&D Category : General


Classification of ZnO Blocks

Name : Nitin Jha Division : S4-R&D Category : General


Pressure Relief Plate Assembly

Name : Nitin Jha Division : S4-R&D Category : General


Common Terms in Lightning Arresters

Name : Nitin Jha Division : S4-R&D Category : General 50


General Terminologies

• Rated Voltage (Ur)


• Continuous Operating Voltage (Uc)
• Maximum Continuous Operating Voltage
(MCOV)
• Reference Voltage (Uref)
• Residual Voltage (Ures)

Name : Nitin Jha Division : S4-R&D Category : General


General Terms

• Rated Voltage- Decides Temporary over voltage


capability
• MCOV- Decides life of LA.
• Residual Voltage – Decides Protection Level
• Line Discharge Class- Decides Energy Handling
Capability.
• Pressure Relief Class- Decides Short Circuit
Capability.

Name : Nitin Jha Division : S4-R&D Category : General


Lightning Impulse Current

• 8/20 (pronounced 8 by 20) current wave is used by manufacturers


to simulate lightning current to test distribution arrester designs
• “8” is the peak rise time in microseconds
• “20” is the time to reach 50% of the peak value
• Real world lightning usually has a 1 to 4 microsecond rise time,
especially with repeat.

.5 -10 µs
20-100µs

0µs

Name : Nitin Jha Division : S4-R&D Category : General


Switching Impulse Current

– The switching surge, is a self induced surge on the


power system
– It is called a switching surge because it is generally
associated with some sort of switching activity
– Switching action does not cause a switching surge
of any significance on systems below 200kV
– As per IEC the Switching Impulse Current front time
should be >30μsec & <100μsec.

Name : Nitin Jha Division : S4-R&D Category : General


Over Voltage in the protective equipment by Arrester
Surge

Line

Uequ.
Ures.

Uequ. = Ures. + (2*S*Xs)/Vtw


Xs = Distance between arrester and Protective
equipment
Ures. = LI protection Level of the arrester (kV)
S = Front steepness of over voltage (kV/µs) Arrester Transformer
S~ 11xMCOV (kV/µs)
Vtw= Prorogation speed of surge
for OHL= 300 m/µs
for cables= 150 to 200 m/µs

Name : Nitin Jha Division : S4-R&D Category : General


How Class of Blocks are decided?

X-Axis = Ratio of SI
Residual Voltage to
the Rated Voltage.

Y-Axis= Specific
Energy in kJ/kV

Name : Nitin Jha Division : S4-R&D Category : General


Designing of Lightning Arresters

Name : Nitin Jha Division : S4-R&D Category : General 57


System / Arrester Parameters

 Uwl= Lightning Impulse withstand Level

Insulation  Uws= Switching Impulse Withstand Level


Level  Wpl= Lightning Impulse Protection Level
Uwl / Uws
Protection  Wps= Switching Impulse Protection Level
Level  TOV= Temporary over voltage
Upl / Ups
 Uc= Continuous operating voltage

 Um=maximum system voltage

TOV Capability
TOV
Ur
Uc MCOV

SYSTEM PARAMETERS ARRESTER PARAMETERS

Name : Nitin Jha Division : S4-R&D Category : General


Inputs Required for Designing
– System Voltage
– Rating of Surge Arrester
– Class of surge arrester
– System TOV
– BIL level
– Type of surge arrester and its nominal discharge
current
– Terminal connector, Type of earth terminal and
surge counter (if any).

Name : Nitin Jha Division : S4-R&D Category : General


Design Procedure

• The design is carried out in two major steps:


– Matching the Electrical characteristics of the
arrester to the system's electrical demand.
– Matching the mechanical characteristics of the
arrester to the system's mechanical and
environmental requirements.

Name : Nitin Jha Division : S4-R&D Category : General


Flow Chart for Electrical Parameter Selection
System Voltage
(Um)

System Earthing Rated Voltage (Ur0)

Earth Fault Duration/Factor Select Max of


both rated voltage

Rated Voltage
Other TOV Ur1= Utov/T1........
(Amplitude & Duration) From TOV curves

Line
Line Discharge
Discharge
Class & Arrester Type
Energy

Choose
Next
Arrester Protection Levels Higher
Upl and Ups at coordination Discharge
currents Class
No
Calculation of Protection Electrical
Margins
Acceptable Selection
[(Uwl/Upl)-1] X 100 margin
yes
Complete
[(Uws/Ups)-1] X 100

Name : Nitin Jha Division : S4-R&D Category : General


Flow chart for Mechanical Design

Pollution Level creepage Distance

Short Circuit No
Housing Dimension
Rating

Adequate Mechanical
safety
margin?
Selection
Yes completed
Terminal Load

Wind Load Static /


Dynamic
Combination Our tested mechanical
strength for this load
Seismic Load

Other Load

Name : Nitin Jha Division : S4-R&D Category : General


Testing of Lightning Arresters

Name : Nitin Jha Division : S4-R&D Category : General 63


Tests on Lightning Arresters
Test on Arrester as per IEC:60099-4

Capabilities Tests
Voltage limiting capabilities Residual voltage test
High current short duration & low
Impulse discharge capability
current long duration test
Power frequency voltage withstand
Temporary over voltage test
capability
Mechanical withstand force withstand
Bending moment & seismic test
capability
Electrical insulation withstand
Dielectric test
capability
Environmental withstand capability Pollution, aging & contamination test

Name : Nitin Jha Division : S4-R&D Category : General


List of Type Test as per IEC:60099-4

Test Block Complete Product


1. Insulation Withstand Test on Arrester
Housing NO Yes
2. Residual Voltage Test
a. Steep current Impulse Voltage test. Yes NO
b. Lightning Impulse Residual Voltage Test. Yes Yes
c. Switching Impulse Residual Voltage test. Yes NO
3. Long Duration Impulse Withstand Test Yes NO
4. Operation Duty Test:
a. High Current Impulse operating duty test. Yes NO
b. Switching Surge Operating Duty Test Yes NO
5. Short Circuit Test (Pr. Relief) NO Yes
6. Arrester Disconnector/ Fault Indicator Test Yes NO
7. Pollution Housing Test NO Yes
8.Internal Partial Test NO Yes
9. Bending Moment test NO Yes
10. Environmental Test NO Yes
11. Seal Leakage Test NO Yes
12. Radio Interference Test (RIV Test) NO Yes
13. Accelerated Ageing test Yes Yes

Name : Nitin Jha Division : S4-R&D Category : General


List of Routine Test as per IEC:60099-4

Test Block Complete Product

1. Measurement of Reference
Voltage Test Yes Yes
2. Measurement of Residual
Voltage Test Yes Yes
3. Internal Partial Discharge Test NO Yes
4. Seal Leakage Test NO Yes
5.Long Duration Current Impulse
withstand Test Yes NO
6. Current Distribution on Multi
Column Arresters Yes -

Name : Nitin Jha Division : S4-R&D Category : General


Routine Test on Surge Arrester
Reference Standards :
IEC 60099-4 , ANSI IEEE C62-11 , I S 3070
1) Reference Voltage Test : Measurement of
Reference Voltage at Reference Currents ranging
from 1mA to 7 mA peak.
2) Partial Discharge Test : Test Method as per IEC
270, Acceptable value < 10pC.
3) Lightning Impulse Residual Voltage Test : Residual
Voltage measurement at 250A peak 8/20 uSec
current wave & extrapolation to NDC.
4) Seal Leakage Test : By Vaccum Evacuation Method.

Name : Nitin Jha Division : S4-R&D Category : General


Field Testing of Lightning Arresters

Name : Nitin Jha Division : S4-R&D Category : General 68


Field Testing of Arresters

Common Arrester Field Testing Methods

Infrared Thermography

Partial Discharge Detection

VI Characteristics Change

Leakage Current

Name : Nitin Jha Division : S4-R&D Category : General


Infrared Thermography

*>31.9°C

What is the 30.0

temperature difference 25.0


that should cause 37.2
20.0
concern? 16.5

15.0

*<10.0°C

Name : Nitin Jha Division : S4-R&D Category : General


Infrared Thermography

The fastest growing method of assessing the


condition of arresters is with the use of
infrared Thermography. The reason for its
popularity is its clear differentiation
between a good arrester and one nearing
the end of life.

The reasons for its lack of pervasive use


however is because of two issues.
1.The equipment to perform the analysis is
not common toolbox gear.
2.The process can be time consuming.

Name : Nitin Jha Division : S4-R&D Category : General


Infrared Thermography

This is only

The most significant


possible if the
arrester has been
energized for a
issue with Infrared number of hours

Thermography is that if
the arrester is not
energized, it will not
exhibit overheating and
cannot be assessed.

Name : Nitin Jha Division : S4-R&D Category : General


VI Characteristics Change

120.0
The arrester VI
100.0 Typical VI Characteristic
for a 22kV MCOV Arrester
characteristic is one of the
80.0
most fundamental
descriptors of the health of
Voltage (kV)

60.0
an arrester.
40.0

Leakage Current, Watts Loss and Vref


20.0
tests all measure different aspects of this
0.0
characteristic.
1E-05 0.001 0.1 10 1000 100000
Current (A)

Name : Nitin Jha Division : S4-R&D Category : General


Leakage Current Testing

The Issue
The difficulty of leakage current testing
is separating the capacitive and
resistive currents. The only leakage Voltage
current of any value is the resistive
current. The capacitive current is quite
insensitive to changes in the arrester as
it nears end of life.
For this reason, simple clamp-on amp
meters cannot be used for this
purpose.
Capacitive Current
Total Current
Resistive Current

Name : Nitin Jha Division : S4-R&D Category : General


Leakage Current Testing

The Solution MOV Arrester Conduction Simulation


To effectively measure leakage Disk Voltage Capacitive Current Resistive Current Total Current

current, test equipment that can 5 2


4
differentiate the capacitive 1.5
3
component from the resistive 1
2
component must be used.

Disk Current (mA)


Disk Voltage (kV)

1 0.5

0 0
Oscilloscopes with sensitive voltage -1
-0.5
and resistive current probes as well -2
as 3rd harmonic meters are two -3 -1

examples that work well. -4 -1.5

-5 -2

Name : Nitin Jha Division : S4-R&D Category : General


Leakage Current Testing

Arrester Base Insulators


Another consideration with leakage
current testing is that the arrester
current must be guided through a
unique ground cable where the
current can then be metered. This is
done by raising the arrester off of
ground with insulators and running
the ground lead to the Current
monitor

Graphic Courtesy ABB

Insulators Leakage Current Monitor

Name : Nitin Jha Division : S4-R&D Category : General


Causes of Failure of Arresters

Name : Nitin Jha Division : S4-R&D Category : General 77


Common Causes of Failure of Arresters

– TOV
– Moisture
• This is the single biggest cause of failure of all arrester
designs
• Was a big issue when converting from SiC to MOV.
• Ferroresonance, ungrounded systems are other sources of
TOV failures.
– Animals
• Large birds that contaminate insulators are an issue
worldwide.
• Squirrels are a big issue in many urban areas

Name : Nitin Jha Division : S4-R&D Category : General


Common Causes of Failure of Arresters

– Lightning
• This is a much smaller cause of failure than is some time
thought. This is based on 25 years of analysis of arrester
failures and comparing them to high current failures in the
lab.
– Switching Surges
• This author is unaware of switching surge failures.
– Misapplication
• Applying arresters to ungrounded systems of the wrong
MCOV is a small but real problem

Name : Nitin Jha Division : S4-R&D Category : General


Common Causes of Failure of Arresters
• MOV material can be affected by high current impulses in a subtle
way that permanently changes the VI Characteristic. This high
current change is universally found in all MOV material, however
the amplitude of change can differ from one formulation to
another

Name : Nitin Jha Division : S4-R&D Category : General


S4-New Development
UHV Surge Arresters

Name : Nitin Jha Division : S4-R&D Category : General 81


1200 kV SA Testing at CPRI Hyderabad:

Name : Nitin Jha Division : S4-R&D Category : General 82


SIGNIFICANT ACHIEVEMENT
Rated Voltage= 850kV
MCOV= 723 kV
SIGNIFICANT ACHIEVEMENTS – last 2 yrs
Line Discharge Class= Class 5 (55MJ)
U20kV LI-Residual Voltage= 1700kVp
U2kA SI-Residual Voltage= 1500kVp
Number of column= 04

The First 1200 kV Surge Arrester from CG


successfully commissioned at National
UHV Test Station, PGCIL at Bina in May
2012.

Name : Nitin Jha Division : S4-R&D Category : General 83


Development of 800kV Surge Arrester

Product Specification
Product Type : Lightning Arrester
Rated Voltage : 624 kV
Rated Discharge Current : 20 kA
LI Residual Voltage at NDC : ≤ 1480 kVp
SI Residual Voltage at 2kA : ≤ 1220 kVp
Rated Pr. Relief current : 63kA /0.2 sec &
600A/1 sec
Rated Frequency : 50Hz
Applicable Standard : IEC 60099-4
Customer : PGCIL

Name : Nitin Jha Division : S4-R&D Category : General


Digital Surge Counter:
Indigenously Developed Digital Surge Counter
(DSC-15-1):

We have developed a digital solution which monitors:


• Total leakage current
• Transients on the network by measuring surge counts
• Magnitude of surge counts
• Total Surge Counts
• Date and time of occurrence
• Provides real-time surge and total leakage current information to control room through
MODBUS protocol on RS485

Name : Nitin Jha Division : S4-R&D Category : General 1


Salient Features:
Sr. No Particulars Values
Measuring Range of total Leakage Current 0.5mA to 15 mA
Total Leakage
1 Current Error in total leakage current measurement < 5%
Measurement
Frequency 50 or 60 Hz
Below 100 A
100 A ~ 999 A
Amplitude classification of 8/20µsec wave 1000 A ~ 4999 A
5000 A ~ 9999 A
Surge Counting / Above 10000 A
2
Registration
Minimum counting threshold (8/20µsec wave) 50 A
Error in impulse current amplitude measurement < 20%
Time stamp, resolution Yes, < 0.5 s
1000 registration
Memory Capacity
(FIFO Type)
Protocol MODBUS on RS485
3 Communication
Range 500 m
230 ±10% V AC / 110~230 V
4 Power Supply
DC

Name : Nitin Jha Division : S4-R&D Category : General 1


Monitoring from Remote end:

Name : Nitin Jha Division : S4-R&D Category : General 1


Thank you

Name : Nitin Jha Division : S4-R&D Category : General 88

Potrebbero piacerti anche