Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
net/publication/312044307
CITATIONS READS
0 393
1 author:
Fernando Garnacho
Universidad Politécnica de Madrid
48 PUBLICATIONS 244 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Fernando Garnacho on 04 January 2017.
(1) Iberdrola Distribución; (2) LCOE; (3) UPM; (4) DIAEL; (5) Iberdrola Ingeniería
Spain
SUMMARY
A new on-line PD system has been used for monitoring of power transformer
applying power signal processing numerical tools for filtering and PD clustering and using
non-invasive sensors (HF and UHF) placed in each input phase of the power transformer and
an additional HFCT sensor at the tank earth connection. The signal acquisition of each sensor
is synchronized to discriminate where an eventual PD source found is placed, inside or
outside the transformer.
This paper presents the selection and the testing setup of the PD sensors used when the
power transformer is connected to the grid by oil-air bushing or by cable terminal. Different
alternatives of sensors are taking into account for this approach: coupling capacitor with
measuring impedance, high frequency current transformers clamped to the grounding cable
sheath, high frequency current transformers clamped to earth connection of the transformer
tank and UHF sensors placed on the cable sheaths or close to the transformer bushing when
used. The signal processing tools used for noise suppression, PD clustering, PD location and
PD phase resolved pattern recognition are also presented to get an appropriate diagnosis. The
signal processing analysis permits to identify whether the PD source is in the power
transformer, in the bushing, in the cable termination or along the cable system. Measurements
of load current, voltage and ambient temperature are also complementary parameters used to
correlate PD activity behavior. A histogram of the hourly distribution of the PD activity along
with a monitoring period of several weeks allows a better understanding of correlation
between the insulation defect and these parameters, in order to have a better insulation
diagnostic.
hgago@iberdrola.es
1
KEYWORDS
1. INTRODUCTION
According to IEC 60270 [1] and IEC 60076-3 [2], PD measurements in power
transformers should be performed using a coupling capacitor Ck in parallel to the insulation Ca
under test. The coupling capacitor Ck can be replaced by the capacitive bushing according to
the testing setup shown in Figure 1. The apparent charge is measured using a PD instrument
connected to a measuring impedance CD. The circuit should be calibrated before any PD
measurement is done. For this purpose a calibrator is connected between the high voltage
terminal and the earth tap of the bushing, and a reference charge is injected. The reading of
PD instrument must be set to the calibration signal. After installation of a new power
transformer an off-line PD measurement is recommended. The PD test is considered
successful if no continuous PD activity is greater than the specified apparent charge amplitude
at any bushing, and if there is not any rising trend in the apparent charge amplitude during the
long duration test. It is known that the real apparent charge at the defect site cannot be
measured, especially in power transformers. PD signals which originate within the
transformer are influenced by their propagation path [3], [4] and [5]. The same defect
occurring at different places inside the transformer will give different readings in the
measuring device. In consequence, the measurement of the real apparent charge is not
possible in power transformers. Furthermore, for on-line PD measurements the background
noise level is usually bigger than the admissible value and consequently a PD measurement
according to the IEC 60270 standard is not viable either. UHF-VHF-HF PD measuring
methods can be applied IEC 62478-TS [6] to verify PD activity inside power transformers
during on-line PD measurements. Although, in most cases, PD activity in power transformers
can be detected by Dissolved Gases Analysis (DGA), PD monitoring applying
electromagnetic methods gives complementary information about:
Z: Filter impedance
Ck: Coupling capacitor
Cm: Measuring capacitor
Ca: Insulation capacitance
CD Coupling device
CC Coaxial cable
MI: Measuring Instrument
2
2. GENERAL APPROACH FOR CONTINUOUS ON LINE PD MONITORING IN
POWER TRANSFORMERS USING INVASIVE UHF SENSORS
An invasive UHF sensor inside the grounded transformer tank is used to achieve a
significant level of electromagnetic shield against external disturbances at UHF frequencies
(e.g. corona, mobile telephones, radar, etc.). UHF signals propagating inside the tank present
only a moderate attenuation. Consequently, different commercial solutions are offered in the
market using invasive UHF to avoid interferences and to trigger PD measuring instruments
for conducted PD signals.
When applying this approach two typical types of UHF sensors can be used: a) an antenna
UHF sensor to be placed in standardized oil valves DN50/DN80, b) an UHF plate sensor to be
installed in new transformers onto a tank wall. The depth achieved when inserting the
antenna UHF sensor has a decisive influence on the PD sensitivity. Antenna insertion is often
limited to ensure no damage to the active part of the transformer. The conducted PD signals
can be captured using bushing taps (see Figure 2), if they are available, or non-invasive
sensors, that operate in the frequency range from hundreds of kHz to a few MHz.
Corona
PD Measuring
Instrument
Trigger
Computer
Defect
UHF PD
Measuring
Instrument
Figure 2. PD monitoring approach using an invasive UHF sensor to trigger PD sensors placed in the
transformer bushings.
3
3. NEW APPROACH FOR CONTINUOUS ON LINE PD MONITORING WITH
NO INVASIVE UHF SENSORS
The general UHF method described in previous section is not applicable for power
transformers with oil valves different to the standardized ones (DN50/DN80) nor for
power transformers in which invasive UHF sensors in the power transformers are not
permitted. In these cases, the following on line PD monitoring approach is proposed,
where the invasive UHF sensor is replaced by multi non-invasive UHF sensors based on
patch type couplers placed on the base of each transformer bushing (see Figure 3.b).
Two different sensors are used in each transformer bushing: a HF sensor and a UHF
sensor (see Figure 3.a). An additional HFCT sensor is installed on the earth connection of
the transformer tank. UHF sensors are placed close to the base of each transformer
bushing (see Figure 3.b) where electromagnetic radiation can go out. HF measurements
(0,1 MHz – 20 MHz) are performed through the test taps of the bushings: using HFCT
(see Figure 3.c) or using a measuring impedance (see Figure 3.d). Alternatively a HFCT is
used on the earth connection of each cable sheath (see Figure 3.e) in case the power
transformer is cable-connected. This is due to that the spectral content of conducted PD
pulses coming from inside a power transformer is only around a few MHz [7]. The output
of each UHF sensor is in the range from 0,3 MHz to 0,8 MHz. This signal is amplified
and converted to a single HF pulse to be injected as an input of the same Measuring
System (MSi) of 100 MegaSamp./s to be recorded and processed.
b)
a) Corona
c)
HF
PD Measuring
UHF System
d)
Defect
e)
4
For indoor transformers connected by cable to HV GIS and to MV metal-enclosed
switchgear additional HFCT sensors can be placed at earth connection of the cable ends of
the GIS and MV cabins according to the monitoring setup shown in Figure 4.
CAS
HF signals associated to each transformer bushing (the signal from HF sensor and the
signal from UHF sensor converted to HF signals) are filtered by means of a powerful filtering
software in order to save only pulses whose waveform is likely to be from PD (damping
oscillating transient signal). The noise suppression tool was developed on the basis of the
wavelet transform plus a statistical signal treatment [8]. The efficiency of the filtering
software is shown analysing the residual background noise of a Phase Resolved PD (PRPD)
pattern after filtering in each MSi (see PRPD pattern in the first row and first column of
Table 1). The base level of the PRPD pattern may be completely seen after filtering.
The filtered pulses of each MSi are sent to the Classification Automatic System (CAS)
where they are classified in different PD sources. PD sources located in different places are
identified applying the methods described in “PD location tool” and the PD sources located in
the same places are distinguished by “PD clustering tool”.
5
3.4 PD location tool
To get a correct PD location it is necessary to determine the delay between two PD pulses
generated by the same PD source traveling to two HFCT sensors placed indifferent locations.
Special attention must be paid to short cable links between transformer and GIS or between
transformer and MV metallic-enclosed switchgear. PD location through synchronized
measurements usually produces an error around 3.4 m when the synchronization uncertainty
is 10 ns taking into account a propagation speed around ±0,168 m/ns. Due to this reason a
complementary signal analysis must be performed to identify if a PD source is inside a
transformer or inside the cable termination when a PD source is located close to the limit
between both.
Cable side
Cable side
Figure 5). Pulse polarity analysis: a) when a PD pulse comes from the cable side its polarity in the
HFCT sensor placed at the cable sheath is the same to the voltage, b) when it comes from the
transformer side its polarity in the HFCT sensor of the cable sheath is reverse to the voltage.
A PD pulse is considered inside the power transformer if the two following conditions are
satisfied:
1) The pulse acquired by the HFCT of the cable sheath has reverse polarity
than half cycle of the voltage and/or the pulse acquired by the HFCT of the
earth connection of the transformer tank has the same polarity than half
cycle of the voltage (see Figure 5).
2) The signal from the UHF sensor and the signal from HFCT sensor of the
same transformer bushing appear at the same instant (see Figure 6).
6
HF signal
a) After
Filtering
HFCT
sensor
MSi CAS
UHF Filter UHF/HF
sensor 0,3 -0,8 MHz converter
UHF signal
converted in
a HF signal
b) Signals and filtered
acquired
by HFCT
2 ms/div
10 mV/div
c)
PD pulse detected FFT of the PD pulse
10 MHz/div
20 dB/div
200 ns/div
10 mV/div
Figure 6. Logic process to classify PD pulses wave-shapes: a) signal treatment from HFCT and UHF
sensors associated to the same transformer bushing, b) Wave-shapes obtained in different steps of the
signal treatment, c) PD pulse originated inside a power transformer.
7
Table 1
Exemple of 3-D PD clustering
Phase Resolved Cluste #1 Cluste #2 Cluster #3
PD pattern after
software filtering
β β β
α α α
f f f
PD pulse
waveform
Phase Resolved
PD pattern of
each PD source
0 20 ms
18 0 24 h 0 24 h 0 24 h
0 6 12 24 h
Figure 7: Trend of the average PD activity of each day versus load, voltage and ambient temperature.
8
4. EXPERIENCE OF A PD MEASUREMENT IN SERVICE
An on line PD monitoring was carried out in three power transformers 132 kV / 20kV, of
40 MVA each one, installed in an indoor substation of IBERDROLA. Oil filled cables of 40
years old were replaced by XLPE cables. This change involved a modification of the cable
connection box at the transformer side.
9
4.2. On-line PD monitoring
Taking into account PD activity was only observed for voltages much higher than the
service voltage (inception voltage was 114 kV) approximately at 1,5.Uo (1,5x132/√3=114kV)
no critical problem in transformer insulation was considered. However, on-line PD
monitoring was recommended to analyse the PD trend.
An on-line PD monitoring was performed three months later the commissioning test
using the testing setup of PD sensors (HFCT and UHF) and measuring systems as indicated in
section 3. The sensors were installed on the HV transformer bushings and an additional HFCT
sensor on the earth connection of the transformer tank. After one month of PRPD patterns
were detected on phases U, V and W with similar characteristics and equivalent activity
behaviour as the ones obtained during onsite testing (see Figure 8).
During on-line PD monitoring, the PD source related to phases U and W had very low
activity and the one related with phase V had a higher activity. This behaviour was similar to
the experience observed under different voltage levels during off-line PD measurements: only
significant PD pulses related with phase V were detected at lower voltage levels while pulses
related with phase U were also detected at higher voltages. In phase W low PD activity was
also observed. The PD sources were detected by HFCT sensors placed on the HV cable
connections and at the HFCT sensor placed at the earth connection of the tank. PD correlation
analysis using current sensors classified PD sources inside transformer due to the polarity of
the pulses. PD pulses were also detected by UHF antenna installed on cable connections. This
fact confirms the existence of PD close to the interface between cable and transformer.
An analysis of the PD activity correlated with voltage and load current of the
transformer was carried out to know more about the behaviour of the PD activity. This
analysis on the first on-line PD monitoring concluded that: 1) During 14% of the period of
time monitored there was PD activity, 2) the probability of PD activity increases after a load
peak when it starts to decrease.
After ten and sixteen months from the first PD on-line monitoring, two additional on-
line PD monitoring measurements were performed during one month. Lower PD activity was
detected in both: in the second PD monitoring, PD activity was detected in phases U and V
during 3% of the monitored period, being this figure only 1% of the monitored time in
phase U, during the third PD monitoring (see Table 4). The justification was that eventual
bubbles in oil are dissolved as the transformer stays longer loaded in service.
10
13th-June 14th-June 15th-June 16th-June
Figure 10: PD activity (amplitude red curve and rate per period green curve) versus voltage and load.
a) Off-line PD test
March-2014
b) On-line PD test
June-2014
c) On-line PD test
No PD activity
May-2015
d) On-line PD test
No PD activity No PD activity
Nov-2015
Figure 11: Results of PD measurement: a) First row off-line test, b) Frist on-line PD monitoring,
c) second PD on-line monitoring, d) third PD on-line monitoring.
CONCLUSIONS
This paper presents an on-line PD monitoring system designed for power transformers
without using invasive sensors. Periodic synchronized PD measurements performed by means
of no invasive HFCT sensors and UHF sensors combined with a powerful filtering tool allows
identifying the location of the PD source. Analysis of PD amplitude, polarity of the pulses
detected and time delay to the different PD sensors used during an on-line PD test permits to
identify whether the PD source is inside or outside the transformer. A 3D wave-shape PD
clustering is used to separate different PD sources which will be helpful to know if the defect
is critical.
An off-line PD test and three on-line PD tests performed in a power transformer located in
an urban substation are presented. The analysis of the PD signals has allowed us to know the
PD evolution of internal PRPD patterns. The off-line PD measurements were confirmed by an
on-line PD test performed in service conditions. The comparison of both techniques off-line
and on-line PD tests is shown and analyzed. The analysis of the trend of the PD sources found
with similar characteristics and equivalent activity behavior has proved the effectiveness of
this approach.
11
BIBLIOGRAPHY
12