Technical Specifications :
Feeder Name : CFC041 (DG # 4 Control panel)
Feeder Location : Generator control room
Relay Make: VAMP I CT Ratio: 800/5 A
Relay Model: VAMP 265 I’ CT Ratio: 800/1A
Relay Sr.N.: 036735 VT Ratio: 11000/110 V
Prerequisites: During this checking, Engine should be stopped, Testing Kit earth point should be connected to earth.
Methodology: Each enabled protection of VAMP265 to be tested by means of Secondary injection method. Each protection should be
tested at setting values with considering the respective curve and measure the trip timing of relay trip contacts and Relay Pick-up time. Be
sure that no voltage or current will be transferred to any external circuit.
Remarks: The Differential Protection Stage DI>, found healthy at pre-determined set values/settings.
Remarks: The Differential Protection Stage DI>>, found healthy at pre-determined set values/settings.