Sei sulla pagina 1di 5

2 Overview

Protection Coordination burden (internal CT burden, plus burden of con-


nected lines plus relay burden).
Furthermore, a transient dimensioning factor has
Instrument transformers to be considered to cover the influence of the DC
component in the short-circuit current.
Instrument transformers
In general, an accuracy of 1 % in the range of 1 to
2 Instrument transformers must comply with the 2 times nominal current (class 5 P) is specified.
applicable IEC recommendations IEC 60044, The rated symmetrical short-circuit current factor
formerly IEC 60185 (CT) and 60186 (PT), Kssc should normally be selected so that at least the
ANSI/IEEE C57.13 or other comparable stan- maximum short-circuit current can be transmit-
dards. ted without saturation (DC component not con-
sidered).
Potential transformers This results, as a rule, in rated symmetrical short-
Potential transformers (PT) in single or double- circuit current factors of 10 or 20 depending on
pole design for all primary voltages have typical the rated burden of the CT in relation to the con-
single or dual secondary windings of 100, 110 or nected burden. A typical specification for protec-
tion cores for distribution feeders is 5P10, 10 VA
115 V/ 3 with output ratings between 10 and
or 5P20, 5 VA.
300 VA, and accuracies of 0.2, 0.5 or 1 % to suit
the particular application. Primary BIL values are The requirements for protective current trans-
selected to match those of the associated formers for transient performance are specified in
switchgear. IEC 60044-6.
In many practical cases, iron-core CTs cannot be
Current transformers designed to avoid saturation under all circum-
Current transformers (CT) are usually of the stances because of cost and space reasons, particu-
single-ratio type with wound or bar-type prima- larly with metal-enclosed switchgear.
ries of adequate thermal rating. Single, dual or tri- The Siemens relays are therefore designed to toler-
ple secondary windings of 1 or 5 A are standard. ate CT saturation to a large extent. The numerical
1 A rating should however be preferred, relays proposed in this guide are particularly sta-
particularly in HV and EHV stations, to reduce ble in this case due to their integrated saturation
the burden of the connected lines. Output power detection function.
(rated burden in VA), accuracy and saturation
characteristics (rated symmetrical short-circuit Glossary of used abbreviations
current limiting factor) of the cores and secondary (according to IEC 60044-6, as defined)
windings must meet the particular application. Kssc = rated symmetrical short-circuit current factor
(example: CT cl. 5P20 Q KSSC = 20)
The CT classification code of IEC is used in the
K'ssc = effective symmetrical short-circuit current factor
following:
Ktd = transient dimensioning factor
Measuring cores Issc max = maximum symmetrical short-circuit current
These are normally specified with 0.5 % or 1.0 % Ipn = CT rated primary current
accuracy (class 0.5 FS or 1.0 FS), and an rated Isn = CT rated secondary current
symmetrical short-circuit current limiting factor
Rct = secondary winding d.c. resistance at 75°C
of 5 or 10. (or other specified temperature)
The required output power (rated burden) should Rb = rated resistive burden
be higher than the actually connected burden. R'b = Rlead + Rrelay = connected resistive burden
Typical values are 5, 10, 15 VA. Higher values are TP = primary time constant (net time constant)
normally not necessary when only electronic me-
VK = kneepoint voltage (r.m.s.)
ters and recorders are connected.
Rrelay = relay burden
A typical specification could be: 0.5 FS 10, 15 VA. Rlead 2 ⋅ρ⋅l
=
Cores for billing values metering A
with
In this case, class 0.2 FS is normally required. l = single conductor length from CT to relay in m
ρ = specific resistance = 0.0175 Ω mm2/m (copper wires)
Protection cores at 20 °C (or other specified temperature)
A = conductor cross-section in mm2
The size of the protection core depends mainly on
the maximum short-circuit current and the total

2/52 Siemens SIP · 2006, revised: Jan. 2007


2 Overview

CT dimensioning formulae CT design according to BS 3938/IEC 60044-1 (2000)


K'ssc = Kssc · Rct + Rb (effective) IEC Class P can be approximately transfered into
Rct + R' b
the IEC Class PX (BS Class X) standard definition
I SCC max by following formula:
with K'ssc W Ktd · (required)
I pn
(Rb + Rct ) ⋅ I sn ⋅ K ssc
The effective symmetrical short-circuit current VK =
factor K'ssc can be calculated as shown in the table
13
. 2
Example:
above.
IEC 600/1, 5P10, 15 VA, Rct = 4 Ω
The rated transient dimensioning factor Ktd de- 60044:
pends on the type of relay and the primary DC IEC PX or BS: VK =
(15 + 4) ⋅ 1 ⋅ 10 V = 146 V
time constant. For relays with a required satura- 1.3
tion free time from w 0.4 cycle, the primary (DC) Rct = 4 Ω
time constant TP has only little influence.
For CT design according to ANSI/IEEE C 57.13
please refer to page 2/56

Table 2/1 CT requirements

Relay type Transient dimensioning factor Ktd Min. required sym. short- Min. required kneepoint voltage VK
circuit current factor K’ssc

Overcurrent-time protection – I High set point I High set point


K'ssc ≥ VK ≥ · (Rct + R'b) · Isn
7SJ511, 512, 531 I pn . ⋅ I pn
13
7SJ45, 46, 60 20
7SJ61, 62, 63, 64 at least: 20 at least: · (Rct + R'b) · Isn
13
.

Line differential protection – I scc max (ext. fault) I scc max (ext. fault)
K'ssc ≥ VK ≥ · (Rct + R'b) · Isn
(pilot wire) I pn 13. ⋅ I pn
7SD600
and: and:

3 ( K' ssc ⋅I pn )end1 4 3 (VK / ( Rct + R' b ) ⋅ I pn / I sn )end1 4


≤ ≤ ≤ ≤
4 ( K' ssc ⋅I pn )end2 3 4 (VK / ( Rct + R' b ) ⋅ I pn / I sn )end2 3

Line differential protection Busbar / Gen. / K'ssc ≥ VK ≥


(without distance function) Transformer Line Motor I I scc max (ext. fault)
Ktd · scc max (ext. fault) Ktd · · (Rct + R'b) · Isn
7SD52x, 53x, 610 (50/60 Hz) 1.2 1.2 1.2 I pn 13. ⋅ I pn
Transformer / Generator Busbar / Gen. / and (only for 7SS): and (only for 7SS):
differential protection Transformer Line Motor
100
7UT612 4 4 5 K'ssc ≤ 100 (measuring range) VK ≤ · (Rct + R'b) · Isn (measuring range)
7UT613, 633, 635 3 3 5 13
.
7UM62 4 – 5

Busbar protection for stabilizing factors k ≥ 0.5


7SS5, 7SS600 0.5

Distance protection primary DC time constant TP [ms] K'ssc ≥ VK ≥


7SA522, 7SA6, 7SD5xx*) I scc max (close -in fault) I scc max (close -in fault)
≤ 30 ≤ 50 ≤ 100 ≤ 200 Ktd (a) · Ktd (a) · · (Rct + R'b) · Isn
*) with distance function I pn . ⋅ I pn
13
Ktd (a) 1 2 4 4 and: and:
Ktd (b) 4 5 5 5 I scc max (zone 1- end fault) I scc max (zone 1-end fault)
Ktd (b) · Ktd (b) · · (Rct + R'b) · Isn
I pn 13. ⋅ I pn

Siemens SIP · 2006, revised: Jan. 2007 2/53


2 Overview

Protection Coordination
The CT requirements mentioned in Table 2/1 on page 2/53 are simplified in order to allow fast CT
calculations on the safe side. More accurate dimensioning can be done by more intensive calculation
with Siemens’ CTDIM (V 3.21) program. Results of CTDIM are released by the relay manufacturer.
2 Adaption factor for 7UT6, 7UM62 relays (limited resolution of measurement)
(also 7SD52, 53, 610, when transformer inside protected zone)

I pn I Nrelay I pn ⋅ 3 ⋅ VnO I Nrelay


FAdap = ⋅ = ⋅ Q Request : ¼8 ≤ FAdap ≤ 8
I nO I sn SNmax I sn

with
InO = rated current of the protected object
VnO = rated voltage of the protected object
INrelay = rated current of the relay
SN max = maximum load of the protected object (for transformers: winding with max. load)
Attention: when low impedance REF is used, the request for the REF side (3-phase) is:
¼ ≤ FAdap ≤ 4, (for the neutral CT: ¼8 ≤ FAdap ≤ 8
Further condition for 7SD52x, 53x, 610 relays
(when used as line differential protection without transformer inside protected zone)
Maximum ratio between primary currents of CTs at the end of the protected line:
I pn max
≤8
I pn min

Example 1: CT verification for 7UM62, 7UT6, 7SD52 (7SD53, 7SD610)

Fig. 2/92

2/54 Siemens SIP · 2006, revised: Jan. 2007


2 Overview

Example 1 (continued)
Verification of the numerical differential protection

-T (G S2), 7UM62 -T (T LV1), 7UT633 -T (T HV), 7UT633 -T (L end 1), 7SD52


c ⋅ S NG S NT S NT
Iscc max (ext. fault) = Iscc max (ext. fault) = Iscc max (ext. fault) = Iscc max (ext. fault) = 17 kA (given)
3 ⋅VNG ⋅ x d" 3 ⋅VNT ⋅ u k 3 ⋅VNT ⋅ u k
1.1 ⋅ 120000 kVA 120000 kVA 240000 kVA
= = 34516 A = = 35860 A = = 7498 A
3 ⋅13.8 kV ⋅ 0.16 3 ⋅13.8 kV ⋅ 0.14 3 ⋅132 kV ⋅ 0.14

Ktd = 5 (from Table 2/1) Ktd = 3 (from Table 2/1) Ktd = 3 (from Table 2/1) Ktd = 1.2 (from Table 2/1)
I scc max (ext. fault) I scc max (ext. fault) I 2
K'ssc ≥ Ktd · K'ssc ≥ Ktd · K'ssc ≥ Ktd · scc max (ext. fault)
I pn I pn I pn
31378 A 35860 A 7498 A
=5· = 28.8 =3· = 17.9 =3· = 18.7
6000 A 6000 A 1200 A

Sn 20 VA Sn 20 VA Sn 50 VA
Rb = = = 20 Ω Rb = = = 20 Ω Rb = = =2Ω
I 2 sn 1 A 2 I 2 sn 1 A 2 I 2 sn 5 A 2

R'b = Rlead + Rrelay R'b = Rlead + Rrelay R'b = Rlead + Rrelay R'b = Rlead + Rrelay

2 ⋅ρ⋅l 2 ⋅ρ⋅l 2 ⋅ρ⋅l 2 ⋅ρ⋅l


= + 0.1 Ω = + 0.1 Ω = + 0.1 Ω = + 0.1 Ω
A A A A
Ω mm 2 Ω mm 2 Ω mm 2 Ω mm 2
2 ⋅ 0.0175 ⋅ 60 m 2 ⋅ 0.0175 ⋅ 40 m 2 ⋅ 0.0175 ⋅ 100 m 2 ⋅ 0.0175 ⋅ 60 m
= m m m m
= = =
4 mm 2 4 mm 2 4 mm 2 4 mm 2

+ 0.1 Ω + 0.1 Ω + 0.1 Ω + 0.1 Ω


= 0.625 Ω = 0.450 Ω = 0.975 Ω = 0.625 Ω

Rct + Rb Rct + Rb Rct + Rb I scc max (ext. fault)


K'ssc = Kssc · K'ssc = Kssc · K'ssc = Kssc · VK ≥ Ktd · · (Rct + R'b) · Isn
Rct + R' b Rct + R' b Rct + R' b 1.3 ⋅ I pn
18 Ω + 20 Ω 18 Ω + 20 Ω 0.96Ω + 2 Ω 17000 Α
= 20 · = 40.8 = 20 · = 41.2 = 20 · = 30.6 = 1.2 · · (0.8 Ω + 0.625 Ω)·
18 Ω + 0.625 Ω 18 Ω + 0.450 Ω 0.96Ω + 0.975 Ω 5 A 13 . ⋅ 1000 Α

= 111.8 V

K'ssc required = 28.8, K'ssc required = 17.9, K'ssc required = 18.7, VK required = 111.8 V,
K'ssc effective = 40.8 K'ssc effective = 41.2 K'ssc effective = 30.6 VK effective = 200 V
28.8 < 40.8 17.9 < 41.2 18.7 < 30.6 111.8 V < 200 V
Q CT dimensioning is ok Q CT dimensioning is ok Q CT dimensioning is ok Q CT dimensioning is ok

I pn ⋅ 3 ⋅ VnO I Nrelay I pn ⋅ 3 ⋅ VnO I Nrelay I pn ⋅ 3 ⋅ VnO I Nrelay I pn max


FAdap = ⋅ FAdap = ⋅ FAdap = ⋅ ≤8
S Nmax I sn S Nmax I sn S Nmax I sn I pn min
1500 A
= 1.5 ≤ 8 Q ok!
6000 A ⋅ 3 ⋅ 13.8 kV 1 A 6000 A ⋅ 3 ⋅ 13.8 kV 1 A 1200 A ⋅ 3 ⋅ 132 kV 5 A 1000 A
= ⋅ = ⋅ = ⋅
120000 kVA 1A 240000 kVA 1A 240000 kVA 5A

= 1.195 = 0.598 = 1.143


1/8 ≤ 1.195 ≤ 8 Q ok! 1/8 ≤ 0.598 ≤ 8 Q ok! 1/8 ≤ 1.143 ≤ 8 Q ok!

Siemens SIP · 2006, revised: Jan. 2007 2/55


2 Overview

Protection Coordination Relay burden


The CT burdens of the numerical relays of
Example 2: Siemens are below 0.1 VA and can therefore be
Stability-verification of the numerical busbar neglected for a practical estimation. Exceptions
protection relay 7SS52 are the busbar protection 7SS60 and the pilot-wire
relays 7SD600.
2 Intermediate CTs are normally no longer neces-
sary as the ratio adaptation for busbar and trans-
former protection is numerically performed in the
relay.
Analog static relays in general have burdens below
about 1 VA.
Mechanical relays, however, have a much higher
burden, up to the order of 10 VA.
This has to be considered when older relays are
connected to the same CT circuit.
Fig. 2/93 In any case, the relevant relay manuals should al-
ways be consulted for the actual burden values.
I SCC.max. 30 ,000 A
= = 50
I pn 600 A Burden of the connection leads
The resistance of the current loop from the CT to
According to table 2/1 on page 2/53 Ktd = ½)
the relay has to be considered:
1
K'ssc ≥ ⋅ 50 = 25
2
2 ⋅ρ⋅l
15 VA Rlead =
Rb = = 15 Ω A
1 A2
l = single conductor length from the CT
Rrelay = 0.1 Ω to the relay in m.
Specific resistance:
2 ⋅ 0.0175 ⋅ 50 Ω ⋅ mm 2
Rlead = = 0.3 Ω ρ = 0.0175 (copper wires) at 20 °C
6 m
R'b = Rlead + Rrelay = 0.3 Ω + 0.1 Ω = 0.4 Ω A = conductor cross-section in mm2
Rct + Rb 4 Ω + 15 Ω
K'ssc = ⋅ K ssc = ⋅ 10 = 43.2
Rct + R' b 4 Ω + 0.4 Ω CT design according to ANSI/IEEE C 57.13
Result: Class C of this standard defines the CT by ist sec-
The effective K'ssc is 43.2, the required K'ssc is ondary terminal voltage at 20 times rated current,
25. Therefore the stability criterion is fulfilled. for which the ratio error shall not exceed
10 %. Standard classes are C100, C200, C400 and
C800 for 5 A rated secondary current.
This terminal voltage can be approximately calcu-
lated from the IEC data as follows:

ANSI CT definition
K ssc
Vs.t.max = 20 ⋅ 5 A ⋅ Rb ⋅
20
with
Pb
Rb = 2
and I Nsn = 5 A , we get
I sn
Vs.t.max Pb ⋅ K ssc
=
5A
Example:
IEC 600/5, 5P20, 25 VA
60044:
ANSI
C57.13: Vs.t.max =
(25 VA ⋅ 20) = 100 V, acc. to class C100
5A

2/56 Siemens SIP · 2006, revised: Jan. 2007

Potrebbero piacerti anche