Sei sulla pagina 1di 11

Environ Monit Assess (2010) 161:473–483

DOI 10.1007/s10661-009-0761-8

Assessment of microbiological indoor air quality


in an Italian office building equipped
with an HVAC system
Sa. Bonetta · Si. Bonetta · S. Mosso ·
S. Sampò · E. Carraro

Received: 25 July 2008 / Accepted: 27 January 2009 / Published online: 18 February 2009
© Springer Science + Business Media B.V. 2009

Abstract The purpose of this study was to eval- A high fungal concentration was measured due
uate the level and composition of bacteria and to a flood that occurred during the winter. The
fungi in the indoor air of an Italian office building indoor seasonal distribution of fungal genera was
equipped with a heating, ventilation and air con- related to the fungal outdoor distribution. Sig-
ditioning (HVAC) system. Airborne bacteria and nificant seasonal and daily variation in airborne
fungi were collected in three open-space offices microorganisms was found, underlining a relation-
during different seasons. The microbial levels in ship with the frequency of HVAC system switch-
the outdoor air, supply air diffusers, fan coil air ing on/off. The results of this monitoring highlight
flow and air treatment unit humidification water the role of the HVAC system on IAQ and could
tank were used to evaluate the influence of the be useful to better characterise bacterial and fun-
HVAC system on indoor air quality (IAQ). A gal population in the indoor air of office buildings.
medium–low level of bacterial contamination (50–
500 CFU/m3 ) was found in indoor air. Staphylo- Keywords Bacteria · Fungi · Indoor air ·
coccus and Micrococcus were the most commonly HVAC system · Office building
found genera, probably due to human presence.

Introduction

Indoor air quality (IAQ) is an increasingly im-


Electronic supplementary material The online version portant issue for occupational and public health
of this article (doi:10.1007/s10661-009-0761-8) contains (Clarke and Nikkel 1995; Reynolds et al. 2001).
supplementary material, which is available to Health effects related to IAQ have increased,
authorized users.
perhaps due to some energy-saving measures pro-
Sa. Bonetta · Si. Bonetta · S. Sampò · E. Carraro (B) vided for buildings such as tight sealing (Jones
Dipartimento di Scienze dell’Ambiente e della Vita,
1999), air recirculation and the introduction of
University of Piemonte Orientale “Amedeo
Avogadro”, Via Bellini 25/G, heating ventilation air conditioning (HVAC) sys-
15100 Alessandria, Italy tems (Nathanson 1995). In addition, an ageing
e-mail: elisabetta.carraro@mfn.unipmn.it population, an increasing number of sensitive in-
dividuals and a tendency to spend more time
S. Mosso
Telecom Italia Laboratories, indoors (90% of life time) further worsen this
Via G. Reiss Romoli 274, 10148 Turin, Italy problem (Tringe et al. 2008). Although discussions
474 Environ Monit Assess (2010) 161:473–483

about indoor air contamination frequently con- associated with respiratory allergies and asthma
centrate on chemical pollutants, the health effects and have been linked to the airborne transmission
of inhaled biological particles should not be over- of various infections known as building-related
looked, as a large variety of biological material is illnesses (e.g. Legionnaires’ disease, aspergillosis;
present in indoor environment (Montanaro 1997). Stetzenbach 1997; Huang et al. 2008). Airborne
Bioaerosols are airborne particles that are ei- bacteria and fungi can also be the cause of non-
ther living (e.g. bacteria, fungi) or originate from specific diseases such as sick building syndrome
living organisms that are ubiquitous, highly vari- (SBS). Numerous scientific studies have docu-
able and complex and are natural or man-made mented that SBS is surprisingly common even in
in origin. The sampling and analysis of airborne buildings without widespread health complaints
microorganisms in indoor air has received atten- (Mendell et al. 2008). Moreover, epidemiological
tion in recent years (Kim and Kim 2007; Huttunen investigations showed that SBS and hypersensitiv-
et al. 2008; Stanley et al. 2008). Bioaerosols con- ity diseases (humidifier fever or asthma) are often
tribute to about 5–34% of indoor air pollution associated with high airborne microbial concen-
(Srikanth et al. 2008). The source of bioaerosols tration exposure (ACGIH 1999; Shoemaker and
in indoor air include furnishing and building ma- House 2006).
terials, microbiological contamination within the To contribute to the knowledge on IAQ, this
walls, and ceiling and floor cavities. Another sig- study evaluates the level and composition of bac-
nificant source of airborne bacteria in the indoor terial and fungal contamination of indoor air in
environment is the occupants (Loftness et al. 2007; an Italian office building equipped with an HVAC
Stanley et al. 2008). Many indoor bioaerosols orig- system during different seasons. The influence of
inate outdoors through the opening of doors and the HVAC characteristics and human activities on
windows or through cracks in the building enve- IAQ was also investigated.
lope. However, one of the most important factors
affecting IAQ is how the building is heated, ven-
tilated and air conditioned (Seppänen and Fisk Materials and methods
2002), considering that in many cases, particularly
in office buildings, these functions are integrated Description of the site
into an HVAC system.
Although HVAC systems can help remove and/ The study was carried out in an office building
or dilute more than 80% of aerosols from the out- (35 years old) with a central HVAC system and
doors, they can also provide favourable breeding open-space offices located in a busy and subur-
grounds for bioaerosols to colonise (Law et al. ban zone of Turin (Piedmont, Italy). There were
2001). A microbiological growth may occur in two or three occupants per office, computers and
an HVAC system equipped with low-efficiency printers. The HVAC system was composed of the
filters, humidifiers that use water recycling or in following: an intake for outdoor air located on the
areas in which water condensation remains stag- roof of the building, vent ducts at the ceiling for
nant and large recirculation of the air is present air removal, and a duct bringing outdoor air to
(Wu et al. 2005; Huang et al. 2008). Microor- the air treatment unit (ATU, 4 years old). In the
ganisms can thus spread in the indoor air by ATU, fresh (50% minimum) and recycled air were
the HVAC system and be inhaled by the people mixed and filtered (85% removal for ≥3 μm parti-
working or living in buildings (Parat et al. 1997; cles prefilter according to ASHRAE 52–76 with a
Mendell et al. 2008). bag-type filter), heated or cooled, dehumidified or
Numerous studies published during the past humidified (air humidification tank) and distrib-
10–15 years have produced rather solid scien- uted through a duct network to vent ducts placed
tific evidence that indoor aerosol particles, es- in the false ceiling. Heating and cooling devices
pecially in the respirable fraction, are associated (fan coil units) were distributed in open spaces
with health effects. Viable bioaerosol particles, to heat or cool indoor recycled air. The windows
including viruses, bacteria and fungi, have been were locked, and building occupants could only
Environ Monit Assess (2010) 161:473–483 475

regulate the fan coil units by switching them on (three parameters: bacteria at 22◦ C, bacteria at
or off. 37◦ C and fungi) × (three offices: A, B and C) ×
(two daily samplings: a.m./p.m.) × (three times a
week: Monday, Wednesday and Friday) × (four
Sampling seasons: winter, spring, summer, winter2) + [(one
outdoor sample + two ventilation shafts + three
A diagram of the sampling points is shown in fan coil units) × (four seasons: winter, spring,
Fig. 1. Three open-space offices (A, B and C) were summer, winter2)].
selected to follow the air duct distribution from Airborne bacteria and fungi were collected
the fresh air intake to the end. Air was sampled using a calibrated impactor sampler (SAS Super
for microbiological analysis in the centre of each 180™, International PBI, Milan) at an air flow rate
open-space office, at 1.5 m from the floor (at the of 180 L/min (sampling time 1.10 and 1.20 min
workstation level) and was collected twice a day for fungal and bacterial samplings, respectively).
(at 9.00 a.m. and 4.30 p.m.), three times a week Three plates per each sampling point were taken
(Monday, Wednesday and Friday) and 1 week to evaluate the different microbiological parame-
during different seasons (winter, spring, summer). ters and quality assurance/quality control aspect.
Since an unusual flood occurred during the winter, Field blank plates for quality control (a mini-
another sampling was repeated during the follow- mum of one for each medium) accompanied the
ing winter (winter2). sampler during the transport and air monitoring.
To evaluate the HVAC influence on in- These field blanks were processed and analysed
door microbiological contamination, additional exactly as the other plates.
evaluations were performed once a week (on
Wednesday) for each season. In particular, the
bacterial and fungal counts at the intake point Microbiological analyses
of the ATU system (Fig. 1) and at the level of
the two ventilation shafts in the indoor air (the Total bacterial counts were evaluated on trypti-
first and the last ventilation shafts after the ATU case soy agar supplemented with cycloheximide
system) were analysed. Microbiological analyses (100 μg/L), and fungal counts were performed
were also performed on the ATU humidification on Rose-Bengal Agar with chloramphenicol
water tank. The air flow of the fan coil units was (100 μg/L). Petri dishes were incubated for 24 h
also sampled in the same offices in which IAQ at 37◦ C and 48h at 22◦ C for bacterial counts and
was monitored to evaluate its influence on air 4–8 days at 24◦ C for fungal counts. The mean
contamination. A total of 240 air samples were value of the triplicate samples was calculated,
collected for bacterial and fungal measurements: and results were expressed in colony forming

Fig. 1 Diagram of the INTAKE POINT o


sampling points in
the office building
FILTER OPEN SPACE OFFICES
w UTA
WATER TANK
a b c

A B C

S1 S2

FIRST SHAFT LAST SHAFT

O: outdoor air;
S1: first ventilation shaft;
S2: last ventilation shaft;
W: humidification water tank;
A,B,C: offices;
a,b,c: fan coil units.
476 Environ Monit Assess (2010) 161:473–483

units per cubic meter (CFU/m3 ), corrected based their micro- and macro-morphological character-
on the sampler’s manufacturer instructions. The istics using standard taxonomic keys (Von Arx
consistency of triplicate counts was evaluated us- 1981).
ing a χ 2 index to confirm the suitability of the
mean value of the three measurements. The most Statistical analyses
widespread bacterial and fungal colonies for each
sampling were selected and isolated from indoor SYSTAT software for Windows, version 8.0, was
and outdoor air samples on the basis of their used for statistical analysis. Analysis of variance
morphology. (ANOVA) was performed on bacteria (22◦ C and
Water samples collected in the air humidifica- 37◦ C counts) and fungi indoor concentrations us-
tion tank of the ATU were analysed for Legionella ing season, day of the working week, and morning
spp. (ISO 1998) and total bacterial counts (22◦ C or afternoon as main parameters. Pearson’s corre-
and 37◦ C counts; EN ISO 1999). lation coefficient was used to study the relation-
ship among the microbial parameters analysed.
Microbial identification

Bacterial identifications by metabolic fingerprint- Results


ing analysis were performed using the Biolog
system (Biolog Inc., Hayward, CA, USA), orig- Microbiological indoor air quality
inally created for soil and water microorganisms
identification (Avidano et al. 2005). This method Table 1 summarises the values of bacterial and
tests the ability of a microorganism to utilise or ox- fungal indoor contamination during seasonal sam-
idise different carbon sources. Tetrazolium violet plings. For each season, bacterial and fungal
is used as a redox dye. Briefly, bacteria were counts detected in the three offices (A, B and C)
grown on Biolog Universal Growth agar at 37◦ C on Monday, Wednesday and Friday were pooled
for 24 h or at 22◦ C for 48 h. Colonies were sus- and reported as a weekly mean with minimum and
pended in a 0.4% saline solution and the inoculum maximum values. The counts observed were com-
density adjusted to the specified turbidity range. pared with categories of contamination indicated
The bacterial suspensions were inoculated in a in the guidelines of the Commission of European
Biolog GP Microplate and were incubated at 37◦ C Communities (CEC 1993, Table 2).
or 22◦ C then manually read after 24 h. The pattern The first winter sampling revealed unusually
of purple wells was analysed by Biolog Microlog high indoor fungal concentrations. During this
2 software. sampling, high fungal contamination was found
Fungal genera were identified by colony char- in all offices and a value >2,000 CFU/m3 was
acteristics and microscopic examination based on observed in office C (Table 1). This finding is

Table 1 Indoor air bacterial (22◦ C and 37◦ C) and fungal concentrations (CFU/m3 ) during seasonal samplings
Parameter (CFU/m3 ) Winter (n = 18)a Spring (n = 18)a Summer (n = 18)a Winter2 (n = 18)a
Meanb Min Max Meanb Min Max Meanb Min Max Meanb Min Max
Bacteria 37◦ C m 102 32 248 97 36 256 198 120 368 253 116 496
a 76 44 128 65 32 96 136 68 324 158 84 268
Bacteria 22◦ C m 72 32 200 120 56 320 176 112 240 271 128 500
a 28 4 56 129 40 308 134 52 368 160 72 304
Fungi 24◦ C m 514 50 1,528 321 55 465 44 25 90 49 10 100
a 872 30 2,315 43 25 100 44 10 75 39 10 70
m morning, a afternoon, Min minimum value, Max maximum value
a Number of samples analysed for each parameter
b Weekly mean of microbiological counts recovered in the three offices (A, B, and C) on Monday, Wednesday, and Friday
Environ Monit Assess (2010) 161:473–483 477

Table 2 Categories of CFU/m3 (mixed population of bac-


teria and of fungi) for non-industrial indoor environments
and fungal indoor contamination related to the
(CEC 1993) season (Table 3). The bacterial counts (22◦ C and
Category Bacteria Fungi
37◦ C) increased from spring to summer and win-
ter2, while the fungal concentration increased
Very low <50 <25
Low <100 <100 in the spring. Similar trends were also observed
Intermediate <500 <500 in other studies (Sen and Asan 2009). Further-
High <2,000 <2,000 more, a significant difference in daily bacterial
Very high >2,000 >2,000 (22◦ C and 37◦ C) and fungal indoor contamina-
These categories are based on the range of values obtained tion was detected, showing a trend with higher
in indoor environments and not on a health risk evaluation contamination levels in the morning than in the
afternoon (Table 3). A significant work week
trend of bacterial indoor contamination (22◦ C) of
probably related to a flood that occurred in Friday > Wednesday > Monday was revealed by
Turin near the investigated building during sam- the ANOVA.
pling. Massive mould growth was also reported No significant relationship among bacterial
in other studies on flood-damaged homes (Riggs concentrations at 22◦ C and 37◦ C and fungal
et al. 2008; Rao et al. 2007). For this reason, counts was revealed by the Pearson’s correlation
another sampling was repeated the following win- coefficient.
ter (winter2).
In the other seasonal samplings (spring, sum- HVAC system
mer and winter2), the fungal concentration de-
creased, and values lower than 500 CFU/m3 Air treatment unit
(medium–low contamination levels in spring) and
100 CFU/m3 (very low–low contamination levels To study the influence of the ATU system on
in summer and winter2) were observed. The low IAQ, microbial contamination of outdoor and in-
contamination reported in winter2 confirms that door air sampled near supply air diffusers was
the high fungal levels encountered in the first evaluated (Table 4). Fungal and bacterial (22◦ C)
winter sampling do not represent typical winter levels from outdoor air increased from winter to
contamination and that they had been influenced summer, except for the fungal air concentration
by the flood (Riggs et al. 2008; Rao et al. 2007). measured during the flood, which was unusually
Bacterial concentrations (37◦ C) ranged be- high. As reported by other authors (Pastuszka
tween 32 and 496 CFU/m3 (mean 136 CFU/m3 ), et al. 2000; Shelton et al. 2002; Lee et al. 2006),
with values lower than 500 CFU/m3 (medium–low seasonal high temperatures and humidity can in-
contamination levels). A similar trend was ob- crease microbiological activity, leading to an in-
served for bacteria at 22◦ C, showing a mean con- crease of bacterial and fungal counts.
centration of 136 CFU/m3 (range 4–500 CFU/m3 ). In the first winter sampling, similar fungal
The ANOVA test performed on total raw data counts in outdoor and indoor air diffusers (>3,000
(excluding the first winter sampling) revealed sig- CFU/m3 , SAS upper detection limit) were ob-
nificant differences in bacterial (22◦ C and 37◦ C) served, so it is possible that the ATU could not

Table 3 The analysis of variance on bacterial and fungal counts with respect to season, sampling point (office), day of work
week, and sampling hour
Bacteria 22◦ C Bacteria 37◦ C Fungi 24◦ C
Season p < 0.001 (Sp > Su > W2) p < 0.001 (Sp > Su > W2) p < 0.001 (W2 ≈ Su > Sp)
Office n.s. n.s. n.s.
Days of working week p < 0.05 (F > W > M) n.s. n.s.
Hour p < 0.05 (m > a) p < 0.05 (m > a) p < 0.05 (m > a)
Values obtained excluded the anomalous winter sample
n.s. not significant, Sp spring, Su summer, W2 winter2, F Friday, W Wednesday, M Monday, m morning, a afternoon
478 Environ Monit Assess (2010) 161:473–483

Table 4 Bacterial (22◦ C and 37◦ C) and fungal concentration (CFU/m3 ) in outdoor air and at the ventilation shafts during
seasonal samplings
CFU/m3 Winter Spring Summer Winter2
Meana ± SD Meana ± SD Meana ± SD Meana ± SD
Bacteria 37◦ C O 114 ± 62 96 ± 17 284 ± 86 248 ± 53
Bacteria 22◦ C O 189 ± 17 352 ± 57 600 ± 127 308 ± 87
Fungi 24◦ C O >3,268b 145 ± 15 695 ± 145 115 ± 8
Bacteria 37◦ C S1 20 ± 4 44 ± 5 84 ± 11 132 ± 16
Bacteria 22◦ C S1 4±2 144 ± 39 120 ± 30 228 ± 70
Fungi 24◦ C S1 >3,268b 60 ± 10 70 ± 4 20 ± 8
Bacteria 37◦ C S2 48 ± 5 48 ± 20 76 ± 38 76 ± 40
Bacteria 22◦ C S2 16 ± 1 104 ± 2 60 ± 28 48 ± 11
Fungi 24◦ C S2 >3,268b 30 ± 3 50 ± 18 40 ± 23
SD standard deviation, O outdoor air collected at the intake point of the ATU system, S1 indoor air at the level of the first
ventilation shaft after the ATU system, S2 indoor air at the level of the last ventilation shaft after the ATU system
a Mean value of the three measurements
b SAS upper detection limit calculated, according to the manufacturer, considering the maximum number of colonies in the

Petri dishes counted with the SAS Super 180

remove the high fungal contamination in the out- fungal counts were found in indoor and outdoor
door air. Otherwise, in this sampling, outdoor air. During other samplings, both bacterial and
bacterial values (22◦ C and 37◦ C) were lower than fungal concentrations were medium–low or some-
fungal counts, and the ATU was able to remove times very low (<500 or <50 CFU/m3 ), similar
most of it. levels to that observed in the indoor air.
During all the other samplings, the microbio-
logical contamination of the air measured at the
Indoor–outdoor ratio
ATU air diffusers revealed a lower bacterial and
fungal concentration than outdoors, with values
The indoor/outdoor ratio (I/O; Table 6) was cal-
lower than 500 or 100 CFU/m3 .
culated using the indoor (mean values obtained in
the open-space offices on Wednesday) and out-
Fan coil air door microbial counts obtained during the four
samplings. I/O ratios showed that fungal counts
Table 5 summarises bacterial and fungal concen- and 22◦ C bacterial concentrations were always
trations in the fan coil unit air flow during seasonal higher outdoors than indoors, in agreement with
samplings. High fungal contamination (range 500– other studies performed in office buildings (Burge
2,000 CFU/m3 ) of the fan coil unit air flow was et al. 2000). On the other hand, I/O values close
observed in the first winter sampling when high to 1 for bacterial counts at 37◦ C indicated higher

Table 5 Bacterial (22◦ C and 37◦ C) and fungal concentration (CFU/m3 ) in the fan coil unit’s air flow during seasonal
samplings
Parameter (CFU/m3 ) Winter (n = 3)a Spring (n = 3)a Summer (n = 3)a Winter2 (n = 3)a
Meanb Min Max Meanb Min Max Meanb Min Max Meanb Min Max
Bacteria 37◦ C 82 60 113 52 36 80 128 32 200 96 80 112
Bacteria 22◦ C 36 20 47 71 44 116 95 32 128 180 160 200
Fungi 24◦ C 935 560 1,465 15 10 20 50 30 65 60 20 100
Min minimum value, Max maximum value
a Number of samples analysed for each parameter
b Mean of microbiological counts recovered at the three fan coils air flow (office A, B, and C) on Wednesday
Environ Monit Assess (2010) 161:473–483 479

Table 6 Indoor/outdoor ratios calculated for bacterial and


fungal loads in seasonal samplings cus), in the external ear auditory meatus (Staphy-
lococcus auricularis) or on the human scalp
Season Ia /Ob
(Staphylococcus capitis) were also found. Some
Bacteria 22◦ C Bacteria 37◦ C Fungi 24◦ C
of the identified bacteria (Staphylococcus epider-
Winter 0.63 0.82 0.34
Spring 0.39 1.08 0.80
midis, S. haemolyticus, Staphylococcus warneri
Summer 0.80 1.06 0.38 and Staphylococcus hominis) can be considered to
Winter2 0.70 1.13 0.28 be opportunistic pathogens, while others (Kurtia
a Means of microbiological counts obtained at the level of
gibsonii, Kocuria rosea erythromixa and Tsuka-
open-spaces on Wednesday murella inchonensis) are typically found in envi-
b Microbiological counts obtained at the intake point of the
ronmental samples. Bacterial species found in the
ATU system on Wednesday fan coil air flow were similar to those recovered in
indoor air. In outdoor air, environmental species
such as Aerococcus viridans and T. inchonensis
were mainly encountered.
bacterial contamination inside the building than Considering that to our knowledge, this is
outside. the first time that the BIOLOG system has
been used for airborne bacterial identification,
Microbiological analyses of the humidification this method had a good performance, leading to
water tank the good identification of 94.3% of the analysed
colonies.
Results reported on Table 7 showed that the total
bacterial count in the humidification water tank Fungal identification
was high (range between 1 × 103 CFU per 100 mL
and 1.5 × 105 CFU per 100 mL) with an increasing Figure 2 shows the seasonal distribution of the
trend during warmer seasons (spring and sum- fungal genera in indoor air. According to other
mer). Legionella spp. was never recovered in the studies, Penicillium spp., Aspergillus spp. and
ATU humidification water. Cladosporium cladosporioides and C. sphaeros-
permum were the most widespread fungal gen-
Bacterial identification era identified in indoor air (Pasanen et al. 1992;
Hyvärinen et al. 1993; Nevalainen and Seuri 2005;
The identification of the most widespread bac- Sampò and Luppi Mosca 1988, 1989). Penicillium
teria in indoor air found Micrococcus (32% of was predominant in indoor air during the winter
species) and Staphylococcus (44%) as the most (68%) and spring (60%), while Cladosporium was
frequently occurring genera. These results support the most widespread genus in summer. This trend
the general idea that, in indoor air, the main was similar to that commonly reported in outdoor
represented bacteria are micrococci and staphy- air (Jo and Seo 2005). The fungal genera identi-
lococci (Nevalainen 1989; Maroni et al. 1993). fied (Penicillium, Aspergillus and Cladosporium)
Micrococcus luteus and Staphylococcus haemolyti- in indoor air are recognised as possible causes of
cus were found in all indoor air samples. Species respiratory allergies (Jones 1999), and Penicillium
commonly found on human skin (Micrococcus species can be associated with sick building syn-
lylae, M. luteus and Staphylococcus saprophyti- drome (Schwab and Straus 2004).

Table 7 Microbiological contamination of humidification water tank


Winter Spring Summer Winter2
Bacteria at 37◦ C (CFU/100 mL) 1,900 29,200 43,000 1,800
Bacteria at 22◦ C (CFU/100 mL) 1,100 150,000 136,000 15,600
Legionella spp. (CFU/L) <100a <100a <100a <100a
a<100 CFU/L: detection limit for Legionella spp. analysis
480 Environ Monit Assess (2010) 161:473–483

Fig. 2 Distribution of
fungal genera in indoor 100%
air during different Other
seasons
80% Mycelia sterilia
Cladosporium
60% Aspergillus
Penicillium
40%

20%

0%
Winter1 Spring Summer Winter2

Discussion outdoor ratio close to 1 for bacteria at 37◦ C


(0.82 ≤ I/O ≤ 1.13). As observed in other studies
This study evaluated the number and composi- (Pastuszka et al. 2000), the high bacterial count
tion of bacteria and fungi in the indoor air of an within the building compared to that observed
Italian office building equipped with an HVAC outdoor could be associated with various internal
system. It was not performed in response to occu- sources, including human activities. Otherwise,
pant complaints but rather to describe the build- the fungal I/O ratio <1 (0.28 ≤ I/O ≤ 0.8) indi-
ing’s air quality over time. As represented by our cated the absence of an indoor air contamination
data, bacterial and fungal concentrations in all source. Moreover, as observed by Burge et al.
offices ranged from 50 to 500 CFU/m3 , indicating (2000) and Shelton et al. (2002), the seasonal dis-
a medium–low contamination level (CEC 1993). tribution of fungal genera in indoor air confirmed
The values obtained were in the range reported the influence of outdoor air. The data analysis
in other studies of non-complaint office buildings revealed the absence of any relationship between
around the world (Parat et al. 1997; Law et al. bacterial and fungal counts, confirming their ori-
2001; Sessa et al. 2002; Shelton et al. 2002; Tsai and gin from different sources.
Macher 2005). On the other hand, during the first Although some bacterial species encountered
winter sampling, a high fungal contamination was in indoor air can be considered to be opportunistic
recorded (range between 500 and 2,000 CFU/m3 ) pathogens (S. haemolyticus, S. epidermidis and
in indoor air. This result is probably related to S. hominis), the heterogeneity of the bacterial
the flood that occurred during that period, leading species and the low counts recorded do not sug-
to water stagnation and environmental conditions gest any particular risk for occupant health. In
(e.g. relative humidity and nutrients) favouring contrast, the high fungal contamination and the
fungal growth. No significant difference in the presence of potentially allergenic genera (Peni-
microbial air contamination was found among the cillium) observed in the first winter sampling
offices, probably because the three offices consid- (related to the flood) point out a possible health
ered were located in an open space without any risk in that situation.
particular source of microbial contamination. This Important information about influence of the
homogeneous distribution of bacterial and fungal HVAC characteristics (e.g. ATU, fan coil, water)
counts was also observed in other studies (Parat on IAQ can be obtained from the detailed analysis
et al. 1997). of bacterial and fungal counts. In particular, the
Considering the bacterial species identified in significant daily trend of indoor air bacterial (22◦ C
indoor air, the predominance of Micrococcus and and 37◦ C) and fungal contamination could be as-
Staphylococcus genera could be due to the human sociated with air movement caused by the daily
presence. This finding is supported by the indoor/ HVAC system being switched on in the morning
Environ Monit Assess (2010) 161:473–483 481

and switched off at the end of the working day. tive measure. It was also speculated that great care
This trend suggests that bacteria and fungi could should be taken during the cleaning operation of
proliferate in the ATU filter and vent ducts when the water tank in the ATU system. Although in
the HVAC system is switched off. Then, when the the investigated building there was no particular
HVAC system is switched on, the microorganisms risk observed, except for the unusual flood, it is
could spread in the air. The emission of bacteria important to note the usefulness of an IAQ pre-
and fungi due to incubation during the night- ventive evaluation to avoid occupant complaints
time HVAC shutdown was also observed in other or health effects. In fact, although the preventive
studies (Law et al. 2001). investigation may be initially more expensive and
The significant seasonal trend of microbial time consuming, it may prove to be useful by pre-
counts observed in indoor air, which differed from venting building environmental problems whose
outdoor air, was probably due to many factors solution could be very difficult and need greater
such as internal air circulation and the intermit- investment.
tent use of HVAC system, which varied according
to the season. Therefore, as observed by other Acknowledgements This study was carried out with fi-
authors (Parat et al. 1997; Tsai and Macher 2005), nancial support from the Telecom Italia Laboratories. The
authors wish to thank Prof. Roberto Bono and Dr. Elisa
indoor microbial counts do not seem to be related Gamalero for critical reading of the manuscript.
to outdoor levels in the presence of low microbial
contamination. The results of the ATU investiga-
tion demonstrated the good efficiency of micro-
bial contamination removal of the unit. Except References
for the first winter sampling, in normal climatic
ACGIH (1999). Bioaerosol: Assessment and control (1st
conditions the ATU seems to have removed air ed.). Cincinnati, OH: American Conference of Gov-
microbial contamination. ernmental Industrial Hygienists.
A relevant role in air movement might be at- Avidano, L., Gamalero, E., Cossa, G. P., & Carraro, E.
tributed to building occupants’ personal choice to (2005). Characterisation of soil health in an Italian
polluted site by using microorganisms as bioindicators.
switch on or off the fan coil units. The analysis
Applied Soil Ecology, 30, 21–33. doi:10.1016/j.apsoil.
of the fan coil unit air flow revealed microbial 2005.01.003.
contamination levels lower than the indoor air. Burge, H. A., Pierson, D. L., Groves, T. O., Strawn, K. F., &
Moreover, bacterial species found in the fan coil Mishra, S. K. (2000). Dynamics of airborne fungal
populations in a large office building. Current Micro-
unit air flow were similar to those recovered in biology, 40, 10–16. doi:10.1007/s002849910003.
the indoor air. These results suggest that fan CEC (1993). Indoor air quality & its impact on man. Bio-
coil units determined air movement, but in this logical particles in indoor environments. Commission
case, they were not directly involved in indoor air of European Communities. Report 12. Cost Project
613. EUR. 14988 EN.
contamination.
Clarke, D., & Nikkel, D. (1995). Office air: A worker’s
In regards to the water investigation, high guide to air quality in offices, schools, and hospi-
bacteria in the humidification water tank was tals. Report of the Federal–Provincial Advisory Com-
recorded, underlining a microbial proliferation, mittee on Environmental and Occupational Health,
Canada. 93-EHD-174.
especially during warmer seasons.
EN ISO (1999). Water quality—Enumeration of culturable
In conclusion, this study can help better char- micro-organism—colony count by inoculation in a nu-
acterise bacterial and fungal populations in the in- trient agar culture medium. International Organization
door air of office building, highlighting the role of for Standardization (EN ISO Standard 6222–1999).
Huang, R., Agranovski, I., Pyankov, O., & Grinshpun, S.
the HVAC system on IAQ. The results obtained
(2008). Removal of viable bioaerosol particles with a
suggest that the uninterrupted functioning of the low-efficiency HVAC filter enhanced by continuous
HVAC system may be recommended, with the emission of unipolar air ions. Indoor Air, 18, 106–112.
possible application of an energy-saving device. doi:10.1111/j.1600-0668.2007.00512.x.
Huttunen, K., Rintala, H., Hirvonen, M. R., Vepsäläinen,
Moreover, a programmed and periodical clean-
A., Hyvärinen, A., Meklin, T., et al. (2008). Indoor air
ing operation and maintenance activities of the particles and bioaerosols before and after renovation
HVAC system should be organised as a preven- of moisture-damaged buildings:the effect on biological
482 Environ Monit Assess (2010) 161:473–483

activity and microbial flora. Environmental Research, Parat, S., Perdrix, A., Fricker-Hidalgo, H., Saude, I.,
107, 291–298. doi:10.1016/j.envres.2008.02.008. Grilloy, R., & Baconnier, P. (1997). Multivariate
Hyvärinen, A., Reponen, T., Husman, T., Ruuskanen, J., & analysis comparing microbial air content of an air-
Nevalainen, A. (1993). Characterizing mold problem conditioned building and a naturally ventilated build-
buildings: Concentrations and flora of viable fungi. ing over one year. Atmospheric Environment, 31,
Indoor Air, 3, 337–343. doi:10.1111/j.1600-0668.1993. 441–449. doi:10.1016/S1352-2310(96)00212-9.
00017.x. Pasanen, A., Niininen, M., Kalliokoski, P., Nevalainen, A.,
ISO (1998). Water quality-detection and enumeration of Le- & Jantunen, M. (1992). Airborne Cladosporium and
gionella. International Organization for Standardiza- other fungi in damp versus reference residences.
tion (ISO Standard 11731–1998). Atmospheric Environment, 26, 121–124.
Jo, W. K., & Seo, Y. J. (2005). Indoor and outdoor Pastuszka, J. S., Paw, U. K. T., Lis, D. O., Wlazlo, A.,
bioaerosol levels at recreation facilities, elementary & Ulfig, K. (2000). Bacterial and fungal aerosol in
schools, and homes. Chemosphere, 61, 1570–1579. indoor environment in Upper Silesia, Poland. At-
doi:10.1016/j.chemosphere.2005.04.103. mospheric Environment, 34, 3833–3842. doi:10.1016/
Jones, A. P. (1999). Indoor air quality and health. S1352-2310(99)00527-0.
Atmospheric Environment, 33, 4535–4564. doi:10.1016/ Rao, C. Y., Riggs, M. A., Chew, G. L., Muilenberg, M. L.,
S1352-2310(99)00272-1. Thorne, P. S., Van Sickle, D., et al. (2007). Character-
Kim, K. Y., & Kim, C. N. (2007). Airborne microbiologi- ization of airborne molds, endotoxins, and glucans in
cal characteristics in public buildings of Korea. Build- homes in New Orleans after hurricanes Katrina and
ing and Environment, 42, 2188–2196. doi:10.1016/j. Rita. Applied and Environmental Microbiology, 73,
buildenv.2006.04.013. 1630–1634. doi:10.1128/AEM.01973-06.
Law, A. K. Y., Chau, C. K., & Chan, G. Y. S. (2001). Reynolds, S. J., Black, D. W., Borin, S. S., Breuer, G.,
Characteristics of bioaerosol profile in office buildings Burmeister, L. F., Fuortes, L. J., et al. (2001). In-
in Hong Kong. Building and Environment, 36, 527– door environmental quality in six commercial of-
541. doi:10.1016/S0360-1323(00)00020-2. fice buildings in the midwest United States. Applied
Lee, T., Grinshpun, S. A., Martuzevicious, D., Adhikari, Occupational and Environmental Hygiene, 16, 1065–
A., Crawford, C. M., Luo, J., et al. (2006). Relationship 1077. doi:10.1080/104732201753214170.
between indoor and outdoor bioaerosols collected Riggs, M. A., Rao, C. Y., Brown, C. M., Van Sickle, D.,
with a button inhalable aerosol sampler in urban Cummings, K. J., Dunn, K. H., et al. (2008). Resident
homes. Indoor Air, 16, 37–47. doi:10.1111/j.1600-0668. cleanup activities, characteristics of flood-damaged
2005.00396.x. homes and airborne microbial concentrations in New
Loftness, V., Hakkinen, B., Adan, O., & Nevalainen, A. Orleans, Louisiana, October 2005. Environmental Re-
(2007). Elements that contribute to healthy building search, 106, 401–409. doi:10.1016/j.envres.2007.11.004
design. Environmental Health Perspectives, 115, 965– Sampò, S., & Luppi Mosca, A. M. (1988). Fungi from the
970. walls of a flat in Turin. Allionia, 28, 175–184.
Maroni, M., Bersani, M., Cavallo, D., Anversa, A., & Sampò, S., & Luppi Mosca, A. M. (1989). A study
Alcini, D. (1993). Microbial contamination in build- of the fungi occurring on 15th century frescoes in
ings: Comparison between seasons and ventilation Florence, Italy. International Biodeterioration, 25,
systems. In O. Seppanen (Ed.), Proceedings of indoor 343–353.
air’93, Helsinki, international conference on indoor air, Schwab, C. J., & Strauss, D. C. (2004). The roles of Peni-
quality and climate (Vol. 4, pp. 137–142). cillium and Aspergillus in sick building syndrome. Ad-
Mendell, M. J., Lei-Gomez, Q., Mirer, A. G., Seppänen, O., vances in Applied Microbiology, 55, 215–238.
& Brunner, G. (2008). Risk factors in heating, ventilat- Sen, B., & Asan, A. (2009). Fungal flora in indoor and
ing, and air-conditioning systems for occupant symp- outdoor air of different residential houses in Tekirdag
toms in US office buildings: The US EPA BASE City (Turkey): Seasonal distribution and relationship
study. Indoor Air, 18, 301–316. doi:10.1111/j.1600- with climatic factors. Environmental Monitoring and
0668.2008.00531.x. Assessment. doi:10.1007/s10661-008-0262-1.
Montanaro, A. (1997). Indoor allergens: Description and Seppänen, O., & Fisk, W. J. (2002). Association of ventila-
assessment of health risks. In E. J. Bardana, & A. tion system type with SBS symptoms in office work-
Montanaro (Eds.), Indoor air pollution and health. ers. Indoor Air, 12, 98–112. doi:10.1034/j.1600-0668.
New York: Marcel Dekker. 2002.01111.x.
Nathanson, T. (1995). Indoor air quality in office buildings: Sessa, R., Di Pietro, M., Schiavoni, G., Santino, I.,
A technical guide. Report of the Federal–Provincial Altieri, A., Pinelli, S., et al. (2002). Microbiologi-
Advisory Committee on Environmental and Occupa- cal indoor air quality in healthy buildings. The New
tional Health, Canada. 93-EHD-166. Microbiologica, 25, 51–56.
Nevalainen, A. (1989). Bacterial aerosols in indoor air. Shelton, B. G., Kirkland, K. H., Flanders, W. D., &
Ph.D. diss, University of Kuopio, Finland. Morris, G. K. (2002). Profiles of airborne fungi in
Nevalainen, A., & Seuri, M. (2005). Of microbes and buildings and outdoor environments in the United
men. Indoor Air, 15, 58–64. doi:10.1111/j.1600-0668. States. Applied and Environmental Microbiology, 68,
2005.00344.x. 1743–1753. doi:10.1128/AEM.68.4.1743-1753.2002.
Environ Monit Assess (2010) 161:473–483 483

Srikanth, P., Sudharsanam, S., & Steinberg, R. (2008). Bio- anisms. Neurotoxicology and Teratology, 28, 573–588.
aerosols in indoor environment: Composition, health doi:10.1016/j.ntt.2006.07.003.
effects and analysis. Indian Journal of Medical Micro- Tringe, S. G., Zhang, T., Liu, X., Yu, Y., Lee, W. H., Yap,
biology, 26, 302–312. J., et al. (2008). The airborne metagenome in an in-
Stetzenbach, L. D. (1997). Introduction to aerobiology. In door urban environment. PLoS ONE, 3, 1–10.
C. J. Hurst, G. R. Knudsen, M. J. Mc Inerney, & L. D. Tsai, F. C., & Macher, J. M. (2005). Concentrations of
Stetzenbach (Eds.), Manual of environmental microbi- airborne culturable bacteria in 100 large US office
ology. Washington, DC: ASM Press. buildings from the BASE study. Indoor Air, 15, 71–81.
Stanley, N. J., Kuehn, T. H., Kim, S. W., Raynor, P. C., doi:10.1111/j.1600-0668.2005.00346.x.
Anantharaman, S., Ramakrishnan, M. A., et al. Von Arx, J. A. (1981). The genera of fungi sporulating
(2008). Background culturable bacteria aerosol in two in pure culture. Lubrecht & Cramer Ltd. Vaduz,
large public buildings using HVAC filters as long Germany.
term, passive, high-volume air samplers. Journal of Wu, P. C., Li, Y. Y., Chiang, C. M., Huang, C. Y.,
Environmental Monitoring, 10, 474–481. doi:10.1039/ Lee, C. C., Li, F. C., et al. (2005). Changing micro-
b719316e. bial concentrations are associated with ventilation per-
Shoemaker, R. C., & House, D. E. (2006). Sick build- formance in Taiwan’s air-conditioned office buildings.
ing syndrome (SBS) and exposure to water-damaged Indoor Air, 15, 19–26. doi:10.1111/j.1600-0668.2004.
buildings: Time series study, clinical trial and mech- 00313.x.

Potrebbero piacerti anche