Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
11.9.1 General
Control places
Two control places can be connected to base unit and two more to extension
unit. Furthermore, two push buttons can be connected to base unit, these
push buttons are counted as one control place. If, due to winch construction,
more push buttons are needed, parallel connection is to be used to connect
necessary amount of push buttons.
Winch control can be done from only one control place at a time so, that
controls are accepted only from control place where signals were first given.
64/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
Control place can be changed only after the controller (or push buttons) are
returned to 0-position.
Controller
By using controller, motor can be driven with all (max 3) speeds to both
directions if, driving is permitted considering overcurrent, overload etc.
conditions. If controller is turned directly to high speed, lower speeds will be
driven first. Winch will stay in every lower speed step before changing to
higher speed step, until adjusted starting time has passed. Changing to lower
speed can be done withouit delay. However, if the controller is take from 3-
step to 0-position so quickly, that neither 2- nor 1-speed step are switched on,
a motor braking of adjusted lenght will be performed at 1-speed before closing
motor brake.
Push buttons
With push buttons, assembled next to winch claw clutch, motor can be driven
with slow speed in/out to make clutch operating easier.
Anchor drive
Anchor drive will be switched on, when inductive sensor in anchor winch claw
clutch is activated (led 1 will be switched off). This will cause:
• possible automatic can not be switched on
• electronic current control will be switched off (thermal current control
remains in function)
• speedsteps higher than nominal, can not be switched on.
65/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
When inductive sensor in mechanical high gear claw clutch is activated, led 2
will be switched off and possible automatic can not be switched on. This
function has no affect to base unit operation.
66/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
11.10.1 General
The task of mooring automatic is to keep tension in mooring line within pre-
adjusted limits.
11.10.2 Function
The automatic keeps rope tension within hysteresis range. If rope tension is
changing outside hysteresis range, automatic will start winch and tension is
driven back to hysteresis range. While automatic is on, rope tension can be
changed with automatic setting switch.
If desired, alarm can be received when too much rope has been payed out,
e.g. in case that external load is higher than automatic setting value and
automatic is continuously paying out. For pay out control, a sensor is to be
installed to winch to measure drum rotation. A closing contact signal is
available in base unit terminals 0X19 and 0X20 when alarm is activated.
3-speed can not be connected, if set 3-speed prevention limit has been
exeeded in manual drive. Automatic unit is provided with separate limits for
nominal gear and mechanical high gear.
67/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
Led's H1...H8 are installed to automatic unit for disturbance indication. Further
more, a closing contact disturbance signal is available in base unit terminals
0X21 and 0X22.
11.10.3 Connections
Load sensor
Two automatic setting switch can be connected to base unit (MPC-200) and
two more to extension unit (MPC-210).
Tension meter
Rope tension can be seen from tension meter installed in control column.
68/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
Drum rotation sensor is installed to winch, when needed for rope pay out
control.
69/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
11.11.1 Commissioning
Before switching voltage on, all connections according starter circuit diagram
must be connected to the unit. Also possible expansion unit and automatic
unit must be connected when voltage is off. When re-assembling base unit
MPC-200 (e.g. spare part), ensure before switching voltage, that jumpers
J1...J5 are according starter circuit diagram (1 = jumper unbroken, 0 = jumper
broken). When taking unit in to operation, the cover must be closed to ensure
undisturbed operation.
11.11.2 Connections
70/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
71/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
11.11.3 Adjusting
Jumpers J1...J5
J1 J2 J3 J4 J5 Jumper
1 No direction change in anchor drive
0 Direction change in anchor drive
1 0 Nominal speed 1
1 1 Nominal speed 2
0 1 Nominal speed 3
1 0 Dahlander with 1-speed
1 1 Dahlander with 2-speed
0 1 Dahlander with 3-speed
1 = jumper unbroken
0 = jumper broken
72/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
A separate current limit is provided for motors every speed steps. Electronic
current control is acting also as an over load protection for winch.
1-speed = P2
2-speed = P3
3-speed = P4
Red leds located next to trimmers are indicating when adjusted current limit
has been exeeded. Current limits are not used during starting. As there is a
common current sensor, several current limits can be activated
simultaneously, but only limit for speed which is in use is checked by control
electronics.
Starting time for every speed steps can be adjusted with 10-step code switch.
Electronical current control is not working during adjusted starting time and
changing to higher speed step is possible only after starting time of lower
speed stap has gone.
1-step = S1
2-step = S2
3-step = S3
73/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
Switch starting
position time (s)
0 0.5
1 1 <- S1,S2 factory setting
2 1.5
3 2 <- S3 factory setting
4 3
5 4
6 5
7 6
8 7
9 8
switch braking
position time (s)
10 0.5 <- factory setting
1 1
2 1.5
3 2
4 3
5 4
6 5
7 6
8 7
9 8
74/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
11.11.4 Disturbances
Disturbances at starting
If motor temperature will rise too high while motor is running, it will cause
thermistor disturbance. The motor will stop immediately, and disturbance relay
will be energized. Disturbance situation will disappear after motor temperature
has decreased under allowed value.
If acceptable brake current will not occur after switching on brake contactor or
if brake current will not disappear after switching off brake contactor,
disturbance relay will be energized for a short moment. After this, control
electronics will start operation from beginning and starting conditions
according item 4.1 will be checked.
75/89
USE AND MAINTENANCE MANUAL
51 4- D 4 6 8 /6 9 /7 0 /7 1 /7 2/73 /74 /7 5
If the current limit adjusted for speed step is exeeded after adjusted starting
time:
• disturbance situation will occur if motor was running on nominal speed or
slower than nominal speed or if possible automatic was switched on.
• if a speed step higher than nominal was used, control electronics will
automatically change to nominal speed. To switch back to high speed, the
controller must be taken to nominal speed and then back to high speed.
Disturbance relay will be energized for a short moment. After this, control
electronics will start operation from beginning and starting conditions
according item 4.1 will be checked.
Feedback disturbance
Disturbance relay will be energized for a short moment. After this, control
electronics will start operation from beginning and starting conditions
according item 4.1 will be checked.
Unknown disturbance
76/89