X SERIES
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Daikin Airconditioning (Singapore) Pte. Ltd.


10 Ang Mo Kio Industrial Park 2 Singapore 569501
Phone: +65 5583 8888
Website: www.daikin.com.sg
Cooling Only 50 Hz

VRV is a trademark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trademark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

Cooling Only 50 Hz
Specifications, designs and other content appearing in this brochure are current as of July 2019 but subject to change without notice.
c All rights reserved 07/18 SS
Exceeding Boundaries with
Innovative Energy Savings
First launched in Japan in 1982, the Daikin VRV system has been embraced C o n t e n t s
by world markets for over 35 years. Now, Daikin proudly introduces the new
VRV User Benefits 3
VRV X. By combining the technologies of VRV, VRT and VAV, we have attained VRV Outdoor Units Series 18
both energy savings and comfortable air conditioning. VRV lndoor Units 25

VRV + VRT + VAV


Residential Indoor Units with Connection to BP Units 63
Air Handling Unit 67
Air Treatment Equipment Lineup 68
Control Systems 85
Option List 97
Daikin Engineering Supports 104

VRV X series
movie

Automatic refrigerant
Energy savings High reliability
charge function
•Optimised operation efficiency •New inverter PC board
Uniting VRV, VRT and VAV
•Higher installation quality •Double backup operation
technologies
•Easier installation •Refrigerant cooling for PC board

* VRV is a trademark of Daikin Industries, Ltd.

1 2
VRV User Benefits For
Comfortable environment
USERS While operating optimally at low load, VRT
For property smart operation maintains the indoor

OWNERS
First launched in 1982, the Daikin VRV system has been
temperature and ensures a comfortable
providing comfort and reliability to building owners and their environment.
tenants for over 35 years. Leveraging the latest in
BP unit
energy-saving technology, Daikin has further improved
Residential indoor units*
energy savings while reducing space requirements. This Min. sound
level
added value is one reason why Daikin is the right choice for Because indoor units developed for residential use can be connected, it 19 dB(A)
is possible to realise quiet operation.
building owners.
You can include indoor units that operate at min.19 dB(A), and to reduce
the noise of refrigerant passing through the piping by remotely installing
Energy saving & an BP unit.
*For indoor units connectability, please refer to the indoor unit product lineups under individual outdoor unit series.

comfortable environment
Based on the idea of using only as much space as
Max. total
absolutely required, Daikin first launched its
For Varied lineup of models
piping length

CONSULTANT
commercial multi-split air conditioning systems in 1982. 1000 m

Since then, customers have benefitted from much


System applications range from family
increased energy efficiency. Now, our revolutionary new
and DESIGN
residences to large commercial buildings.
systems dramatically reduce energy with VRT Smart
With various types of indoor units available, Max. level
Control. During operating periods, control programs Max. equivalent
piping length
difference
between the

OFFICES
comfortable airflow is ensured in every space. outdoor units
ensure thermal loading is generally low, thus boosting 190 m and the indoor
units
energy efficiency. This greatly reduces the amount of
Long piping provides more
90 m
energy required for building air conditioning.

While optimally operating at low load, it


flexible system design
Conventional air-conditioning method Fully automatic energy-saving
maintains a comfortable indoor Changes in the room temperature: Large refrigerant control Greater design freedom is provided because
environment. The power consumption attributed to the Changes in the room temperature: Small
star t-stop loss also increases the load. Wasted power consumption is also
equivalent piping between indoor and outdoor
Start minimised. unit can run as large as 190 m and reach a maximum height difference of 90 m.
Room Temperature

Compatible with engineering software


temperature setting
Turned off by Turned off by Turned off by *Graph shown above is for
the thermostat the thermostat the thermostat illustration purposes only.

We at Daikin provide the software, the simulation results, and drawing


Efficient space utilisation materials to support the business-information modeling (BIM) currently
entering the mainstream in construction industries.
Daikin VRV system can be used to develop a Cooling tower VRV X series
large-scale air conditioning system on a single Energy efficient
refrigerant system, thus reducing the space required
for air conditioning equipment. Because the difference Daikin’s innovative energy-saving technology helps
in height between the indoor and the outdoor unit can you to achieve your green building solution.
be as large as 90 m, even with a 20-storey building all
of the outdoor units can be placed on the rooftop for
Garage
more efficient utilisation of space.

For Automatic refrigerant charge function


High reliability
INSTALLERS The automatic refrigerant charge function automates the charging of the
Double backup operation proper refrigerant amount and the closing of shut-off valves by simply
Unit backup operation Compressor backup pressing a switch after pre-charging. Simplified installation eliminates
Daikin VRV outdoor unit goes beyond just highly function operation function excessive and insufficient refrigerant charge amounts due to calculation
reliable compressors with a backup system that
Emergency Malfunction mistakes, and this has led to higher installation quality.
ensures continued operation.
operation
Unit backup Lightweight and compact large-capacity single units
Should one outdoor unit in a multiple unit system fail, the
other outdoor units switch to emergency operation. If for Systems can be configured with single modules providing up to 20 HP.
some reason a failure occurs, the system for that unit does The lightweight and compact bodies are both easy to install and can be
not completely stop, and air conditioning is maintained. transported in elevators.
Malfunction
Compressor backup
Emergency operation
Simple piping, easy wiring
Since units are equipped with two compressors, even if one
compressor fails, the other compressor carries on in The REFNET piping system and DIII-NET system simplify refrigerant piping and
emergency mode. control wiring installation.

3 4
X SERIES New Heights in Energy Efficiency During Actual Operation

Advanced technologies
for greater energy savings VRV + VRT + VAV
By uniting advanced software and hardware technologies for greater energy savings during
actual operation and combining the technologies of VRV, VRT and VAV, we have attained
RXUQ-A
both energy savings and comfortable air conditioning.
Software
VRT Smart Control (Fully A utomatic Energy-sav ing Ref rigerant Control )
technology
Cooling Only Optimally supply only for the needed capacity of indoor units
Daikin developed VRT smart control by combining air volume control (VAV: Variable Air Volume)
6 HP - 60 HP for indoor units with conventional VRT control, which optimises compressor speed by
calculating the required load for the entire system and optimal target refrigerant temperature
(16 kW) (168 kW) based on data sent from each indoor unit. Coordination with the air volume control reduces
compressor load and minimises operation loss based on detailed control. VRT smart control
ensures energy savings and comfortable air conditioning to meet actual operating conditions. VRT Smart
Control
•Overview of the control (system control flow) Function
movie
Different automatic energy-saving refrigerant control applies depending on the indoor units connected.

Greater energy savings during low-load operation Subject to VRT smart control
Target indoor units
Subject to VRT control
1
Temperature
data received
from indoor units

The key to innovative energy •Correlation between the load factor for the rated capacity and operation time
(in office buildings in Singapore)
Co o rd in a t e d c o n t rol
savings is to increase efficiency *According to a survey by Daikin (based on Air Conditioning Network Service System data)

during low-load operation.


The following items are The VRT smart control also controls the
Using data gathered from actual operation, forecast and calculated based airflow rate of indoor units automatically*,
Load factor of 50% or less to attain detailed energy-saving control.
Daikin discovered that air conditioning on the required capacity:
accounts for 80% of * Airflow rate should be set to “Auto”.

2
Select the target
3
•Indoor fan air volume
Operation period

systems operate at a load factor of 50% or annual operation period. Compressor


•Target value of refrigerant temperature refrigerant
less for 80% of their annual operation speed control
temperature
period.
This inspired us to develop new The smooth control •Changes in the air-conditioned room temperature during low-load operation*
technologies to enhance energy efficiency (which keeps the compressor Conventional air-conditioning method Fully automatic energy-saving
during low-load operation. running) saves energy and refrigerant control
Changes in the room temperature: Large
Utilising these technologies, Daikin’s new ensures comfort during low-load The power consumption attributed to the Changes in the room temperature: Small
VRV X series raises the standard of energy star t-stop loss also increases the load. Wasted power consumption is also
operation. Start minimised.
efficiency.
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Temperature
Room temperature setting
Turned off by Turned off by Turned off by
Load factor for the rated capacity the thermostat the thermostat the thermostat
*Graph shown above is for illustration purposes only.

Note:
•For the classification of indoor units (VRT smart control and VRT control), refer to page 25–26.
•If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
•If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart control and VRT control are disabled.
Higher Coefficient of Performance (COP) Annual power
consumption
Optimum utilisation of VRT Smart Control and VRT Control
COP for 10 HP 20%* lower Effectiveness can be demonstrated for VRT Smart Control and VRT Control when all the indoor units operate under low load conditions in
a similar manner.
* Simulation conditions :
8.84 Low load conditions are the time when room temperature approaches set temperature.
9 8.42 8.19 ࠮Location : Bangkok, Thailand
࠮System : Outdoor unit (10 HP) x 1 For this reason, please note the following to maximise energy efficiency.
Cooling Operation COP

8 7.37 Indoor unit (2 HP, Round Flow with Sensing type) x 5


࠮Operation time : 8:00-20:00 5 days/week •When selecting indoor units
7 6.43 ࠮Outdoor units : Indoor units are installed in a system so that they operate largely under the same conditions.
6 5.69 New model : RXUQ10A (VRV X series) Energy efficiency decreases for the installation patterns shown below.
5 5.08 Conventional model : RXQ10T (VRV IV) Example:
4.45 1) A load imbalance occurs because an indoor unit in the same system is installed near the perimeter of the room or in the vicinity of a
4 VRV IV (RXQ10T)
room entrance.
3 X SERIES 2) Different operating hours for indoor units.
0 *Cooling operation conditions: Indoor temp. of •Time of Use
30% 40% 50% 60% 70% 80% 90% 100% Load 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB. 1. Energy efficiency decreases when the set temperature of a specified indoor unit is excessively lowered during cooling operation.
2. The airflow rate setting is set to “Auto” during VRT Smart Control.

7 5 6 8
New Heights in Energy Efficiency During Actual Operation

Available on Hardware
New Scroll Compressor all models technology Advanced oil temperature control
Standby power consumption is reduced
Refrigerant leakage is minimised during low-load operation.
The advanced oil temperature control reduces standby power consumption by up to 65.4%* annually compared to
Operation loss due to refrigerant leakage is reduced by the proprietary
conventional models. Standby power needed for preheating refrigerator oil, which consumed substantial standby power, was
back pressure control mechanism to ensure stable low-load operation.
reduced to save energy when the air conditioner is stopped.
•Compressor efficiency* * Operation calculation conditions: VRV X series 14 HP
New compressor Location: Singapore
Conventional compressor New Scroll Operation time: 08:00–18:00 on weekdays
Compressor efficiency

Compressor
movie

The back pressure control mechanism


increases the efficiency during
Higher efficiency is provided during rated operation.
low-load operation.
COP at 100% operation load
Load factor
*Graph shown above is for illustration purposes only.
5 4.95
4.65
4.45
Back pressure control mechanism 4.41
4.32 4.29 4.23
4.07
Conventional mechanism New intermediate 4 3.95 3.91
The movable scroll is pressed pressure mechanism 3.80 3.74 3.78

Cooling operation COP


by the pressure difference The force pressing the
3.46
between high and low movable scroll is optimised
3.25
pressures. according to operating 3.11
The force pressing the conditions. The behavior of 3
movable scroll decreases the movable scroll has been
during low-load operation, stabilised to increase
resulting in compression efficiency during low-load
leakage from movable parts. operation.
VRV IV VRV
0 X SERIES

6 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP
Cooling operation conditions : Indoor temp, of 27°CDB, 19°CWB, and outdoor temp, of 35°CDB.

Extensive product lineup


•The VRV X series achieves higher efficiency in a design that is more compact and lightweight than the VRV IV High-COP type,
and the capacity of the lineup has been further expanded. (12 HP– 50 HP 6 HP–60 HP)

VRV IV
High-COP type (18 HP) X SERIES (18 HP)

The force pressing the The intermediate pressure COP 4.40 4.54 3% Increase
movable scroll decreases keeps pressing the movable
during low-load operation. scroll during low-load operation.
Installation space 2.13 m 2 1.66 m 2 22% Decrease
2,790 mm 400 kg 28% Decrease 2,170 mm
Product weight 555 kg
765 mm 765 mm
Intermediate pressure
adjustment port

The intermediate pressure Lineup New lineup


(back pressure) optimises
the force pressing the HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
movable scroll depending
on the operating condition. Single outdoor units
VRV X SERIES Double outdoor units
Triple outdoor units

9 7 8 10
Connection Ready Systems

Automatic refrigerant charge function Comfort


Contribute to optimised operation efficiency, Low operation sound
higher quality and easier installation Optimised Operation /PNOLMMPJPLUJ`OLH[L_JOHUNLYOLSWZ[VHJOPL]LSV^VWLYH[PVUZV\UK
Automatic
Refrigerant Sound level(dB(A))
Charge Function
Optimised operation efficiency movie 6 HP 8/10 HP 12 HP 14/16 HP
The automatic refrigerant charge function X SERIES 54 56 58 59
automatically determines the optimal Efficiency Cooling
amount of refrigerant to be charged. capacity
This function prevents a capacity Insufficient Excessive Large airflow, high static pressure and quiet technology
refrigerant charge refrigerant charge
shortage or energy loss due to excessive (K]HUJLKHUHS`[PJ[LJOUVSVNPLZHYL\[PSPZLK[VVW[PTPZLMHUKLZPNUHUK
or insufficient refrigerant. PUJYLHZLHPYMSV^YH[LHUKOPNOL_[LYUHSZ[H[PJWYLZZ\YL
Optimal refrigerant Refrigerant charge amount
amount
Streamlined air grille Streamlined scroll fan
Higher quality and easier installation ItWYVTV[LZ[OLKPZJOHYNLVM TOLZOHYWLKNLVMLHJOMHUISHKLOHZH
Z^PYSPUNHPYMSV^M\Y[OLYYLK\JPUN JLY[HPUJ\Y]H[\YLYLK\JPUNIV[O[OL
The automatic refrigerant charge function automates the charging of the proper refrigerant amount and the closing of
[OLWYLZZ\YL ]PIYH[PVUHUK[OLWYLZZ\YLSVZZ
shut-off valves by simply pressing a switch after pre-charging.
SVZZ
Simplified installation eliminates excessive and insufficient refrigerant charge amounts due to calculation mistakes, and
this has led to higher installation quality. :[YLHTSPULK
VRV IV
ZJYVSSMHU

1 2 3 4 5
Calculate necessary Recalculate refrigerant Charge refrigerant Regularly check refrigerant Complete by manually
refrigerant amount from amount from final weight on weighing scale closing valves when proper 0SS\Z[YH[LKMHU
design drawing installation drawing weight is reached

X SERIES
1 2 3 Automatic completion by proper
refrigerant amount
Calculation of necessary Pre-charge of refrigerant* Start of automatic
refrigerant amount from refrigerant charge operation
design drawing Monitoring refrigerant charging is
unnecessary Nighttime quiet operation function
No recalculation of charge amounts due For areas where there are stringent limitations to sound levels, the outdoor unit sound
to minor design changes locally level can be reduced during the nighttime, to meet the requirement.

*Pre-charge amount changes according to conditions, and


The automatic night quiet mode will initiate 8 hours*¹ after the peak temperature is
pre-charging is unnecessary when necessary refrigerant reached in the daytime, and normal operation will resume 9 hours*² after that.
amount is 4 kg and under.
Even if a refrigerant leak occurs from local piping after installation, the proper Please refer to Engineering Data Book for details. *1. Initial setting is 8 hours. Can be selected from 6, 8 and 10 hours.
*2. Initial setting is 9 hours. Can be selected from 8, 9 and 10 hours.
refrigerant amount can still be charged without needing to calculate the *3. In case of 10 HP outdoor unit.
necessary amount.
Starting the automatic refrigerant charge operation again will ensure that
optimum operation efficiency and installation quality are maintained.

Peak in outdoor temperature

High reliability Conventional inverter New inverter PC board 100% 8 hrs 9 hrs

New inverter PC board


50%
The control functions of inverter technology have been
integrated on printed circuit boards. As well as improving
reliability, this has reduced the number of parts and enabled 56dB(A) Night quiet mode Note:
downsizing. · The night quiet mode lowers operating sound by reducing
capacity. This function is available in setting at site.
• New waveform control improves tolerance of variations in min. 40 dB(A) · The operating sound in quiet operation mode is the actual value
40dB(A)
power supply voltage. Even if the power supply has measured by our company. Because priority is given to
8:00 12:00 16:00 20:00 0:00 4:00 8:00 protection mode, such as for oil recovery, the operating sound
irregularities, rises in current are suppressed and operation may become higher temporarily.
continues. Load % · The relationship of outdoor temperature (load) and time shown
• Durability of the inverter printed circuit board improved by Operating sound dB(A) above is just an example.
changing the electrolytic capacitors for the compressor to Film capacitor
Electrolytic capacitors
film capacitors.

11 9 10 12
Connection Ready Systems Refined Design Meets Advanced Technologies

Realising compact technology with performance


Air Conditioning Network Service System Highly integrated heat exchanger
Preventive Maintenance The unique 4-sided all round heat exchanger ensure sufficient surface area for the heat exchanger.
The intelligent Touch Manager can be connected to Daikin’s own Air Conditioning Network Service System for remote This improves the heat exchanger performance without increasing the footprint.
monitoring and verification of operation status for VRV system. By its ability to predict malfunctions, this service provides
customers with additional peace of mind.
ZPKLKOLH[L_JOHUNLY /PNOLMMPJPLUJ`OLH[L_JOHUNLYPZYLHSPZLKI`YLK\JPUN
HPYMSV^YLZPZ[HUJL^P[OHKVW[PVUVMZTHSSJVVSPUN[\ILZ^P[O
Enhanced convenience with link to the Air Conditioning Network Service System
HKPHTL[LYVMĸ
The intelligent Touch Manager connects seamlessly to Daikin’s 24-hour Air Conditioning Network Service System.

ACC centre
Personnel at the centre monitor the
occurrence of malfunctions and track their
Trouble
cause via the Internet.
Advance malfunction warnings help prevent
the sudden occurrence of problems later.
Even malfunctions difficult to identify
Air Conditioning Network Service System*
can be monitored remotely.
Repair *Because of restrictions
Allows dispatching of Enable prompt repairs as in applicable areas and
service engineers without service engineers know the release times, please consult
cause of the problem a Daikin representative
a call from customers. separately for details.
beforehand.

Daikin Offers a Variety of Control Systems >HMMSL-PU


(^HMMSLKZOHWLKMPU^P[OMPU
20 HP
WP[JOVMTT^HZ YV^ZTHSSWPWLKLZPNU
Convenient controllers that offer more freedom to administrators HKVW[LK[VYLHSPZLZ\MMPJPLU[ PUJYLHZLZOLH[[YHUZMLY
OLH[L_JOHUNLYHYLHMVY LMMPJPLUJ`
VW[PT\T\UP[LMMPJPLUJ`

Ease of use and expanded control functions


The user-friendly controller features colours, multilingual function, and icons in the display for
ease of understanding. A wide variety of control methods can be accommodated, permitting
administrators to monitor and operate the system even when they are away from the controller.
DCS601C51 Optimised inner design to ensure
)LSSTV\[O
Connect VRV system to your BMS via BACnet® or LONWORKS ® smooth airflow
Compatible with BACnet® and
LONWORKS®, the two leading open
BACnet® LONWORKS® ,SLJ[YPJJVTWVULU[Z^LYLKV^UZPaLKHUKWVZP[PVULKPU
network comunication protocols, Seamless connection Facilitating the network [OLKLHKZWHJLVM[OLILSSTV\[OZPKL[VKLJYLHZL
between VRV system
Daikin offers interfaces that provide integration of HPYMSV^YLZPZ[HUJL
and BACnet® open VRV system
a seamless connection between VRV network protocol. and LONWORKS®
system and your BMS.
DMS502B51 DMS504B51
(Interface for use in BACnet® ) (Interface for use in LONWORKS® )
Dedicated interfaces make ,SLJ[YPJ*VTWVULU[:WHJL
Daikin air conditioners freely Note : 1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and
compatible with open networks Air-Conditioning Engineers (ASHRAE).
2. LONWORKS® is a trademark of Echelon Corporation registered in the United States and other countries.

Smart phone will be a remote controller of VRV system (Option)


Easy maintenance Electrical component
For house VRV Smart Phone Control System The electrical components are strategically located
Up to 64 indoor units can be controlled. VRV Indoor unit on the top which eases the maintenance process.
Just add SVMPR2 to
Moreover, the heat exchanger on the front side can
this system be used effectively to improve its performance.

SVMPR2
VRV
Outdoor unit
LAN cable
You can control Monitor Control
VRV system from
anywhere in your house
Wi-Fi router Smart phone through Wi-Fi

13 11 12 14
Refined Design Meets Advanced Technologies Flexible System DesignSystem Design
Flexible

Sufficient cooling for


Positive
Eliminate suction More options for installation
More options location
for installation
electrical component pressure space resistance issue Long piping length Long piping length
The VRV X series is designed with Without affecting the fan
the electrical box strategically volume, the electric ;OLSVUNWPWPUNSLUN[OWYV]PKLZTVYLKLZPNUMSL_PIPSP[`^OPJOJHUTH[JOL]LUSHYNLZPaLKI\PSKPUNZ
positioned between a region of components are designed to
positive and negative pressure. This be at the top and this ulitises For connection of only VRV indoor units For connection of only VRV indoor units
)L[^LLU[OLV\[KVVY
Between the outdoor Between the outdoor
design allows large airflow from dead space. This eliminates IYHUJOHUK[OLSHZ[
branch and the last branch and the last
the problem of suction V\[KVVY\UP[
outdoor unit outdoor unit
negative pressure to positive Negative pressure
pressure due to the high pressure space resistance. Max. 13 m Max. 13 m
difference. Even Max.
Max. total
total piping
piping length
length 1000 m Max. total piping length 1000 m
negative )L[^LLU[OL
Between the
pressure V\[KVVY\UP[Z
outdoor units
space
High pressure since Max. 5 m
air enters near the fan
blower inlet
High pressure
difference

4H_SL]LSKPMMLYLUJL
Max. level difference
IL[^LLU[OLV\[KVVY
between the outdoor
4H_LX\P]HSLU[
Max. equivalent Max. equivalent \UP[ZHUK[OLPUKVVY
units and the indoor
WPWPUNSLUN[O
piping length piping length units
units

190 m 190 m 90 m 2
High reliability at high ambient temperature
)L[^LLU[OLMPYZ[PUKVVY 4H_SL]LSKPMMLYLUJL
Max. level difference Max. level d
0[PZWVZZPISL[VRLLWVWLYH[PVUZ[HISLL]LUH[OPNOHTIPLU[[LTWLYH[\YLZI`JVVSPUN[OLPU]LY[LYWV^LYTVK\SL IYHUJOHUK[OLMHY[OLZ[
branch and the farthest branch andIL[^LLU[OLPUKVVY
between the indoor
the farthest between th
PUKVVY\UP[
indoor unit indoor unit units
units uni
;OPZOLSWZTHPU[HPUHPYJVUKP[PVUPUNJHWHJP[`HUKYLK\JLZMHPS\YLYH[PV
Max. 90 m 1 301 m
Max. 90 m 30 m

PC Board

Heat Power Module

Refrigerant Refrigerant 5V[L!;OLHIV]LPZQ\Z[HZJOLTH[PJKPHNYHT


Note: The above is just a schematic diagram. Note: The a
Refrigerant Jacket

Using refrigerant to cool the inverter power module helps minimise


the size of the electronic components, and this results in reduction of
airflow resistance and high efficiency of the heat exchanger. Actual piping length (Equivalent) Actual piping length (Equivalent) 165 m (190 m)
Total piping length
ActualWPWPUNSLUN[O,X\P]HSLU[ Total piping length 1651000 m T
T190
Maximum allowable piping length Maximum allowable piping length
*VU[YVSIVHYKMHPS\YLYH[PV ;V[HSWPWPUNSLUN[O 90 m m1
1000
Maximum allowable piping length
H[Z[HISLVWLYH[PVUPZYLK\JLK Between the outdoor branch and the last outdoor unit (Equivalent)
)L[^LLU[OLMPYZ[PUKVVYIYHUJOHUK[OLMHY[OLZ[PUKVVY\UP[ 1090
Between the outdoor branch and the last
m m
(13
outdoor
 m) unit (Equivalent)
Between the outdoor units (Multiple use) Between the outdoor units (Multiple
)L[^LLU[OLV\[KVVYIYHUJOHUK[OLSHZ[V\[KVVY\UP[,X\P]HSLU[ 5 m T
10use)
T13
Maximum allowable level difference Maximum
Between the indoor units allowable level difference
)L[^LLU[OLV\[KVVY\UP[Z4\S[PWSL\ZL Between the indoor units 30
5 mm
Maximum allowable level difference Between the outdoor units
)L[^LLU[OLPUKVVY\UP[Z and the indoor units Between the outdoor units and the indoor
30mmunits
90 2

1. No special requirements up to 40 m. The maximum)L[^LLU[OLV\[KVVY\UP[ZHUK[OLPUKVVY\UP[Z


actual piping1.length
No special
can be requirements
90 m, depending
up to 40
on m.
conditions. The VRV
The maximum actual
A series
pipingislength
easy tocanextend
be 90tom, m
90depending
m by2 on conditions. Th
lessening the conditions from conventional VRV IV models. Be surelessening
to refer to
thethe
conditions
Engineering
fromData
conventional VRV IVofmodels.
Book for details these conditions
Be sure toand referrequirements.
to the Engineering Data Book for detail
5VZWLJPHSYLX\PYLTLU[Z\W[VT;OLTH_PT\THJ[\HSWPWPUNSLUN[OJHUIL TKLWLUKPUNVUJVUKP[PVUZ;OLVRV?ZLYPLZPZLHZ`[VL_[LUK[V TI`
Outer Rotor DC Motor (ODM) 2. When level differences are 50 m or more, the diameter of the main 2. When
liquid level
pipingdifferences
size must are
be increased.
50 m or more,
If thethe
outdoor
diameter
unitofisthe
above
main the
liquid
indoor
SLZZLUPUN[OLJVUKP[PVUZMYVTJVU]LU[PVUHSVRV0=TVKLSZ)LZ\YL[VYLMLY[V[OL,UNPULLYPUN+H[H)VVRMVYKL[HPSZVM[OLZLJVUKP[PVUZHUKYLX\PYLTLU[Z
on the outdoor unit is required. Refer to the Engineering Data Bookon andthecontact
outdooryourunitlocal
is required.
dealer for
Refer
more
to information.
piping
unit,size
a dedicated
must be increased.
setting
the Engineering Data Book and contact your local dealer for more informat
>OLUSL]LSKPMMLYLUJLZHYLTVYTVYL[OLKPHTL[LYVM[OLTHPUSPX\PKWPWPUNZPaLT\Z[ILPUJYLHZLK0M[OLV\[KVVY\UP[PZHIV]L[OLPUKVVY\UP[HKLKPJH[LKZL[[PUN
If the outdo

Only Daikin has adapted an ODM with the feature of stable rotation and volumetric efficiency. VU[OLV\[KVVY\UP[PZYLX\PYLK9LMLY[V[OL,UNPULLYPUN+H[H)VVRHUKJVU[HJ[`V\YSVJHSKLHSLYMVYTVYLPUMVYTH[PVU

Connection ratio Connection ratio


Conditions of VRV indoor unit connection capacity Conditions of VRV indoor unit connection capac
Advantages of ODM ODM UNIQUE
(Outer Type) Connection capacity at maximum is 200%. Connection
Applicable
capacity at maximum is 200%. Applicable Other VRV indoor
Thanks to large diameter of the rotor, VRV indoor units VRV indoor units unit models*1
Large torque with same electromagnetic force Rotor Connection ratio FXD(S)Q,
Connection ratioFXSQ, FXMQ-PA, FXAQ, FXB(P)Q models FXD(S)Q, FXSQ, FXMQ
Stable rotation in all range, and can be
Conventional Motor 50%–200% Single outdoor units50%–200% Single outdoor units 200%

200% 20
operated with small number of rotations (Inner Type)

Rotor Double outdoor units Double outdoor units 160%


F
Connection ratio = Triple outdoor unitsratio =
Connection Triple outdoor units 130%
Total capacity index of the indoor units *1 For the FXF(S)Q25 and FXVQ
Total capacity models,
index of maximum
the indoor units connection *1
ratio
Foristhe FXF(S)Q25
130% for the and
entire
FXVQ
rangemodels,
of maximum c
outdoor units. outdoor units.
Capacity index of the outdoor units Note: Capacity index of the outdoor units Note:
F
HIGH TORQUE MORE indoor units.
*Refer to page 46 for outdoor unit combination details.
indoor units.
*Refer to page 46 for outdoor unit combination details.
with low energy efficient

15 13 39 14 16
Flexible System Design
A SERIES A SERIES Reliable and Stable System

More accurate test operation and stable system


d residential For
indoor
mixed
units
combination of VRV and residential indoor units
Connection ratio Efficient automatic test operation Automatic check

Connection ratio Wiring


*VUULJ[PVUJHWHJP[`H[TH_PT\TPZ  Daikin VRV X series incorporates a simplified and efficient test operation check
50%–200%
Max. total piping length 250 m
function, not only greatly accelerating the installation process, but effectively
VRV:VRV indoor unit VRV:VRV indoor unit
improving the field setting quality as well.

VRV A SERIES

VRV A SERIES
RA:Residential indoor unit RA:Residential indoor unit
Piping
Automatically checks the wirings between outdoor units and indoor units check
;V[HSJHWHJP[`PUKL_VM[OLPUKVVY\UP[Z
Between BP unit
Max. level difference Connection ratio =Between BP unit to confirm whether there is a defective wiring.
between the outdoorand indoor unit *HWHJP[`PUKL_VM[OLV\[KVVY\UP[Z
and indoor unit
unit and the BP units
Max. 15 m Max. 15 m
Confirms piping length to optimise operation. Stop valve
BP unitequivalent
Max. BP unit
piping length
40 m Automatically checks whether the stop valve in each outdoor unit is in check
normal status to ensure the smooth operation of air conditioning system.
120 mof VRV indoor unit connection capacity
Conditions Max. level Max. level
Max. level
RA RA difference differenceRA RA difference
5m 15 m

Simplified commissioning and after-sales service


between between the between the
BP unit (WWSPJHISL BP unit outdoor BP
unitunit
and OtherVRVindoor
outdoor unit and
the indoor unit the indoor unit
VRVPUKVVY\UP[Z \UP[TVKLSZ


Max. level FXDQ, 50 m FXMQ-PA, FXAQ, FXB(P)Q models


FXSQ, 50 m
Function of information display by
Max. level
RA difference
level between
RA difference between 7-segment digital display Conventional LED display
Singleindoor branch and
outdoor units Max. 200%

200%
the farthest
RA VRV the indoor units
difference RA the indoor units

luminous digital tube


indoor unit -PN\YLZV\[
Double outdoor units between the BP
15
unit and the m 15 m 160% Z`Z[LT

Triple outdoor m1
Max. 50units indoor unit 130%
VWLYH[PVU
+PZWSH`Z PUMVYTH[PVUI`

*1 For the -?-:8 and FXVQ models, 5m maximum connection ratio is 130% for the entire range of outdoor units.
VRV?ZLYPes\[PSPZLZZLNTLU[S\TPUV\ZKPNP[HS[\ILZ[VKPZWSH` Z`Z[LT
VWLYH[PVU
YLHKPUNSPNO[
LTP[[PUNZ[H[L
Note: 0M[OLVWLYH[PVUHSJHWHJP[`VMPUKVVY\UP[ZPZTVYL[OHU SV^HPYMSV^VWLYH[PVUPZLUMVYJLKPUHSS[OLPUKVVY\UP[Z Z`Z[LTVWLYH[PVUPUMVYTH[PVULUHISPUN[OLVWLYH[PVUHSZ[H[L[VIL PUMVYTH[PVU VMKPMMLYLU[
KPYLJ[S`
9LMLY[VWHNLMVYV\[KVVY\UP[JVTIPUH[PVUKL[HPSZ ]PZ\HSS`KPZWSH`LK^OPSZ[MHJPSP[H[PUNZPTWSPMPLKJVTTPZZPVUPUNHUK KPVKLZ^OPJO
PZIV[O
VRV VRV HM[LYZHSLZZLY]PJL PULMMPJPLU[HUK
MHSSPISL
Note: The above is just a schematic diagram. Note: The above is just a schematic diagram.

High external static pressure


d residentialWhen
door units are
indoor
VRV
a mixed
connected
units iscombination of VRV and residential indoor units is
X series
connected outdoor
or when unit
only has beenindoor
residential
dissipation and stable Actual
operation
achieved
of
unitshigh
are external
connectedstatic pressure up to 78.4 Pa, ensuring the efficient heat
equipment in either hierarchical or intensive arrangement.
Advanced control main PC board
(Equivalent) 100piping length
m (120 m) (Equivalent) 100 m (120 m)
branch and BP unit or VRV indoor unit is branch and BP unit or VRV indoor unit is SMT* packaging technology Computer control board
Total piping
250length
m over 20 m, it is necessary to increase the gas 250 m over 20 m, it is necessary to increase the gas surface adopting SMT
If indoor unit capacity index < 60. Between 2 m–15 m If indoor unit capacity index < 60. 2 m–15 m :4;WHJRHNPUN[LJOUVSVN`HKVW[LKI`[OL^OVSLJVTW\[LY packaging technology
BP unit :4;WHJRHNPUNTH[LYPHS
Maximum allowable
If indoorpiping
unit capacity and indoor
lengthindex is 60 and 71.
unitm
2 m–8
indoor branch and BP unit or VRV indoor
If indoor
unit. If theunit capacity
piping indexofisthe
diameter 60 sized
and 71.
up 2 m–8 m
indoor branch and BP unit or VRV indoor
unit. If the piping diameter of the sized up
JVU[YVSWHULSPTWYV]LZ[OLHU[PJS\[[LYWLYMVYTHUJL

78.4 Pa
piping exceeds the diameter of the piping piping exceeds the diameter of the piping
VRV indoor unit
50 m 1
VRV indoor unit
50 m 1 7YV[LJ[Z`V\YJVTW\[LYIVHYKZMYVT[OLHK]LYZLLMMLJ[VMZHUK`
latter also requires a liquid piping and gas latter also requires a liquid piping and gas HUKO\TPK^LH[OLY *VTW\[LYJVU[YVSIVHYK
5m piping size up. Please refer to Engineering 5m piping size up. Please refer to Engineering :4;!:\YMHJLTV\U[LK[LJOUVSVN`

units 4VYLVW[PVUZPU[OLVWLUPUNHUNSLVMSV\]YL
15 m
Between the indoor units Data Book for details. 15 m Data Book for details.
6\[Z[HUKPUNOLH[KPZZPWH[PVULMMLJ[PUIV[O
15 m
Between BP units *When a mixed combination of VRV and 15 m *When a mixed combination of VRV and

Wide operation temperature


OPLYHYJOPJHSHUKPU[LUZP]LHYYHUNLTLU[
residential indoor units is connected or when residential indoor units is connected or when

I-demand function
or unit If the outdoor
Maximumunit allowable
is above. 50 m
Between the If the outdoor unit is above.
outdoor unit only 50 m
residential indoor units are connected, only residential indoor units are connected,
level difference
If the outdoor unit is below. and the indoor
40 m unit If the outdoor
connection ratio unit
mustisbe
below.
50% to 130%. 40 m connection ratio must be 50% to 130%.

YHUNL\W[V ͵
or unit and the BP unit Between the
40 m Refer
outdoor unit and thetoBP
page
unit46 for outdoor unit 40 m Refer to page 46 for outdoor unit
combination details. combination details.
t and the indoor unit Between the
5 mBP unit and the indoor unit 5m Limit to power consumption can be set precisely to
one of 11 levels. Peak power cut-off can be
accomplished according to each user situation. The versatile operation range
 á*+)
*Set on the circuit board of the outdoor unit. of the VRV X series works to 50
reduce limitations on

Outdoor temperature (°CDB)


pressure
High external static pressure When set to 70% demand
Power consumption More
Total of 11 levels installation locations.
The operation temperature 40

VRV A series outdoor unit has been


100% range for cooling can be
performed with outdoor
78.4 Pa 78.4 Pa
up to achieved high external static pressure up to 30
Can be set in
70% 5% increments temperatures as high as
More
dissipation andoptions
stableinoperation
the of More options in the 49˚C. 20
ensive
opening/angle of louvre
equipmentOutstanding
in either hierarchical or intensive
opening/angle of louvre 50% This enables reliable
arrangement.
heat dissipation Outstanding heat dissipation 40%
effect in both hierarchical and effect in both hierarchical and operation even under high
intensive arrangement intensive arrangement temperature conditions. 10
Cooling

0%
Less

5V[L!>OLUV\[KVVY[LTWLYH[\YLMHSSZILSV^͵[OL[OLYTVZ[H[ZO\[Z6--
Time [OLV\[KVVY\UP[Z[VWZHUKVWLYH[PVUZ^P[JOLZMYVTJVVSPUN[VMHU
VWLYH[PVU

17 15 40 16 18
Outdoor Unit Lineup

Automatic sequencing operation X Series


X
VRV A Series Outdoor
Outdoor Units
Units Outd
During start-up, Daikin VRV X series outdoor unit sequencing operation will be automatically enabled to The outdoor unit capacity is up to 60 HP (168 kW) in increment of 2 HP.
ensure balance operation of each outdoor unit to improve longevity of equipment and operation stability.
Stage 1 Stage 2 Stage 3 VRV X offers aa high
A series outdoor unit offers high capacity
capacity of of up
up to
to 60
60 HP,
HP, responding
respondingto
tothe
theneeds
needsof
oflarge-sized
large-sizedbuilding.
building.
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process,
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process,
Automatic Automatic but
Withalso
the bringing the system
outdoor unit flexibility
capacity increasedto ainnew level. of 2 HP, customers' needs can be precisely met.
increment
sequencing sequencing With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met.

Priority: Priority: Priority:


Lineup New lineup

HP 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60

Single
Single outdoor
outdoor units
units

Double backup operation functions


X SERIES Double
VRV A Double outdoor
outdoor units
units
Triple outdoor
Triple outdoor units
units

Daikin VRV X series outdoor unit boasts double backup operation functions, which can secure the use of air
conditioners in this area to the greatest extent by emergently enabling double backup operation functions
even if failure occurs in a set of air conditioning equipment. Single Outdoor Units Double Outdoor Units
In the event of a failure, emergency operation can be conveniently enabled to allow the remaining system to Single
•Single Outdoor
6, 8 HP Outdoor Units
10, 12,Units
14, 16, Double
•Double
12, Outdoor
14, 16 HP Units
Outdoor Units
18, 20 HP 22, 24, 26, 28, 30, 32, 34, 36,
operate in a limited fashion.
6, 6,
8, 810,
HP12 HP 18,
10, 12,
14,20 14,
16,HP18,16,
20 HP 12,18,
14,20,
16 22,
HP 24 HP 18,26,
20 28,
HP 30 HP 22, 40
38, 24,HP
26, 34,
32, 28, 36,
30, 38,
32, 40
34,HP
36,
Unit backup operation function Compressor backup operation function 18, 20 HP 38, 40 HP

If one of the unit in a multiple outdoor system The outdoor unit is equipped with two compressors. Even
malfunctions, the other outdoor units provide if one compressor malfunctions, the other compressor
emergency operation until repairs can be made. provides emergency operation, reducing the risk of air
* For systems composed of two or more outdoor units. conditioning shutdown due to compressor failure.
(The capacity is saved during backup operation.)
* For a single outdoor unit system RXUQ14-20AYM models. On-site settings are
Emergency required using the printed circuit board of the outdoor unit.
Malfunction
operation
RXUQ6AYM(W)
RXQ6AYM(W) RXUQ10AYM(W)
RXQ14AYM(W) RXUQ12AMYM(W)
RXQ18AMYM(W) RXUQ18AMYM(W)
RXQ26AMYM(W)RXUQ22AMYM(W) RXUQ32AMYM(W)
RXQ32AMYM(W)
RXUQ6AYM
RXUQ8AYM(W) RXUQ10AYM
RXUQ12AYM(W)
RXQ16AYM(W) RXUQ12AMYM
RXUQ14AMYM(W)
RXQ20AMYM(W) RXUQ18AMYM
RXUQ20AMYM(W)
RXQ28AMYM(W) RXUQ22AMYM
RXUQ24AMYM(W) RXUQ32AMYM
RXUQ34AMYM(W)
RXQ34AMYM(W)
RXQ8AYM(W)
RXUQ8AYM RXUQ12AYM
RXUQ14AYM(W)
RXQ18AYM(W) RXUQ14AMYM
RXUQ16AMYM(W)
RXQ22AMYM(W) RXUQ20AMYM
RXQ30AMYM(W) RXUQ24AMYM
RXUQ26AMYM(W) RXUQ34AMYM
RXUQ36AMYM(W)
RXQ36AMYM(W)
Emergency RXQ10AYM(W)
RXUQ14AYM
RXUQ16AYM(W)
RXQ20AYM(W) RXUQ16AMYM
RXQ24AMYM(W) RXUQ26AMYM
RXUQ28AMYM(W) RXUQ36AMYM
RXUQ38AMYM(W)
RXQ38AMYM(W)
operation RXQ12AYM(W)
Malfunction RXUQ16AYM
RXUQ18AYM(W) RXUQ28AMYM
RXUQ30AMYM(W) RXUQ38AMYM
RXUQ40AMYM(W)
RXQ40AMYM(W)
RXUQ18AYM
RXUQ20AYM(W) RXUQ30AMYM RXUQ40AMYM
RXUQ20AYM
•Triple Outdoor Units
Triple Outdoor
42, 44 HP Units 46, 48, 50, 52, 54, 56, 58, 60 HP *1. For multiple co
Triple Outdoor
18, 20 HPUnits 42, 44, 46, 48, 50, 52, 54, 56, 58, 60 HP *2. Values inside b

Ease of Maintenance 18, 20 HP 42, 44, 46, 48, 50, 52, 54, 56, 58, 60 HP
130% for triple

For mixed co
VRV X series provides maintenance feature* which allows the shutdown of indoor unit without shutting down the
whole VRV system. This feature comes in handy during maintenance period as the remaining indoor units residential in
continue to operate.

RXQ42AMYM(W) RXQ46AMYM(W) RXQ54AMYM(W)


RXQ44AMYM(W) RXQ48AMYM(W) RXQ56AMYM(W)
RXUQ18AM1YM(W) RXQ50AMYM(W)
RXUQ42AMYM(W) RXQ58AMYM(W)
RXUQ50AMYM(W) RXUQ58AMYM(W)
Area A Area B Area C RXUQ18AM1YM
RXUQ20AM1YM(W) RXQ52AMYM(W)
RXUQ42AMYM
RXUQ44AMYM(W) RXQ60AMYM(W)
RXUQ50AMYM
RXUQ52AMYM(W) RXUQ58AMYM
RXUQ60AMYM(W)
RXUQ20AM1YM RXUQ44AMYM RXUQ52AMYM
RXUQ46AMYM(W) RXUQ54AMYM(W) RXUQ60AMYM
* Field setting is required. RXUQ46AMYM RXUQ54AMYM
RXUQ48AMYM(W) RXUQ56AMYM(W)
This feature does not apply to residential indoor unit connection and is not applicable for all situations. Note:
RXUQ48AMYM RXUQ56AMYM
For more information, please contact Daikin sales office. Note: Models with (W) are the outdoor units with anti-corrosion specifications. For details, refer to page 25-26 for more information.
*1. Only single out
Total capacity i

19 17 27 18 20
X SERIES X SERIES

Outdoor Unit
Unit Combinations
nit Combinations
Outdoor Combinations Outdoor Unit Combinations (SG Models)

VRV X SERIES
oor unitsFor
only
HP
connection
kW
Capacityof VRV indoor units only
Model name Combination Outdoor unit multi Total capacity index of Maximum number of MODEL RXUQ24AMYM-SG RXUQ24AMYM-SG RXUQ30AMYM-SG RXUQ32AMYM-SG RXUQ34AMYM-SG RXUQ36AMYM-SG RXUQ38AMYM-SG RXUQ40AMYM-SG
index connection piping kit*1 connectable indoor units*2 connectable indoor units*2
6 HP 16.0 Capacity
150 Outdoor unit multi
RXUQ6A Total capacity index of
RXUQ6A Maximum number ofOutdoor –
unit multi Total
75capacity
to 195 index
(300)of Maximum number of
9 (15) RXUQ8AYM RXUQ10AYM RXUQ6AYM RXUQ8AYM RXUQ8AYM RXUQ6AYM RXUQ6AYM RXUQ6AYM
HP
Combination kW Model name Combination
index connection piping kit*1 connectable indoor units*2 connectable indoor connection
units*2 piping kit*1 connectable indoor units*2 connectable indoor units*2
8 HP 22.4 200 RXUQ8A RXUQ8A – 100 to 260 (400) 13 (20)
Combination units
6 HP
RXUQ6A 16.0 150 –
RXUQ6A RXUQ6A
75 to 195 (300) 9 (15) – 75 to 195 (300) 9 (15) RXUQ14AYM RXUQ14AYM RXUQ10AYM RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ14AYM
10 HP 28.0 250 RXUQ10A RXUQ10A – 125 to 325 (500) 16 (25)
8 HP
RXUQ8A 22.4 200 –
RXUQ8A 100 to 260 (400)
RXUQ8A 13 (20) – 100 to 260 (400) 13 (20) ― ―
12 HP 33.5 300 RXUQ12A RXUQ12A – 150 to 390 (600) 19 (30) RXUQ14AYM RXUQ12AYM RXUQ14AYM RXUQ18AYM RXUQ20AYM RXUQ20AYM
RXUQ10A
10 HP 28.0 250 –
RXUQ10A 125 to 325 RXUQ10A
(500) 16 (25) – 125 to 325 (500) 16 (25)
14 HP 40.0 350 RXUQ14A RXUQ14A – 175 to 455 (700) 22 (35)
12 HP 33.5
RXUQ12A 300 –
RXUQ12A 150 to 390 RXUQ12A
(600) 19 (30) – 150 to 390 (600) 19 (30) Power supply 3-phase 4-wire system, 380-415 V/380 V, 50/60 Hz
16 HP 45.0 400 RXUQ16A RXUQ16A – 200 to 520 (800) 26 (40)
14 HP 40.0
RXUQ14A 350 –
RXUQ14A 175 to 455 RXUQ14A
(700) 22 (35) – 175 to 455 (700) 22 (35) 213,000 232,000 287,000 305,000 327,000 339,000 362,000 382,000
18 HP 50.0 450 RXUQ18A RXUQ18A – 225 to 585 (900) 29 (45) Btu/h
16 HP 45.0
RXUQ16A 400 –
RXUQ16A 200 to 520 RXUQ16A
(800) 26 (40) – 200 to 520 (800) 26 (40) Cooling capacity
20 HP 56.0 500 RXUQ20A RXUQ20A – 250 to 650 (1,000) 32 (50)
18 HP 50.0
RXUQ18A 450 –
RXUQ18A 225 to 585 RXUQ18A
(900) 29 (45) – 225 to 585 (900) 29 (45) kW 62.4 68.0 84.0 89.4 95.9 99.5 106 112
12 HP 32.0 300 RXUQ12AM RXUQ6A + RXUQ6A 150 to 390 (480) 19 (24)
20 HP 56.0
RXUQ20A 500 –
RXUQ20A 250 to 650 (1,000)
RXUQ20A 32 (50) – 250 to 650 (1,000) 32 (50)
22 (28) Power consumption kW 14.3 15.8 19.0 20.4 22.1 23.8 25.8 27.5
14 HP 38.4 350 RXUQ14AM RXUQ6A + RXUQ8A 175 to 455 (560)
RXUQ6A12 HP
+ RXUQ6A
32.0 300 RXUQ12AM 390 (480)+ RXUQ6A 19 (24)
150 toRXUQ6A 150 to 390 (480) 19 (24)
16 HP 44.8 400 RXUQ16AM RXUQ8A + RXUQ8A BHFP22P100 200 to 520 (640) 26 (32) %
RXUQ6A14 HP
+ RXUQ8A
38.4 350 RXUQ14AM 455 (560)+ RXUQ8A 22 (28)
175 toRXUQ6A 175 to 455 (560) 22 (28) Capacity control 7-100 6-100 5-100 5-100 4-100 4-100 4-100 4-100
18 HP 50.4 450 RXUQ18AM RXUQ8A + RXUQ10A 225 to 585 (720) 29 (36)
RXUQ8A16 HP
+ RXUQ8A
44.8 400 BHFP22P100
RXUQ16AM 520 (640)+ RXUQ8A 26 (32)
200 toRXUQ8A BHFP22P100 200 to 520 (640) 26 (32) Casing colour Ivory white (5Y7.5/1)
20 HP 55.9 500 RXUQ20AM RXUQ8A + RXUQ12A 250 to 650 (800) 32 (40)
RXUQ8A18 +
HPRXUQ10A
50.4 450 RXUQ18AM 225 to 585 (720)
RXUQ8A + RXUQ10A 29 (36) 225 to 585 (720) 29 (36)
18 HP 48.0 450 RXUQ18AM1 RXUQ6A × 3 225 to 585 (585) 29 (29) Type Hermetically sealed scroll type
RXUQ8A20 +
HPRXUQ12A
55.9 500 RXUQ20AM 250 to 650 (800)
RXUQ8A + RXUQ12A 32 (40) BHFP22P151 250 to 650 (800) 32 (40)
20 HP 54.4 500 RXUQ20AM1 RXUQ6A × 2 + RXUQ8A 250 to 650 (650) 32 (32)
18 HP × 348.0
RXUQ6A 450 RXUQ18AM1 225 to 585 (585) × 3
RXUQ6A 29 (29) 225 to 585 (585) 29 (29) Compressor
22 HP 61.5 550 RXUQ22AM RXUQ10A + RXUQ12A 275 to 715 (880) 35 (44) Motor (3.4×1)+(3.4×1) (4.2×1)+(3.4×1) (2.4×1)+(4.2×1) (3.4×1)+(5.2×1) (3.4×1)+(5.2×1) (2.4×1)+(5.2×1) (2.4×1)+(5.2×1) (2.4×1)+(3.4×1)
BHFP22P151 BHFP22P151 kW
RXUQ6A20× HP
2 + RXUQ8A
54.4 500 RXUQ20AM1 250RXUQ6A × 2 + RXUQ8A 32 (32)
to 650 (650) 250 to 650 (650) 32 (32) output +(2.9×1) +(2.9×1) +(3.4×1)+(2.9×1) +(5.2×1) +(3.4×1)+(2.9×1) +(3.7×1)+(4.3×1) +(4.9×1)+(4.2×1) +(2.9×1)+(4.9×1)
24 HP 67.0 600 RXUQ24AM RXUQ12A × 2 300 to 780 (960) 39 (48) +(4.2×1)
RXUQ10A22 HP
+ RXUQ12A
61.5 550 RXUQ22AM 275 to 715 (880)+ RXUQ12A 35 (44)
RXUQ10A 275 to 715 (880) 35 (44)
26 HP 73.5 650 RXUQ26AM RXUQ12A + RXUQ14A 325 to 845 (1,040) 42 (52)
24 HP × 67.0
RXUQ12A 2 600 RXUQ24AM 300 to 780 (960)
RXUQ12A ×2 39 (48) 300 to 780 (960) 39 (48) Airflow rate m3/min 178+218 178+218 119+178+218 178+191+191 178+191+218 119+191+268 119+191+297 119+218+297
28 HP 78.5 700 RXUQ28AM RXUQ12A + RXUQ16A 350 to 910 (1,120) 45 (56)
RXUQ12A26 HP
+ RXUQ14A
73.5 650 RXUQ26AM 325 toRXUQ12A
845 (1,040)+ RXUQ14A 42 (52) 325 to 845 (1,040) 42 (52)
30 HP 83.5 750 RXUQ30AM RXUQ12A + RXUQ18A 375 to 975 (1,200) 48 (60)
RXUQ12A28 HP
+ RXUQ16A
78.5 700 RXUQ28AM 350 toRXUQ12A
910 (1,120)+ RXUQ16A 45 (56) BHFP22P100 350 to 910 (1,120) 45 (56) (1,657×930×765) (1,657×1,240×765)
(1,657×930×765) (1,657×930×765) (1,657×930×765) (1,657×930×765) (1,657×930×765) (1,657×930×765)
32 HP 89.5 800 RXUQ32AM RXUQ12A + RXUQ20A 400 to 1,040 (1,280) 52 (64) Dimensions (H×W×D) mm +(1,657×1,240×765) +(1,657×1,240×765)
+(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765)
RXUQ12A30 HP
+ RXUQ18A
83.5 750 RXUQ30AM 375 toRXUQ12A
975 (1,200)+ RXUQ18A 48 (60) 375 to 975 (1,200) 48 (60) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765) +(1,657×1,240×765)
34 HP 96.0 850 RXUQ34AM
BHFP22P100 RXUQ14A + RXUQ20A BHFP22P100 425 to 1,105 (1,360) 55 (64)
RXUQ12A + RXUQ20A
32 HP 89.5 800 RXUQ32AM 400 toRXUQ12A + RXUQ20A 52 (64)
1,040 (1,280) 400 to 1,040 (1,280) 52 (64)
36 HP 101 900 RXUQ36AM RXUQ16A + RXUQ20A 450 to 1,170 (1,440) 58 (64)
RXUQ14A + RXUQ20A
34 HP 96.0 850 RXUQ34AM 425 toRXUQ14A + RXUQ20A 55 (64)
1,105 (1,360) 425 to 1,105 (1,360) 55 (64)
61 (64) Machine weight kg 185+275 215+275 185+215+275 185+215+215 185+215+275 185+215+291 185+215+291 185+275+291
38 HP 106 950 RXUQ38AM RXUQ18A + RXUQ20A 475 to 1,235 (1,520)
RXUQ16A36 HP 101
+ RXUQ20A 900 RXUQ36AM 450 toRXUQ16A + RXUQ20A 58 (64)
1,170 (1,440) 450 to 1,170 (1,440) 58 (64)
40 HP 112 1,000 RXUQ40AM RXUQ20A × 2 500 to 1,300 (1,600) 64 (64) Sound level dB(A) 61 61 62 62 63 64 66 66
RXUQ18A + RXUQ20A
38 HP 106 950 RXUQ38AM 475 toRXUQ18A + RXUQ20A 61 (64)
1,235 (1,520) 475 to 1,235 (1,520) 61 (64)
42 HP 117 1,050 RXUQ42AM RXUQ12A × 2 + RXUQ18A 525 to 1,365 (1,365)
RXUQ20A
40 HP × 112
2 1,000 RXUQ40AM 500 to 1,300 (1,600) × 2
RXUQ20A 64 (64) 500 to 1,300 (1,600) 64 (64) Operation range ℃DB 10 to 49
44 HP 123 1,100 RXUQ44AM RXUQ12A × 2 + RXUQ20A 550 to 1,430 (1,430)
RXUQ12A42× HP
2 + RXUQ18A
117 1,050 RXUQ42AM 525 to 1,365 (1,365)
RXUQ12A × 2 + RXUQ18A 525 to 1,365 (1,365)
46 HP 130 1,150 RXUQ46AM RXUQ12A + RXUQ14A + RXUQ20A 575 to 1,495 (1,495) Type R-410A
RXUQ12A44× HP
2 + RXUQ20A
123 1,100 RXUQ44AM 550 to 1,430 (1,430)
RXUQ12A × 2 + RXUQ20A 550 to 1,430 (1,430) Refrigerant
48 HP 135 1,200 RXUQ48AM RXUQ12A + RXUQ16A+ RXUQ20A 600 to 1,560 (1,560)
RXUQ12A + RXUQ14A
46 HP + RXUQ20A
130 1,150 RXUQ46AM 575 to 1,495
RXUQ12A (1,495)
+ RXUQ14A + RXUQ20A 575 to 1,495 (1,495) Charge kg 6.6+9.7 8.3+9.7 6.4+8.3+9.7 6.6+8.5+8.5 6.6+8.5+8.5 6.6+8.5+9.7 6.4+8.5+11.7 6.4+8.5+11.7
50 HP 140 1,250 RXUQ50AM RXUQ12A + RXUQ18A + RXUQ20A 625 to 1,625 (1,625)
RXUQ12A + RXUQ16A
48 HP + RXUQ20A
135 1,200 RXUQ48AM 600 to 1,560
RXUQ12A (1,560)
+ RXUQ16A + RXUQ20A BHFP22P151 600 to 1,560 (1,560)
52 HP 146 1,300 RXUQ52AM RXUQ12A + RXUQ20A × 2 650 to 1,690 (1,690) 64 (64) Liquid mm φ15.9 (Brazing) φ19.1 (Brazing)
RXUQ12A + RXUQ18A
50 HP + RXUQ20A
140 1,250 RXUQ50AM 625 to 1,625
RXUQ12A (1,625)
+ RXUQ18A + RXUQ20A 625 to 1,625 (1,625) Piping
54 HP 152 1,350 RXUQ54AM
BHFP22P151 RXUQ14A + RXUQ20A × 2 64 (64) BHFP22P151 675 to 1,755 (1,755) 64 (64) connections
RXUQ12A52+ HP
RXUQ20A
146 × 2 1,300 RXUQ52AM 650 to 1,690 (1,690)
RXUQ12A + RXUQ20A × 2 650 to 1,690 (1,690) Gas mm φ26.6 (Brazing) φ34.9 (Brazing) φ41.3 (Brazing)
56 HP 157 1,400 RXUQ56AM 700 to 1,820 (1,820)
RXUQ14A54+ HP
RXUQ20A
152 × 2 1,350 RXUQ54AM 675 to 1,755 (1,755)
RXUQ14A + RXUQ20A × 2 675 to 1,755 (1,755)
58 HP 162 1,450 RXUQ58AM RXUQ18A + RXUQ20A × 2 725 to 1,885 (1,885)
RXUQ16A56+ HP
RXUQ20A
157 × 2 1,400 RXUQ56AM 700 to 1,820 (1,820)
RXUQ16A + RXUQ20A × 2 700 to 1,820 (1,820)
60 HP 168 1,500 RXUQ60AM RXUQ20A × 3 750 to 1,950 (1,950)
RXUQ18A58+ HP
RXUQ20A
162 × 2 1,450 RXUQ58AM 725 to 1,885 (1,885)
RXUQ18A + RXUQ20A × 2 725 to 1,885 (1,885)
Note: *1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
RXUQ20A
60 HP × 168
3 inside1,500
*2. Values RXUQ60AM
brackets are 750ofto
based on connection 1,950
indoor (1,950)
RXUQ20A
units × maximum
rated at 3 750units,
capacity, 200% for single outdoor to 1,950
160%(1,950)
for double outdoor units, and
Note: *1.
ulti connection piping 130%
For for triple
multiple
kit (separately outdoor
connection,
sold) units. Refer to
the outdoor
is required. page
unit 20connection
multi for notes on connection
piping capacitysold)
kit (separately of indoor units.
is required.
*2. Values
ction of indoor units rated inside capacity,
at maximum brackets are
200%based on connection
for single of indoor
outdoor units, 160%units
forrated
doubleat outdoor
maximum capacity,
units, and 200% for single outdoor units, 160% for double outdoor units, and
21 for notes on connection 130% for triple
capacity outdoor
of indoor units. Refer to page 21 for notes on connection capacity of indoor units.
units.

VRV andFor
residential
mixed combination
indoor unitsoforVRV
connection
and residential
of indoor units or connection of
ly residential indoor units only
Total capacity index of connectable indoor units*2 Total capacity index of connectable indoor units*2
Capacity Capacity Maximum number of Maximum number of
Model name*1 kW
Combination (%)*2HP Combination (%)*2
connectable indoor units connectable indoor units
index index
50% 100% 130% 50% 100% 130%
150 RXUQ6AYM(W)
75 16.0
150 6 195 150 75 9 150 195 9
200 RXUQ8AYM(W)
100 22.4
200 8 260 200 100 13 200 260 13
250 RXUQ10AYM(W)
125 28.0
250 10 325 250 125 16 250 325 16
300 RXUQ12AYM(W)
150 33.5
300 12 390 300 150 19 300 390 19
350 RXUQ14AYM(W)
175 40.0
350 14 455 350 175 22 350 455 22
400 200
RXUQ16AYM(W) 45.0
400 16 520 400 200 26 400 520 26
450 225
RXUQ18AYM(W) 50.0
450 18 585 450 225 29 450 585 29
500 RXUQ20AYM(W)
250 56.0
500 20 650 500 250 32 500 650 32
W)) can be connected.
Note: *1. Only single outdoor unit (RXUQ6-20AYM(W)) can be connected.
nits must be 50%–130% *2.ofTotal
the capacity index of the
connectable
outdoor unit.
indoor units must be 50%–130% of the capacity index of the outdoor unit.

21 19 28 20 22
Indoor Unit Lineup A SERIES

Enhanced range of choices Residential indoor units with connection to BP units


25 35 50 60 71
Indoor units subject to Indoor units subject to
VRV indoor units
VRV indoor units
New lineup
New lineup VRT
smart Indoor
VRT units subject to
VRT smart control
smart VRT smart control
VRT
VRT
Indoor units subject to
VRT control
VRT control
Type Model Name Rated Capacity (kW) 2.5 3.5 5.0 6.0 7.1
20 25 32 40 50 63 71 80 100 125 140 200 250 400 500 Capacity Index 25 35 50 60 71
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP 16 HP 20 HP
Type Model Name
Capacity Index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500 FDKS-EAVMB VRT

VRV A SERIES
(700 mm width type)
Slim Ceiling
Ceiling Mounted Cassette Mounted Duct
FXFSQ-AVM VRT
New
Ceiling
(Round Mounted
Flow withCassette
Sensing) smart capacity
FXFSQ-AVM VRT
smart FDKS-C(A)VMB VRT
(Round Flow with Sensing) • If a system has indoor units subject to both
Max. (900/1,100 mm width type) VRT smart and VRT control, the system is operated under VRT control.
Ceiling Mounted Cassette
Ceiling
(Round Mounted
Flow) Cassette FXFQ-AVM VRT
FXFQ-AVM
smart
VRT
New
capacity 64 indoor
units
• If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart
control and VRT control are disabled.
(Round Flow) smart FTKJ-NVMW VRT

Ceiling Mounted Cassette FXZQ-MVE VRT


Ceiling
(CompactMounted Cassette
Multi Flow)
(Compact Multi Flow)
FXZQ-MVE VRT FTKJ-NVMS VRT

4-Way Flow Ceiling FXUQ-AVEB VRT


Ceiling Mounted Cassette
Suspended FXCQ-MVE VRT Wall Mounted FTKS-DVM VRT
(Double Flow)
Ceiling Mounted Cassette
Ceiling FXCQ-AVM VRT
(DoubleMounted
Flow) Cassette FXEQ-AV36 smart
VRT FTKS-BVMA VRT
(Single Flow)
Ceiling Mounted Cassette FXEQ-AV36 VRT
FXDQ-PDVE VRT
(Single Flow) (with drain pump) smart FTKS-FVM VRT
Slim Ceiling Mounted Duct FXDQ-PDVET VRT (700mm width type)
Slim Ceiling FXDSQ-AVM
(without drain pump) smart
VRT Note: BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.
Mounted Duct
FXDQ-NDVE VRT
(Standard Series) FXDQ-PDVE
(with drain pump) smart
VRT
(with drain pump) smart
FXDQ-NDVET VRT
FXDQ-PDVET
(without smart
drain pump) VRT
(900 / 1,100mm width type)
(700mm width type)
VRV indoor units combine with residential indoor units, all in one system.
Slim Ceiling Mounted Duct (without drain pump) smart
Slim Ceiling VRV indoor unit only system
(Standard Series) FXDQ-NDVE VRT
FXDQ-SPV1
Mounted Duct VRT
(with drain pump) smart
(Compact Series)
Middle Static FXDQ-NDVET VRT (900 / 1,100mm width type)
(without drain pump) smart
Pressure Ceiling FXSQ-PAVE VRT
smart
Mounted Duct
Slim Ceiling Mounted Duct FXDQ-SPV1 VRT
(Compact Series) FXMQ-PAVE VRT
Ceiling Mounted smart
Middle Static Pressure
Duct VRT
FXSQ-PAVE
Ceiling Mounted Duct FXMQ-MVE9 smart
VRT VRV indoor units only
Outdoor-Air FXMQ-PAVE VRT Max. • If a system has indoor units subject to both VRT smart and VRT control, the system is operated under VRT control.
FXMQ-MFV1 smart
Processing Unit
Ceiling Mounted Duct FXMQ-MVE9 VRT
64 indoor
units
• If a system has both outdoor-air processing air conditioners and outdoor-air processing type indoor units, VRT smart
control and VRT control are disabled.
4-Way Flow Ceiling FXUQ-AVEB VRT
Suspended FXMQ-PVM VRT
smart
Residential indoor unit and VRV indoor unit mix system
Outdoor-Air
Ceiling Processing Unit
Suspended FXMQ-MFV1
FXHQ-MAVE VRT

FXHQ-MAVE VRT
Ceiling
Wall Suspended
Mounted FXAQ-PVE VRT
FXHQ-AVM VRT BP unit
Wall Mounted FXAQ-AVM VRT
Floor Standing FXLQ-MAVE VRT
smart

Floor Standing FXLQ-MAVE VRT


Concealed FXNQ-MAVE
Floor Standing FXNQ-MAVE
VRT Max. Residential indoor units VRV indoor units
Concealed Floor Standing
32
VRT indoor
units • BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.
FXVQ-NY1 VRT
VRT • If a system has both residential indoor units and VRV indoor units, the system is operated under VRT control.
FXVQ-NY1
Floor Standing
Floor Standing Duct
Duct FXVQ-NY16
FXVQ-NY16 VRT
(high static pressure type) VRT
(high static pressure type)
Residential indoor unit only system
FXBQ-PVE
FXBQ-PVE VRT
VRT
Clean Room
Clean
Air Room Air Conditioner
Conditioner
FXBPQ-PVE
FXBPQ-PVE VRT
VRT

Heat Reclaim
Heat Reclaim Ventilator
Ventilator
with DX-Coil
DX-Coil and Humidifier
VKM-GAV1
VKM-GA(M)V1
/h
Airflow rate 500-1000 m 3/h
3
BP unit BP unit
with
Heat Reclaim
Heat Reclaim Ventilator
Ventilator VAM-GJVE
VAM-GJVE
/h
Airflow rate 150-2000 m 3/h
3

Air Handling
Handling Unit
Unit AHUR 6–120 HP
HP Max. Residential indoor units only
6–120
Air AHUR
32 indoor
units • BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20AYM(W)) can be connected.
• If a system has only residential indoor units, the system is operated under VRT control.

23 21 22 24
48
VRV X Series Outdoor Units RXUQ-A

46+,3 RXUQ6AYM RXUQ8AYM RXUQ10AYM RXUQ12AYM RXUQ14AYM RXUQ16AYM RXUQ18AYM RXUQ20AYM RXUQ12AMYM RXUQ14AMYM RXUQ16AMYM RXUQ18AMYM RXUQ20AMYM RXUQ18AM1YM RXUQ20AM1YM RXUQ22AMYM RXUQ24AMYM RXUQ26AMYM
ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ RXUQ6AYM RXUQ6AYM RXUQ8AYM RXUQ8AYM RXUQ8AYM RXUQ6AYM RXUQ6AYM RXUQ10AYM RXUQ12AYM RXUQ12AYM
*VmIinatioUunits ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ RXUQ6AYM RXUQ8AYM RXUQ8AYM RXUQ10AYM RXUQ12AYM RXUQ6AYM RXUQ6AYM RXUQ12AYM RXUQ12AYM RXUQ14AYM
ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ ɬ RXUQ6AYM RXUQ8AYM ɬ ɬ ɬ
PV^eYsuWWS` WOHZL^PrLZ`Z[LT==/a WOHZL^PrLZ`Z[LT==/a
Btuh                      
*oolinNcaWacit`
RW                  
7V^LYJVUZ\TW[PVU RW                  
*HWHJP[`JVU[YVS                
*asinNcolour 0]VY`^OP[L@ 0]VY`^OP[L@
T`We /LYTL[PJHSS`ZLHSLKZJYVSS[`WL /LYTL[PJHSS`ZLHSLKZJYVSS[`WL
*VTWYLZZVY
4V[VYV\[W\[ RW í í íí íí ííí íí
(PYMSV^YH[L m3min                          
í í í íí í
+imensioUZHíWí+ mm í í íí í íí í íííí
íí í í

4HchinL^eight Rg          


SounKle]el dB(              
OWeratioUrange ͵+B [V [V
T`We 9( 9(
9eMrigerant
*Oarge Rg                 
7PWPUN 3PXuid mm ˋ )YHaPUN ˋ)YHaPUN ˋ )YHaPUN ˋ)YHaPUN ˋ )YHaPUN ˋ )YHaPUN
connections .as mm ˋ )YHaPUN ˋ)YHaPUN ˋ)YHaPUN ˋ)YHaPUN ˋ )YHaPUN

46+,3 RXUQ28AMYM RXUQ30AMYM RXUQ32AMYM RXUQ34AMYM RXUQ36AMYM RXUQ38AMYM RXUQ40AMYM RXUQ42AMYM RXUQ44AMYM RXUQ46AMYM RXUQ48AMYM RXUQ50AMYM RXUQ52AMYM RXUQ54AMYM RXUQ56AMYM RXUQ58AMYM RXUQ60AMYM
RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ14AYM RXUQ16AYM RXUQ18AYM RXUQ20AYM RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ12AYM RXUQ14AYM RXUQ16AYM RXUQ18AYM RXUQ20AYM
*VmIinatioUunits RXUQ16AYM RXUQ18AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ12AYM RXUQ12AYM RXUQ14AYM RXUQ16AYM RXUQ18AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM
ɬ ɬ ɬ ɬ ɬ ɬ ɬ RXUQ18AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM RXUQ20AYM
PV^eYsuWWS` WOHZL^PrLZ`Z[LT==/a WOHZL^PrLZ`Z[LT==/a
Btuh                     
*oolinNcaWacit`
RW                  
7V^LYJVUZ\TW[PVU RW                    
*HWHJP[`JVU[YVS     
*asinNcolour 0]VY`^OP[L@ 0]VY`^OP[L@
T`We /LYTL[PJHSS`ZLHSLKZJYVSS[`WL /LYTL[PJHSS`ZLHSLKZJYVSS[`WL
*VTWYLZZVY
4V[VYV\[W\[ RW íí ííí
(PYMSV^YH[L m3min               
+imensioUZHíWí+ mm íííí íííííí
4HchinL^eight Rg                      
SounKle]el dB(           
OWeratioUrange ͵+B [V [V
T`We 9( 9(
9eMrigerant
*Oarge Rg            
PiWing 3PXuid mm ˋ )YHaPUN ˋ )YHaPUN
connections .as mm ˋ )YHaPUN ˋ)YHaPUN ˋ)YHaPUN

5V[L!:WLJPMPJH[PVUZHYLIHZLKVU[OLMVSSV^PUNJVUKP[PVUZ"
 ࠮*VVSPUN!0UKVVY[LTW!͵+) ͵>)6\[KVVY[LTW!͵+),X\P]HSLU[WPWPUNSLUN[O!T3L]LSKPMMLYLUJL!T
 ࠮:V\UKSL]LS!(ULJOVPJJOHTILYJVU]LYZPVU]HS\LTLHZ\YLKH[HWVPU[TPUMYVU[VM[OL\UP[H[HOLPNO[VMT
+\YPUNHJ[\HSVWLYH[PVU[OLZL]HS\LZHYLUVYTHSS`ZVTL^OH[OPNOLYHZHYLZ\S[VMHTIPLU[JVUKP[PVUZHUKVPSYLJV]LY`TVKL
>OLU[OLYLPZJVUJLYUMVYUVPZL[V[OLZ\YYV\UKPUNHYLHZ\JOHZYLZPKLUJLZ^LYLJVTTLUKPU]LZ[PNH[PUN[OLPUZ[HSSH[PVUSVJH[PVUHUK[HRPUNZV\UKWYVVMPUNTLHZ\YLZ


25 23 24 26
Indoor Unit Lineup
Daikin offers a wide range of indoor units includes both VRV and residential models P.171 Ceiling Suspended Type P.155
Outdoor-Air
responding to variety of needs of our customers that require air-conditioning solutions. Processing Unit
FXHQ-MAVE

FXMQ-MFV1

VRV indoor units FXHQ-AVM

Combine fresh air treatment


Ceiling Mounted Cassette P.129 Ceiling Mounted Cassette P.129 and air conditioning,
supplied from a single system.
(Round Flow with Sensing) Type (Round Flow) Type

FXFSQ-AVM FXFQ-AVM
Wall Mounted Type P.157 Floor Standing Type P.159

FXAQ-AVM FXLQ-MAVE
temperature can be detected to distribution and offers a comfortable
provide comfort and energy savings. living environment.
Concealed Floor Standing Type
Ceiling Mounted Cassette P.139 4-Way Flow Ceiling P.140
FXNQ-MAVE
P.160
(Compact Multi Flow) Type Suspended Type
harmonised with your interior Suitable for perimeter zone air
FXZQ-MVE FXUQ-AVEB décor. conditioning.

This slim and stylish indoor unit


achieves optimum air distribution,
Quiet, compact, and designed for and can be installed without the
Floor Standing Duct Type P.161 Clean Room Air Conditioner P.162 Air Handling Unit P.169
user comfort. need for ceiling cavity. FXVQ-NY1 FXBQ-PVE AHUR

FXVQ-NY16 FXBPQ-PVE
Ceiling Mounted Cassette P.141 Ceiling Mounted Cassette P.143
(high static pressure type)
(Double Flow) Type (Single Flow) Type

FXCQ-AVM FXEQ-AV36

Integrate your air handling


Thin, lightweight, and easy to install in
large spaces. unit in a total solution for
narrow ceiling spaces
Flexible interior design Suitable for hospitals and large size spaces such as
for each tenant. other clean spaces factories and large stores.

Slim Ceiling Mounted Duct Type P.145 Slim Ceiling Mounted P.147

Duct Type

FXDSQ-AVM FXDQ-PDVE(T) Residential indoor units with connection to BP units


FXDQ-NDVE(T)
Stylish & compact design, and 3D Slim Ceiling Mounted Duct Type Wall Mounted Type
P.165 P.166 Wall Mounted Type P.167
Slim design, quietness and
provide comfort and energy savings. static pressure switching. FDKS-EAVMB FTKJ-NVMW FTKS-DVM

Slim Ceiling Mounted P.148 Middle Static Pressure P.149


FTKS-BVMA
Duct Type (Compact Series) Ceiling Mounted Duct Type
FDKS-C(A)VMB FTKJ-NVMS
FXDQ-SPV1 FXSQ-PAVE
FTKS-FVM
Slim and smooth design suits Elegant appearance with
your shallow ceiling European style with your interior décor

Indoor Unit Lineup


Slim and compact design for easy and Middle static pressure and slim design

Ceiling Mounted Duct Type P.151 Ceiling Mounted P.153


Air treatment equipment
Duct Type
FXMQ-PAVE
Heat Reclaim Ventilator with P.175 Heat Reclaim Ventilator P.179
FXMQ-PVM
FXMQ-MVE9 DX-Coil

Middle and high static pressure High static pressure allows VKM-GAV1 VAM-GJVE

27 25
127 2628
128
New Round Flow

Indoor Unit Lineup VRV Indoor Units


Cassette movie at

YouTube site.

Ceiling Mounted Cassette Ceiling Mounted Cassette


(Round Flow with Sensing) Type (Round Flow) Type

FXFSQ-A FXFQ-A Ceiling Mounted Cassette (Round Flow with Sensing) Type
MODEL FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM
Power supply 1-phase, 220 - 240 V/220-230 V, 50/60 Hz
with sensing Cooling capacity
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Power consumption kW 0.028 0.035 0.056 0.061 0.092 0.164 0.170 0.194
Casing Galvanised steel plate
Wide variety of decoration panels (Option) m3/min 13/12.5/11.5/11/10 17/13.5/12.5/12/11 23/20.5/19/14.5/11 23.5/21/20/16/13.5 24.5/22/20.5/20/15 33.5/30.5/27/23.5/21 34.5/31.5/28.5/25.5/23 35.5/32.5/29.5/26.5/23
cfm 459/441/406/388/353 600/477/441/424/388 812/724/671/512/388 830/741/706/565/477 865/777/724/706/530 1,183/1,077/953/830/741 1,218/1,112/1,006/900/812 1,253/1,147/1,041/935/812
Designer choice has been given a boost with the increase in number of new types of decoration panels. Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 38/35/34.5/29.5/27 38/36/35.5/31.5/28 39/37/36/35.5/31 44/41/38/35/33 45/42.5/39.5/37/35 46/43.5/40.5/38/35
Dimensions (H×W×D) mm 256×840×840 298×840×840
Machine weight kg 19 24 22 25 26
Liquid (Flare) 6.4 9.5
Piping
connections Gas (Flare) mm 12.7 15.9
Drain VP25 (External Dia. 32/Internal Dia. 25)

Ceiling Mounted Cassette (Round Flow) Type


MODEL FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXFQ80AVM FXFQ100AVM FXFQ125AVM FXFQ140AVM
Power supply 1-phase, 220
220-- 240 V/220-230 V, 50/60 Hz
Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 54,600
Cooling capacity
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0
Power consumption kW 0.029 0.036 0.040 0.063 0.096 0.158 0.178 0.203
Casing Galvanised steel plate
m3/min 13/12.5/11.5/11/10 17/13.5/13/12/11 18/17/13.5/12.5/11 21/20/16/15/13.5 22.5/21.5/21/20/15 32/29/26/23/21 33/30.5/28/25.5/21 35.5/32.5/29.5/26.5/23
- Fresh White - - Fresh White - - Black - cfm 459/441/406/388/353 600/477/459/424/388 635/600/477/441/388 741/706/565/530/477 794/759/741/706/530 1,130/1,024/918/812/741 1,165/1,077/988/900/741 1,253/1,147/1,041/935/812
Sound level (H/HM/M/ML/L) dB(A) 30/29.5/28.5/28/27 35/29.5/29/28/27 35/33.5/29.5/28.5/27 36/35.5/31.5/31/28 37/36.5/36/35.5/29.5 43/40.5/37.5/35/33 44/41.5/39/36.5/33 46/43.5/40.5/38/35

FXFSQ series only Designer panel Standard panel Dimensions (H×W×D) mm 256×840×840 298×840×840
Machine weight kg 19 22 25 26
Standard panel - Black - - Fresh White - Liquid (Flare) 6.4 9.5
with sensing Piping
Gas (Flare)
connections mm 12.7 15.9
Drain VP25 (External Dia. 32/Internal Dia. 25)
Designer panel (Option) •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

Close to ideal styling


During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Decoration Panel (Option) Round Flow with Sensing Type Round Flow Type
FXFSQ-A FXFQ-A
New designer panel Standard Model BYCQ125EEF (Fresh White) / BYCQ125EEK (Black) —
panel
Dimensions(H×W×D) mm 50×950×950 —
with
sensing Weight kg 5.5 —
FLAT
F LAT C LE
EAAN RO U ND Model BYCQ125EAF (Fresh White ) / BYCQ125EAK (Black)
Standard
panel Dimensions(H×W×D) mm 50×950×950
Flatter styling: Clean-cut form: Subtle distinction: Weight kg 5.5
Model BYCQ125EAPF (Fresh White)
Suction panel grid Soiling is hard to see around suction inlets Designer
panel Dimensions(H×W×D) mm 97×950×950
texture smoothed. on smart-looking panel. silvering is a tasteful touch.
Weight kg 6.5
Auto Model BYCQ125EASF (Fresh White)
grille Dimensions(H×W×D) mm 105×950×950
panel
Decoration Panel Lineup (Option)
Weight kg 8

Function List Round Flow with Sensing Type Round Flow Type

Indoor Unit Lineup


FXFSQ-A FXFQ-A
Wired BRC1E63 — BRC1E63 —
Remote controller
Wireless — BRC7M635F(K) — BRC7M635F(K)
Dual sensors *1
FXFSQ series only 1

Standard panel with sensing*1 Standard panel*2 Designer panel*2 Sensing sensor low mode *1
BYCQ125EEF (Fresh White) BYCQ125EAF (Fresh White) BYCQ125EAPF (Fresh White) Sensing sensor stop mode *1

Switchable 5 step fan speed

Auto swing
FXFSQ series only *1.Sensing function is applicable when Auto grille panel*2
sensing panel is installed. Swing pattern selection
Standard panel with sensing*1 Standard panel *2 BYCQ125EASF
*2.These panels do not contain the (Fresh White) High ceiling application
BYCQ125EEK (Black) BYCQ125EAK (Black) sensing function. *1. Applicable when sensing panel is installed.

29 27
129 2830
130
New Round Flow

Indoor Unit Lineup VRV Indoor Units


Cassette movie at

YouTube site.

Daikin Advanced Sensing Functions


Ceiling Mounted Cassette
*1,2
FXFSQ series only (Round Flow with Sensing) Type FXFSQ-A

Dual Sensors*1 *1. Applicable when sensing panel (BYCQ125EEF/EEK) is installed.


*2. Applicable when wired remote controller BRC1E63 is used.
Comfort and Energy Saving Preventing Overcooling*6 rate should be set to “Auto”.

Floor temperature is detected and overcooling prevented. Cooling


Without sensing function With sensing function
Infrared presence sensor
The sensor detects the presence of people in each of the 4 areas.
Ceiling height 2.7m 3.5m 4.0m
30°C near ceiling 30°C near ceiling
Detection range approx. approx. approx.
(diameter)*3 8.5m 11.5m 13.5m Room 2 Room temperature is
temperature is calculated as 27°C in the area which
detected as is in the vicinity of the person.
30°C.

1 24
with sensing
automatically adjusts operation of the indoor unit to
Detecting the
presence of people reduce the temperature difference between the ceiling Area around feet gets too cold because the air conditioner Automatic control using the
in each of the 4 areas continues until the temperature near the ceiling reaches the which is lower than near temperature near the person
set temperature. the ceiling, is detected. as the room temperature.
Ceiling height 2.7m 3.5m 4.0m
Detection range approx. approx. approx. The temperature near the person is automatically calculated by detecting the temperature of the
Energy
C (diameter)*4 11m 14m 16m savings
B D
A Standard range for infrared presence sensor *

Sensing Sensor Functions*7,8,9 *7. Applicable when sensing panel (BYCQ125EEF/EEK) is installed.
*8. These functions are not available when using the group control system.
*9. User can set these functions with remote controller.

Detecting the
2.7m
ceiling
Sensing sensor low mode (default: OFF)
height When there are no people in a room,
average temperature
the set temperature is shifted automatically. Operation is
- The system automatically saves energy by detecting reduced in places
80cm whether or not the room is occupied. The set temperature where there are
approx.8.5m is shifted automatically if the room is unoccupied. no people.
*[Concerning infrared presence sensor]
- People are detected by large movements such as the motion of people walking at a • Cooling set temperature: 26°C • Shift temperature: 1.0°C
certain distance away from sensor. Example
- Human detection is not possible for blind areas of sensor. • Shift time: 30 min. • Limit cooling set temperature: 30°C

Set temperature (°C)


- The detected temperature may sometimes be affected by a heat source, window, or *10
device emitting heat in the detection range. 28 *10
28°C
27 27°C
*5 26 26°C 26°C If people do not return,
Occupied Automatically reverts the air conditioner will
when people return. raise the set
Unoccupied
(default: OFF) Cooling Dry temperature 1°C every
30 minutes and then
operate at 30°C.
When human presence is not detected When human presence is detected After 30 min After another 30 min
Time

Shift temperature and time can be selected from 0.5 to 4°C in 0.5°C increments and 15, 30, 45, 60, 90 or 120 minutes respectively
with remote controller.

Indoor Unit Lineup


*10. On basic screen of remote controller, set temperature does not change.

Sensing sensor stop mode (default: OFF)


When there are no people in a room, the system stops automatically.*11,12
- The system automatically saves energy by
detecting whether or not the room is occupied. Absent stop time can be selected from
- Based on preset user conditions, the system 1 to 24 hrs in 1 hr increments with
automatically stops operation if the room is remote controller.
Optimal air direction Swing (narrow)
Optimal air direction by “Auto” by “Auto” unoccupied. *11.Please note that upon re-entering the room,
the air conditioner will not switch on automatically.
*12.To protect the machine, the standby system may
When presence is detected, air direction is set operate temporarily.
to “Swing (narrow)” to deliver cool air to users.

131
31 29 3032
132
New Round Flow

Indoor Unit Lineup VRV Indoor Units


Cassette movie at

YouTube site.

Ceiling Mounted Cassette


*1
*1. Applicable when wired remote controller BRC1E63 is used. (Round Flow with Sensing) Type FXFSQ-A Ceiling Mounted Cassette
(Round Flow) Type FXFQ-A

areas that were either too cool or not cool enough. Comfort to the Entire Room with Even Temperatures and No Cold Air Pockets at Floor Level
Problem 1 4-way cassette (Swing)
30.0
29.0
Comparison Conditions
28.0 Room size:
Hot outdoor air entering through 27.0 Width 7.5m x depth 7.5m
26.0 x height 2.6m
windows and walls causes these
areas to become hot. 4-Way Flow 25.0
24.0
Indoor unit capacity: 80 class
Outdoor air temperature: 35°C
23.0
22.0
21.0 high / swing
Problem 2 20.0

Cool air accumulating directly Hot Areas at floor level are


outdoor
underneath causes cold air air cold while areas
around walls are hot.

Problem 3 1 Approx. 5% energy


*2

savings by reducing
causes discomfort for people in 3 uneven temperatures
the room. *2.Calculated under the following comparison
conditions: When the average temperature at a
Problem 4 temperature. (26°C)
Quick descent of cool air causes 4 2
Full comfort is
the room. provided with no
cold feet.

During 2-way 1 (Straight) 2 (Horizontally)

Hot was achieved.


outdoor air
Conventional flap*3 *3. FXFQ-S model
Conventional flap*3 New wide flap

blowing air directly on people. 30° air direction

When set to 20° the


Cannot blow more than
airflow route gets
30° horizontal.
Cool air moves down along Approx. narrow.
Comfort without cold air *3. FXFQ-S model
the walls and to every corner doubled Even at 20°, the
hot air near windows and walls. New wide flap
of the room. 20° airflow route is
sufficiently
inhibits ceiling dirt and grime. horizontal
flow maintained.

20° air direction


directed downward.
A more horizontal 20° flow is realized. Velocity
10%
3 Increased velocity in *4
increase!

(Strongly)
All-round Two-way
flow flow

Indoor Unit Lineup


*4
Cools the entire room to deliver comfort that never feels cold.
Operation Performs repeatedly
[Table 1]
(at start) Airflow Distance to wall from indoor unit
Main points for use
direction When the set Installation conditions Indoor unit FXF(S)Q FXF(S)Q FXF(S)Q
Effectiveness may differ according to room conditions, room size, capacity
changes temperature is reached, and distance to walls.
25-50 63/80 100-140
Round flow
Maximum
normal operation Airflow operation differs when using the designer panel. (Operation repeatedly distance 1.5m-4m 1.5m-5m 1.5m-7m

(all-round flow) begins. switches from 3-way horizontal flow to 4-way downward flow [swing] to
[Table 2]

Wall surface
2-way horizontal flow to 4-way downward flow [swing].)
Distance Minimum distance between Minimum distance between indoor units
Circulation airflow functions during connection with wired remote controller. to wall indoor units [Table 2]
Note: (BRC1E63). However, use is not possible for the following conditions: [Table 1] Indoor unit FXF(S)Q FXF(S)Q FXF(S)Q
Results may vary depending on capacity 25-50 63/80 100-140
Cools areas around Cools entire room using Cools areas around Cools entire room using 1.8m or more above floor surface
walls using walls using equipment conditions, room size, - When a sealing material of air discharge outlet and branch ducts are used;
4-way swing flow 4-way swing flow - When individual airflow setting is selected;
Minimum
4m or more 5m or more 7m or more
2-way horizontal flow 2-way horizontal flow and distance from indoor unit to walls.
- When using group control other than round flow.
Floor surface distance

133
33 31 3234
134
New Round Flow

Indoor Unit Lineup VRV Indoor Units


Cassette movie at

YouTube site.

Ceiling Mounted Cassette


*1
(Round Flow with Sensing) Type FXFSQ-A Ceiling Mounted Cassette
(Round Flow) Type FXFQ-A

Other Functions
*1. Applicable when wired remote controller BRC1E63 is used.

Comfortable air conditioning for all room layouts and conditions


individually adjusted for each air Easy setting is possible with a wired remote controller. Comfort
discharge outlet to deliver
optimal air distribution.

There are
Position 0
marks near
( the air outlets.
highest position) Remote controller L-shaped Opposite
BRC1E63 screen

No individual Position 0 (Highest point) (E.g., installed in (E.g., installed (E.g., installed in (E.g., installed in
setting middle of ceiling) near a wall) a corner) a long room)
Position 1
( )
Position 2
Note:
Position 3 Required * - Whatever the discharge direction, the same type of panel is used. If installing for other than all-round
distance to
Swing Position 4 Position 4 (Lowest point) wall surface
Minimum distance
of 500mm
(Up/down) ( Swing for closing -
* 200mm for corner
-
lowest position) air discharge * closing

Individual settings are possible as stated above.


outlet Wall surface

Optimal comfort and convenience assured by 3 air discharge modes


Position 0 Draft prevention setting Ceiling soiling prevention
Position 0 Air direction Standard setting1 setting2
The airflow is at the
highest setting (Position 0) For shops with
for people who Desired situation For gentle drafts. When drafts are unwanted. light coloured ceilings that
Swing dislike air blowing must be kept spotless.
Discussions near Swing is set for directly on them.
a hot window meetings near
the windows.
Auto-swing
quickly heat up.
Note:
1
Air direction is set to the
5-level standard position when the
unit is shipped from the
air direction setting factory. The position can be
changed from the remote
The air direction is set automatically to the memorised controller.
It’s quite pleasant Auto air direction position of the previous air direction. 2
Closing of the corner
It is very cold here, when cold air isn’t control discharge outlets is
isn’t it?… Discussions also blowing on us. recommended.
go smoothly.
Switchable fan speed: 5 steps and Auto
For shops and restaurant
Suitable for high ceilings

Indoor Unit Lineup


Criteria for ceiling height and number of air discharge outlets
(Ceiling height is reference value)
Standard Setting Setting Number of air discharge outlets used
Swing FXF(S)Q25-80A FXF(S)Q100–140A
Swing is All round 4-way 3-way 2-way All round 4-way 3-way 2-way
selected for
areas near No individual (Auto) 3.6 4.2 Standard 2.7 m 3.1 m 3.0 m 3.5 m 3.2 m 3.4 m 3.6 m 4.2 m
the windows. 3.2 Ceiling
Auto is set for people m m height
High ceiling 3.0 m 3.4 m 3.3 m 3.8 m 3.6 m 3.9 m 4.0 m 4.2 m
sitting farthest from
m High ceiling 3.5 m 4.0 m 3.5 m - 4.2 m 4.5 m 4.2 m -
Sitting here is hot The seats here the entrance. Note:
because of the hot air are comfortable The aforementioned is for standard panels. See the installation manual for designer panels.
from outside. though…

can be accommodated. (FXF(S)Q100-140A)

35 33
135 3436
136
Indoor Unit Lineup VRV Indoor Units

Ceiling Mounted Cassette


Quick and Easy Installation (Round Flow with Sensing) Type FXFSQ-A Ceiling Mounted Cassette
(Round Flow) Type FXFQ-A
Washer
Lightweight Easy hanging
All models can be installed without using a lifter. Easy Maintenance
in place and prevent washers from
Installable in tight ceiling spaces falling for easy installation. Drain pan and drain water check Auto grille panel (option)
Standard panel The condition of the drain pan and drain water can be
256 mm (25-80A) 261 mm (25-80A) Easy removal of checked by removing the suction grille and drain plug. a stepladder by lowering the grille.
298 mm (100-140A) 303 mm (100-140A) corner cover Note: For inquiries concerning auto grille panel installations,
please contact your local dealer or Daikin representative. A dedicated remote controller for the auto grille panel (BRC16A2)
It is possible to easily is included.
Designer panel remove without use Operation is not possible using BRC1E63.
of screws or tools.
256 mm 261 mm e
en th e!
+42 mm*1 The drop length corresponds to
298mm 303 mm p
t o l ceiling height and can be set for
42 mm*1 Drain outlet Jus ion gril
suct
(with rubber plug) 8 different levels.

*1.Body height (ceiling required space) is 42 mm higher than standard panel. Ceiling Height
Drop Length
Standard (m)
Auto grille panel
2.4 1.2
256 mm 261 mm 2.7 1.6
298 mm +55 mm*2
55 mm*2
303 mm
24 mm diameter drain outlet 3.0 2.0
The drain outlet allows 3.5 2.4
*2.Body height (ceiling required space) is 55 mm higher than standard panel.
3.8 2.8
*When the ceiling space is limited, an optional panel spacer is available. dental mirror for inspection 4.2 3.1
(See page 207)
98) of the internal cleanliness 4.5 3.5
of the drain pan. Removal 5.0* 3.9
Ease in temporary hanging of the suction panel
Easy height adjustment of decoration panel enables access. Please refer to “criteria for ceiling height
Each corner of the unit has an and number of air discharge outlets” on
adjuster pocket that lets you In addition to the temporary page 34.
136.

easily adjust the unit's


suspended height. normally used, corner part

Note: are provided.


If the wireless remote controller is installed, Corner part mounting
a signal receiver unit is housed in one of Temporary hanging
the adjuster pockets. See page 98
207

Maintenance is not required in normal shops or


Temporary placement of control Drain pump
box lid Equipped as standard
accessory with
Because the control box lid can be temporarily hung 850 mm
850 mm lift.
on the unit, there is no need to climb down the
stepladder to retrieve it. 175 mm
Cleanliness

Silver ion anti-bacterial drain pan


Transparent drain socket A built-in antibacterial Flaps can be detached without use of tools.
treatment that uses silver Condensation does not easily
ion in the drain pan form and dirt does not cling to

Indoor Unit Lineup


The detached lid can prevents the growth of
be hung on a hook. slime, bacteria, and mould They are easy to clean.
Hanging height adjustment that cause odours and
clogging.
Installed in any direction dimensions from the ceiling to the hanger bracket also change (The lifespan of a silver ion Filter has anti-mould and
during height adjustment for indoor unit.
Since the orientation of the
A Dimensions
cartridge depends on the
usage environment, but
antibacterial treatment
suction grille can be Hanger
bracket
adjusted after installing,
Standard panel 125-130mm
should be changed once Prevents mould and microorganisms growing out of the
Designer panel 167-172mm
the direction of the suction A
every two to three years.)
Auto grille panel 180-185mm
Chamber option*+ standard panel 175-180mm
when multiple units are Ceiling
surface
installed. fresh air intake

137
37 35 3638
138
Indoor Unit Lineup VRV Indoor Units

Ceiling Mounted Cassette (Compact Multi Flow) Type FXZQ-M 4-way Flow Ceiling Suspended Type FXUQ-A

This slim and stylish indoor unit


achieves optimum air distribution,
Quiet, compact, and designed for user comfort
and can be installed without
the need for ceiling cavity.

Unit body and suction panel adopted round shapes and Built-in electronic Current model New model

1 Wide discharge angle: 0° to 60° Dimensions correspond with 600 mm X 600 mm architectural realised a slim appearance design. The unit can be used for expansion valve
Auto swing Fixed angles: 5 levels various locations such as the ceilings with no cavity and eliminates the need for
bare ceilings. a BEV unit, which
Low operation sound level BEV unit is
needed
BEV unit is
not needed
Flaps close automatically when the unit stops, which gives a installation.
Drain pump is equipped as standard accessory with
0° 0° 0° simple appearance.
750 mm lift.
60° 60° 60° 60° adoption of a new heat exchanger with smaller tubes, DC
*Angles can be also set on site to prevent drafts (0°-35°) fan motor and DC drain pump motor.
or soiling of the ceiling (25°-60°), other than standard setting (0°-60°). capacities are installed in the same area.
750 mm Drain pump is equipped as a standard accessory, and the lift
2 direction adjustment can be individually set for each air height has been improved from 500 mm to 600 mm.
enabling installation in the corner of a room. Depending on installation site requirements or room
selected with wired remote controller BRC1E63, which conditions, 2-way, 3-way and 4-way discharge patterns are
realises the optimum air distribution. available.

Position 0 Position 2

Position 3 Swing
L-shaped

An antibacterial treatment that uses


* silver ions has been applied to the drain pan,
(option) must be used to close each unused outlet. preventing the growth of slime, mould and
bacteria that cause blockages and odours.
(The lifespan of a silver ion cartridge depends
be selected with wired remote controller BRC1E63. on the usage environment, but should be
MODEL FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE
changed once every two to three years.)
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Power consumption kW 0.073 0.076 0.089 0.115
MODEL FXUQ71AVEB FXUQ100AVEB
Casing Galvanised steel plate
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
m3/min 9/7 9.5/7.5 11/8 14/10
Btu/h 27,300 38,200
cfm 318/247 335/265 388/282 493/353 Cooling capacity
kW 8.0 11.2
Sound level 230 V 30/25 32/26 36/28 41/33
dB(A) Power consumption kW 0.090 0.200
(H/L) 240 V 32/26 34/28 37/29 42/35
Casing Fresh white
Dimensions (H×W×D) mm 286×575×575
m3/min 22.5/19.5/16 31/26/21

Indoor Unit Lineup


Machine weight kg 18
cfm 794/688/565 1,094/918/741
Liquid (Flare) 6.4
Piping Sound level (H/M/L) dB(A) 40/38/36 47/44/40
mm
connections Gas (Flare) 12.7
Dimensions (H×W×D) mm 198×950×950
Drain VP20 (External Dia. 26/Internal Dia. 20)
Machine weight kg 26 27
Model BYFQ60B3W1
Liquid (Flare) 9.5
Panel Colour White (6.5Y9.5/0.5) Piping
(Option) Gas (Flare) mm 15.9
Dimensions(H×W×D) mm 55×700×700 connections
Drain VP20 (External Dia. 26/Internal Dia. 20)
Weight kg 2.7

• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions

139
39 37 3840
140
Indoor Unit Lineup VRV Indoor Units

Ceiling Mounted Cassette (Double Flow) Type FXCQ-A

Energy saving : Reduction of energy consumption


Stylish unit blends easily with any interior.
reduced by specially developed Power consumption comparison (Cooling)
Integrated ceiling surface with small tube heat exchanger and 300 278

sophisticated panel design with the DC fan motor.

Power consumption (W)


216
200
157 149
132 132
100
95 90
81
59 63
Conventional model:FXCQ-M 31 39 41
New model:FXCQ-A 0
New panel design
20 25/32 40 50 63 80 125
Model class

Enhanced functions from various aspects such as maintenance

Drain pump is equipped as standard accessory


*1
condensate and get dirty. with 850 mm lift.
Airfow direction can be individually adjusted for each air discharge outlet to deliver optimal air distribution.
*1. Applicable when wired remote controller BRC1E63 is used. Check contamination in drain pan by simply remove suction
grille and panel.
Easy setting is possible with a wired 850 mm
remote controller.
maintenance interval.

Adjuster pockets mount at four


There are
corners of the unit enable to An antibacterial treatment
marks near adjust the main unit without that uses silver ions has been
the air outlets. removing the panel. applied to the drain pan,
preventing the growth of slime,
mould and bacteria that cause
Adjuster Pocket
blockages and odours.
Swing (The lifespan of a silver ion
Position 0 (Up / Down) cartridge depends on the
Easy visual inspection of drainage
through the transparent usage environment, but
highest position) No individual setting Position 0 (Highest point) should be changed once
body drain socket.
Position 1 Position 2 Position 3 Drain socket part every two to three years.)
Position 4 (Lowest point) Swing

Individual settings are possible as stated above.

MODEL FXCQ20AVM FXCQ25AVM FXCQ32AVM FXCQ40AVM FXCQ50AVM FXCQ63AVM FXCQ80AVM FXCQ125AVM


Switchable fan speed: 5 steps and Auto Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 7,500 9,600
12,300 15,400 19,100 24,200 30,700 47,800
Cooling capacity
kW 2.2 3.6 2.8 4.5 5.6 7.1 9.0 14.0
Power consumption kW 0.031 0.039 0.041 0.059 0.063 0.090 0.149
Casing Galvanised steel plate
m3/min 10.5/9.5/9/8/7.5 11.5/10.5/9.5/8.5/8 12/11/10.5/9.5/8.5 15/14/13/11.5/10.5 16/15/14/12.5/11.5 26/24/22.5/20.5/18.5 32/29.5/27.5/25/22.5
cfm 371/335/318/282/265 406/371/335/300/282 424/388/371/335/300 530/494/459/406/371 565/530/494/441/406 918/847/794/724/653 1,130/1,041/971/883/794
Suitable for high ceilings Sound level (H/HM/M/ML/L) dB(A) 32/31/30/29/28 34/33/31/30/29 34/33/32/31/30 36/35/33/32/31 37/36/35/33/31 39/38/37/35/32 42/40/38/36/33 46/44/42/40/38
Dimensions (H×W×D) mm 305x775x620 305x990x620 305x1,445x620

Indoor Unit Lineup


Even in spaces with high ceilings maximum 3.5 m, Machine weight kg 19 22 25 33 38
Liquid (Flare) 6.4 9.5
Piping mm
connections Gas (Flare) 12.7 15.9
Drain VP25 (External Dia. 32/Internal Dia. 25)
Model BYBCQ40CF BYBCQ63CF BYBCQ125CF
Panel Colour Fresh white (6.5Y 9.5/0.5)
(Option) Dimensions (H×W×D) mm 55x1,070x700 55x1,285x700 55x1,740x700
Weight kg 10 11 13
3.5 m
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

141
41 39 4042
142
Indoor Unit Lineup VRV Indoor Units

Ceiling Mounted Cassette (Single Flow) Type FXEQ-A

New Remote Controller (Option)


„Wireless Remote Controller
zStylish new design giving more satisfaction of ownership
LCD Backlight
zComes in white colour
z

zBack light function helps operating in dark rooms


zThe body features a compact design with a height of just zThe novel smooth panel
200 mm and depth 470 mm, making the installation design makes dust
possible in tight ceiling spaces.
thus causing the cleaning The LCD panel lights up during use, making the remote
more conveniently. controller easy to handle even in dark.
BRC4M63
200 mm 255 mm
Trave
80 mm

zDrain pump is equipped „ Navigation Remote Controller


„Navigation
Indoor unit as standard accessory (Wired Remote Controller)
255 mm with 850 mm lift.

adjusted with the new wired


z remote controller.
adjusted freely with the remote controller, providing 3D zServicing of common
parts such as the control
box etc. can be
performed easily only with
Front view Side view the suction panel BRC1F61
removed.

MODEL FXEQ20AV36 FXEQ25AV36 FXEQ32AV36 FXEQ40AV36 FXEQ50AV36 FXEQ63AV36


Power supply 1-phase, 220-240 V, 50 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1

to left or right within 45° swinging between 20° to 70° Power consumption kW 0.026 0.027 0.034 0.046 0.048 0.067
Casing Galvanised steel plate
Airflow rate m3/min 6.0/5.4/4.9/4.4/4.0 6.9/6.4/5.8/5.3/4.8 8.0/7.5/7.0/6.3/5.5 9.8/8.8/7.8/7.0/6.2 12.5/11.4/10.4/9.5/8.7 15.0/13.6/12.2/11.0/9.8
z (H/HM/M/ML/L) cfm 212/191/173/155/141 244/226/205/187/169 282/265/247/222/194 346/311/275/247/219 441/402/367/335/307 530/480/431/388/346
and quiet operation mode, which provides comfortable Sound level (H/HM/M/ML/L) dB(A) 30/29/28/27/26 32/31/30/29/28 35/34/33/32/30 38/37/35/33/31 38/37/35/33/31 43/41/39/37/35
Dimensions (H×W×D) mm 200×840×470 200×1,240×470

Indoor Unit Lineup


Machine weight kg 17 18 23
zDC motor is adopted both in the fan and drain pump of Liquid (Flare) 6.4 9.5
the indoor unit, not only enhancing the energy saving Piping
Gas (Flare) mm 12.7 15.9
performance, but also reducing the operating sound and connections
the vibration incurred to the unit. Drain PVC26 (External Dia. 26/Internal Dia. 20)
Model BYEP40AW1 BYEP63AW1
Panel Colour Fresh white
zWhile creating a cozy indoor environment, the unit can
(Option) Dimensions(H×W×D) mm 80×950×550 80×1,350×550
prevent the suspended ceiling from being soiled by
adjusting its louvre angle. Weight kg 8.0 10.0

Note: Specifications are based on the following conditions;


• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.

143
43 41 4244
144
Indoor Unit Lineup VRV Indoor Units

Slim Ceiling Mounted Duct Type (3D Airflow with Sensing) FXDSQ-A

Stylish & compact design, Dual Intelligent Eye Technology


and 3D airflow with sensing Dual intelligent eye
function to provide comfort ■Infrared presence sensor
and energy savings. built-in sensing function provides
The presence sensor detects where people are and

superior comfort and energy-savings


more comfortable environment. automatically adjusts operation of the indoor unit to


reduce the temperature difference between the ceiling

Horizontal & Vertical direction can be adjusted freely Comfort and energy saving preventing over cooling *1
by the remote controller settings as to provide 3D
Cooling
60
°

Cooling range 30°C near ceiling


of swing
Room temperature is
45° 45° calculated as 27°C in the area which
Horizontal is in the vicinity of the person.
flaps
Automatic control using the
Vertical flaps
Can freely select 5 positions and swing mode which is lower than near
24
temperature near the person
for each up/down and left/right direction with the ceiling, is detected. as the room temperature.
remote controller.
Up and Down: Energy Energy is saved, because the area
savings around the feet does not get too cold.
P0 P1 P2 P3 P4 Swing
P0

Smooth & Classy Panel Sensing sensor mode *2 *3


Left and Right: ■Sensing sensor low mode (default:OFF) ■Sensing sensor stop mode (default:OFF)
with ceiling styling and your home design. P0 P1 P2 P3 P4 Swing
Airflow direction adjustment When there are no people in a room, the set temperature When there are no people in a room, the system stops
button
Condensation proof panel which resultsless liable Up and Down Left and Right shifts automatically to save energy. automatically to save energy.*4
tocondensation and dripping.
* Can operate the same by wired remote controller, too. *1
*2. These functions are not available when using the group control system.
*3. User can set these functions with remote controller.
*4. Please note that upon re-entering the room, air conditioner will not switch on automatically.
Slim Size
It comes with a slim and compact Only 450 mm
design with a height of only 200 mm 200 mm Specifications
accordance to the difference between room that requires as little as 240 mm in
height for the ceiling space between MODEL FXDSQ20AVM FXDSQ25AVM FXDSQ32AVM FXDSQ40AVM FXDSQ50AVM FXDSQ63AVM
temperature and set temperature, which provides Power supply 1-phase, 220-240/220-230 V, 50/60 Hz
the drop-ceiling and ceiling slab.
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
The depth of the product is only 450 *Indicated sizes are for the Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1
mm which is suitable to install in main body only.
Panel dimensions are not Power consumption *1 kW 0.028 0.029 0.032 0.049 0.054
Level 1 (Low) Level 2 Level 3 (Medium) limited spaces. included. Casing Galvanized steel plate
m3/min 8.7/8.1/7.6/7.0/6.5 9.0/8.5/8.0/7.5/7.0 10.0/9.3/8.6/7.9/7.2 12.0/11.2/10.5/9.7/9.0 15.0/14.0/13.0/11.5/10.5 19.0/17.0/15.0/13.0/11.5
External static pressure Pa 10-0 *2
It is available in two types – ceiling
Sound level (H/HM/M/ML/L)*1 *3 dB(A) 31/29/27/26/24 31/29/27/26/24 34/32/30/29/27 39/37/35/33/31 39/37/35/33/30
return and ordinary duct to suit
Dimensions (H×W×D) mm 200×700×450 200×900×450 200×1,100×450
different installation conditions. 750 mm Machine weight kg 17 20 23

Indoor Unit Lineup


Liquid (Flare) 6.4 (flare) 9.5 (flare)
Drain pump is equipped as standard Piping mm 12.7 (flare) 15.9 (flare)
accessory with 750 mm lift. connections Gas (Flare)
Drain PVC26 (External Dia. 26 / Internal Dia. 20)
Ceiling
3D Auto Dimensions (H×W×D) mm 180×722×70 180×922×70 180×1,122×70
Auto Level 5 (High) Level 4 swing Colour Fresh white
Remote Controller panel Weight kg 1.0 1.5 2.0
Wireless Remote Controller
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Wired Remote Controller •Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
*1 : Values are based on external static pressure of 10 Pa.
*2 : External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory setting is 10 Pa )
*3 : The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).

BRC4M65 BRC1F61

145
45 43 4446
146
Indoor Unit Lineup VRV Indoor Units

Slim Ceiling Mounted Duct Type (Standard Series) FXDQ-PD / ND Slim Ceiling Mounted Duct Type (Compact Series) FXDQ-SP

Slim design, quietness and Slim and compact design for easy
static pressure switching

Only 200 mm in height, this model can be installed in It comes with a slim and compact design with a height of only
Suitable to use in drop-ceilings! rooms with as little as 240 mm in height for the ceiling 200 mm that requires as little as 240 mm in height for
space between the drop-ceiling and ceiling slab. the ceiling space between the drop-ceiling and ceiling slab.
Only 700 mm in width Great for The depth of the product is only 450 mm which is suitable to
and 23 kg in weight, hotel use! FXDQ20-32PD
install in limited spaces.
FXDQ40/50ND
this model is suitable
to install in limited spaces * 1,100 mm in width for Great for
like drop-ceilings in hotels. 200 mm the FXDQ63ND model.
900 mm 200 mm residential use
200 mm
Only 700 mm Suspension bolt*
700 mm* Only 450 mm
AIR 240 mm *For FXDQ20-32SP models

Discharge
It is available in two types – ceiling return and ordinary
grille * Suction grille *
duct to suit different installation conditions.
remote controller BRC1E63. AIR * To be obtained locally

Low operation sound level. FXDQ-PD and FXDQ-ND models are available in two Duct Canvas Duct
types to suit different installation conditions. bellows
and air
External static pressure selectable Air suction Air
FXDQ-PD/NDVE: with a drain pump (750 mm lift) panel
discharge discharge
by remote controller switching as a standard accessory
make this indoor unit a very FXDQ-PD/NDVET: without a drain pump
Air suction Air suction
10 Pa-30 Pa/factory set:
10 Pa for FXDQ-PD models.
15 Pa-44 Pa/factory set: 750 mm Drain pump is equipped as
15 Pa for FXDQ-ND models.
standard accessory with 750

450 mm
200 mm
mm lift.

600 mm
Ceiling 240 mm 750 mm
and
above 700 mm

Specifications
Ceiling
Ceiling
Side view Top view
with drain pump FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE
MODEL
without drain pump FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1 MODEL FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1
Power consumption Power supply 1-phase, 220-240 V, 50 Hz
(FXDQ-PD/NDVE) 1 kW 0.086 0.089 0.160 0.165 0.181
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
Power consumption kW 2.2 2.8 3.6 4.5 5.6 7.1
kW 0.067 0.070 0.147 0.152 0.168
(FXDQ-PD/NDVET) 1 Power consumption 1 kW 0.072 0.075 0.078 0.180 0.180 0.196
Casing Galvanised steel plate Casing Galvanised steel plate
m3/min 8.0/7.2/6.4 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0 m3/min 8.7/7.6/6.5 9.0/8.0/7.0 10.0/9.0/8.0 15.0/13.0/10.5 20.0/16.0/12.5
cfm 282/254/226 371/335/300 441/388/353 583/512/459 cfm 307/268/229 318/282/247 353/318/282 530/459/371 706/565/441

Indoor Unit Lineup


External static pressure Pa 30-10 2
44-15 2 External static pressure Pa 30-10 2 50-20 2 40-20 2
Sound level (HH/H/L) 1 3 dB(A) 28/26/23 28/26/24 30/28/26 33/30/27 33/31/29 Sound level (HH/H/L) 1 3 dB(A) 33/31/29 34/32/30 35/33/31 37/35/33
Dimensions (H×W×D) mm 200×700×620 200×900×620 200×1,100×620 Dimensions (H×W×D) mm 200×700×450 200×900×450 200×1,100×450
Machine weight kg 23 27 28 31 Machine weight kg 17 20 23
Liquid (Flare) 6.4 9.5 Liquid (Flare) 6.4 9.5
Piping Piping mm
Gas (Flare) mm 12.7 15.9 connections Gas (Flare) 12.7 15.9
connections
Drain VP20 (External Dia. 26/Internal Dia. 20) Drain VP20 (External Dia. 26/Internal Dia. 20)
Note: Note:
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. •Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
1 : Values are based on the following conditions: FXDQ-PD: external static pressure of 10 Pa; FXDQ-ND: external static pressure of 15 Pa. 1 : Values are based on the following conditions: FXDQ20-32SP: external static pressure of 10 Pa; FXDQ40-63SP: external static pressure of 20 Pa.
2 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard".(Factory setting is 2 : External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory setting is 10 Pa for FXDQ20-32SP models and 20 Pa
10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND models.) for FXDQ40-63SP models.)
3 : The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). 3 : The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).

47 45
147 4648
148
Indoor Unit Lineup VRV Indoor Units

Middle Static Pressure Ceiling Mounted Duct Type FXSQ-PA

Middle static pressure and slim design Easy maintenance


Inspection and cleaning is facilitated by separating the
drain pipe and inspection opening and by the
drain pan maintenance check hole.

Separate drain pipe


and inspection opening

Drain pan maintenance check hole


Slim design Adjustable external static pressure
With a height of only 245 mm, installation is possible Using a DC fan motor, the external static pressure can An antibacterial treatment that uses silver ions has been
even in buildings with narrow ceiling spaces. be controlled within a range of 30 Pa* to 150 Pa.
applied to the drain pan, preventing the
growth of slime,mould and bacteria that
Adjustable external static pressure
cause blockages and odours.
245 mm (The lifespan of a silver ion cartridge depends
30 Pa* 150 Pa on the usage environment, but should be
changed once every two to three years.)
Easy installation
Set to low static Set to high static pressure for
245 mm

pressure when ducts advanced needs such as when During installation, even if the external static pressure
are short. using dampers and long ducts.

can be automatically adjusted to within the unit’s


Ceiling
external static pressure range.
duct length.

*30 Pa–150 Pa for FXSQ20-40PAVE controller during test operation. It is automatically


Standard DC drain pump 50 Pa–150 Pa for FXSQ50-125PAVE adjusted to the range between approximately ±10% of
DC drain pump is 50 Pa–140 Pa for FXSQ140PAVE
equipped as standard 850 mm
accessory with
850 mm lift.
Ceiling
Comfort MODEL FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100
Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6
Bottom suction possible control. Power consumption kW 0.058 1 0.066 1 0.101 1
0.075 1

Bottom suction is possible which facilitate installation Casing Galvanised steel plate

and maintenance. Wiring connections and (H/M/L)


m3/min 9/7.5/6.5 9.5/8/7 15/12.5/10.5 17/14.5/11.5
maintenance of control box can be done from under cfm 318/265/230 335/282/247 530/441/371 600/512/406 Note:
•Cooling: Indoor temp.: 27°CDB, 19°CWB,
the unit with an optional shield plate for side plate*, External static pressure Pa 30-150 (50) 2 50-150 (50) 2
automatically controlled in Outdoor temp.: 35°CDB, Equivalent piping
extending the degree of freedom for installation in the Sound level (H/M/L) dB(A) 33/30/28 34/32/30 36/33/30 34/32/29 length: 7.5 m, Level difference: 0 m.
accordance with the •Capacity of indoor unit is only for reference. Actual
ceiling. Dimensions (H×W×D) mm 245×550×800 245×700×800 245×1,000×800
difference between room Machine weight kg 25 27 35
capacity of indoor unit is based on the total
capacity index. (See Engineering Data Book for
Air conditioner temperature and set Liquid (Flare) 6.4 details.)
Joist
temperature. Piping •Sound level: Anechoic chamber conversion value,
connections Gas (Flare) mm 12.7 measured at a point 1.5 m downward from the
Drain VP25 (External Dia. 32/Internal Dia. 25) unit centre.
Air suction be selected with wired During actual operation, these values are
ceiling remote controller BRC1E63. MODEL FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE normally somewhat higher as a result of ambient
conditions.

Indoor Unit Lineup


Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
1: Power consumption values are based on
Air suction direction can be altered from rear to Btu/h 24,200 30,700 38,200 47,800 54,600 conditions of rated external static pressure.
Low operation sound level Cooling capacity 2:
bottom suction. (dB(A)) kW 7.1 9.0 11.2 14.0 16.0
a remote controller that offers thirteen
Power consumption kW 0.106 1
0.126 1
0.151 1
0.206 1
0.222 1
(FXSQ20-40PA), eleven (FXSQ50-125PA)
Rear suction Bottom suction FXSQ-PAVE 20/25 32 40 50 63 Casing Galvanised steel plate or ten (FXSQ140PA) levels of control. These
values indicate the lowest and highest possible
Shield plate for side plate* (Option) m3/min 21/17.5/14.5 23/19.5/16 32/27/22.5 37/31.5/26 39/33.5/28
(H/M/L) static pressures. The rated static
Sound level cfm pressure is 50 Pa.
(H/M/L) 33/30/28 34/32/30 36/33/30 34/32/29 36/32/29 741/618/512 812/688/565 1,130/953/794 1,306/1,112/918 1,377/1,183/988
External static pressure Pa 50-150 (50) 2 50-140 (50) 2
Sound level (H/M/L) dB(A) 36/32/29 37.5/34/30 39/35/32 42/38.5/35 43/40/36

FXSQ-PAVE 80 100 125 140 Dimensions (H×W×D) mm 245×1,000×800 245×1,400×800 245×1,550×800


Switch bottom plate Machine weight kg 35 37 46 47 52

Sound level Liquid (Flare) 9.5


(H/M/L) 37.5/34/30 39/35/32 42/38.5/35 43/40/36 Piping
*An optional shield plate for side plate is required if wiring connections and connections Gas (Flare) mm 15.9
maintenance of control box are needed from under the unit. This option is only Drain VP25 (External Dia. 32/Internal Dia. 25)
available for FXSQ20-125PA models.

14947
49 48150
50
IndoorUnit
Indoor UnitLineup
Lineup VRV Indoor Units

CeilingMounted
Ceiling MountedDuct
DuctType
Type FXMQ-PA
FXMQ-PA/ /MM

Middleand
Middle andhigh
highstatic
staticpressure
pressure MODEL
MODEL FXMQ20PAVE
FXMQ20PAVE FXMQ25PAVE
FXMQ25PAVE FXMQ32PAVE
FXMQ32PAVE FXMQ40PAVE
FXMQ40PAVE FXMQ50PAVE
FXMQ50PAVE
Power
Power supply
supply 1-phase,
1-phase, 220-240
220-240 V/220
V/220 V, 50/60
V, 50/60 Hz Hz
Btu/h
Btu/h 7,500
7,500 9,600
9,600 12,300
12,300 15,400
15,400 19,100
19,100
Cooling
Cooling capacity
capacity
kWkW 2.22.2 2.82.8 3.63.6 4.54.5 5.65.6
Power
Power consumption
consumption kWkW 1
0.056
0.056 1 1
0.060
0.060 1 1
0.151
0.151 1 1
0.128
0.128 1

Casing
Casing Galvanised
Galvanised steel
steel plate
plate
Using
Using a DC
a DC fanfan motor,
motor, thethe external
external static
static pressure
pressure can
can
bebe controlled
controlled within
within a range
a range of of
3030 Pa*
Pa* to to 200
200 Pa*.
Pa*. m3/min
m3/min 9/7.5/6.5
9/7.5/6.5 9.5/8/7
9.5/8/7 16/13/11
16/13/11 18/16.5/15
18/16.5/15
cfmcfm 318/265/230
318/265/230 335/282/247
335/282/247 565/459/388
565/459/388 635/582/530
635/582/530
Adjustable
Adjustable external
external static
static pressure
pressure External
External static
static pressure
pressure Pa Pa 30-100
30-100 (50)(50)
2 2 30-160
30-160 2
(100)
(100) 2 50-200
50-200 2
(100)
(100) 2

Sound
Sound level
level (HH/H/L)
(HH/H/L) dB(A)
dB(A) 33/31/29
33/31/29 34/32/30
34/32/30 39/37/35
39/37/35 41/39/37
41/39/37
Dimensions
Dimensions (H×W×D)
(H×W×D) mmmm 300x550x700
300x550x700 300x700x700
300x700x700 300x1,000x700
300x1,000x700
30Pa*
30 Pa* 200Pa*
200 Pa* Machine
Machine weight
weight kg kg 25 25 27 27 35 35
Liquid
Liquid (Flare)
(Flare) 6.46.4
Piping
Piping
Gas
Gas (Flare)
(Flare) mmmm 12.7
12.7
connections
connections
SetSet to low
to low static
static SetSet to high
to high static
static pressure
pressure for for
Drain
Drain VP25
VP25 (External
(External Dia,Dia, 32/Internal
32/Internal Dia,Dia,
25)25)
pressure
pressure whenwhen ducts
ducts advanced
advanced needs
needs such
such as as when
when
areare short.
short. using
using dampers
dampers andand long
long ducts.
ducts. MODEL
MODEL FXMQ63PAVE
FXMQ63PAVE FXMQ80PAVE
FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE
FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
FXMQ140PAVE
Power
Power supply
supply 1-phase,
1-phase, 220-240
220-240 V/220
V/220 V, 50/60
V, 50/60 Hz Hz
Btu/h
Btu/h 24,200
24,200 30,700
30,700 38,200
38,200 47,800
47,800 54,600
54,600
Cooling
Cooling capacity
capacity
conditions
conditions such
such asas duct
duct length.
length. kWkW 7.17.1 9.09.0 11.2
11.2 14.0
14.0 16.0
16.0
Power
Power consumption
consumption kWkW 0.138
0.138 1 1 0.185
0.185 1 1 0.215
0.215 1 1 0.284
0.284 1 1 0.4051
0.405 1
*30*30 Pa–100
Pa–100 PaPa
forfor FXMQ20PA-32PA
FXMQ20PA-32PA
Casing
Casing Galvanised
Galvanised steel
steel plate
plate
*30*30 Pa–160
Pa–160 PaPa
forfor FXMQ40PA
FXMQ40PA
*50*50 Pa–200
Pa–200 PaPa
forfor FXMQ50PA-125PA
FXMQ50PA-125PA m3/min
m3/min 19.5/17.5/16
19.5/17.5/16 25/22.5/20
25/22.5/20 32/27/23
32/27/23 39/33/28
39/33/28 46/39/32
46/39/32
*50*50 Pa–140
Pa–140 PaPa
forfor FXMQ140PA
FXMQ140PA cfmcfm 688/618/565
688/618/565 883/794/706
883/794/706 1,130/953/812
1,130/953/812 1,377/1,165/988
1,377/1,165/988 1,624/1,377/1,130
1,624/1,377/1,130
External
External static
static pressure
pressure Pa Pa 50-200
50-200 2
(100)
(100) 2 50-140
50-140 2
(100)
(100) 2
AllAll models
models areare only
only 300
300 mmmm
in in height
height andand
thethe
Sound
Sound level
level (HH/H/L)
(HH/H/L) dB(A)
dB(A) 42/40/38
42/40/38 43/41/39
43/41/39 44/42/40
44/42/40 46/45/43
46/45/43
weight
weight of of
thethe FXMQ40-140PA
FXMQ40-140PA hashas been
been reduced.
reduced.
Dimensions
Dimensions (H×W×D)
(H×W×D) mmmm 300×1,000×700
300×1,000×700 300×1,400×700
300×1,400×700
Drain
Drain pump
pump is is equipped
equipped asas Machine
Machine weight
weight kg kg 35 35 45 45 46 46
standard
standard accessory
accessory with
with 700700
mmmm Liquid
Liquid (Flare)
(Flare) 9.59.5
700
700 mmmm lift.lift. Piping
Piping
Gas
Gas (Flare)
(Flare) mmmm 15.9
15.9
Separate
Separate drain
drain pipe
pipe connections
connections
Ceiling
Ceiling
Easy
Easy maintenance
maintenance andand inspection
inspection opening
opening Drain
Drain VP25
VP25 (External
(External Dia,Dia, 32/Internal
32/Internal Dia,Dia,
25)25)
Inspection
Inspection and
and cleaning
cleaning is is •Cooling:
•Cooling: Indoor
Indoor temp.:
temp.: 27°CDB,
27°CDB, 19°CWB,
19°CWB, Outdoor
Outdoor temp.:
temp.: 35°CDB,
35°CDB, Equivalent
Equivalent piping
piping length:
length: 7.5 7.5 m, Level
m, Level difference:
difference: 0 m.0 m.
facilitated
facilitated byby separating
separating thethe •Capacity
•Capacity
•Sound
•Sound
of indoor
of indoor
level:
level:
unit unit
Anechoic
Anechoic
is only
is only
chamber
chamber
for reference.
for reference.
conversion
conversion
Actual
Actual
value,
value,
capacity
capacity
measured
measured
of indoor
of indoor
at a at
unit unit
a point
point 1.5 m
is based
is based
1.5downward
on total
on the
m downward
the total
fromfrom
capacity
capacity
the unit
the unit
index.
index. (See(See
centre.
centre.
Engineering
Engineering DataData
BookBook for details.)
for details.)

selected
selected with
with wired
wired remote
remote controller
controller BRC1E63.
BRC1E63. drain
drain pipe
pipe andand inspection
inspection 1: Power
1: Power
During
During actual
actual
consumption
consumption
operation,
operation,
values
values
these
these
are based
are based
values
values are normally
are normally
on conditions
on conditions of rated
of rated
somewhat
somewhat
external
external static
higher
higher as aas
static
a result
result
pressure.
pressure.
of ambient
of ambient conditions.
conditions.

Low
Low operation
operation sound
sound level
level opening
opening andand
bybythethe drain
drain panpan control.
control. These
These values
values indicate
indicate the lowest
the lowest andand highest
highest possible
possible static
static pressures.
pressures. The The rated
rated static
static pressure
pressure is 50isPa
50for
Pa FXMQ20-32PA
for FXMQ20-32PA
andand
100 100 Pa FXMQ40-140PA.
Pa for for FXMQ40-140PA.

maintenance
maintenance check
check hole.
hole. Drain
Drain panpan maintenance
maintenance
check
check hole
hole MODEL
MODEL FXMQ200MVE9
FXMQ200MVE9 FXMQ250MVE9
FXMQ250MVE9
DCDC
fanfan motor
motor is is used
used to to realise
realise energy-saving
energy-saving
Power
Power supply
supply 1-phase,
1-phase, 220-240
220-240 V/220
V/220 V, 50/60
V, 50/60 Hz Hz
operation.
operation. AnAn antibacterial
antibacterial treatment
treatment thatthat
usesuses silver
silver ions
ions hashas Btu/h
Btu/h 76,400
76,400 95,500
95,500
Cooling
Cooling capacity
capacity
Easy
Easy installation
installation been
been applied
applied to to
thethe drain
drain pan,pan, preventing
preventing thethe kWkW 22.4
22.4 28.0
28.0
growth
growth of of slime,
slime, mould
mould andand bacteria
bacteria thatthat cause
cause Power
Power consumption
consumption kWkW 1
1.294
1.294 1 1
1.465
1.465 1

during
during test
test operation.
operation. It is
It is automatically
automatically adjusted
adjusted to to
thethe blockages
blockages andand odours.
odours. (The
(The lifespan
lifespan of of a silver
a silver ionion Casing
Casing Galvanised
Galvanised steel
steel plate
plate
range
range between
between approximately
approximately ±10%
±10% of of
thethe rated
rated HHHH taptap cartridge
cartridge depends
depends ononthethe usage
usage environment,
environment, butbut m3/min
m3/min 58/50
58/50 72/62
72/62
should
should bebe changed
changed once
once every
every twotwoto to three
three years.)
years.)

Indoor Unit Lineup


cfmcfm 2,047/1,765
2,047/1,765 2,542/2,189
2,542/2,189
External
External static
static pressure
pressure Pa Pa 2
132-221
132-221 2 2
191-270
191-270 2

220220
V V 48/45
48/45
Sound
Sound level
level (H/L)
(H/L) dB(A)
dB(A)
Built-in
Built-in Drain
Drain Pump
Pump (Option)
(Option) 240240
V V 49/46
49/46
Pressure
Pressure Control
Control Housing
Housing thethe drain
drain pumppump inside
inside thethe unit
unit reduces
reduces thethe Dimensions
Dimensions (H×W×D)
(H×W×D) mmmm 470×1,380×1,100
470×1,380×1,100
External
External static
static pressure
pressure cancan space
space required
required forfor installation.
installation. kg kg
Machine
Machine weight
weight 137137
bebe easily
easily adjusted
adjusted using
using a a Without
Without drain
drain pump
pump With
With drain
drain pump
pump
change-over
change-over switch
switch inside
inside Liquid
Liquid (Flare)
(Flare) 9.59.5
Piping
Piping
thethe electrical
electrical boxboxto to meet
meet thethe GasGas (Brazing) mmmm
(Brazing) 19.1
19.1 22.2
22.2
0–2500–250 connections
connections
resistance
resistance in the
in the duct
duct mm mm
Drain
Drain PS1B
PS1B
system.
system. 470470
mm mm 470470
mm mm
FXMQ200/250MVE9
FXMQ200/250MVE9 222 mm
222 mm • Cooling:
• Cooling: Indoor
Indoor temp.:
temp.: 27°CDB,
27°CDB, 19°CWB,
19°CWB, Outdoor
Outdoor temp.:
temp.: 35°CDB,
35°CDB, Equivalent
Equivalent piping
piping length:
length: 7.5 7.5 m, Level
m, Level difference:
difference: 0 m.0 m.
25 mm25 mm • Capacity
• Capacity of indoor
of indoor unit unit is only
is only for reference.
for reference. Actual
Actual capacity
capacity of indoor
of indoor unit unit is based
is based on total
on the the total capacity
capacity index.
index. (See(See Engineering
Engineering DataData
BookBook for details.)
for details.)
• Sound
• Sound level:
level: Anechoic
Anechoic chamber
chamber conversion
conversion value,
value, measured
measured at a at a point
point 1.5 m1.5downward
m downward fromfrom the unit
the unit centre.
centre.
During
During actual
actual operation,
operation, these
these values
values are are normally
normally somewhat
somewhat higher
higher as aas a result
result of ambient
of ambient conditions.
conditions.
Indoor
Indoor unitunit Indoor
Indoor unitunit
1: Power
1: Power consumption
consumption values
values are based
are based on conditions
on conditions of standard
of standard external
external static
static pressure.
pressure.
2: External
2: External static
static pressure
pressure is changeable
is changeable to change
to change overover the connectors
the connectors inside
inside electrical
electrical box,box,
this this pressure
pressure meansmeans "Standard-High
"Standard-High static
static pressure".
pressure".

51151
49 52
50152
Indoor Unit Lineup VRV Indoor Units

Ceiling Mounted Duct Type FXMQ-P

Easy maintenance
High static pressure allows Inspection and cleaning is facilitated by separating
the inspection opening and the drain pan maintenance
check hole.

Easy installation
Adjustable external static pressure
Using a DC fan motor, the external static pressure can be During installation, even if the external static pressure Heat exchanger, drain pan and fan deck can be easily
controlled within a range of 50 Pa to 250 Pa. accessed and removed from bottom for maintenance.
can be automatically adjusted to within the unit’s external
Adjustable external static pressure static pressure range.

during test operation. It is automatically adjusted to the


range between approximately ±10 % of the rated HH

Set to low static Set to high static pressure for


pressure when ducts advanced needs such as when
are short. using dampers and long ducts.

To cater for easy installation

MODEL FXMQ200PVM FXMQ250PVM


Compact design Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Light weight by changing copper tube diameter of heat Btu/h 76,400 95,500
Cooling capacity
exchanger from 8 to 7 mm. kW 22.4 28.0
Power consumption kW 0.55 1 0.67 1

Casing Galvanised steel plate


m3/min 74/61/50 84/71/58
Drain pump kit (Option) cfm 2,612/2,153/1,765 2,965/2,506/2,047
Steeper gradient realises External static pressure Pa 50-250 (150) 2
50-250 (150) 2

FXMQ-PVM 200 250 Sound level (HH/H/L) dB(A) 42/38/35 44/40/37


drainage. Dimensions (H×W×D) mm 470x1,490x1,100 470x1,490x1,100
Reduce power High-lift is especially useful
Power consumption (kW) 0.55 0.67 Machine weight kg 95 105
consumption
for long length of drain
Liquid (Flare) 9.5
piping. Piping mm
Drain pump is offered as connections Gas (Flange) 19.1 22.2
Control of the 74/61/50 84/71/58
(HH/H/L) optional accessory with Drain BSP1"

Indoor Unit Lineup


(m3/min)
750 mm lift.
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Sound level •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Low operation 42/38/35 44/40/37 •Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
sound level (HH/H/L)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
(dB(A)) 1 : Power consumption values are based on conditions of rated external static pressure.

These values indicate the lowest and highest possible static pressures. The standard static pressure is 150 Pa.

53 51
153 52154
54
Indoor Unit Lineup VRV Indoor Units

Ceiling Suspended Type FXHQ-MA / A

FXHQ32 / 63 / 100MA FXHQ125 / 140A


Quiet operation
Slim body with quiet Uses quiet stream fan
Sound
absorption Flexible installation
and other quiet member
technologies.
(FXHQ32-100MA) [ Required installation space (mm) ]

Quiet stream fan 30 or more 30 or more


is produced Straightening vane

dB(A)
Sound level
Indoor unit
H M L *Water used in the test-run can be drained from the air
discharge opening rather than from the side as was formerly
FXHQ32MA 36 ----- 31
the case.
New 125 / 140 models provide greater capacity FXHQ63MA 39 ----- 34
for large spaces FXHQ100MA 45 ----- 37
The technology of the DC fan motor, wide sirocco fan, FXHQ125A 46 41 37 Drain pump kit (option) can be easily incorporated.
FXHQ140A 48 42 37
and quiet operation. Drain pipe connection can be done inside the unit.
Refrigerant and drain pipe outlets are at the same
opening.
Sophisticated design Easy maintenance
Flap neatly closes when 600
not in use. Condensation does not easily mm
form on and dirt does not cling to
Drain pump kit
It is easy to clean. Non-dew flap (built inside the unit)

Suitable for high ceilings All wiring and internal servicing can be done from
the unit. under the unit.
4.3 Oil-resistant plastic is used for the air suction grille.
m Easier piping work for rear side
environments. by removable frame

Switchable fan speed: 3 steps


MODEL FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE FXHQ125AVM FXHQ140AVM
3-step. Power supply 1-phase, 220-240 V/220 V, 50/60 Hz 1-phase, 220-240 V/220-230 V, 50/60 Hz
Btu/h 12,300 24,200 38,200 48,000 52,900
Cooling capacity
kW 3.6 7.1 11.2 14.1 15.5
Power consumption kW 0.111 0.115 0.135 0.168 0.181
Drain pump kit (option) includes a silver ion antibacterial Comfort Casing Sheet Metal / White (10Y9/0.5) Sheet Metal / White
agent that assists in preventing the growth of slime, Auto swing (up and down) and louvers (left and right by m3/min 12/-/10 17.5/-/14 25/-/19.5 34/26/20 36/27/20
bacteria, and mould that cause smells and clogging. hand) bring comfort to the room. cfm 424/-/353 618/-/494 883/-/688 1,200/918/706 1,271/953/706

Indoor Unit Lineup


Sound level (H/M/L) dB(A) 36/-/31 39/-/34 45/-/37 46/41/37 48/42/37
Dimensions (H×W×D) mm 195×960×680 195×1,160×680 195×1,400×680 235×1,590×690
Wireless LCD remote controller
Machine weight kg 24 28 33 41
A signal receiver
Liquid (Flare) 6.4 9.5
must be added to BRC7M56 Piping
connections Gas (Flange) mm 12.7 15.9
the indoor unit.
Drain VP20 (External Dia. 26/Internal Dia. 20)

• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
Signal receiver unit (Installed type) During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Wireless remote controller is supplied
in a set with a signal receiver.

55
15553 54156
56
Indoor Unit Lineup VRV Indoor Units

Wall Mounted Type FXAQ-A

Flat panel can be cleaned with only the single pass of a cloth across their smooth surface.
Flat panel can also be easily removed and washed for more thorough cleaning.

with your interior décor Flexible installation

Drain pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.

Height of drain-up

An invisible air intake


1,000 mm
An invisible air intake at the top of the unit at the top of the unit

Indoor unit
Drain pump kit
The louver closes automatically when the unit stops.

Enhanced comfort is achieved.

5 step discharge angles can be set by remote controller.

Discharge angle is automatically set at the same angle as previous operation when restart.

MODEL FXAQ20A FXAQ25A FXAQ32A FXAQ40A FXAQ50A FXAQ63A


H 9.1 9.4 9.8 12.2 15.0 19.0
m³/min
L 7.0 7.0 7.0 9.7 12.0 14.0

Lower sound level


Whisper quiet in operation, with sound levels as low as 28.5 dB(A)*
*Sound level for FXAQ20-32A

An ideal solution for a wide range of commercial spaces,

MODEL FXAQ20AVM FXAQ25AVM FXAQ32AVM FXAQ40AVM FXAQ50AVM FXAQ63AVM


Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
Wireless LCD remote controller Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity
A signal receiver must be added to the indoor unit. kW 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption kW 0.040 0.040 0.040 0.050 0.060 0.100

Indoor Unit Lineup


Casing Resin / White N9.5
m3/min 9.1/7.0 9.4/7.0 9.8/7.0 12.2/9.7 15.0/12.0 19.0/14.0
BRC7M676
cfm 321/247 332/247 346/247 431/342 530/424 671/494
Sound level (H/L) dB(A) 33.0/28.5 35.0/28.5 37.5/28.5 37.0/33.5 41.0/35.5 46.5/38.5
Dimensions (H×W×D) mm 290×795×266 290×1,050×269
Machine weight kg 12 15
Liquid (Flare) 6.4 9.5
Piping
connections Gas (Flange) mm 12.7 15.9
Drain VP13 (External Dia. 18/Internal Dia. 15)

MODEL FXAQ20A FXAQ25A FXAQ32A FXAQ40A FXAQ50A FXAQ63A


•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
H 33.0 35.0 37.5 37.0 41.0 46.5 •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Sound level dB(A) •Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
L 28.5 28.5 28.5 33.5 35.5 38.5
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

15755
57 56158
58
Indoor Unit Lineup VRV Indoor Units

Floor Standing Type FXLQ-MA Concealed Floor Standing Type FXNQ-MA

Designed to be concealed
Suitable for perimeter zone air conditioning in the perimeter skirting-wall

Floor Standing types can be hung on the wall for easier The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.
cleaning. Running the piping from the back allows the
unit to be hung on walls. Cleaning under the unit, where
The connecting port faces downward,
dust tends to accumulate, is considerably easier.
greatly facilitating on-site piping work.
Connecting
port

original design to prevent condensation also helps Refrigerant


prevent staining and makes cleaning easier. piping
Wall hanging Floor installation
* Applies also to Floor Standing type (FXLQ-MA).

equipped as standard accessory.


* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

MODEL FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE MODEL FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
Cooling capacity Cooling capacity
kW 2.2 2.8 3.6 4.5 5.6 7.1 kW 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption kW 0.049 0.090 0.110 Power consumption kW 0.049 0.090 0.110
Casing Ivory white (5Y7.5/1) Casing Galvanised steel plate
m3/min 7/6 8/6 11/8.5 14/11 16/12 m3/min 7/6 8/6 11/8.5 14/11 16/12
cfm 247/212 282/212 388/300 494/388 565/424 cfm 247/212 282/212 388/300 494/388 565/424
220 V 35/32 38/33 39/34 40/35 220 V 35/32 38/33 39/34 40/35
Sound level (H/L) dB(A) Sound level (H/L) dB(A)
240 V 37/34 40/35 41/36 42/37 240 V 37/34 40/35 41/36 42/37
Dimensions (H×W×D) mm 600×1,000×222 600×1,140×222 600×1,420×222 Dimensions (H×W×D) mm 610×930×220 610×1,070×220 610×1,350×220
Machine weight kg 25 30 36 Machine weight kg 19 23 27
Liquid (Flare) 6.4 9.5 Liquid (Flare) 6.4 9.5
Piping mm 12.7 15.9 Piping mm 12.7 15.9
Gas (Flare) connections Gas (Flare)
connections
Drain 21O.D. Drain 21O.D.

•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.

Indoor Unit Lineup


•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) •Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

61
15957
59 62
58160
60
Indoor Unit Lineup VRV Indoor Units

Floor Standing Duct Type FXVQ-N Clean Room Air Conditioner FXB(P)Q-P

Flexible interior design for each tenant. Suitable for hospitals and
other clean spaces

conditioning evenly in spacious areas.


Easily provides the high cleanliness Select the air flow system and installation method to
Adding the plenum chamber (option) allows for simple environment required by various industries match the layout and purpose of the room
* Note that the operation sound increases by approximately 5dB(A). Daikin’s clean room air conditioners are specially designed to Two types of clean room air conditioners are available – an
achieve an environment cleanliness class 10,000. integrated unit model and a separate outlet unit model.
These air conditioners easily realize a cleanliness-class It is also possible to configure the air flow system to ceiling
The high static pressure type driven by the belt drive system allows for use environment and help create a proper environment of intake or floor-level intake according to the panel selected.
hospitals, food and beverage factories, electronics factories,
installation is possible. and other spaces that require clean air. to any room layout or use.
Design with high maintainability that allows major services and maintenance
services to be performed at the front.
Instances of installation by type (for a hospital)

accessory. * 8 hr/day, 26 day/month. For dust concentration of 0.15 mg/m3


Ceiling intake type Floor-level intake type
Type
(gentle wind distribution/high cleanness class model)

Construction work is simple and a ceiling installation is possible. Easy to increase the cleanness and air-conditioning effect.
Outdoor air intake mode is useable as an All-fresh (using outdoor air only) system Return + Outdoor air mixed system
Features

outdoor-air processing air conditioner. Outside Outside


Circulated air

Air Air Cleanness class*1 100,000 to 10,000 10,000


*When using the unit as an outdoor-air processing unit, there are conditioning conditioning
Engineering Data Book. Wind speed 1.0m/s or higher Approximately 0.5m/s

Outdoor air Outdoor air z Concentrated air conditioning centered z Total air conditioning with an emphasis
introduction introduction directly under the unit on cleanliness
z Easy installation
Intake
* Air introduced from the outside and circulated air must be mixed in the Integrated (sourced locally)
air conditioner primary side before introduction into the air conditioner. outlet unit
model

Applications: Surgery prep rooms, recovery rooms, nurse stations, etc. Applications: Operating theatres, delivery rooms, etc.
Blow
method
MODEL FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 FXVQ400NY1 FXVQ500NY1 FXVQ500NY16 z Somewhat concentrated air conditioning z Total air conditioning with an emphasis
centered directly under the outlet on cleanliness
Power supply 3-phase 4-wire system, 380–415 V, 50 Hz z Can provide air conditioning in rooms with z Maintenance possible from a different
irregular shapes Outlet Air room
Separate
Btu/h 47,800 76,400 95,500 154,000 191,000 outlet unit
unit conditioner Intake
Cooling capacity (sourced locally)

kW 14.0 22.4 28.0 45.0 56.0 model

Power consumption kW 0.53 1.33 1.61 3.97 2.62 4.70


Applications: CCU*2, sterile rooms, etc. Applications: Premature nurseries, newborn nurseries, ICU*3, etc.
Casing colour Ivory white (5Y7.5/1)
Dimensions (H×W×D) mm 1,670×750×510 1,670×950×510 1,670×1,170×510 1,900×1,170×720 1,900×1,470×720
Machine weight kg 118 144 169 236 281 306 *2. CCU (Cardiac Care Unit). A ward dedicated to the admission of patients with myocardial infarctions and other heart diseases.
*3. ICU (Intensive Care Unit). A ward for the careful treatment and nursing of patients with serious illnesses, injuries, or recovering from operations.
Sound level *1 dB(A) 52 56 60 65 62 66
Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing)

Indoor Unit Lineup


Piping Can be easily installed in
Gas mm 15.9 (Brazing) 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing)
connections
Drain mm Rp1 (PS1B internal thread) existing buildings approximately 0.5m/s
Type
kW 5.5
A simple structure makes it easy to z
Motor output 0.75 1.5 3.7
realize a highly clean environment with (operating theatre)
m /min
3
43 69 86 134 165 172 Outlet (m3/sec)
the same installation work as for a typical 3m 0.6
Fan cfm 1,518 2,436 3,036 4,730 5,825 6,072 air conditioner. Can be easily installed in eliminating the feeling of drafts. 0.5
External static pressure *2 Pa 152 217 281 420 142 390 new buildings, existing structures, and Broadly air-conditions the room with a 0.4

Drive system Belt drive system refurbishments. 0.3


0.2
comfortable environment. Intake
0.1
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
0 0
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) with the integrated outlet model. 3m 0 Operating Intake 3m
*1: Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value). table

*2: The value is the external static pressure with standard pulley.

63 59
61
161 64
60162
62
Indoor Unit Lineup VRV Indoor Units

Clean Room Air Conditioner FXB(P)Q-P

Filtration Type Integrated outlet unit model Separate outlet unit model
Indoor unit FXBQ40PVE FXBQ50PVE FXBQ63PVE FXBPQ63PVE
MODEL
(sold separately) Outlet unit Integrated with the indoor unit BAF82A63
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h 15,400 19,100 24,200
Cooling capacity
kW 4.5 5.6 7.1
Power consumption kW 0.31 0.45
„ 70% by gravimetric method
99.97% by DOP method *5
Indoor unit weight kg 140 *3 185 *3 120 *6
Casing Galvanised steel plate
m3/min 19.5/17.5 26/22.5
etc. Installation example (in a medical facility) (H/L)
cfm 688/618 918/794
Sound level (H/L) *4 dB(A) 44/42
* It may not be possible to maintain cleanliness in rooms with low air tightness. Dimensions (H×W×D) mm 492×1,788×1,000 492×1,788×1,300 492×1,078×1,300
Outlet unit weight kg – 65 *3
Liquid (Flare) 6.4 9.5
Piping 12.7 15.9
Gas (Flare) mm
Antibacterial connections
Drain PT1B
Suppresses the propagation of bacteria in the duct with a proprietary antibacterial coating Filter(Option) BAFH82A50 BAFH82A63
Panel Ceiling intake type Model BYB82A50C BYB82A63C BYB82A63CP
(Option) Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP
organic antibacterial material that is effective against germs) that prevents mould.
This enhances the antibacterial properties of the duct. •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
An antibacterial treatment using a silver-based organic substance reduces mould. Fan •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)

*2: HEPA The is 99.97 %.

*4: Anechoic chamber conversion value under JIS B 8616 test conditions. Value usually increases slightly in practice due to surrounding conditions.
*5 : The clean room air conditioner does not support DOP testing (leak test) based on GMP standards (Standards for Manufacturing Control and
near the intake, cleaning performance is further enhanced. Quality Control for Medical Devices ) due to slight leakage at time of product installation.
*6: Weight including panel.
* Please be aware that antibacterial products suppress the propagation of bacteria but do not have a sterilizing effect.
Also, mould may grow in places where dust or soot accumulates. *In the case of an installation in an operating theatre etc. where an air conditioner malfunction may have serious consequences, please build
Outlet panel Sheet steel Intake panel in redundancy with two or more outdoor units.
law (Act on the Evaluation of Chemical Substances and Regulation of Their Manufacture, etc) is used for the
antibacterial material.
(punched) drain pan (punched)
(antibacterial treated)

Labor-saving
z Because the ceiling intake type provides concentrated air conditioning that blows directly under z
Easy access from underneath unit provides easy maintenance the outlet. Accordingly, please be aware of the following. type in the following kind of
locations.
• In the case of utilization in a hospital, some patients may be susceptible to cool drafts, so please ensure that they do • Locations in which heating of the
· Fan · Drip pan inspection not come directly under the outlet.
replacement inspection Warning • Install multiple units using two or more outdoor unit systems for installations to rooms such as operating rooms where
lower part or the entire room is
important.
of perspectives, including a service access system that eliminates the necessity the failure of the air conditioner may have serious consequences. • Locations necessitating a
• In order to maintain static pressure in a room, the indoor fan continues to operate even when an abnormality occurs
for service panels. due to the thermostat shutting off, defrost operation, protection device operation, or similar issue.
particularly high cleanliness
factor and in which there are
• When incorporating outdoor air from the fresh air intake, install a damper or similar device to the duct routing and many people.
have it interlocked with the indoor fan so that the outdoor air is shut out when the fan stops.
air conditioner operation.

• When using gas to disinfect hospital operating rooms where this unit is installed, stop operation and cover the air inlet

Indoor Unit Lineup


and outlet with plastic sheets to prevent the gas from reaching and damaging the air conditioner.

Quiet
All models incorporate an industry-leading quiet
design, operating at under 41dB
Operating noise is substantially reduced by employing a proprietary

low-fan speed operation).

65 61
163
63 66
62164
64
Indoor Unit Lineup Residential Indoor Units with Connection to BP Units

Slim Ceiling Mounted Duct Type (A)


FDKS-EA/C(A) Wall Mounted Type FTKJ-N

Standard accessory
Elegant appearance
Note: Remote controllers
other than the standard
accessory wireless remote
with European style
controller cannot be used. Standard
accessory

Elegant Appearance with Curved Panel


Slim and smooth design suits your shallow ceiling The sleek design of the FTKJ-N indoor unit features
a uniquely European style. This elegant body from blowing directly to a person’s body. During cooling
Models in the FDKS-EA series are only 700 mm in width Low operation sound level (H/L/SL) houses state-of-the-art technology which delivers
and 21 kg in weight, made the installation easy in limited
FDKS25 FDKS35 FDKS50 FDKS60 superior performance. impacts.
spaces. With only 200 mm in height, all models can be
installed in rooms with as little as 240 mm depth between
The FTKJ-N series
35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A) offers a versatile
the drop ceiling and ceiling slab, making them ideal for
even shallow ceilings. choice for
Home Leave Operation prevents large increase or decrease in the
FDKS-EA indoor temperature by continuing operation* while someone is sleeping
home-owners,
Great for
or left the house. This means that an air-conditioned welcome awaits designers and
hotel use!
when someone wakes up or returns. It also means that the indoor architects alike.
temperature can quickly return to the preferred comfort setting.
* Home Leave Operation can set to any temperature from 18 to 32˚C for cooling
200 mm operation.
* Home Leave Operation function must be set by using the remote controller when going
Only 700 mm to sleep or leaving the house, and after waking up or returning home. Two-Area Intelligent Eye
circulates air to every part of a room for uniform cooling,
FDKS25EA FDKS35EA FDKS25CA FDKS35CA Air discharge duct* Suspension bolt* Suction duct*
Dimensions (H x W x D) 200 x 700 x 620 mm 200 x 900 x 620 mm Air discharge grille*
even for large spaces.
Weight 21 kg 25 kg If there is no movement in a room for 20 minutes,
8.7 m3/min 9.5 m3/min 10 m3/min AIR
AIR 240 mm Intelligent Eye automatically adjusts the set push both the Vertical
External static pressure 30 Pa 40 Pa temperature by approximately 2°C to save energy. and Horizontal
Chamber Auto-Swing buttons.
Signal receiver wire Air suction Area 1 Area 2 Area 1 Area 2
240 mm Length = 1,900 mm Signal
grille*

Note:
receiver AIR
AIR * Locally obtained parts swing in turn.
1. To prevent an increase of the operation noise, avoid installing the air suction
grille directly below the suction chamber.
2. Grilles, piping connections, ducts, and installation parts should be obtained
locally. Slim Ceiling Mounted Duct type models do not have drain-up pumps.
3. The signal receiver unit must be located near the air suction inlet, because the
directed away from him/her. directed away from him/her.
unit includes a sensor that detects room temperature.
expands the comfort zone.

Signals from the wireless remote controller are


transmitted to the signal receiver.

MODEL FTKJ25NVMW FTKJ25NVMS FTKJ35NVMW FTKJ35NVMS FTKJ50NVMW FTKJ50NVMS


MODEL FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz

Indoor Unit Lineup


Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Front panel colour White Silver White Silver White Silver
m3/min (cfm) 8.7 (307) 9.5 (335) 10.0 (353) 12.0 (424) 16.0 (565)
m /min(cfm) 8.9 (313) 10.9 (385)
Sound levels (H/L/SL)* dB (A) 35/31/29 37/33/31 38/34/32
Sound levels (H/L/SL) dB (A) 38/25/19 45/26/20 46/35/29
Fan speed 5 steps, quiet and automatic
Fan speed 5 steps, quiet and automatic
Temperature control Microcomputer control
Dimensions (H×W×D) mm 200×700×620 200×900×620 200×1,100×620 Temperature control Microcomputer control
Machine weight kg 21 25 27 30 Dimensions (H×W×D) mm 303x998x212
Liquid (Flare) 6.4 Machine weight kg 12
Piping Gas (Flare) mm 9.5 12.7 Liquid (Flare) 6.4
connections
Drain VP20 (External Dia. 26/Internal Dia. 20) Piping
mm 9.5 12.7
connections Gas (Flare)
Heat insulation Both liquid and gas pipes 18.0
Drain
External static pressure Pa 30 40
Heat insulation Both liquid and gas pipes
Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa
for FDKS-C(A). Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C(A).

16563
65 66
64166
Indoor Unit Lineup Residential Indoor Units with Connection to BP Units

Wall Mounted Type FTKS-D/B/F BP Units for Connection to Residential Indoor Units
FTKS25D / FTKS35D

Standard accessory*

FTKS50B

Standard accessory*

FTKS50F / FTKS60F / FTKS71F The BP units can be


installed inside the ceiling.

Standard accessory*
* Remote controllers other than the standard accessory
wireless remote controller cannot be used.
Connectable to Residential Indoor Units Quiet Operating Sound
BP units allow VRV systems to be connected to Daikin’s Expansion valves tend to create refrigerant passing
Wall Mounted indoor units achieve quiet sound levels Titanium Apatite Deodorising Filter stylish and quiet residential indoor units. noise. However, this noise can be reduced by installing
of 22 dB (A). (H/L/SL)
apatite effectively adsorbs odours and allergens, ceiling or roof-space far from an indoor unit.
FTKS25D FTKS35D FTKS50F FTKS60F FTKS71F
as well as deodorises odours. Some Daikin residential indoor units also provide
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A) minimum sound levels of just 19 dB(A). Together these
Intelligent Eye with its infrared sensor features ensure your system continues to operate as
automatically controls air conditioner operation quietly as possible.
according to human movement in a room. When Titanium Apatite
Deodorising Filter
there is no movement, it adjusts the temperature BP unit
by 2˚C for energy savings.
Min. sound
level
19 dB(A)

When you are in the room When you go out

combines Vertical
and Horizontal
Auto-Swing to
circulate air to every
part of a room for
uniform cooling of adsorption of odours and allergens and deodorisation
MODEL BPMKS967A3 BPMKS967A2
even large spaces. Power supply 1-phase, 220-240 V/220 -230 V, 50/60 Hz
A uniform temperature of odours are only effective for substances which are Number of ports 3 (connectable to 1-3 indoor units) 2 (connectable to 1-2 indoor units)
* This function is available for is achieved throughout
the entire room. directly attached to the Titanium Apatite Deodorising Power consumption W 10
FTKS50/60/71F.
Filter. Running current A 0.05
Dimensions (HXWXD) mm 180X294 (+356*)X350
BPMKS967A3

Indoor Unit Lineup


Machine weight kg 8 7.5
MODEL FTKS25DVM FTKS35DVM FTKS50BVMA FTKS50FVM FTKS60FVM FTKS71FVM Number of wiring connections
3 for power supply (including earth wiring), 2 for power supply (including earth wiring),
2 for interunit wiring (outdoor unit-BP, BP-BP), 2 for interunit wiring (outdoor unit-BP, BP-BP),
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz 4 for interunit wiring (BP-indoor unit) 3 for interunit wiring (BP-indoor unit)
Front panel colour White Main 9.5X1
Piping Liquid mm
m3/min (cfm) 8.7 (307) 8.9 (314) 11.4 (402) 14.7 (519) 16.2 (572) 17.4 (614) Branch 6.4X3 6.4X2
connections
Sound levels (H/L/SL) dB (A) 37/25/22 39/26/23 44/35/32 43/34/31 45/36/33 46/37/34 (Brazing) Main 19.1X1
Gas mm
Fan speed 5 steps, quiet and automatic Branch 15.9X3 15.9X2
Heat insulation Both liquid and gas pipes
Temperature control Microcomputer control
Connectable indoor units 2.5 kW class to 7.1 kW class
Dimensions (HXWXD) mm 283X800X195 290X795X238 290X1,050X238
BPMKS967A2 Min. rated capacity of kW 2.5
Machine weight kg 9 12 connectable indoor units
Liquid (Flare) 6.4 Max. rated capacity of kW 20.8 14.2
Piping connectable indoor units
Gas (Flare) mm 9.5 12.7 15.9
connections
18.0 Note: * Total auxiliary piping length.
Drain
Heat insulation Both liquid and gas pipes

16765
67 66168
68
Air Handling Unit Indoor
Air Unit Lineup
Treatment Equipment Lineup

Air Handling Unit Ceiling Mounted Duct Type


Integrate your air handling unit in a total solution for large size A recent trend rapidly gaining popularity is for air treatment to be required
Daikin’s air treatment systems as well as air conditioning. Daikin’s Outdoor-Air Processing Unit can
spaces such as factories and large stores. creating
Middleaand higher combine fresh air treatment and air conditioning, supplied from a single
high static pressure
system. It adjusts the temperature of air from outdoors using a fixed
air quality environment
allows for flexible duct design
discharge temperature control. Along with Outdoor-Air Processing Units,
Components we also offer Heat Reclaim Ventilator systems. The Heat Reclaim
AHUR of Indoor Air Quality Ventilator VAM-GJ series units in particular have been praised for their
Capacity range : 6 – 120 HP
Using a DC fan motor, the external staticcompactness,
pressure can energy conservation and extensive operation range of
be controlled within a range of 30 Pa* to outdoor 200 Pa*.temperatures. This series provides higher enthalpy efficiency,
Ventilation Humidification due to the greatly enhanced performance of the thin film element.
Adjustable external static pressure
Furthermore, improved external static pressure offers more flexibility for
installation. The Heat Reclaim Ventilator VKM-GA series units, equipped
30 Pa*
Air Processing* 200 Pa* with a DX-coil, provide further advanced features, such as temperature
adjustment to suit conditions indoors and to prevent hot air from blowing
Set to low static
on people directly during cooling operation. The series also realises
Set to high static pressure for
*Refers to processing outdoor air close to indoor
pressure and distributing it indoor. advanced needssignificant
when ducts
temperatures such as whenenergy savings by exercising heat recovery.
are short. using dampers and long ducts.

Comfortable airflow is achieved in accordance with


conditions such as duct length.
*30 Pa–100 Pa for FXMQ20P-32PA Heat Reclaim Ventilator
Easy design and installation *30 Pa–160 Pa for FXMQ40PA Outdoor-Air
Processing Unit
*50 Pa–200 Pa for FXMQ50PA-125PA VKM-GA Type VAM-GJ Type
The system is easy to design and install since no additional water
*50 Pa–140 Pa for FXMQ140PA
systems such as boilers, tanks and gas connections etc are
required. All models are only 300 mm in height and Humidification
Ventilation
the Ventilation Humidification Ventilation Humidification
weight of the FXMQ40-140PA has been reduced.
Inverter controlled units Air Processing* Air Processing*
Air Processing*
Control of air temperature
Drain pump is equipped as
standard accessory with 700 mm
via standard Daikin wired remote control for standard series
700 mm lift.
Separate drain pipe
Easy maintenance
Ceiling
and inspection opening
Control of the airflow rate can be selected from 3-step Inspection and cleaning is
control and Auto. Auto airflow rate control can be facilitated by separating the
System overview Refrigerant Piping Connectable
selected with wired remote controller BRC1E63.
Connections
Connectable
drain pipe and inspection
Not connectable
with VRV Wiring Connectable Connectable Connectable
Low operation sound level
systems
opening and by the drain pan
After-cool Control Available Available
maintenance check hole. Not available
Energy-efficient Drain pan maintenance

Air Handling Unit


Heat Exchange Element — Energy savings obtained Energy savings obtained
check hole
DC fan motor is used to realise energy-saving
High Efficiency Filter Option Option Option
operation. An antibacterial treatment that uses silver ions has
Ventilation System Air supply only Air supply & air exhaust Air supply & air exhaust
Easy installation been applied to the drain pan, preventing the
Airflow
Power Supplyrate can be controlled 220-240
using a V,
remote
50 Hz controller growth
220-240 V, 50ofHz
slime, mould and bacteria
220-240 thatV, cause
V/220 50 Hz/60 Hz
Air handling unit
blockages and odours. (The lifespan ofma3silver
3
during test operation. It is automatically adjusted to the 150 /h ion
250 m /h
range between approximately ±10% of the rated HH tap cartridge depends on the usage environment, but
350 m3/h
airflow for FXMQ20P–125PA. should
500 m3/hbe changed once every two500 to three
m3/h years.)
Airflow Rate 650 m3/h
3
800 m /h 800 m3/h
1000 m 3
/h 1000
Built-in Drain Pump (Option) m3/h
1080 m /h Simplified Static
3
1500 m3/h
1680 m3/h Pressure Control Housing the drain pump inside3 the unit reduces the
2000 m /h
space required for installation.
2100 m3/h External static pressure can

Air Treatment
Equipment Lineup
be easily adjusted using a Without drain pump With drain pump
Daikin communication wire (F1, F2 communication) Liquid pipe *Refers to processing outdoor air close to indoor temperatureschange-over
and distributing it indoor.
switch inside
Other communication wire Gas pipe the electrical box to meet the 0–250
resistance in the duct
mm

Daikin air handling units can be connected to VRV systems. FXMQ200/250M system. 470 mm 470 mm
222 mm
This combination can be built to order as a system. Outdoor air series is also possible. Please contact your 25 mm
local sales office for details.
Indoor unit Indoor unit

69 67
169 70
68170
Air Treatment Equipment Lineup
Outdoor-Air Processing Unit
• The unit introduces outdoor air and adjusts ࠮ High-performance
࠮;OL\UP[PU[YVK\JLZV\[KVVYHPYHUKHKQ\Z[Z • High-performance
filters with dust
filters
collection
with dust collection
the outdoor air thetemperature
outdoor airvia temperature
fixed discharge
via fixed discharge efficiencies (JIS
efficiencies
calorimetry)
(JISof
calorimetry)
90% and 65%
of 90%
are and 65% are
temperature control,
temperature
therebycontrol,
reducing
thereby
the air
reducing the air also availablealso
as options.
available as options.
Combine fresh air treatment and air conditioning, supplied from a single system. conditioning load.conditioning load.
* The system can *operate
The system
with can
outdoor-air
operatetemperatures
with outdoor-air
ranging For the VRV system,
temperatures ranging For the VRV
a system, a
Lineup MYVT[V͵/LH[PUNWLYMVYTHUJLPZZVTL^OH[HK]LYZLS`
from -5 to 43℃. Heating performance is somewhat adversely variety of control
variety
systems
of control systems
Model Name FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 HMMLJ[LK^OLU[OLV\[KVVYHPY[LTWLYH[\YLPZ͵VYILSV^
affected when the outdoor-air temperature is 0℃ or below. can be deployed, can be
including
deployed, including
Capacity Index 125 200 250 * >OLUZOPWWLKMYVT[OLMHJ[VY`[OL[OLYTVZ[H[PZZL[H[͵
* When shipped from the factory, the thermostat is set at 18℃
remote control remote
from control from
for cooling. The set
fortemperature
cooling. Thecan
set be
temperature
varied within
canthe
be range
variedof
within the range of
13–25℃ during cooling operation, in the local setting modedistances
¶͵K\YPUNJVVSPUNVWLYH[PVUPU[OLSVJHSZL[[PUNTVKL\ZPUN using of up
distances
to 500 m. of up to 500 m.
the wired remote the
controller.
wired remote
The temperature,
controller. The
however,
temperature,
is not however, is *not Group control is*not
Group
possible
control
between
is not possible between
BRC1E63 BRC1E63
displayed on the remote
displayed controller.
on the remote controller. this unit and standard
this unit
typeand
indoor
standard Navigation
type indoorRemoteNavigation
Controller Remote Controller
* While in machine* While
protection
in machine
mode and protection
depending
modeonandoutdoor
depending
air on outdoor air Remote controllers
units. units. Remote
connectcontrollers
to (Wired connect tocontroller)
remote (Wired remote controller)
conditions, discharge
conditions,
air temperature
dischargemayair temperature
not be at themay each unit separately. (option)
set not be at the set each unit separately. (option)
temperature. temperature.
* The fan stops when
* Theoperating
fan stopsinwhen
defrosting,
operating
oil returning
in defrosting,
and hot ࠮;OL¸ZLSMKPHNUVZPZM\UJ[PVU¹PUKPJH[LZ[OLVJJ\Y
oil returning and hot • The “self-diagnosis function” indicates the occur-
Fresh air treatment and air conditioning start operations. The
startfan
operations.
may stopThe duefan
to mechanical
may stop due protection
to mechanical protection
rence and nature rence ofand
abnormalities
nature of abnormalities
in the systemin the system
can be achieved with a single system by control. control.
by displaying by
codes
displaying
on the codes
remoteon
controller.
the remote controller.
using heat pump technology—without the
usual troublesome air supply and air ࠮ Ceiling mounted
• Ceiling
ductmounted
units with
duct
three
units
different ࠮ A central control
with three different • A central
system control system
discharge balance design. Fan coil units capacities arecapacities
available. are
These
available.
can beThese
connected
can be connectedcompatible withcompatible
the VRV with the VRV
for air conditioning and an outdoor-air to VRV seriesto outdoor
VRV series
unitsoutdoor
to meet units
a variety
to meet a variety system can be system
installed.
can be installed.
processing unit can be connected to the of different requirements.
of different requirements. * It is not possible* to
It is
change
not possible
the to change the
same refrigerant line. This results in discharge air temperature
dischargesettings
air temperature settings
enhanced design flexibility and significant Airflow rate from the central control
from thesystem.
central control system.
reduction in total system costs. FXMQ125MFV1FXMQ125MFV11,080 m3/ h 1,080 m*3/Do
h not associate* Do
thisnot
equipment
associate this equipment
Combination with VRV system FXMQ200MFV1FXMQ200MFV11,680 m3/ h 1,680 m3/inh areas which standard
in areasindoor standard indoorDCS302CA61
whichunits units DCS302CA61
are installed, as central
are installed,
control as central Central remote controller
control Central remote controller
FXMQ250MFV1FXMQ250MFV12,100 m3/ h 2,100 m3/ h (option) (option)
cannot be used withcannot
them.be used with them.

࠮6W[PVUHSLX\PWTLU[PUJS\KLZSVUNSPMLMPS[LYZ
• Optional equipment includes long-life filters. ࠮>P[O[OLVRV• With
system,
the VRV
the equipment
system, the
employs
equipment
the employs the
¸Z\WLY^PYPUNZ`Z[LT¹ZV[OH[[OL^PYPUNSPURPUN[OL
“super wiring system” so that the wiring linking the
࠮*VTWH[PISL^P[OV\[KVVY[LTWLYH[\YLZMYVT͵[V
• Compatible with outdoor temperatures from -5℃ to and outdoor
indoor indoor units
and outdoor
can alsounits
be utilised
can also
forbe utilised for
͵ 43℃. central control.
central control.
Air conditioning and outdoor air processing can be accomplished using a single system.
Note: Note:
Usage LimitationsUsage Limitations
* Linked control of* Linked
the productcontroland ofthe
theHeat
product Reclaim
and the
Ventilator
Heat Reclaim
is Ventilator is

id 32
id 32
not supported. not supported.

ity

ity
VRV Outdoor Units

lat dit ive

lat dit ive


Re umi elat

Re umi elat
* This equipment *isThis intended
equipment
for theistreatment
intended for of outdoor
the treatment
air only.of outdoor air only.

m
ive y

ive y
Hu

Hu
H R

H R
0%

0%
It is not to be used It is
fornot
maintaining
to be used indoor
for maintaining
air temperature,
indoor air temperature,

10

10
Installing or use with
Installing
standard or use
indoor
withunits.
standard
Be sureindoor
to position
units. Bethe sure to position the

%
re re

90

90
ra
tu
ra
tu air discharge openings
air discharge
of the product
openings in positions
of the product
whereinthepositions
airflow where the airflow
Outdoor-Air Processing Unit p e p e
m
Te )
Supported m Cooling Supported Cooling will not blow on people
Te B) will notdirectly.
blow onWhen people outdoor-air
directly. When
processing
outdoor-air
is processing is
ir Operationir
o r A ͵> o r A ℃W Range Operation Range
in excess, the unitinswitches
excess, the to thermo-off
unit switches mode, to thermo-off
and outdoor mode,
air and outdoor air
 (
Indoor Unit Indoor Unit t do t do
Ou Ou flows into the room flows
directly.
into the room directly.
tive * Fortive outdoor ducts,
* Forbeoutdoor
sure to ducts,
providebeheat sureinsulation
to provide to heat
preventinsulation to prevent
Fan Fan idity la
Re y it y la
Re ity
Hum mid 0% mcondensation. condensation.
Operation Operation
iv e 2 0% miditive Hu 2 id
Rela
t HuRelat Hu
Heating
% tin
30ea
H g 30% * Group control of* theGroup product
controland ofstandard
the product indoor
andunits
standard
is notindoor units is not
Supported e Supported e
Operation
Ra ng
Operation
Ra ng supported. A separatesupported.
remote A controller
separate remote
should controller
be connected should to be connected to
Air Outdoor –5 –5 15 19 15 19
(33.5) 43 (33.5)
individual unit. individual unit.
43
Conditioning Air Supply * The system will *not The operate
systeminwill fannot
modeoperate
wheninthe fanoutdoor
mode when air the outdoor air
Note: Note:
[LTWLYH[\YLPZ͵VYILSV^
temperature is 5℃ or below.
1. The data shown in1.the
Thegraph
data illustrates
shown in the the graph supported
illustrates operationthe supported
ranges under operation ranges under
the following conditions.
the following conditions. * If the product is *utilised
If the product
to operate is utilised
24 hours to operate
a day, maintenance
24 hours a day, maintenance
Indoor and Outdoor Indoor
Unit and Outdoor Unit (part replacement,(part etc.)replacement,
must be performed etc.) must periodically.
be performed periodically.
Effective piping length:
Effective
7.5 m piping length: 7.5 m * Temperature setting* Temperature
and Powersetting Proportional
and Power Distribution
Proportional
(PPD)Distribution (PPD)
Height differential: 0Height
m differential: 0 m
are not possible evenare notif the
possible
intelligent
evenTouch
if the Controller
intelligent Touch
or the Controller or the
2. The discharge temperature
2. The discharge
can be temperature
set using thecan remote be set controller.
using theHowever, remote controller. However,
the actual temperaturethe may
actual
nottemperature
match the temperature may not match setting under some setting under intelligent
the temperature some Touch Manager
intelligentisTouch
installed.
Manager is installed.
circumstances due to circumstances
the outdoor-air due processing
to the outdoor-airload or mechanicalprocessing load or mechanical * The remote controller
* The remote
wired tocontroller
the outdoor-air
wired toprocessing
the outdoor-air
unit processing unit
Connection Conditions protection controls. protection controls. must not be set as must
the not
master
be setremote
as thecontroller.
master remoteOtherwise,
controller. Otherwise,
3. The system will not
3. The
operate
system
in fan willmode not operate
when the in fan outdoormodeair when temperature
the outdoor is air temperature is
^OLUZL[[V¸(\[V¹[OLVWLYH[PVUTVKL^PSSZ^P[JOHJJVYKPUN[V
when set to “Auto,” the operation mode will switch according to
The following restrictions must be observed in order to maintain the indoor units connected to the same system. ͵VYILSV^ 5℃ or below.
࠮>OLUV\[KVVYHPYWYVJLZZPUN\UP[ZHYLJVUULJ[LK[OL[V[HSJVUULJ[PVUJHWHJP[`PUKL_T\Z[IL [V VM[OLJHWHJP[`PUKL_VM[OLV\[KVVY\UP[Z the outdoor air conditions,
the outdoor regardless
air conditions,
of the regardless
indoor temperature.
of the indoor temperature.
࠮>OLUV\[KVVYHPYWYVJLZZPUN\UP[ZHUKZ[HUKHYKPUKVVY\UP[ZHYLJVUULJ[LK[OL[V[HSJVUULJ[PVUJHWHJP[`PUKL_VM[OLV\[KVVYHPYWYVJLZZPUN\UP[ZT\Z[UV[
exceed 30% of the capacity index of the outdoor units.
Because connection is possible depending on conditions ever when the capacity index of outdoor-air processing units exceeds 30% of the capacity index of the
outdoor units, contact your local distributor.
࠮Outdoor-air processing units can be used without indoor units.

69 72 73 73 70
Air Treatment
Air Treatment
Equipment
Equipment
Lineup
Lineup Air Treatment Equipment Lineup

Standard
Standard
Specifications
Specifications Dimensions
Options
door unitIndoor unit Air suction/discharge grille (Obtain locally)

Type Type Ceiling Mounted Duct


Ceiling
TypeMounted Duct Type FXMQ125/200/250MFV1 Flexible duct
(Option)
Model Model FXMQ125MFV1 FXMQ125MFV1 FXMQ200MFV1 FXMQ200MFV1 FXMQ250MFV1 FXMQ250MFV1
9 1148
RA Local connection piping size
ower supply Power supply 1-phase
1-phase 220 -240 V (also 220 -for
required 240indoor
V (alsounits),
required for indoor units), 50 Hz
50 Hz (Option)
10 SA
Model Gas piping diameter Liquid piping diameter
Btu/h Btu/h47,800 47,800 76,400 76,400 95,500 95,500
ooling capacity *1 Cooling capacity *1 FXMQ125MFV1 15.9 9.5
kW kW 14.0 14.0 22.4 22.4 28.0 28.0 FXMQ200MFV1 19.1 attached piping 9.5
ower consumption Power consumption
kW kW 0.359 0.359 0.548 0.548 0.638 0.638 FXMQ250MFV1 22.2 attached piping Round hood 9.5
Branch duct (Obtain locally)
asing Casing Galvanised steel plateGalvanised steel plate (Obtain locally)

C
mm
mensions (HxWxD)Dimensions (HxWxD) mm
470X744X1,100 470X744X1,100 470X1,380X1,100 470X1,380X1,100
Table of dimensions

B
A
SA Silencer (Option)
Motor output Motor kW
output kW 0.380 0.380 Duct
m3/min m3/min 18 18 28 28 35 35
(Obtain locally) Model A B C D
an Fan
Airflow rate Airflow rate
cfm cfm 635 635 988 988 1,236 1,236 FXMQ125MFV1 744 685 5X100=500 20- 4.7 hole
Thermal insulation material (Obtain locally)
External static pressure External static
220V/240V Papressure 220V/240V Pa185/225 185/225 225/275 225/275 205/255 205/255
D FXMQ200MFV1 1380 1296 11X100=1100 EA 32- 4.7 hole
(All around) OA
FXMQ250MFV1 1380 1296 11X100=1100 32- 4.7 hole
r filter Air filter *2 *2 Option List

(Service space)
650 or more

Approx.
150
Liquid Liquidmm mm 9.5 (flare) 9.5 (flare)
rigerant Refrigerant Type Note:
VAM150 · 250 · 350 · 500 · 650 · 800 · 1000 · 1500 · 2000GJVE
ng Gas piping Gas mm mm15.9 (flare) 15.9 (flare) 19.1 (brazing) 19.1 (brazing) 22.2 (brazing) 22.2 (brazing) Item
Heat Reclaim Ventilator remote controller 1. The attached piping in the diagram is for FXMQ200MFV1 and
BRC301B61
Drain Drain mm mm PS1B female thread PS1B female thread
Residential central remote controller FXMQ250MFV1 only. The*1gas piping connection port ( 2 in the
DCS303A51
achine weight Machine weight kg kg 86 86 123 123 Centralised diagram) has a different bore form with FXMQ125MFV1.
DCS302CA61
ound level *3 Sound level *3
220V/240V dB(A) 220V/240V dB(A)42/43 42/43 47/48 47/48
controlling Central remote controller(Service 1100 or more
space) 2. An air filter DCS301BA61
is not supplied with this unit. Be sure to mount an air
Inspection hole 600 or more
device filter in the suction side. [Use a filter with dust collection efficiency
onnectable outdoorConnectable
units *4 outdoor units *4 6 HP and above 6 HP and above 8 HP and above 8 HP and above 10 HP and above 10 HP and above Schedule timer DST301BA61
of at least 50% (gravimetric method). This is available as an

Controlling device
Wiring adaptor for electrical 1 2 11 6 4 5
peration range Operation range appendices option.] KRP2A61
an mode operation between
(Fan15mode
andoperation
͵ Cooling
between 15 and 19℃) Cooling  [V͵ 19 to 43℃ Discharge side
30 Suction side (Note.2) 3. For outdoor ducts, be sure to provide heat insulation to prevent
KRP50-2

PC Board Adaptor
condensation.
Range of the discharge
ange of the discharge Installation box for adaptor PCB KRP50-2A90 (Mounted electric component assy of Heat Reclaim Ventilator)

3X100=300
Cooling Cooling [V͵ 13 to 25℃
mperature *5 temperature *5 For heater
A Viewcontrol kit BRP4A50

470
FXFSQ-A
B View 1 Liquid pipe connection
FXDQ-PD 7 Power supply wiring connection FXLQ-MA FXBQ-P
Type
: *1. Specifications are
Notebased
: *1. Specifications
on the following areconditions;
based on the following conditions; *4. It is possible to connect
*4. to
It is
the
possible
outdoortounit
connect
if the total
to thecapacity
outdoorof unit
theifindoor
the total
units
capacity
is 50%oftothe indoor units is 50% to For wiring (VRV indoor unit) FXZQ-M FXUQ-A FXCQ-A FXEQ-A FXDSQ-A 2 Gas FXDQ-SP
pipe FXSQ-PA FXMQ-PA FXMQ-M8 FXMQ-P
connection FXHQ-MA FXHQ-A
Transmission wiring FXAQ-A
connection FXVQ-N
• Cooling: Outdoor temp. of 33℃DB, 28℃WB (68% RH), and discharge temp. of100%
࠮*VVSPUN!6\[KVVY[LTWVM͵+)͵>) 9/HUKKPZJOHYNL[LTWVM͵+) 18℃DB. of the capacity index
100% of the
of the
outdoor
capacity
unit.index of the outdoor unit. FXFQ-A
613 FXDQ-ND FXNQ-MA FXBPQ-P
3 Drain piping connection

50
࠮,X\P]HSLU[YLMLYLUJLWPWPUNSLUN[O!TTOVYPaVU[HS
• Equivalent reference piping length: 7.5 m (0 m horizontal) *5. Local setting mode is *5.
notLocal
displayed
setting
onmode
the remote
is not displayed
controller. on the remote controller.
KRP1C11A KRP1BA57 —
760
KRP1B61 — KRP1C64 KRP1B56 — Hanger bracket
KRP1C64 KRP1B619 KRP1C13A KRP1BA54 — KRP1B61 KRP1C67 KRP1B61
Note 3 Note 4 Electric parts
Note 2, 3box
*2. An intake filter is not supplied,
*2. An intake
so befilter
sure
is to
notinstall
supplied,
the optional
so be sure long-life
to install or optional long-life filter or ࠮;OPZLX\PWTLU[JHUUV[ILPUJVYWVYH[LKPU[V[OLYLTV[LNYV\WJVU[YVSVM[OLVRV
filterthe • This equipment cannot be incorporated into the remote group system.
control of the VRV system. 4 10 Discharge
Note 3 companion
Note 3 Noteflange
1100
high-efficiency filter. Pleasehigh-efficiency
mount it in the filter.
duct
Please
system
mount
of the
it insuction
the duct
side.
system of the suction side. Note 2, 3 Note 4 Note 2, 3 Note 2, 3 2, 3 —
Select a dust collection efficiency
Select a dust
(gravity
collection
method) efficiency
of 50% or(gravity
more. method) of 50% or more.
Installation box for adaptor PCB KRP1H98A KRP1BA101 KRP1BA97 KRP1B96 — BRP9A90 KRP1BA101
5 Ground— terminal
KRP4A98 KRP4A97 11—Water KRP1CA93
supplyKRP1D93A
port KRP4AA93
*3. Anechoic chamber conversion
*3. Anechoic
value,
chamber
measured conversion
at a point
value,
1.5 m measured
downward at afrom
point
the1.5
unit
m centre.
downward from the unit centre. 3 6 Name plate 12 Attached piping (Note. 1)
These values are normally These
somewhat
valueshigher
are normally
during somewhat
actual operation
higherasduring
a resultactual
of ambient
operation as a result of ambient
conditions. conditions. 2.
* box isdiagrams
Note: 1. InstallationThese necessaryare
for based
each adaptor marked and
on FXMQ200 . *1 For residential use only. When connect with a Heat Reclaim Ventilator (VAM), you can
FXMQ250MFV1.
only switch the power ON/OFF. It cannot be used with other central control equipment.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.

FXMQ200/250MFV1 FXMQ125MFV1

Options
Options
245
Type VAM150GJVE VAM250GJVE
Item 60 12 VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE 61
VAM1000GJVE VAM1500GJVE VAM2000GJVE
Silencer — KDDM24B50 KDDM24B100 KDDM24B100X2

Additional
function
Nominal pipe diameter mm — 200 250

3X100=300

3X100=300
KAF242J25M KAF242J50M KAF242J65M KAF242J80M KAF242J100M KAF242J80MX2 KAF242J100MX2

360
330

360
330
door unitIndoor unit KAF241J25M KAF241H50M KAF241J65M KAF241J80M KAF241J100M KAF241J80MX2 KAF241J100MX2

390

390
296

296
250

250
25

25
Flexible duct (1 m) K-FDS101D K-FDS151D K-FDS201D K-FDS251D
Flexible duct (232-
m) 7 hole K-FDS102D K-FDS152D K-FDS202D
20- 7 hole 5X100=500
K-FDS252D
Model Model FXMQ125MFV1 FXMQ125MFV1 FXMQ200MFV1 FXMQ200MFV1 FXMQ250MFV1 FXMQ250MFV1 11X100=1100
(All around) — (All around) YDFA25A1
Operation remote controller
Operation remote controller BRC1E63/BRC1C62 BRC1E63/BRC1C62
Duct adaptor 1200
1230
30
8 —
600 30
8 250
Nominal pipe diameter mm 630
Operation/control

Central remote controller


Central remote controller DCS302CA61 DCS302CA61 CO2 sensor A View BRYMA65 A View BRYMA100 BRYMA65 BRYMA100
Unified ON/OFF controller
Unified ON/OFF controller DCS301BA61 DCS301BA61 BAF249A150
580 BAF249A300 BAF249A350 BAF249A500 — BAF429A20A
BAF249A150C BAF249A300C BAF249A350C BAF249A500C — BAF429A20AC
Schedule timer Schedule timer DST301BA61 DST301BA61
*Refer to page 184-186 for details.
Wiring adaptor for electrical
Wiringappendices
adaptor for(1)electrical appendices (1) KRP2A61 KRP2A61

200
360
346
200
360
330

250
250
Wiring adaptor for electrical
Wiringappendices
adaptor for(2)electrical appendices (2) KRP4AA51 KRP4AA51
Long-life replacementLong-life
filter replacement filter KAFJ371L140 KAFJ371L140 KAFJ371L280 KAFJ371L280 PC board adaptor for heater control kit (BRP4A50) 5X200=1000 2X200=400

High-efficiency Colourimetric
High-efficiency Colourimetric methodKAFJ372L140
method 65% 65% KAFJ372L140 KAFJ372L280 KAFJ372L280 7 7 580
Filters

1230
filter filter
When the installation of an electric heater is required in a cold region, this adaptor with an internal timer function eliminates the
16-M5 hole 10-M5 hole 630
Colourimetric Colourimetric methodKAFJ373L140
method 90% 90% KAFJ373L140 KAFJ373L280 KAFJ373L280
complicated timer connecting
(All around) work that was necessary with conventional heaters.
B View (For FXMQ200MFV1)
(All around)
Filter chamber *1 Filter chamber *1 KDJ3705L140 KDJ3705L140 KDJ3705L280 KDJ3705L280 B View

M2.5 filtration unit *2PM2.5 filtration unit *2 BAF429A20A BAF429A20A Notes when installing
1004 Indoor Outdoor
M2.5 with activatedPM2.5
carbonwith activated
filtration carbon filtration unit *2
unit *2 BAF429A20AC BAF429A20AC
using the electric heater based on the standard and
ain pump kit Drain pump kit KDU30L250VE KDU30L250VE RA EA regulation of each country.

200
360
330
daptor for wiring Adaptor for wiring KRP1B61 KRP1B61 Heat Reclaim Ventilator Supply the electric heater and safety production devices
250

SA Heater OA such as a relay and a thermostat, etc of which qualities


: *1. Filter chamberNote
has a: *1.
suction-type
Filter chamber
flange.
has(Main
a suction-type
unit does not.)
flange. (Main unit does not.)  ࠮:VTLVW[PVUZTH`UV[IL\ZLKPUJVTIPUH[PVU
• Some options may not be used in combination. (Obtain locally) satisfy the standard and regulation of each country at site.
• Dimensions and weight of the equipment may vary depending on the options
࠮+PTLUZPVUZHUK^LPNO[VM[OLLX\PWTLU[TH`]HY`KLWLUKPUNVU[OLVW[PVUZ\ZLK ࠮6WLYH[PUNZV\UKTH`PUJYLHZLZVTL^OH[KLWLUKPUNVU[OLVW[PVUZ\ZLK
used. • Operating sound may increase somewhat depending on the options used.
5X200=1000 Thermostat
࠮:VTLVW[PVUZTH`UV[IL\ZHISLK\L[V[OLLX\PWTLU[PUZ[HSSH[PVUJVUKP[PVUZZVWSLHZL
• Some options may not be usable due to the equipment installation conditions, so please
confirm prior to ordering.confirm prior to ordering. BRP4A50
7 1230
(Obtain locally)
(ON when the temperature heater. Be sure to use 2 m or more between the electric
*2. Refer to page 166-168 *2. Refer
for details.
to page 82-84 for details. 16-M5 hole is at or below -10°C)
(All around) heater and the Heat Reclaim Ventilator for safety.
Thermostat (Obtain locally) For the Heat Reclaim Ventilator, use a different power
(OFF when the temperature is at or more B View (For FXMQ250MFV1) Power supply (Obtain locally)
than 5°C) Relay box supply from that of the electric heater and install a circuit
breaker for each.

71 74 74 183
75 72
Air Treatment Equipment Lineup

Heat Reclaim Ventilator (Option) with for VAM DX-Coil


/ FXMQ-MF series —
VKM
Rapid series
urbanization has increased industrial and automobile emissions, resulting in higher PM2.5 levels.
This has become the source of respiratory diseases and poses a serious threat to a long term health
A compact unit packed with Daikin’s cutting-edge technologies.
issue. As the air quality has worsened, research has shown the harmful effects of PM2.5 on the health Exhaust Fan
ofThe Heat Reclaim
the general public. Ventilator lineup features the DX-coil in response to recently Heat Exchanger Elements

diversifying outdoor air introduction requirements. EA Damper Motor


(Exhaust air to outdoors) Damper
Lineup
With DX Coil Type RA
Model Name VKM50GAV1 VKM80GAV1 VKM100GAV1 OA (Return air from room)
(Fresh air from outdoors)
Capacity Index 31.25 50 62.5

HEP Element
(Anti-mould)
Air Supply Fan
SA
(Supply air to room)
Operation of the heat exchanger element Electronics Box
(Control box)
DX-coil
Outdoor Indoor

30.6°C SA
62% RH 27.4°C
63% RH

Front Filter DX-coil SA

The Heat Reclaim Ventilator features DX-coil RA


Temperature
and humidity
Integrally-
formed liner

that contributes to the prevention of hot 26°C


50% RH
RA

airflow colliding people directly during cooling 32°C DX-coil (Direct expansion coil)
70% RH
operation, due to the after-cool operations
Integrally-formed liner

Efficient outdoor air introduction is possible done beforehand.


The Heat Reclaim Ventilator (VKM series) series Heat exchange and cooling process
introduces fresh outdoor air with minimum heat High static pressure
Structure of The supply air is cooled from 29°C to 17.2°C with DX-coil.
losses, with a wide variety of features cater to High external static pressure means enhanced VKM series Outdoor Indoor
customer requirements. design flexibility. After heat exchange
Total heat exchange 29°C Cooling by DX-Coil
element

Exhaust Air Supply Air


To the Outdoor 32.9°C
To the Indoor 17.2°C
Air conditioning and outdoor air processing can be accomplished using a single system. DX-Coil: Heat Exchanger which cool the supply
those smaller than the grid mesh. air by the refrigerant provided from VRV outdoor
Return Air unit’s refrigerant.
Outdoor Air From the Indoor 27°C
VRV Outdoor Units From the Outdoor 35°C

Daikin Electrostatic
Heat Reclaim Ventilator with Normal Filtration
Dust Collecting
DX Coil Filtration
Efficient fresh outdoor air supply with heat exchange and cooling operation.
Outdoor Air

Exhaust Air Indoor Unit Indoor Unit 100 80


Total heat exchange + Cooling 60
Schematic diagram
Indoor unit with outdoor air treatment
Return Using outdoor air, the temperature can be brought near room Comfortable + Energy Saving Effect of total heat

Relative humidity (%)


temperature with minimal cooling capacity through the use of outdoor exchange
Air Air Effect of cooling
40
Air-Conditioning Air Supply
air.
With the capturing effect of static electricity,
Supply Air
Outdoor
temperature temperature
20
Schematic diagram Other features
Indoor temperature

• Integrated system includes ventilation and air processing operations.

Air Treatment
Equipment Lineup
Connection Conditions • Ventilation and cooling are possible with one remote controller.
The following restrictions must be observed in order to maintain the indoor units connected to the same system. –5 0 5 10 15 20 25 30 35 40
continuous
• When Supply
the Heat Reclaim Air isVKM
Ventilator guaranteed.
series units are connected, the total connection capacityand
indexthus ventilation
must be 50% to 130%effect is reduced.
of the capacity index of the outdoor units.
Dry bulb temperature (°CDB)

Dust collection capacity decreases


collection capacity remarkably after use for a period of time.

17573 76 74176
Air Treatment Equipment Lineup

Specifications Dimensions
Refrigerant
MODEL VKM50GAV1 VKM80GAV1
R-410A
VKM100GAV1
VKM50/80/100GAV1
Power Supply 1-phase, 220–240 V, 50 Hz
Airflow rate m³/h 500 750 950 Supply air fan Damper plate Direct expansion coil Hanger bracket
Ultra-high 387
1688
4-14 x 40 oval hole
Static pressure Pa 180 170 150 Exhaust air fan 160
235

20
Airflow Rate & Static Airflow rate m³/h 500 750 950
Pressure (Note 6) High
Static pressure Pa 150 120 100

D
B
Airflow rate m³/h 440 640 820 RA
Low EA Return air from room
Static pressure Pa 110 80 70 Exhaust air to outdoors 210

E
G
560 620 670

A
Heat Ultra-high

C
exchange High W 490 560 570 SA
mode 420 470 480 Supply air to room
Low OA

34
42
153
Power Consumption
560 620 670 Fresh air from outdoors
Ultra-high (Outdoor air)

130
Bypass

20
High W 490 560 570

60
More than 600
mode 153 160
Low 420 470 480 28

150– 250
Maintenance Cover
94
Fan Type Sirocco Fan Control box
Inspection Inspection 144
Motor Output kW 0.280 x 2 0.280 x 2 0.280 x 2 Maintenance cover
hatch hatch 210
Ultra-high 38/38.5/39 40/41/41.5 40/40.5/41
Heat
Maintenance space for the heat exchanger elements 360 (In case of 450 inspection hatch)
exchange High dB(A) 36/36.5/37 37.5/38/39 38/38.5/39 the air filters, fans 140 (In case of 600 inspection hatch)
mode Low 33.5/34.5/35.5 34.5/36/37 35/36/36.5
Sound Level (Note 4)
(220/230/240 V) Ultra-high 38/38.5/39 40/41/41.5 40/40.5/41
Bypass
High dB(A) 36/36.5/37 37.5/38/39 38/38.5/39 H 1764 I
mode
VKM50GAV1 VKM80/100GAV1 10 515
Low 33.5/34.5/35.5 34.5/36/37 35/36/36.5
A 832 1,214 High efficiency filter (option) 322
Ultra-high 76 78 74
B 248 439
Temp. Exchange High % 76 78 74 C 431 622
Efficiency
D 164 183

K
J
Low 77.5 79 76.5
E 420 592
Ultra-high 64 66 62 F 248 439
Enthalpy Exchange 64 66 62 G 878 1,262 Heat exchanger
High % Gas pipe * The specification subject to change without notice.
Efficiency (Cooling) H 137 89 elements * Be sure to provide two inspection hatch.
connection
Low 67 68 66 I 137 89 Air filters ( 450 or 600) at the service side of filters and elements.
(ø12.7)
* The high efficiency filter (option) can be attached to the SA surface
Ultra-high 67 71 65 J ø196 ø246 Liquid pipe connection Drain outlet
of the heat exchanger elements.
Enthalpy Exchange K ø250 ø263 (ø6.4) (PT3/4 male screw)
High % 67 71 65
Efficiency (Heating)
Low 69 73 69
Casing Galvanised Steel Plate
Insulating Material Self-Extinguishable Urethane Foam
Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange

Options
Heat Exchanger Element Specially Processed Nonflammable Paper
Air Filter Multidirectional Fibrous Fleeces

DX-coil Cooling (Note 2) 2.8 4.5 5.6


Capacity kW
Heating (Note 3) 3.2 5.0 6.4
Type VKM50/80/100GAV1
Height 387 387 387 Item
Dimensions Width mm 1,764 1,764 1,764 Remote controller BRC1E63 / BRC2E61 *1
Depth 832 1,214 1,214 Residential central remote controller DCS303A51 *2
Centralised Central remote controller DCS302CA61
Connection Duct Diameter mm 200 250 controlling
Machine Weight kg 96 109 114 device Unified ON/OFF controller DCS301BA61

Controlling device
Schedule timer DST301BA61
Around Unit 0°C–40°CDB, 80%RH or less
Wiring adaptor for electrical KRP2A61
Unit Ambient Condition OA (Note 7) -15°C–40°CDB, 80%RH or less appendices

PC Board Adaptor
RA (Note 7) 0°C–40°CDB, 80%RH or less For humidifier running ON signal output KRP50-2
Note: 1. Cooling and heating capacities are based on the following conditions. Fan is based on High and 10. Temperature exchange efficiency is the mean value for Cooling and Heating. Efficiency is measured
For heater control kit BRP4A50
Ultra-high. under the following condition: Ratio of rated external static pressure outdoor to indoor is kept Type FXFSQ-A FXDQ-PD FXLQ-MA FXBQ-P
When calculating the capacity as indoor units, use the following figures: constant at 7 to 1.
For wiring (VRV indoor unit) FXZQ-M FXUQ-A FXCQ-A FXEQ-A FXDSQ-A FXDQ-SP FXSQ-PA FXMQ-PA FXMQ-M FXMQ-P FXHQ-MA FXHQ-A FXAQ-A FXVQ-N
VKM50GAV1: 3.5 kW, VKM80GAV1: 5.6 kW, VKM100GAV1: 7.0 kW 11. When connecting with a VRV system heat recovery outdoor unit and bringing the RA (exhaust gas FXFQ-A FXDQ-ND FXNQ-MA FXBPQ-P
2. Indoor temperature: 27°CDB, 19°CWB, Outdoor temperature: 35°CDB intake) of this unit directly in from the ceiling, connect to a BS unit identical to the VRV indoor unit
3. Indoor temperature: 20°CDB, Outdoor temperature: 7°CDB, 6°CWB (master unit), and use group-linked operation. (See the Engineering Data for details.) KRP1C11A KRP1BA57 — KRP1B61 — KRP1C64 KRP1B56 — KRP1C64 KRP1B61 KRP1C13A KRP1BA54 — KRP1B61 KRP1C67 KRP1B61
4. The operating sound measured at the point 1.5 m below the centre of the unit is converted to 12. When connecting the indoor unit directly to the duct, always use the same system on the indoor Note 2, 3 Note 4 Note 2, 3 — Note 3 Note 4 — Note 2, 3 Note 2, 3 — Note 3 Note 3 Note 2, 3 —
that measured in an anechoic chamber built in accordance with the JIS C 1502 conditions. The unit as with the outdoor unit, perform group-linked operation, and make the direct duct connection Installation box for adaptor PCB KRP1H98A KRP1BA101 KRP1BA97 KRP1B96 BRP9A90 KRP1BA101 KRP4A98 KRP4A97 KRP1CA93 KRP1D93A KRP4AA93
actual operating sound varies depending on the surrounding conditions (near running unit’s settings from the remote controller. (Mode No. “17 (27)” – First code No. “5” – Second code No.
sound, reflected sound and so on) and is normally higher than this value. “6”.) Also, do not connect to the outlet side of the indoor unit. Depending on the fan strength and
For operation in a quiet room, it is required to take measures to lower the sound. static pressure, the unit might back up. Note: 1. Installation box  is necessary for each adaptor marked  . *1 Necessary when operating a Heat Reclaim Ventilator (VKM) independently. When operating interlocked
For details, refer to the Engineering Data. 2. Up to 2 adaptors can be fixed for each installation box. with other air conditioners, use the remote controllers of the air conditioners.
5. The noise level at the air discharge port is about 8–11 dB(A) or higher than the unit’s operating 3. Only one installation box can be installed for each indoor unit. *2 For residential use only. When connected with a Heat Reclaim Ventilator (VKM), you can only switch
sound. 4. Up to 2 installation boxes can be installed for each indoor unit. the power ON/OFF, it cannot be used with other central control equipment.
For operation in a quiet room, it is required to take measures to lower the sound.
6. Airflow rate can be changed over to Low mode or High mode.
7. OA: fresh air from outdoor. RA: return air from room.
8. Specifications, design and information here are subject to change without notice.

Air Treatment
Equipment Lineup
9. Power consumption and efficiency depend on the above value of airflow rate.
Type VKM50GAV1 VKM80GAV1 VKM100GAV1
Item
— KDDM24B100
Additional function

Silencer
Nominal pipe diameter mm — 250
Air suction/ White K-DGL200B K-DGL250B
Discharge grille Nominal pipe diameter mm 200 250
High efficiency filter KAF242J80M KAF242J100M
Air filter for replacement KAF241G80M KAF241G100M
Flexible duct (1 m) K-FDS201D K-FDS251D
Flexible duct (2 m) K-FDS202D K-FDS252D

17775 76178
Air Treatment Equipment Lineup

Heat Reclaim Ventilator — VAM series Air conditioning load reduced by approximately 31%!

The Heat Reclaim Ventilator creates a high-quality environment by interlocking


with the air conditioner Total heat exchange ventilation 23% Auto-ventilation Mode
6%
This unit recovers heat energy lost through ventilation and
curbs room temperature changes caused by ventilation, thereby Changeover Switching
Model Names conserving energy and reducing the load on the air conditioning Automatically switches the
system. ventilation mode (Total Heat
VAM150GJVE, VAM250GJVE, VAM350GJVE,
Enthalpy efficiency drastically improved by employing Exchange Mode/Bypass Mode)
VAM500GJVE, VAM650GJVE, VAM800GJVE, according to the operating status
VAM1000GJVE, VAM1500GJVE, VAM2000GJVE thin film element! (VAM-GJ model)
of the air conditioner.
With the thinner film...
Heat Reclaim Ventilator remote controller* • It can decrease the moisture resistance of the partition sheets drastically.
1
Improved Enthalpy Efficiency BRC301B61 (Option)
• Gaining more space for extra layers in the element,
result in increasing of effective area that supply and Thickness of
2 * This remote controller is used in case of independent the partition sheet
Higher External Static Pressure exhaust air can be exposed to.

Enhanced Energy Saving Functions


operation of Heat Reclaim Ventilator.
Moisture absorption increased by approx. 10%! 40 µm
Indoor Outdoor
Sheet structure Pre-cool,
2%
Exhaust air
This VAM series provides higher enthalpy efficiency1 , due to the greatly enhanced performance of the thin film High-humidity air
Pre-heat Control
Molecule of water
element. Furthermore, improved external static pressure2 offers more flexibility for installation. Along with these Exhaust air Miscellaneous gas
CO2 molecule, etc. Reduces air conditioning load
three outstanding improvements, the nighttime free cooling operation contributes to energy conservation and more

40 m
SA
by not operating the Heat
comfortable environment. Precise, thin-film
material Reclaim Ventilator while air is
EA Outdoor air still clean soon after the air
RA
1 For models: VAM150/250/350/650/800/1000/2000GJVE (Exhaust air to outdoors) (fresh air) Supply air Low-humidity air

2 For models: VAM150/350/500GJVE


(unclean
Moisture exchange efficiency is greatly improved by using optimised
conditioner is turned ON.
RA indoor air)
thinner films and moisture-absorption materials in the element.
OA (Return air Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.
(Fresh air from from room)
outdoors)

31%

Air conditioning load reduction (%)


Air Conditioning Load
• The air conditioning load reduction values may vary according to weather and
other environmental conditions at the location of the machine's installation. Reduced by Approximately
SA • The air conditioning load reduction values are based on the following conditions;
(Supply air Application: Tokyo office building
to room) Building form: 6 floors above ground, 2 floors underground, floor area 2,100 m2 20%
Personnel density: 0.25 person/m2
Daikin air conditioner Ventilation volume: 25 m3/h
Indoor unit Indoor air conditioning level: summer 25°C 50% RH, intermediate seasons 24°C 50%
RH, winter 22°C 40% RH 0%
Operating time: 2745 hours (9 hours per day, approx. 25 days per month) Normal VAM-GJ VAM-GJ
Calculation method: simulation based on "MICRO-HASP/1982" of the Japan ventilation fan Individual operation Interlocked operation
• ON/OFF signal Building Mechanical and Electrical Engineers Association. with air conditioner
• Cooling/Heating mode signal
• Set temperature signal
• Ventilation signal

Nighttime free cooling operation*1


• Operating mode signal
• Filter cleaning signal
Interlocking Air conditioning sensible
• Failure detection signal Nighttime free cooling operation is an energy-conserving function that works at night when air heat load reduced by
conditioners are off. By ventilating rooms containing office equipment that raises the room
5% !
*2
LCD remote controller temperature, nighttime free cooling operation reduces the approx.
for indoor unit
cooling load when air conditioners are turned on in the The indoor accumulated heat is discharged at night.
morning. It also alleviates feelings of discomfort in the This reduces the air conditioning load the next day thereby increasing efficiency.
morning caused by heat accumulated during the night.
Heat Reclaim •Nighttime free cooling operation only works to cool and if connected to
Ventilator Building Multi or VRV systems. Cold air
•Nighttime free cooling operation is set to “off” in the factory settings,
Compact Equipment Energy Conservation so if there is a need to turn on, please contact Daikin dealer. Indoor Indoor
unit unit
Exhaust Exhaust
With a height of only 306 mm, the unit easily fits into limited Air conditioning load reduced by approximately 31%! *1 This function can be operated only when interlocked with air conditioners. heat heat
Comfortable!
spaces, such as above ceilings. *2 Value is based on the following conditions: Generated
heat
• Cooling operation performed from April to October.

Air Treatment
Equipment Lineup
• Calculated for air conditioning sensible heat load only
Cold Climate Compatible (latent heat load not included).
Heat is discharged. The load is small so the temperature is rapidly reduced
306 mm to a comfortable level.
Standard operation at *Interlocked operation with an air conditioner
-15˚CDB 50˚CDB
temperatures down to
* For VAM500GJVE -15°C.
-20 -10 0 10 20 30 40 50

17977 78180
Air Treatment Equipment Lineup

Heat Reclaim Ventilator — VAM series Specifications


MODEL VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE
CO2 Sensor Optional Kit Connection Power Supply 1-phase, 220-240 V/ 220 V, 50/60 Hz
Ultra-High 79/79 75/75 79/79 74/74 75/75 72/72 78/78 72/72 77/77
The CO2 sensor controls airflow so that it best matches the changes in CO2 level. Temp. Exchange
Efficiency High % 79/79 75/75 79/79 74/74 75/75 72/72 78/78 72/72 77/77
This prevents energy losses from over-ventilation while maintaining indoor air (50/60 Hz)
Low 84/85 79/79 82/82 80/80.5 77/77.5 74/74.5 80.5/81 75.5/76 79/81
quality with optional CO2 sensor. Enthalpy Ultra-High 66/66 63/63 66/66 55/55 61/61 61/61 64/64 61/61 62/62
Exchange
For Cooling High % 66/66 63/63 66/66 55/55 61/61 61/61 64/64 61/61 62/62
Efficiency
(50/60 Hz) Low 70/70.5 66/66 70/70 59/59.5 64/64.5 64/64.5 68.5/69 64/64.5 66/67

Example of CO2 sensor operation in an office room: Heat


Ultra-High 125/134 137/141 200/226 248/270 342/398 599/680 635/760 1,145/1,300 1,289/1,542
Exchange High W 111/117 120/125 182/211 225/217 300/332 517/597 567/648 991/1,144 1,151/1,315
Power Mode
7- stage control with different airflow levels CO2 level Consumption
Low 57/58 60/59 122/120 128/136 196/207 435/483 476/512 835/927 966/1,039
Airflow for ventilation (50/60 Hz) Ultra-High 125/134 137/141 200/226 248/270 342/398 599/680 635/760 1,145/1,300 1,289/1,542
Bypass
If airflow were High W 111/117 120/125 182/211 225/217 300/332 517/597 567/648 991/1,144 1,151/1,315
Mode
constant Low 57/58 60/59 122/120 128/136 196/207 435/483 476/512 835/927 966/1,039
Airflow down Ultra-High 27-28.5/28.5 27-29/29 31.5-33/33 33-35.5/34 34-36/36 39-40.5/39.5 39.5-41.5/39.5 39.5-41.5/41.5 41.5-43.5/42
Reference Heat

Airflow for ventilation


value Exchange High dB(A) 26-27.5/27.5 26-27.5/28 30-31.5/30 31.5-34/32 33-34.5/34 37-39.5/37.5 37.5-39.5/37.5 37.5-39.5/39.5 39-43/40
Airflow down Mode
Sound Level Low 20.5-21.5/21 21-22/21 23-25/23 25-28.5/24 27.5-29.5/28 35-37.5/34 35-37.5/34.5 35-37.5/36 36-39/39
CO2 level

(50/60 Hz) Ultra-High 28.5-29.5/29.5 28.5-30.5/30.5 33-34.5/34.5 34.5-36/35.5 35-37.5/37.5 40.5-42/41 40.5-42.5/40.5 41-43/42.5 43-45.5/44
Airflow up Bypass
High dB(A) 27.5-28.5/28.5 27.5-29/29.5 31.5-33/31.5 33-34.5/33.5 33-35.5/35.5 38.5-40/39 38.5-40.5/38.5 39.5-41/41.5 40.5-45/42
Mode
Low 22.5-23.5/22 22.5-23/22.5 24.5-26.5/24.5 25.5-28.5/25.5 27.5-30.5/29.5 36-38.5/35.5 36-38.5/35.5 36.5-38/37.5 37.5-39.5/41
indicates energy savings! Casing Galvanised steel plate
Airflow up Energy wastage for ventilation is reduced.
Air conditioning load for ventilation is reduced. Insulation Material Self-extinguishable polyurethane foam
Dimensions (HXWXD) mm 278X810X551 306X879X800 338X973X832 387X1,111X832 387X1,111X1,214 785X1,619X832 785X1,619X1,214
9 10 11 12 13 14 15 16 17 18 19 20 21 Hours Machine Weight kg 24 32 45 55 67 129 157
Heat Exchange System Air to air cross flow total heat (Sensible heat + latent heat) exchange
Sales Sales
Morning Lunch Overtime Heat Exchange Element Material Specially processed nonflammable paper
personnel leave personnel
meetings time work
office return Air Filter Multidirectional fibrous fleeces
Type Sirocco fan
Ultra-High 150/150 250/250 350/350 500/500 650/650 800/800 1,000/1,000 1,500/1,500 2,000/2,000
Airflow Rate
High m3/h 150/150 250/250 350/350 500/500 650/650 800/800 1,000/1,000 1,500/1,500 2,000/2,000
(50/60 Hz)
Low 100/95 155/155 230/230 320/295 500/470 700/670 860/840 1,320/1,260 1,720/1,580
Fan
Ultra-High 120/154 70/96 169/222 105/150 85/125 133/170 168/192 112/150 116/140
Heat Reclaim Ventilator External Static
Pressure High Pa 106/131 54/65 141/145 66/52 53/67 92/85 110/86 73/72 58/32
Air conditioner (50/60 Hz)
Low 56/60 24/20 67/30 32/18 35/38 72/61 85/60 56/50 45/45
Motor Output kW 0.030X2 0.090X2 0.140X2 0.280X2 0.280X4
Connection Duct Diameter mm 100 150 200 250 350

Many people increase CO2 level: Fewer people decrease CO2 level: Unit ambient condition -15°C–50°CDB, 80%RH or less
Note : 1. Sound level is measured at 1.5m below the centre of the body. 10. With large models in particular (1500 and 2000m3/h models), if the supply air
Airflow up Airflow down 2. Airflow rate can be changed over to Low mode or High mode.
3. Sound level is measured in an anechoic chamber.
(SA) grille is installed near the main unit, the noise of the main unit may be heard
from the discharge grille via the duct, and this will result in a marked increase in
Sound level generally becomes greater than this value depending on the noise. In such cases, if peripheral effects are included (such as reverberation of
operating conditions, reflected sound, and peripheral noise. the floor and walls, combination with other equipment, and background noise),
4. The sound level at the air discharge port is about 8 dB(A) higher than the unit's sound level may be as much as 15 dB(A) higher than the indicated value. When
sound level. installing a large model, please provide as much separation as possible between
5. The specifications, designs and information given here are subject to change the main unit and the discharge grille. If the equipment and discharge grille are
without notice. near each other, please consider countermeasures such as the following:
6. Temperature Exchange Efficiency is the mean value between cooling and heating. • Use a sound-muffling box, flexible duct and sound-muffling air supply/discharge
7. Efficiency is measured under the following conditions: grilles
Ratio of rated external static pressure has been maintained as follows; outdoor • Decentralised installation of discharge grilles
side to indoor side = 7 to 1. 11. When installing in a location with particularly low background noise such as a
8. In conformance with JIS standards (JIS B 8628), operating sound level is based on the classroom, please consider the following measures to avoid transmission sound
value when one unit is operated, with the value converted for an anechoic chamber. from the main unit:
This is transmission sound from the main unit, and does not include sound from • Use of ceiling materials with high sound insulating properties (high transmission
the discharge grille. Thus it is normal for the sound to be louder than the loss)
indicated value when the unit is actually installed. • Methods of blocking sound transmission, for example, by adding sound
9. Sound level from the discharge port causes the value to be approximately 8 insulating materials around the bottom of the sound source.
dB(A) (models with the airflow rate of less than 150 to 500m3/h) to approximately Alternatively, consider supplementary methods such as installing the equipment

Air Treatment
Equipment Lineup
11 dB(A) (models with the airflow rate of 650m3/h or more) greater than the in a different location (corridor, etc.)
indicated value. Furthermore, fan rotation and noise from the discharge grille
may increase depending on the on-site duct resistance conditions. Please
consider noise countermeasures when installing the unit.

18179 80182
Air Treatment Equipment Lineup

Dimensions
Options (Option) for VAM / FXMQ-MF series
Air suction/discharge grille (Obtain locally) Rapid urbanization has increased industrial and automobile emissions, resulting in higher PM2.5 levels.
This has become the source of respiratory diseases and poses a serious threat to a long term health
FXMQ125/200/250MFV1 Flexible duct
(Option) issue. As the air quality has worsened, research has shown the harmful effects of PM2.5 on the health
9 1148
RA Local connection piping size of the general public.
(Option)
10 SA
Model Gas piping diameter Liquid piping diameter
FXMQ125MFV1 15.9 9.5
FXMQ200MFV1 19.1 attached piping 9.5
FXMQ250MFV1 22.2 attached piping Round hood 9.5
Branch duct (Obtain locally)
(Obtain locally)
C

Table of dimensions
B
A
SA Silencer (Option)
Duct
(Obtain locally) Model A B C D
FXMQ125MFV1 744 685 5X100=500 20- 4.7 hole
Thermal insulation material (Obtain locally)
D FXMQ200MFV1 1380 1296 11X100=1100 EA 32- 4.7 hole
(All around) OA
FXMQ250MFV1 1380 1296 11X100=1100 32- 4.7 hole
Option List
(Service space)
650 or more

Approx.
150

Type Note:
VAM150 · 250 · 350 · 500 · 650 · 800 · 1000 · 1500 · 2000GJVE
Item
Heat Reclaim Ventilator remote controller 1. The attached piping in the diagram is for FXMQ200MFV1 and
BRC301B61
Residential central remote controller FXMQ250MFV1 only. The*1gas piping connection port ( 2 in the
DCS303A51
Centralised diagram) has a different bore form with FXMQ125MFV1.
DCS302CA61
controlling Central remote controller(Service 1100 or more
2. An air filter DCS301BA61
is not supplied with this unit. Be sure to mount an air
device Inspection hole 600 or more
space)
filter in the suction side. [Use a filter with dust collection efficiency
Front Filter
Schedule timer DST301BA61
of at least 50% (gravimetric method). This is available as an
Controlling device

Wiring adaptor for electrical 1 2 11 6 4 5


appendices option.] KRP2A61
Discharge side
30 Suction side (Note.2) 3. For outdoor ducts, be sure to provide heat insulation to prevent
KRP50-2
PC Board Adaptor

condensation.
Installation box for adaptor PCB KRP50-2A90 (Mounted electric component assy of Heat Reclaim Ventilator)
3X100=300

For heater
A Viewcontrol kit BRP4A50
470

FXFSQ-A
B View 1 Liquid pipe connection
FXDQ-PD 7 Power supply wiring connection FXLQ-MA FXBQ-P
Type
For wiring (VRV indoor unit) FXZQ-M FXUQ-A FXCQ-A FXEQ-A FXDSQ-A 2 Gas FXDQ-SP
pipe FXSQ-PA FXMQ-PA FXMQ-M8 FXMQ-P
connection FXHQ-MA FXHQ-A
Transmission wiring FXAQ-A
connection FXVQ-N
FXFQ-A
613 FXDQ-ND FXNQ-MA FXBPQ-P
3 Drain piping connection
50

KRP1C11A KRP1BA57 —
760
KRP1B61 — KRP1C64 KRP1B56 — Hanger bracket
KRP1C64 KRP1B619 KRP1C13A KRP1BA54 — KRP1B61 KRP1C67 KRP1B61
Note 3 Note 4 Electric parts
Note 2, 3box
4 10 Discharge
Note 3 companion
Note 3 Noteflange
1100
Note 2, 3 Note 4 Note 2, 3 Note 2, 3 2, 3 —
Installation box for adaptor PCB KRP1H98A KRP1BA101 KRP1BA97 KRP1B96 — BRP9A90 KRP1BA101
5 Ground— terminal
KRP4A98 KRP4A97 11—Water KRP1CA93
supplyKRP1D93A
port KRP4AA93
3 6 Name plate 12 Attached piping (Note. 1)
2.
* box isdiagrams
Note: 1. InstallationThese necessaryare
for based
each adaptor marked and
on FXMQ200 . *1 For residential use only. When connect with a Heat Reclaim Ventilator (VAM), you can
FXMQ250MFV1.
only switch the power ON/OFF. It cannot be used with other central control equipment.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.

FXMQ200/250MFV1 FXMQ125MFV1
245
Type VAM150GJVE VAM250GJVE
Item 60 12 VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE 61
VAM1000GJVE VAM1500GJVE VAM2000GJVE
Silencer — KDDM24B50 KDDM24B100 KDDM24B100X2
Additional

those smaller than the grid mesh.


function

Nominal pipe diameter mm — 200 250


3X100=300

3X100=300

KAF242J25M KAF242J50M KAF242J65M KAF242J80M KAF242J100M KAF242J80MX2 KAF242J100MX2


360
330

360
330

KAF241J25M KAF241H50M KAF241J65M KAF241J80M KAF241J100M KAF241J80MX2 KAF241J100MX2


390

390
296

296
250

250
25

25

Flexible duct (1 m) K-FDS101D K-FDS151D K-FDS201D K-FDS251D


Flexible duct (232-
m) 7 hole K-FDS102D
11X100=1100
K-FDS152D K-FDS202D
20- 7 hole 5X100=500
K-FDS252D Daikin Electrostatic
Duct adaptor
(All around) 1200 30
8
— (All around) 600 30 YDFA25A1 Normal Filtration
1230
Nominal pipe diameter mm — 630 8 250 Dust Collecting Filtration
CO2 sensor A View BRYMA65 A View BRYMA100 BRYMA65 BRYMA100
BAF249A150
580 BAF249A300 BAF249A350 BAF249A500 — BAF429A20A
BAF249A150C BAF249A300C BAF249A350C BAF249A500C — BAF429A20AC
*Refer to page 184-186 for details. Schematic diagram
200
360
346
200
360
330

250
250

PC board adaptor for heater control kit (BRP4A50) 5X200=1000 2X200=400

7 1230 7 580
When the installation of an electric heater is required in a cold region, this adaptor with an internal timer function eliminates the
16-M5 hole 10-M5 hole
complicated timer connecting
(All around) work that was necessary with conventional heaters. (All around)
630
With the capturing effect of static electricity,
B View (For FXMQ200MFV1) B View

Notes when installing


1004 Indoor Outdoor
using the electric heater based on the standard and Schematic diagram
regulation of each country.

Air Treatment
Equipment Lineup
RA EA
200
360
330

Heat Reclaim Ventilator Supply the electric heater and safety production devices
250

SA Heater OA such as a relay and a thermostat, etc of which qualities


(Obtain locally) satisfy the standard and regulation of each country at site.
5X200=1000 Thermostat continuous Supply Air is guaranteed. and thus ventilation effect is reduced.
BRP4A50
7 1230
(Obtain locally)
(ON when the temperature heater. Be sure to use 2 m or more between the electric
16-M5 hole is at or below -10°C)
(All around) heater and the Heat Reclaim Ventilator for safety.
Thermostat (Obtain locally) For the Heat Reclaim Ventilator, use a different power Dust collection capacity decreases
(OFF when the temperature is at or more B View (For FXMQ250MFV1) Power supply (Obtain locally)
than 5°C) Relay box supply from that of the electric heater and install a circuit collection capacity remarkably after use for a period of time.
breaker for each.

18381
75 76
82184
Air Treatment Equipment Lineup

(Option) for VAM / FXMQ-MF series PM2.5 Filtration Unit


Models BAF249A150 BAF249A300 BAF249A350 BAF249A500 BAF429A20A
more comfortable environments Dimensions (H × W × D)
Connection Duct Diameter
220×603×366
100
220×603×366
150
300×623×366
150
300×623×366
200
470×971×370
580×348
150 250 350 500 2,100
Initial Pressure Drop 34 30 31 42 less than 40
Filter Lifetime 1 1 year
PM2.5 Filter 2
99% or higher
Filter Material No. 3 BAF244A300 BAF244A500 BAF424A20A
Note: 1. Annual usage: 400 hrs/month x 12 months = 4,800 hrs
Removal Rate el numbers.

PM2.5 with Activated Carbon Filtration Unit


*Test results by the Heating, Ventilation and Air Conditioning Lab at Tongji University
Test environment: temperature 25-26°CDB, humidity 58-60%RH Models BAF249A150C BAF249A300C BAF249A350C BAF249A500C BAF429A20AC
Dimensions (H × W × D) mm 220×603×366 220×603×366 300×623×366 300×623×366 470×971×370
Connection Duct Diameter mm 100 150 150 200 580×348
m3/h 150 250 350 500 2,100
Extra-High Performance Filter Against Sulfur Oxides and Initial Pressure Drop Pa 34 30 31 42 less than 40
Nitrogen Oxides PM2.5 Filter
Filter Lifetime 1
2
1 year
99% or higher
Effective Use of Active Carbon Material to Filter Material No. 3 BAF244A300 BAF244A500 BAF424A20A
Enlarge the Adsorption Area Initial Pressure Drop Pa 3 5 5 9 less than 10
Activated 1 year
Filter Lifetime
Carbon Filter
Filter Material No. 3 BAF244A300C BAF244A500C BAF424A20AC
Total Initial Pressure Drop for PM2.5
Pa 37 35 36 51 less than 50
with Activated Carbon Filtration Unit
Note: 1. Annual usage: 400 hrs / month × 12 months = 4,800 hrs.
Note: Surface area of active carbon: 700 m2/g
Given a newspaper page of 40.6 cm wide by 54.6 cm long, each gram of active
carbon has a surface area of 3,000 newspaper pages. el numbers.

The special substance added in the pores of active carbon can exclusively
target sulfur oxide and nitrogen oxide gases and stick to them without

Adhesives

Air Treatment
Equipment Lineup
77
18583 8478
186
Control Systems

Individual Control
Individual Control Systems
Systems for VRV Systems
for VRV Systems

Navigation Remote
Navigation Remote Controller
Controller (Wired
(Wired remote
remote controller)
controller) (Option)
(Option) Convenience
Convenience Setback Recovery
temperature differential
࡛ Setback (default:
•Setback (default: OFF)
OFF) Setback Recovery
This simple,
This simple, modern
modern designed
designed remote
remote controller
controller with
with fresh
fresh white
white colour
colour Cooling 33 37ºC
temperature -2 -8ºC
differential
Maintains the room temperature in a specific range during unoccupied period
matches your
matches your interior
interior design.
design. Operation
Operation is
is much
much easier
easier and
and smoother,
smoother, just
just by temporarily
by temporarily starting
starting air
air conditioner
conditioner that
that was
was turned
turned OFF.
OFF.
follow the
follow the indications
indications on
on the
the navigation
navigation remote
remote controller.
controller. Cooling 33 37°C -2 -8°C
Ex) Setback
Ex) Setback temperature
temperature Cooling
Cooling :: 35ºC
35ºC Recovery differential
Recovery differential Cooling
Cooling :: -2ºC
-2ºC
When the
When the room
room temperature
temperature goes
goes above
above 35ºC,
35ºC, the
the air
air conditioner
conditioner starts
starts operating
operating in
in Cooling
Cooling automatically.
automatically.
When room
When room temprature
temprature reaches
reaches 33ºC,
33ºC, the
the air
air conditioner
conditioner returns
returns OFF.
OFF.

Clear display
Clear display ࡛ Weekly schedule
•Weekly schedule
࡛ Dot matrix ·ʓ 55 actions
actions per
per day
day can
can be
be scheduled
scheduled for
for each
each day
day of
of the
the week.
week.
•Dot matrix display
display ࡛ Backlight display
•Backlight display
·ʓ The
The holiday
holiday function
function will
will disable
disable schedule
schedule timer
timer for
for the
the days
days that
that have
have been
been set
set as
as holiday.
holiday.
·ʓ A combination of fine dots enables various ·ʓ Backlight
Backlight display
display helps
helps operating
operating in
in
BRC1E63
BRC1E63 ·ʓ 3
3 independent
independent schedules
schedules can
can be
be set.
set. (e.g.
(e.g. summer,
summer, winter,
winter, mid-season)
mid-season)
icons.
icons. Large
Large text
text display
display is
is easy
easy to
to see.
see. dark
dark rooms.
rooms.

College classroom
College classroom sample
sample (a
(a summer
summer Monday
Monday case)
case)

1) 8:30
1) 8:30 ON
ON 2) 10:00
2) 10:00 OFF
OFF 3) 13:00
3) 13:00 ON
ON 4) 15:00
4) 15:00 OFF
OFF
The first period starts and the In the
In the second
second period,
period, the
the classroom
classroom When the
When the third
third period
period starts,
starts, After the
After the third
third period,
period, the
the classroom
classroom
air conditioner
air conditioner starts
starts the
the cooling
cooling is unoccupied
is unoccupied and
and the
the air
air conditioner
conditioner operation starts
operation starts again.
again. becomes vacant
becomes vacant again
again and
and the
the
operation.
operation. stops.
stops. air conditioner
air conditioner stops.
stops.
ON
ON OFF
OFF ON
ON OFF
OFF

BRC1F61
BRC1F61
(Only for
(Only for FXEQ andFXEQ series)
FXDSQ series)

Simple operation
Simple operation
࡛ Large buttons
•Large buttons and
and arrow
arrow keys
keys
࡛Auto display
•Auto display off
off
Large buttons
·ʓ Large buttons and
and arrow
arrow keys
keys enable
enable easy
easy operation.
operation. Basic
Basic setting
setting such
such as
as fan
fan
·ʓ While
While operation
operation is
is stopping,
stopping, LCD
LCD display
display can
can be
be turned
turned OFF.
OFF. ItIt will
will be
be displayed
displayed again
again ifif any
any button
button is
is pressed.
pressed.
speed and
speed and temperature
temperature can
can bebe intuitively
intuitively operated.
operated. For
For other
other settings,
settings, select
select the
the
ʓ· Period
Period can
can be
be preset
preset from
from 10,
10, 30,
30, 60
60 minutes,
minutes, and
and OFF.
OFF. Initial
Initial setting
setting is
is 30
30 minutes.
minutes.
function from
function from the
the menu
menu list.
list.
࡛ Guide on
•Guide on display
display
·ʓ The
The display
display gives
gives an
an explanation
explanation of
of each
each setting
setting for
for easy
easy operation.
operation.
Comfort
Comfort
࡛ Individual airflow direction (*1)
Airflow direction can be individually adjusted for each air discharge outlet to deliver optimal air distribution that conforms to
Energy saving
Energy saving conditions for airflow direction (small and large loads).
*1. Only
*1. Only available
available for
for FXF(S)Q-A,
FXF(S)Q-A and FXUQ-A
FXCQ-A andseries.
FXUQ-A series.
࡛ Setpoint range
•Setpoint range set
set ࡛ Setpoint auto
•Setpoint auto reset
reset
·ʓ Saves
Saves energy
energy by by limiting
limiting the
the min.
min. and
and max.
max. ·ʓ Even
Even ifif the
the set
set temperature
temperature is is changed,
changed, the
the new
new set
set ࡛5-step airflow control (*2)
set
set temperature.
temperature. temperature
temperature returns
returns to
to the
the previous
previous preset
preset value
value Control of airflow rate can be selected from 5-step control, which provides comfortable airflow.
ʓ· Avoids
Avoids excessive
excessive cooling.
cooling. after
after a
a preset
preset duration
duration of
of time.
time. *2 . The number of airflow steps differs according to the type of indoor unit. 5-step airflow is only available for FXF(S)Q-A and FXEQ-A series.
·ʓ This
This function
function isis convenient
convenient when
when the
the remote
remote ʓ· Period
Period selectable
selectable from
from 30,
30, 60,
60, 90,
90, or
or 120
120 min.
min.
controller
controller is
is installed
installed at
at a
a place
place where
where ࡛ Auto airflow rate (*3)
any
any number
number of of people
people may
may operate
operate it.
it. Airflow rate is automatically controlled in accordance to the difference between room temperature and set temperature.
Restaurant sample
Restaurant sample *3 .Only
*3 .Only available
available for
for FXF(S)Q-A,
FXF(S)Q-A, FXCQ-A,
FXEQ-A, FXDQ-PD/ND, FXSQ-PA,
FXEQ-A, FXDSQ-A, FXMQ-PAFXSQ-PA,
FXDQ-PD/ND, and FXUQ-A series. FXUQ-A and FXAQ-A series.
FXMQ-PA,

Restaurant opened
Restaurant opened Full tables
Full tables at
at lunchtime
lunchtime After 30
After 30 minutes*
minutes*
Level 1 (Low) Level 2 Level 3 (Medium) Level 4 Level 5 (High) Auto
Temperature is
Temperature is set
set to
to 27ºC
27ºC Then is
Then is lowered
lowered to
to 24ºC
24ºC Automatically returns
Automatically returns to
to preset
preset
for crowded
for crowded room
room temperature (27ºC)
temperature (27ºC) Returns
Returns to
to
27 °C
27 °C 24 °C
24 °C 27°C
27 °C
automatically
automatically

Control
Systems
࡛ Off timer
•Off timer
·ʓ Turns
Turns off
off the
the air
air conditioner
conditioner after
after a
a preset
preset
period
period of
of time.
time.
ʓ· Period
Period can
can bebe preset
preset from
from 30
30 to
to 180
180 minutes
minutes *Preset-return time
*Preset-return time can
can be
be set
set
at 30,
at 30, 60,
60, 90,
90, or
or 120
120 min
min
in
in 10-minute
10-minute increments.
increments.

18785
79 86188
80
Control Systems

Individual Control Systems for VRV Systems Wide variation of remote controllers for VRV indoor units

FXFSQ FXFQ FXZQ FXUQ FXCQ FXEQ FXDSQ FXDQ FXSQ FXMQ FXHQ FXAQ FXL(N)Q FXVQ FXB(P)Q

(Option) Navigation remote controller


(BRC1E63)

Easy operation with new intuitive design Navigation remote controller


(BRC1F61)

Simple operation
(BRC2E61)
•Using only six buttons, users have direct
access to basic functions. Wireless remote controller*
(Installed type signal receiver unit)
This enables them to easily set comfort to their
preference.
BRC2E61 Wireless remote controller*
(Separate type signal receiver unit)
·ON/OFF ·Operation mode
*Refer to page 103
211 for the name of each model.
·Temperature setting

The wired remote controller supports a wide range of control functions


·ON/OFF timer
In all the series of VRV, Cool/Heat changeover in the same refrigerant circuit can be changed by the
• Control of Cool/Heat
changeover remote controller of the indoor unit.
rate and swing mode depend on the type of indoor unit.

•Group control
Intuitive design Equipment One remote controller can control the
Outdoor related to the operation of max.16 indoor units at
•By using pictograms, the user-friendly interface enables operation is much easier and unit the same time.
central control
smoother.

Compact size
•Measuring only 85 x 85 mm, the new remote controller is extremely compact and Indoor unit
Remote controller
complements any interior design.
Remote controller

Wireless remote controller (Option) Remote


controller
•The wireless remote controller is supplied in a set with a signal receiver.
•Signal receiver unit of installed type is contained inside decoration panel or indoor unit. Forced OFF
input
•Shape of signal receiver unit differs according to the indoor unit.
Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of
FXF(S)Q series. Heat Reclaim
Ventilator
Remote controller Remote
controller Remote
•Backlight LCD of new wireless remote controller controller
Remote controller Remote
Signal receiver unit controller
(Installed type)

1 2 3 4

Pressing the backlight button


BRC-M series helps operating in dark rooms.
1 Control by two remote controllers 2 Remote control
The indoor unit can be connected by the two remote The wiring of remote controller can be extended to max.
controllers, for example one in the room and the other one 500 m and it is possible to install the remote controllers for
•A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is in the control room, which can control the operation of different indoor units in one place.
included. indoor unit freely.(The last command has a priority.)
Of course, the group control by two remote controllers is
* Wireless remote controller and signal receiver unit are sold as a set. also possible.
* Refer to page 211
103 for the name of each model.

Control
Systems
3 Control for the combined operation 4 Expansion of system control

Signal receiver unit The operation of Heat Reclaim Ventilator can be controlled The system can be expanded to add several controllers,
(Separate type) by the remote controller of the indoor unit. Of course, the such as BMS, Forced OFF input and etc.

BRC-C, E series

18987
81 88190
82
Control Systems

Integrated Building Monitoring System


DIII-NET Line
The DIII-NET system provides for:
BACnet®/Ethernet or LONWORKS®
The high speed transmission of DIII-NET enables more advanced control of the VRV system, providing you with Network Communication Line ࠮ Close control and monitoring by integrating a wide variety of air-conditioners in the
enhanced comfort. entire building.
Contact Signal Line ࠮ Saves the in-building cabling using non-polar, two-wire cables. Easier wiring work
with tremendously fewer wiring errors.
RS485 Modbus Line ࠮ Additional setups readily up and running. An extendable cabling up to 2 km in total.
࠮ Different control equipment flexibly joined in the system for hierarchical risk
diversification.
Building Control System ࠮ Daikin's total heat exchangers and other devices under integral control.

Controllers for Centralised Control


VRV

(DCS601C51)
Heat Reclaim Ventilator

(DCM601A51)

Via internet
Residential central
remote controller D -NET Interface Adaptor for SkyAir Series
(DCS303A51) SkyAir
(High Speed Multiple (DTA112BA51)
Transmission)
Via internet
* No adaptor is required for
some indoor units.
ACC Centre Control /Connection Interface
Central Control Adaptor Kit
Air Conditioning Network Service System DIII-NET, Daikin’s unique Packaged
(DTA107A55) Air-conditioner
(There are restrictions in applicable areas and Unification adaptor high speed multiple
release times, therefore please consult us for computerised control transmission system, links
separately for details.) (DCS302A52) air conditioners
(Optional Maintenance Service) and various other building
Home Automation
equipment—in
Master Controller accordance with Interface Adaptor for DIII-NET use
applications, scale and (KRP928BB2S)
Home Automation conditions—and transmits Residential Air-conditioner
Interface Adaptor vast amounts of
(DTA116A51) information between
BMS
them.
(Obtain locally)

Di unit (DEC101A51) Building services equipment


Interface for use in BACnet®
(DMS502B51) Dio unit (DEC102A51) ࠮Electrical equipment
࠮Supply water and drainage equipment
࠮Automatic fire alarm
࠮Parking equipment
࠮Lift
࠮Ventilation equipment
࠮Lighting
࠮Crime and fire prevention equipment
Interface for use in LONWORKS®
(DMS504B51)

VRV Caution:
Limitation may apply to some models and functions. Please contact your local sales office for details.
Consultation is necessary before employing this control system. Please contact your local sales office before
making a purchase.
Wiring adaptor Note: BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning
for electrical appendices Engineers (ASHRAE). LONWORKS® is a trademark of Echelon Corporation registered in the United
(KRP2A61/62/53) States and other countries.

83 89 90 84
Control Systems

Advanced Control Systems for VRV Systems


For Energy Saving & Comfort
One touch selection enables flexible control of equipment in a building. intelligent Touch Manager maximises the advantages of VRV features

intelligent Touch Manager is an advanced multi-zone controller that provides the most cost-effective way to
control and monitor the Daikin VRV system.
The 10.4" LCD touch screen is easy to use with three different screen views to include the floor plan layout
view, icon view and list view and menus for system configurations.
It is also easy to use with standardized remote Web Access from your PC.
It can manage a total of 650 management points consisting of up to 512 Daikin indoor unit groups
(up to 1024 indoor units) along with building equipment control / monitoring with Digital Inputs / Output
DCM601A51 (Di/Dio), Analog Inputs / Output (Ai/Ao) and Pulse input (Pi) optional devices.

Various types of equipment in a building


can be controlled by a single controller. Schedule the operation time for each application. Define the setpoint range that users can change.
With Remote controller
Individual air-conditioning control
This heat is killing me.
The flexible control achieved by the VRV system
Reception: Very cold.
precisely meets different air conditioning needs in each
Office: 9:00-17:00
room (e.g. offices, conference rooms, hotel rooms). 8:00-18:00
Admin: 16°C
8:30-17:00
Machine room:
24 hours

With Control System


Manager room:
Set point range 22°C - 28°C
8:00-20:00

It can not
Why? be set
Common area: below this Oh! Cool.
Lighting control DALI-compatible
DALI-compatible Meeting room: 9:00-17:00
No schedule
DALI-compatible LED lighting systems can be
controlled and monitored. Lighting control is enhanced
22°C
through an interlock function with air conditioners and
other functions.
Turn the unit OFF if a user didn’t. Reset setpoint regularly.

Change to 20°C
Stop Start

Air-conditioning control for large spaces Building equipment control Working hours Turn ON again by remote controller, 24ºC
(Scheduled) forgot to turn OFF, and left. Saved power consumption
Air handling units can also be controlled. Large Various types of equipment other than air conditioners, by control system
spaces, such as entrance halls and shopping malls, including ventilators, fans, and pumps, can also be 20ºC
can be easily controlled to ensure comfort. controlled. Saved power consumption
by control system
8:00 17:00 18:30 8:00 8:00 10:00 18:00 8:00

Pump Fan Turn off Automatically turn OFF


Set at 24°C Reset to 24°C
as scheduled to cut wasteful operation

85 91 92 86
Control Systems

Advanced Control Systems for VRV Systems


In addition to switching lights on and off, advanced lighting control, Tenant Management ( PPD* Option )
such as illuminance adjustment, can be achieved Reporting the power consumption of VRV system for each tenant
Lighting control (Option) With the PPD function, power consumption can be calculated for each indoor unit (Option)
Connection to DALI - compatible lighting control system The energy consumption is proportionally calculated for
DALI-compatible
DALI-compatible each indoor unit. The data can be used for energy
Simple wiring (daisy chain) enables management of LED lighting by the Operational information
Please contact your local sales office for details. management and calculation of air conditioning usage of individual indoor units
intelligent Touch Manager. fees for respective tenants. Tenant A
Various air conditioning and lighting control is enabled through the interlock with HIGH
Operation duration
occupancy sensors and illuminance sensors. Operational information of individual indoor units are Room temperature
Expansion valve
monitored, based on distribution of power consumption opening ratio
Air conditioning and lighting for which power consumption is high can be of outdoor units. Tenant B
LOW
efficiently controlled to promote energy conservation and cost reduction! Automatic calculation of
Lighting control achieved by Daikin’s PPD keeps track of power distribution for each

m om
total power consumption of
indoor unit. It performs air conditioning billing

h al fr
the intelligent Touch Manager

er
individual indoor units

et
kW ign
calculations quickly and automatically.

th se s
System Tenant C

l
[Operation] MEDIUM

Pu
e
Tenant B
It is easy to output PPD data.
• Switch-on/switch-off operation PPD data is output in CSV format to a PC or USB memory Tenant A Tenant C
• Illuminance (1–100%) control device and can be freely processed and managed.
• Various illuminance patterns can be registered DCM009A51
Total power consumption
• Registered pattern can be selected from (BACnet® Client option) LAN *PPD (Power Proportional Distribution) is Daikin’s proprietary calculation method. kWh meter
intelligent Touch Manager

WAGO I/O system


[Monitoring]
BACnet® DALI BUS
Air conditioning bills can be issued by one click
DALI module
• Switch-on/switch-off status monitoring controller
• Lighting abnormality monitoring 750-831
753-647
Electricity bills can be easily calculated for each tenant (Option)
DALI LED driver
• Illuminance monitoring
Sensor The power consumption of VRV controlled by the
• DALI occupancy sensor monitoring LED light (occupancy /
intelligent Touch Manager can be easily managed for Internet / Ethernet
• DALI illuminance sensor monitoring illuminance)
each tenant using a PC. The electricity bill settings
facilitate billing work through easy calculation and HUB
Invoice
SVMPS1
issuance of VRV electricity bills. Invoice Invoice

User’s PC
[Overview of control] [ Main functions ]
• Up to 5 DALI modules can be connected to a • 64 DALI addresses can be freely assigned to up • Up to 16 scenes can be set to a single DALI • Register tenants
single BACnet® controller. to 16 groups using a single DALI module. module.
• Set the electricity unit price for 5 time zones
• Up to 64 DALI LED drivers (64 addresses) can (Each group corresponds to a management point • Up to 12 sensors (occupancy, illuminance) can be • Calculate power consumption and electricity charge for each tenant
be connected to a single DALI module. of the intelligent Touch Manager.) connected to a single DALI module. • Show aggregation results in the specified period for each tenant
• DALI BAS simplifies wiring and setting work by • Output the results (Printout and CSV file)
daisy chain wiring and automatic address setting.

Easy maintenance and energy saving by lighting control


Tenant registration screen Setup screen VRV electricity bill screen
Case1 Case2 Case3
Switch-on / switch-off and illuminance Occupancy sensors are used to Lighting abnormalities (e.g. burned-out
Effective service functions offered to tenants
are controlled based on a schedule to eliminate both wasteful lighting and air bulbs) can be checked on
cut wasteful power consumption. conditioning. the intelligent Touch Manager screen. Smart phone will be a remote controller of VRV system (Option)
When a room is unoccupied, Users can operate and check the status of VRV
• Failing to switch
For buildings VRV Smart Phone Remote Controller
the air conditioning stops and the Lighting maintenance becomes easier and system from their smart phones via Wi-Fi.
off lights is prevented. Up to 1024 indoor units can be controlled. VRV Indoor unit
quicker.
lighting is switched off. It is not necessary to move where a remote controller
Just add SVMPC2 to
is located with this feature. this system
OFF OFF VRV system in other rooms can be operated, and
their status can be checked.
It is also possible to check if air conditioners in other
SVMPC2 VRV
rooms remain switched on etc., helping achieve Outdoor unit
energy saving. LAN cable
The layout screen enables quick You can control
• Optimal illuminance reduces energy.
identification of specific locations. VRV system from
Wi-Fi router Smart phone anywhere through Wi-Fi

87 93 94 88
Control Systems

Advanced Control Systems for VRV Systems


Home Automation Interface Adaptor VRV Tablet Controller : SVMPC1
The VRV system can be operated from the home automation system. TheVRV Tablet
SVMPC1 andto
is easy Smartphone Controller
install, and enables : SVMPC1
monitoring and operation of VRV systems via
Image to use Home Automation Interface Adaptor DTA116A51 tablets
The and smartphones.
SVMPC1 is easy toItinstall,
is optimal for centralized
and enables management
monitoring of VRV
and operation ofsystems in small
VRV systems via
buildings
tabletsor on smartphones.
and individual floorsIt isofoptimal
a building.
for centralized management of VRV systems in small
Up to 16 indoor units can be individually controlled.
Simple and easy
Simple and easy Smart Control
VRV Indoor unit Smart Control Up to 32 indoor units can be monitored and controlled.
• SVMPC1 is easy to install. Just add Up to 32 indoor units can be controlled.
VRV Indoor unit
• SVMPC1 is easy to
DTA116A51 to outdoor
install. Just
unitadd
and SVMPC1 VRV Indoor unit
DTA116A51
connectto it outdoor unit and
to controller. SVMPC1
connect it to to
• Thanks controller.
user-friendly screen, anyone
• Thanks
canto user-friendly
operate easily. screen, anyone
DTA116A51
can operate easily. WiFi DTA116A51
Wi-Fi router VRV
router VRV Outdoor unit
Outdoor unit
Other Home
Home Automation Appliances VRV Indoor unit
Use
Use of
of Modbus
Modbus® protocol
protocol Master Controller VRV Indoor unit

RS485 Modbus®Protocol
Protocol Internet
Internet
Wire length is up to 500m
500 m Television
• Set point range limitation and setback DTA116A51
VRV Outdoor unit • SVMPC1 allows
function operation
achieve energy VRV and
of saving DTA116A51 VRV
VRV Outdoor unit
Simple installation system from anywhere(inside
comfortable and
air-conditioning. Outdoor unit
Compatible with
The VRV outdoor unit and home automation Compatible with Electric curtains outside of air-conditioning
• Daily a premise) through the
operation is
Up to 2 units can be DTA116A51* an existing unit.
connected One Adaptor
adaptor system can be connected simply by using internet.
automatically done by schedule function It is easy to check You can control
requires for a house this dedicated adaptor. • Set point range limitation
with annual calendar.and setback if units have
The system not
can be VRV system from
Lighting function achieve energy saving and beenfrom
operated switched off, You can controlthrough
anywhere
*A separate power supply for Home Automation Interface
Interfere Adaptor
Adaptor is
is necessary.
necessary. equipment
outsideetc.a building system from
VRV WiFi
It may not be installed inside some outdoor unit models. comfortable
e-mail toair-conditioning.
support quick maintenance.
via the Internet. anywhere through
• Daily air-conditioning operation is WiFi
Functions
automatically done by schedule function It is easy to check
if units have not
Functions with annual calendar.
Category Function Detail been switched off,
Monitor Control • Quick
Main notification
screen of malfunction
Status monitoring by On/Off, Setpoint, Operation mode,etc.Fan step, Flap, Error, Error code, Room Temperature
e-mail to supportManual
quick maintenance.
operation On/Off, Setpoint, Operation mode, Fan step, Flap, Scene Control
On/Off On/Off status of indoor units On/Off On/Off control of indoor units
Cooling, Heating, Fan, Dry, Auto Cooling, Heating, Fan, Dry, Auto Automatic Setpoint range limitation* Cool setpoint min/max, Heat setpoint min/max
Operation mode Operation mode control Off timer* Off timer on/off, Off timer duration (5min – 12h, every 5min)
(depend on indoor unit capability) (depend on indoor unit capability)
Setpoint Setpoint of indoor units Setpoint Cooling/Heating setpoint Setback operation* Setback setpoint range (Cool: 24-35°C, Heat: 10-20°C)
Schedule* Action registration: Time, On/Off, Setpoint, Operation mode, Fan step, Flap, Off timer on/off, Setback setpoint
Room temperature Suction temperature of indoor units Fan direction Swing, Stop, Flap direction (depend on indoor unit capability) Functions
Fan direction Swing, Flap direction (depend on indoor unit capability) Fan volume L, M, H (depend on indoor unit capability) Calendar setting: set by date or day of the week *
: only admin user can set
Category Function
Interlock DetailInterlock operation depend on equipment status
Fan volume L, M, H (depend on indoor unit capability) Filter sign reset Reset filter sign of indoor units
Access security
System User login
setting User name, password
Language, Password setting, User administration*, Point setting*
Forced off status Forced off status of indoor units
Retrieve system information Device
userregistration Registered device (Tablet, Smartphone) can access through the internet
Error Malfunction, Warning with Error code
Connected indoor units D -NET address of connected indoor units can be retrieved. *: Only admin
Main screen
can set.
Status monitoring On/Off, Setpoint, Operation mode, Fan step, Flap, Error, Error code, Room Temperature
Filter sign Filter sign of indoor units
Indoor unit capabilities such as operation mode, Manual operation On/Off, Setpoint, Operation mode, Fan step, Flap
Communication status Communication normal/error of indoor units Indoor unit capabilities
fan control, setpoint HV can be retrieved. Category Setpoint range limitation* Cool setpoint
Automatic Detail min/max, Heat setpoint min/max
ConnectableOff timer*
control Number of indoor units Off timer
Maxon/off,
16 (perOff timer duration (5min – 12h, every 5min)
DTA116A51)
units Setback operation*
Number of DTA116A51 Setback
Maxsetpoint rangeof
2 (maximum (Cool: 24-35°C,
32 indoor unitsHeat: 10-20°C)
can be connected)
VRV Smart PhoneControl
Smartphone ControlSystem
System ConnectableSchedule* ActionMax
Number of Tablet/Smartphone registration:
20 Time, On/Off, Setpoint, Operation mode, Fan step, Flap, Off timer on/off, Setback setpoint
device Device type Calendar
iPad,setting:
iPhone,set by date
Android or day
tablet, of the week
Android Phone, Windows Tablet, Windows Phone, Windows PC, Mac
VRV Smart PhoneControl
Smartphone ControlSystem
Systemcan
canbe
berealized
realizedby
bySVMPR1
SVMPR1which
whichisisaanew
newproduct
producttotoutilize
utilizeDTA116A51.
DTA116A51. System setting LanguageWeb browser English, Spanish,
Firefox, Portuguese,
Chrome, Safari Thai, Vietnam, Simplified Chinese, Traditional Chinese
Password setting
VRV Indoor unit
Just add Multi Site Management System by using SVMPC1: MSMPN1
User administration*
Point setting*
Add/Modify/Delete user, Set User name, Password, Accessible points
Set point name, Select icon
SVMPR1 The MSMPN1 enables monitoring and operation of all Function
SVMPR1 DTA116A51 Specifications
VRV system connected via SVMPC1 on each site. Monitoring: All site information show on a MSM screen.
Category Specification Detail Connection status, A/C operation status,
Head Site Site Error status, Energy consumption etc.
LAN cable Connectable
Quarters
MSMPN1
Number of indoor units Max 32 (with additional DTA116A51)
Operation: All SVMPC1 function can use on MSM
You can control units Number of DTA116A51 Max 2
screen.
VRV from Connectable Number of Tablet/Smartphone Max
Internet 20
VRV Indoor unit
anywhere in your device Device type iPad, iPhone, Android tablet, Android Phone, Windows Tablet, Windows Phone, Windows PC, Mac

Control
Systems
VRV Outdoor unit SVMPC1
house through WiFi Web browser Firefox, Chrome, Safari
WiFi router
Smart phone
Smartphone Monitor Control
WiFi DTA116A51
Modbus is a registered trademark of Schneider Electric S.A.
Modbus ®
router
VRV
Outdoor unit

WiFi router

89
19995 96 90
Option List OptionOption
List List

Outdoor Units VRV Indoor


VRV Units
Indoor Units
X SERIES Options ofACeiling
Options
SERIES Mounted Cassette
of Ceiling ( Round
Mounted Cassette
Flow with
( Round
Sensing
Flow&with
Round
Sensing
Flow )&Type
Round Flow ) Ty
Type RXUQ12A RXUQ12AM RXUQ18AM1 Type
RXUQ6A RXUQ14A RXUQ14AM RXUQ20AM1 Options requiredOptions
for specific
required
operating
forRXQ6A
specific
environments
RXQ8A
operating environments
RXQ12A
RXQ14A
RXQ18A
RXQ20A
RXQ18AM
RXQ20AM
No. RXUQ8A RXUQ16A RXUQ16AM RXUQ22AM No.
RXQ10A RXQ16A RXQ22AM
Item
RXUQ10A RXUQ18A
RXUQ20A
RXUQ18AM
RXUQ20AM
Ultra long-life
Item Ultra
filterlong-life
unit filter unit Fresh air intake kit air
Fresh intake
Note 1,
Note 1.22 kit Note 1,
Note 1.22
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H
KHRP26M22H, KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H Even
Even in dusty
1 in dusty environments
Even
REFNET
environments
Distributive Even inwhere
header
in dustythe
where
dusty environments
the air
air conditioning
environments
conditioning where
where
(Max. 4 branch) the
the air Using this
Using this(Max.
air conditioning
(Max. 8 branch) conditioning kit, 4a
kit, abranch)
duct (Max.
duct can
Using
can
Using be
8be this
connected
this
branch) kit, a
connected
kit,
(Max. a8 branch)
duct
to take
duct
to take
can be
can be
in outdoor
in outdoor
connected to
connected to take
take in
in
Distributive REFNET header piping
1
piping
(Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
is constantly operating, is the
REFNETconstantly
jointultra long-life
operating,
filter the
onlyultra
KHRP26A22T, long-life filter
KHRP26A33T air.only
air. There
There are
are two
two chamber
KHRP26A22T, air. There
chamber
air. types
There
types
KHRP26A33T, are
arethat
two
that
two have
chamber
have
KHRP26A72T intake
intaketypes
chamber in
in two
twothat
types that have
have intake
intake ii
REFNET joint KHRP26A22T, KHRP26A33T KHRP26A22T, KHRP26A33T, KHRP26A72T has 2to
has to be
beOutdoor
cleaned
cleaned once
once
unit multi has
a year.
has
a year.
to be
to be
connection cleaned
cleaned
piping kit once a
once a year.
year. places:
places: with T-duct
— with T-duct joint
places:
joint and
and without
places: with T-duct
T-duct
without
with T-duct
joint
T-duct joint.
joint and
and without
joint. without T-duct
BHFP22P100 T-duct joint.
joint.
2 Outdoor unit multi connection piping kit — BHFP22P100
Filter
Filter chamber
chamber Filter chamber
Filter chamber Outside
Outside Outside
Outside
Type
(Can be used with high-efficiency
(Can
filter)
be used with high-efficiencyRXQ34AM
RXQ24AM filter) RXQ42AM RXQ52AM
Type RXUQ24AM RXUQ34AM RXUQ42AM RXUQ52AM RXQ26AM RXQ36AM RXQ44AM RXQ54AM
RXUQ26AM RXUQ36AM RXUQ44AM RXUQ54AM No. RXQ28AM RXQ38AM RXQ46AM RXQ56AM
No. RXUQ28AM RXUQ38AM RXUQ46AM RXUQ56AM RXQ30AM RXQ40AM RXQ48AM RXQ58AM
RXUQ30AM RXUQ40AM RXUQ48AM RXUQ58AM Item Ultra long-life filter Ultra long-life filter
RXQ32AM RXQ50AM RXQ60AM
Item RXUQ32AM RXUQ50AM RXUQ60AM
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Dusty area: annual
1
filter change
Distributive Dusty
REFNET area: annual filter change
header The units
units can
can be
be The
The
installed
units in
in
can
thebe
befollowing
following
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
The installed
units can
the installed in
installed in the
the followi
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch) followi
Distributive REFNET header *For dust
*For piping
dust concentration
concentration of
of 0.3
0.3 mg/m
mg/m*For
*For
(Requires
dust concentration
dust concentration
separately sold
of Air
of 0.3purifier.)
0.3
different ways
different
mg/m (Requires separately sold Air purifier.)
mg/m
different ways
ways different ways
3
3 3
3

1 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)


piping 1 year
1 year (Approx.
(Approx. 5,000
5,000 hr)
hr) 15
15 hr/day
hr/day
REFNET1x
1 xyear
year
28joint
28 day/month
(Approx. 5,000
day/month
(Approx. 5,000
x 12
x 12hr)
hr)
month/year
15 hr/day
hr/day x
month/year
15 x 28
28 day/month
day/month x
x 12
12 month/year
month/year
KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
2 Pipe size reducer KHRP26M73TP, KHRP26M73HP
2
Ordinary Pipeorsize
store reducer
office: filterOrdinary
change store
every or
4 years
office: filter change every 4 years Chamber
Chamber type (without
type Chamber
KHRP26M73TP, KHRP26M73HP
(withoutChamber
T-duct type
type
T-duct joint)
joint) (without
Note 3.4.5
(without
Note 3, 4, 5 T-duct joint)
T-duct joint) Note
Note 3,
3.4.5
4, 5
*For dust
*For dust concentration
Outdoorof
3 concentration of 0.15
unit mg/m
multi
0.15 mg/m *For dust concentration
connection
*For
3
3
dust concentration of 0.15
piping kit of 0.15 mg/m
mg/m33 BHFP22P100 BHFP22P151
3 Outdoor unit multi connection piping kit BHFP22P100 BHFP22P151 4 years
4 years (Approx.
(Approx. 10,000
10,000 hr)
hr) 8 4 years
8 hr/day
hr/day
4 years
x 25
x (Approx.
25 (Approx.
day/month
day/month10,000
x 12
10,000
x hr) 8
12 month/years
month/years
hr) 8 hr/day
hr/day x
x 25
25 day/month
day/month x
x 12
12 month/years
month/years KDDP55B160
KDDP55B160 KDDP55B160
KDDP55B160
x4
x 4 years
years x4
x 4 years
years
Flexible duct
Flexible duct Flexible duc
Flexible duc
REFNET joint (KHRP26A22/33/72/73T) (obtained locally)
(obtained locally) (obtained lo
(obtained lo
High-efficiency
High-efficiency
filter unit filter unit T-duct joint
T-duct joint T-duct joint
T-duct joint
(obtained locally)
(obtained locally) (obtained lo
(obtained lo
Available in
Available in two
two types:Available
65%
65% and
andin
types:Available in90%
two
two types:
90% colorimetry.
types: 65%
65% and
colorimetry. and 90%
90% colorimetry.
colorimetry.
Suction
Suction Suction
Suction
chamber
chamber chamber
chamber Intake duct
Intake duct Intake duct
Intake duct
(obtained locally)
(obtained locally) (obtained lo
(obtained lo
Filter chamber
Filter chamber Filter chamber
Filter chamber (duct length:
(duct length: 4
4mm max.)
max.) (duct length
(duct length
Connection
Connection Connection
Connection
(Can be used with ultra long-life filter)
(Can be used with ultra long-life filter) chamber
chamber chamber
chamber

Chamber type
Chamber type (with Chamber
Chamber
(with T-duct
T-duct joint) type
type
joint) Note
Note (with
3.4.5
3, (with T-duct joint)
4, 5 T-duct joint) Note 3,
Note 3.4.5
4, 5
Option PCB High-efficiency filter High-efficiency filter
Option PCB KDDP55B160K
KDDP55B160K KDDP55B160K
KDDP55B160K
Type RXUQ10A
RXUQ12AM Type RXQ6A RXQ14A RXQ18AM RXQ26AM
No.
RXUQ6A
RXUQ12A
RXUQ14A
RXUQ14AM
RXUQ16AM
RXUQ18AM Insulation
No.
kitInsulation
for high humidity
kit forRXQ8A
high humidity
RXQ16A RXQ20AM
Flexible duct
Flexible
RXQ28AM
duct Flexible duc
Flexible duc

RXUQ8A RXUQ16A RXUQ20AM RXQ10A RXQ18A RXQ22AM RXQ30AM


RXUQ18AM1 Please use
Please use
Item
if you
if you thinkPlease
thinkPlease
the temperature
the temperature
use if
use if you
you think
think
and
and humidity
theRXQ12A
temperature
humidity
the and
temperature
and humidity
humidity
RXQ20A RXQ24AM T-duct joint
T-duct joint T-duct joint
T-duct joint
RXUQ18A
Item RXUQ20A
RXUQ20AM1 inside
inside
1
the
the ceiling
ceiling exceeds
exceedsinside
inside
DIII-NET expander adaptor
30°C
the
30°C
the and
ceiling
and RH
ceiling
RH exceeds
80%,
exceeds
80%, 30°C
30°C and
and RH
RH 80%,
80%, Suction
Suction DTA109A51 Suction
Suction
chamber chamber Intake duct
Intake duct Intake duct
Intake duct
1 DIII-NET expander adaptor DTA109A51
respectively.
respectively.
2 respectively.
respectively.
External control adaptor
chamber
DTA109A61
chamber
(obtained locally)
(obtained locally) (obtained lo
(obtained lo
Connection
Connection Connection
Connection (duct length:
(duct length: 4
4mm max.)
max.) (duct length
(duct length
2 External control adaptor DTA109A61 3 Top panel
panel
Home Automation Interface
Top insulation(1)
Adaptor
insulation(1) Top panel
Top panel insulation(1)
insulation(1) chamber
chamber
DTA116A51 chamber
chamber
— insulation(2) —
3 Home Automation Interface Adaptor DTA116A51 4 Option plate for control
Top
Top adaptor
panel insulation(2)
panel insulation(2) Top panel
Top panel insulation(2) Direct
Direct installation type
BKS26A *1
installation type
Direct
Direct installation
Noteinstallation
Note 6
6 type
BKS26A *1
type Note 6
Note 6
4 Option plate for control adaptor — BKS26A *1 — BKS26A *1 Top panel
Top panel insulation(3)
insulation(3) Top panel
Top panel insulation(3)
insulation(3)
Type KDDP55X160A
KDDP55X160A KDDP55X160A
KDDP55X160A
Insulation for
Insulation for decoration
decoration panel
panel
Insulation
Insulation
RXQ32AM for decoration
for decoration panel
panelRXQ40AM RXQ48AM RXQ56AM
Type RXUQ22AM RXUQ32AM RXUQ42AM RXUQ52AM Side panel
Side panel insulation
insulation Side
Side panel insulation
panel
RXQ34AM insulation RXQ42AM RXQ50AM RXQ58AM
RXUQ24AM RXUQ34AM RXUQ44AM RXUQ54AM No. Suspension bracket
Suspension bracket insulation
insulation
Suspension
Suspension bracket insulation
bracket insulation
RXQ36AM RXQ44AM RXQ52AM RXQ60AM
No. RXUQ26AM RXUQ36AM RXUQ46AM RXUQ56AM RXQ38AM RXQ46AM RXQ54AM

Item
RXUQ28AM
RXUQ30AM
RXUQ38AM
RXUQ40AM
RXUQ48AM
RXUQ50AM
RXUQ58AM
RXUQ60AM
Panel
1
spacerPanel spacer
Item
DIII-NET expander adaptor Duct flange DTA109A51 Duct flange
(with insulation
insulation material)
material) (with insulation
insulation material)
material)
1 DIII-NET expander adaptor DTA109A51 Use2when
Use whenExternal
only control
only minimal
minimal Use
Usespace
when
space
adaptor when is only
is only
available
minimal
available between
minimal space is
between
space is available
available between
between
(with
DTA109A61
(with
Intake duct
Intake duct Intake duct
Intake duct
2 External control adaptor DTA109A61 drop3 ceilings
drop Home and
ceilings and ceiling
Automation drop
ceiling
drop slabs.
ceilings
Adaptor and
slabs.
ceilings
Interface and ceiling
ceiling slabs.
slabs. DTA116A51 (obtained locally)
(obtained locally) (obtained locally
(obtained locally

3 Home Automation Interface Adaptor DTA116A51 4 Option plate for control adaptor BKS26A *1
Note: Some
Note: Some ceiling
ceiling constructions
constructions
Note:
may
Note:
maySome ceiling
Some ceiling constructions
constructions may
may
4 Option plate for control adaptor BKS26A *1 hinder
hinder installation. Contact
Contact your
your
hinder installation.
installation. Contact
Contact your
your
Note: *1. This plate is necessary for each adaptor marked . installation. hinder
Daikin Dealer
Daikin Dealer before
before installing
installing Daikin Note:
DealerNote:
Daikin Dealer 1. installing
1.
before
before Use of
Use of options
options will
installing Note: 1.
Note:
will increase
increase
1. Use
Use
operating
of options
options
operating
of sound.
will increase
sound.
will increase operating
operating sound.
sound.
Note: *1. This plate is necessary for each adaptor marked . 2. Connecting ducts, fan, insect2. Connecting
nets, fire dampers,
ducts, fan,
airinsect
filters,nets,
and fire dampers, air filter
your unit.
your unit. your unit.
your unit.
40mm
40mm 40mm
40mm
other
other parts
parts should,
should, asas required,
required, other
other beparts
be obtained
parts should,
obtained
should,locally.
as required,
locally.
as required, be be obtained
obtained locally.
locally.
Panel spacer
Panel spacer Panel spacer
Panel spacer
3. When a
3. When a local-obtained
local-obtained fan fan3. isWhen
3.isWhen
used,a
used, aan
an
local-obtained
interlock with
local-obtained
interlock withfanfan
air is
air is
conditioner
used, an
an interlock
conditioner
used, interlock with
with air
air c
c
is
is necessary.Optional
necessary.Optional PCB PCB (KRP1C11A)
is
is necessary.Optional
(KRP1C11A) is required
necessary.Optional
is requiredPCB PCB
for (KRP1C11A)
for (KRP1C11A) is is required
required forfor
Sealing material
Sealing
of air material
dischargeofoutlet
air discharge outlet 4.
interlocking.
interlocking.
4. When
When installing
installing aa fresh
fresh air
air4.
4.
interlocking.
interlocking.
intake
When
intake
Whenkitkitinstalling
(chamber
installing
(chamber a
a fresh
type),air
fresh
type), two
air
twointake
air outlet
intake
air outlet
kit
kit (chamber
(chamber type),
type), two
two
Sealing material
Sealing material block
blockSealing
Sealing
air discharge
air discharge
material
materialopenings
block air
openings
block airnot
discharge openings
not
discharge openings not
not corners
corners are are closed.
closed. corners
corners are are closed.
closed.
5.
5. It
It is
is recommended
recommended that that the 5.
5. volume
the It is recommended
volume
It is recommended
of
of outdoor
outdoor air that
air
thatintroduced
the volume
introduced
the volume of of outdoor
outdoor airair introdu
introdu
used in
used in 2-way
2-way or
or 3-way
3-way
used
blow.
used in 2-way
blow.
in 2-way oror 3-way
3-way blow.
blow.
through the kit is limited to 10% through of thethemaximum
kit is limitedairflowto 10%rate of
of the
the maximum airflow
indoor
indoor unit.
unit. Introducing
Introducing higher
higher indoor
quantities
indoor unit.
unit. Introducing
quantities will
will increase
Introducing
increase higher
the
the quantities
higher quantities will
will increase
increase thethe
Branch duct Branch
chamberduct chamber 6.
operating sound and may also
6. The
The volume
volume of of fresh
fresh air
air for
for6.
operating
6.direct
direct
The
influence
The volume
volume
sound
temperature
installation
and maysensing.
of fresh
installation
of fresh
typeair
type air
is for
is for
also influence temperature sen
approximately
direct installation
approximately
direct installation type
type isis appr
appr
This chamber lets youThis
connect
chamber
a round
letsflexible
you connect
duct to
a round
the flexible duct 1%to of the
the indoor unit airflow.1% of the indoor unit airflow.
air discharge
air discharge opening air
at
at any
opening air discharge
any time
time after
discharge opening
after the
the original
opening at
at any
any time
original time after
after the originalThe
the original The chamber
chamber typetype is
is recommended
recommendedThe
The chamber when
when type
chamber more
moreis
type isfresh
recommended
fresh air
air is
recommended is when
when more
more fresh
fresh air
air
necessary.
necessary. necessary.
necessary.
installation.
installation. installation.
installation.

91 97 93
207 93
207 98 92
Option List

VRV Indoor Units


ing Mounted
Ceiling
Cassette
Mounted
(Compact
Cassette
Multi(Compact
Flow) Type
Multi Flow) Type 4-Way
CeilingFlow Ceiling
Mounted Suspended
Duct Type Type
No. Type FXZQ20M Type
FXZQ25M
FXZQ20M
FXZQ32M
FXZQ25M
FXZQ40M
FXZQ32M
FXZQ50M
FXZQ40M FXZQ50M No. Type
Type FXMQ20PA FXUQ71A FXMQ50PA FXMQ100PA
FXUQ100A FXMQ200M
Item Item Item
No. FXMQ25PA FXMQ40PA FXMQ63PA FXMQ125PA
Decoration panel 1 Decoration panel BYFQ60B3W1 BYFQ60B3W1 1 Sealing material of air discharge outlet KDBHP49B140 FXMQ250M
Item FXMQ32PA FXMQ80PA FXMQ140PA
2
Sealing material of air dischargeSealing
outlet material of air discharge outlet KDBH44BA60 KDBH44BA60 2 Decoration panel for air discharge KDBTP49B140
1 Drain pump kit – KDU30L250VE
Panel spacer 3 Panel spacer KDBQ44BA60A KDBQ44BA60A 3 Replacement long-life filter KAFP551K160
65% KAF372AA36 KAF372B56 KAF372B80 KAF372B160 KAFJ372M280
4
Replacement long-life filter Replacement long-life filter KAF441C60
KAFQ441BA60 KAFQ441BA60
KAF441C60 2
90% – KAF373B56 KAF373B80 KAF373B160 KAFJ373M280
Fresh air intake kit 5 Freshinstallation
Direct air intake kit
type Direct installation type KDDQ44XA60 KDDQ44XA60
3 Filter chamber – KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
Ceiling Suspended Type
4 – KAF371B56 KAF371B80 KAF371B160 KAFJ371M280
5 – KAF375B56 KAF375B80 KAF375B160 –
ing Mounted
Ceiling
Cassette
Mounted
(Double
Cassette
Flow) Type
(Double Flow) Type No. Item White
Type FXHQ32MA
KTBJ25K36W KTBJ25K56W FXHQ63MA
KTBJ25K80W FXHQ100MA–
KTBJ25K160W
ay Flow Ceiling
4-Way Suspended
Flow Ceiling
Type
Suspended Type 16 Service
Drain panel
pump kit Fresh white KDU50N60VE KTBJ25K56F
KTBJ25K36F KTBJ25K80F KDU50N125VE
KTBJ25K160F –
Type Type FXCQ20M 2 Replacement long-life filter (Resin net) Brown KAF501DA56 KTBJ25K56T
KTBJ25K36T KAF501DA80
KTBJ25K80T KAF501DA112–
KTBJ25K160T
No. Type FXCQ20M Type
FXUQ71A FXUQ71A FXUQ100A FXUQ100A
Item No. Item FXCQ25M FXCQ40M FXCQ25M
FXCQ50M FXCQ40M
FXCQ63M FXCQ50M
FXCQ80M FXCQ63M
FXCQ125M FXCQ80M FXCQ125M
37 L-type piping kit
Air discharge (for upward direction)
adaptor KHFP5MA63 KDAJ25K56A
KDAJ25K36A KDAJ25K71A KHFP5MA160
KDAJ25K140A –
Sealing material of air discharge
1 Sealing
outlet material of air discharge outlet
FXCQ32M KDBHP49B140
FXCQ32M KDBHP49B140
Item
Decoration panel for air 2
Item
dischargeDecoration panel for air discharge KDBTP49B140 KDBTP49B140
1
Decoration panel 3 Decoration panel BYBC32G-W1 BYBC50G-W1
BYBC32G-W1 BYBC63G-W1
KAF5511D160BYBC50G-W1 BYBC125G-W1
BYBC63G-W1
KAF5511D160 BYBC125G-W1
Wall Mounted Type
High efficiency filter 65% 1
High efficiency filter 90% 1
HighKAFJ532G36
efficiency filter 65% 1 KAFJ532G56
HighKAFJ533G36
KAFJ532G36
efficiency filter 90% 1 KAFJ533G56
KAFJ533G36
KAFJ532G80
KAFJ532G56
KAFJ533G56
KAFJ533G80
KAFJ532G160
KAFJ532G80
KAFJ533G80
KAFJ533G160
KAFJ532G160
KAFJ533G160 Ceiling Mounted Duct Type Type FXAQ20P
Filter related 2 Filter related No. Item FXAQ25P FXAQ32P FXAQ40P FXAQ50P FXAQ63P
Filter chamber bottom suctionFilterKDDFJ53G36
chamber bottom suction KDDFJ53G36
KDDFJ53G56 KDDFJ53G56
KDDFJ53G80 KDDFJ53G80
KDDFJ53G160 KDDFJ53G160
No.
1 Itempump kit
Drain
Type FXMQ200P     FXMQ250P
K-KDU572EVE
Long life replacement filter LongKAFJ531G36
life replacement filter KAFJ531G36
KAFJ531G56 KAFJ531G56
KAFJ531G80 KAFJ531G80
KAFJ531G160 KAFJ531G160
ing Mounted
Filter chamber Ceiling
is requiredNote: Cassette
if installing
1 Filter
high Mounted
chamber is(Double
efficiency required
filter. Cassette
Flow)
if installing Type
(Double
high efficiency filter. Flow) Type 1 BAFL501A250
2 BAFL502A250
Item No. Item Model Model
FXCQ20A FXCQ25A FXCQ32A
FXCQ20A
FXCQ40A
FXCQ25A
FXCQ50A
FXCQ32A
FXCQ63A
FXCQ40A
FXCQ80A
FXCQ50A
FXCQ125A
FXCQ63A FXCQ80A FXCQ125A Floor
3 Standing Type 65% BAFM503A250
Decoration panel Decoration panel 90% BAFH504A250
1 BYBCQ40CF BYBCQ40CF
BYBCQ63CF BYBCQ63CF
BYBCQ125CF BYBCQ125CF
No.
4 Item Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA
BDD500A250 FXLQ50MA FXLQ63MA
65 % 65 % KAF532C50 KAF532C50
KAF532C80 KAF532C80
KAF532C160 KAF532C160
High efficiency filter *1 2 High efficiency filter *1 Drainlife
pump kit
90 % 90 % KAF533C50 KAF533C50
KAF533C80 KAF533C80
KAF533C160 KAF533C160 15 Long replacement filter KAFJ361K28 BDU510A250VM
KAFJ361K45 KAFJ361K71
6 Insulation kit for high humidity BDT520A250
Filter chamber for bottom 3 suction
Filter chamber for bottom suction KDDFP53B50 KDDFP53B50
KDDFP53B80 KDDFP53B80
KDDFP53B160 KDDFP53B160
Long life replacement filter
4 Long life replacement filter KAF531C50 KAF531C50
KAF531C80 KAF531C80
KAF531C160 KAF531C160
. If installing high efficiency
Note: *1.
filter,
If installing
filter chamber
high efficiency
is required.
filter, filter chamber is required.
Concealed Floor Standing Type
Ceiling
No. Item
Suspended Type Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
ming
Ceiling Mounted
Slim
Mounted Ceiling
Ceiling Duct
Cassette Type
Mounted
Mounted
(Single(Standard
Duct
Cassette
Flow) Type
Series)
Type
(Single(Standard Series)
Flow) Type No.
1 Long life replacement filter Type KAFJ361K28 FXHQ63MA
FXHQ32MA KAFJ361K45
FXHQ100MA KAFJ361K71
FXHQ125A FXHQ140A
Item
Item No. Item Type FXDQ20PD TypeFXEQ32A
FXEQ20AFXDQ25PD FXDQ20PD
FXDQ32PD
FXEQ20AFXDQ25PD
FXDQ40ND FXDQ32PD
FXEQ32AFXDQ50ND
FXEQ50A FXDQ40ND
FXDQ63NDFXDQ50ND
FXEQ50A FXDQ63ND 1 Drain pump kit KDU50N60VE KDU50N125VE KDU50R160
No. 2
Item Insulation kit for high humidity FXEQ25A KDT25N32
Item FXEQ40A
FXEQ25A KDT25N32
FXEQ40A FXEQ63A FXEQ63A
1 KAFJ501D56 KAFJ501D80 KAFJ501D112 KAF501B160
Insulation kit for high humidity KDT25N50 KDT25N63
KDT25N50 KDT25N63
Decoration panel 1 Decoration panel BYEP40AW1 BYEP40AW1 BYEP63AW1 BYEP63AW1 Floor Standing
3
Duct Type
L-type piping kit (for upward direction) KHFP5M63 KHFP5M160 KHFP5N160

Type FXVQ125N FXVQ200N FXVQ250N FXVQ400N FXVQ500N


dle Static Pressure
Middle Static
Ceiling
Pressure
Mounted Ceiling
Duct Type
Mounted Duct Type No. Item
1 Replacement long life filter KAFJ261L140 KAFJ261L224 KAFJ261L280 KAFJ261M450 KAFJ261M560
m Ceiling Mounted
Slim
No.
Ceiling
Duct Type
Mounted
(3D FXSQ20PA
Type Airflow
Duct Type
FXSQ25PA
with(3D
TypeSensing)
Airflow
FXSQ20PA with
FXSQ50PA
FXSQ25PA
FXSQ40PA FXSQ63PA
Sensing)
FXSQ40PA
FXSQ50PA
FXSQ100PA
FXSQ63PA
FXSQ100PA
FXSQ140PA FXSQ140PA
Wall
2 Mounted Type
Ultra long-life filter – KAFSJ9A400 KAFSJ9A560
Item Item FXSQ125PA FXSQ125PA
. Item No. Item Type FXSQ32PA Type
FXDSQ20A FXDSQ25A FXSQ32PA
FXSQ80PA
FXDSQ20A
FXDSQ32A FXDSQ25A FXSQ80PA
FXDSQ40A FXDSQ32A
FXDSQ50A FXDSQ40A
FXDSQ63A FXDSQ50A FXDSQ63A 3No. Item Front suction base flange Type KD-9A140
FXAQ20A FXAQ25A
KD-9A200 FXAQ32A
KD-9A280 FXAQ40A FXAQ50AKD-9A560
KD-9A400 FXAQ63A
65% KAFP632B36
65% KAFP632B56 KAFP632B36KAFP632B80 KAFP632B160
KAFP632B56 KAF632B160B
KAFP632B80 KAFP632B160 KAF632B160B
Flexible duct filter *1 1
High efficiency Flexible duct filter *1
High efficiency BFD37B40 BFD37B40 BFD37B50 BFD37B63 BFD37B50 BFD37B63 4 1 Drain pump kit Suction grille KDGF-9A140 KDGF-9A200 K-KDU572EVE
KDGF-9A280 KDGF-9A400 KDGF-9A560
90% KAFP633B36
90% KAFP633B56 KAFP633B36KAFP633B80KAFP633B56
KAFP633B160
KAFP633B80 KAFP633B160
KAF633B160B KAF633B160B

Discharge and Suction


Filter chamber (for rear suction)
2 Filter
*1 chamber (for rear suction) KDDFP63B36
*1 KDDFP63B56 KDDFP63B36
KDDFP63B80KDDFP63B56 KDDFP63B80
KDDFP63B160 KDDFP63B160
KDDF63B160B KDDF63B160B 5 Front suction filter Filter Replacement long-life filter *1, 2, 3 KAF-91A140 KAF-91A200 KAF-91A280 KAF-91A400 KAF-91A560
Long-life filter *1 3 Long-life filter *1 KAFP631B36 KAFP631B56 KAFP631B36KAFP631B80 KAFP631B160
KAFP631B56 KAFP631B80 KAFP631B160
KAF631B160B KAF631B160B chamber for high chamber Replacement 65% *1, 3
6 KAF-92A140 KAF-92A200 KAF-92A280 KAF-92A400 KAF-92A560
White White
KTBJ25K36W KTBJ25K56W KTBJ25K36WKTBJ25K80WKTBJ25K56W KTBJ25K160W
KTBJ25K80W KTBJ25K160W efficiency filter for high high efficiency
m Ceiling Mounted
Slim Ceiling
Duct Type
Service panel Mounted
(Standard
Duct Type
4 Series)
(Standard Series)
Service
Fresh panel
white Fresh white
KTBJ25K36F KTBJ25K56F KTBJ25K80F
KTBJ25K36F KTBJ25K56F KTBJ25K160F
KTBJ25K80F KTBJ25K160F
7
Floor Standing Type efficiency
filter *1, 2
filter 90% *2, 3 KAF-93A140 KAF-93A200 KAF-93A280 KAF-93A400 KAF-93A560
Brown Brown
KTBJ25K36T KTBJ25K56T KTBJ25K80T
KTBJ25K36T KTBJ25K56T KTBJ25K160T
KTBJ25K80T KTBJ25K160T 8 Filter chamber *1, 2 KDDF-9A140 KDDF-9A200 KDDF-9A280 KDDF-9A400 KDDF-9A560
Type FXDQ20PD FXDQ25PD Type FXDQ20PD FXDQ32PD FXDQ25PD
FXDQ40ND FXDQ32PD
FXDQ50ND FXDQ40ND
FXDQ63ND Type FXLQ20MA
Air discharge adaptor No.
Item 5 Item
Air discharge adaptor KDAP25A36A KDAP25A56A KDAP25A71A
KDAP25A36A KDAP25A140A
KDAP25A56A KDAP25A160A
KDAP25A71A *2FXDQ50NDKDAP25A160A
KDAP25A140A FXDQ63ND *2 9
No. Item chamber *4
Plenum KPCJ140A
FXLQ25MA
KPC5J
FXLQ32MA
KPC8J
FXLQ40MA
KPCJ400A
FXLQ50MA FXLQ63MA
KPC15JA
Insulation
Shield platekitfor
for high
side 1
humidity
6
plate Insulation
Shield platekitfor
for high
side humidity
plate KDT25N32 KDBD63A160 KDT25N32 KDT25N50
KDBD63A160 KDT25N63
— KDT25N50 KDT25N63
— KAF361L28 KAF361L45 KAF361L71
10 Pulley for plenum chamber *4 KPP8JA KPP9JA KPP10JA –
1. If installing high efficiency
Note: *1.
filter
If installing
and long-life
highfilter
efficiency
to the filter
unit, and
filterlong-life
chamberfilter
is required.
to the unit, filter chamber is required.
2. This option is a set of KDAP25A140A
*2. This option andisKDBHP37A160.
a set of KDAP25A140A and KDBHP37A160. 11 Fresh air intake kit KD106D10 KDFJ906A560
12 Rear suction kit KDFJ905A140 KDFJ905A200 KDFJ905A280 KDFJ905A400 KDFJ905A560
dle Static Pressure
Middle Static
Ceiling
Pressure
MountedCeiling
Duct Type
Mounted Duct Type
ing Mounted Ceiling
Duct Type
MountedType
DuctFXSQ20PA
Type Concealed Floor Standing Type
13 Discharge grille for plenum side KD101A10 KD101A20
Type FXSQ20PA
FXSQ50PA FXSQ50PA
No. FXSQ25PA FXSQ25PA
FXSQ40PA FXSQ63PA
FXSQ100PA
FXSQ40PA FXSQ63PA
FXSQ100PA
FXSQ140PA FXSQ140PA
14
No.
Wood base
Item Type KKWJ9A140 KWF1G5P KWF1G8P KKWJ9A400 KWF1G15
FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
Type FXMQ20PA Type FXMQ20PA
FXMQ50PA FXMQ50PA
FXMQ100PA
FXSQ125PA FXMQ100PA
FXSQ125PA
Item Item FXSQ32PA FXSQ32PA
FXSQ80PA FXMQ200M
FXSQ80PA FXMQ200M 15 Vibration isolating frame K-ABSG1406A K-ABSG1407A
KAF361L28 K-ABSG1408A
KAF361L45 K-ABSG1409A KAF361L71
K-ABSG1410A
No. FXMQ25PA FXMQ25PA
FXMQ40PA FXMQ63PA FXMQ125PA
FXMQ40PA FXMQ63PA FXMQ125PA
Item Item
65% KAF632C36
65% KAF632C36
KAF632C56 KAF632C80 KAF632C160
KAF632C56 FXMQ250M
KAF632B160B
KAF632C80 KAF632C160 FXMQ250M
KAF632B160B
High efficiency filter *1 1 High efficiency filter *1 FXMQ32PA FXMQ32PA
FXMQ80PA FXMQ80PA
FXMQ140PA FXMQ140PA Note: *1. When ordering a filter chamber for high efficiency filter (65%), please order with all the respective parts.
Drain pump kit 1 90%
Drain pump kit KAF633C36
90% KAF633C56 KAF633C36
— KAF633C80 KAF633C56
KAF633C160
— KAF633C80 KAF633C160
KAF633B160B
KDU30L250VE KAF633B160B
KDU30L250VE *2. When ordering a filter chamber for high efficiency filter (90%), please order with all the respective parts.
Filter chamber (for rear suction)
2 Filter
*1 chamber (for65% rear suction)KDDFP63B36
*1
KAF372AA36 KDDFP63B56
65%KAF372AA56 KDDFP63B36
KDDFP63B80
KAF372AA36 KDDFP63B56
KAF372AA80KAF372AA56 KDDFP63B80
KDDFP63B160
KAF372AA80
KAF372AA160 KDDFP63B160
KDDF63B160B
KAF372AA160
KAFJ372L280 KDDF63B160B
KAFJ372L280 *3. When replacing with a new filter, please order the replacement filters with the corresponding filter model name.
High efficiency filter 2 High efficiency filter *4. Use the plenum chamber and pulley for plenum chamber in combination.
Long-life filter *1 3 Long-life filter *1 90% KAF373AA36
KAF631C36 90%KAF373AA56
KAF631C56 KAF373AA36
KAF631C36KAF373AA80
KAF631C80 KAF373AA56 KAF373AA80
KAF373AA160
KAF631C160
KAF631C56 KAF631C80 KAF373AA160
KAFJ373L280
KAF631C160
KAF631B160B KAFJ373L280
KAF631B160B
Filter chamber 3 Filter chamber
White KDDF37AA36
White
KTBJ25K36W KDDF37AA56
KTBJ25K56W KTBJ25K36W KDDF37AA80
KDDF37AA36
KTBJ25K80W KDDF37AA160
KDDF37AA56
KTBJ25K56W KDJ3705L280
KDDF37AA80
KTBJ25K160W
KTBJ25K80W KDDF37AA160 KDJ3705L280
KTBJ25K160W
Long lifepanel
replacement filter
4 Long lifepanel
replacement filter
Service 4
5
Long life filter chamber kit
Service
Fresh white
Long life filter chamber kit
Brown
KAF371AA36
Fresh white
KTBJ25K36F
KAF375AA36
Brown
KAF371AA56
KTBJ25K56F
KAF375AA56
KAF371AA80
KAF371AA36
KTBJ25K80F
KTBJ25K36F KAF371AA160
KAF371AA56
KTBJ25K56F
KAF375AA80
KAF375AA36
KAFJ371L280
KAF371AA80
KTBJ25K160F
KTBJ25K80F
KAF375AA160
KAF375AA56 KAF375AA80
KAF371AA160 KAFJ371L280
KTBJ25K160F
KAF375AA160 Clean Room Air Conditioner
KTBJ25K36T KTBJ25K56T KTBJ25K80T
KTBJ25K36T KTBJ25K56T KTBJ25K160T
KTBJ25K80T KTBJ25K160T
White KTBJ25K36W White KTBJ25K56W KTBJ25K36WKTBJ25K80W KTBJ25K160W
KTBJ25K56W KTBJ25K80W KTBJ25K160W
panel adaptor 5
Air discharge
Service Air discharge
Service panel adaptor KDAP25A36A KDAP25A56A KDAP25A71A
KDAP25A36A KDAP25A140A
KDAP25A56A KDAP25A160A
KDAP25A71A *2
KDAP25A140A KDAP25A160A *2 No. Item Type FXBQ40P FXBQ50P FXBQ63P FXBPQ63P
6 Fresh white KTBJ25K36F Fresh white KTBJ25K56F KTBJ25K80F
KTBJ25K36F KTBJ25K80F — KTBJ25K160F
KTBJ25K160F
KTBJ25K56F —
Shield plate for side plate6 Shield plate forBrown
side plate KDBD63A160 KDBD63A160 — —
KTBJ25K36T Brown KTBJ25K56T KTBJ25K80T
KTBJ25K36T KTBJ25K160T
KTBJ25K56T KTBJ25K80T KTBJ25K160T 1 Outlet unit – BAF82A63
. If installing high efficiency
Air discharge Note:7*1.
adaptor filter
If installing
andAir long-life
highfilter
discharge efficiency
to the filter
adaptor unit, and
filter long-life
chamberfilter
KDAJ25K36A is required.
to the unit, filter
KDAJ25K56A chamber is required.
KDAJ25K71A
KDAJ25K36A KDAJ25K140A
KDAJ25K56A KDAJ25K71A KDAJ25K140A
. This option is a set of KDAP25A140A
*2. This option
andisKDBHP37A160.
a set of KDAP25A140A and KDBHP37A160. 2 Filter HEPA filter BAFH82A50 BAFH82A63
3 Ceiling intake type BYB82A50C BYB82A63C BYB82A63CP
Panel
Option
List

Option
List

4 Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP


5 Outside air intake duct flange KDFJ82A80

99 94 94 209
95 100
OptionOption
List List

VRV
Residential
Indoor Indoor
Units Units with connection to BP units Systems
ControlControl Systems New Design New

Slim Ceiling
Floor Mounted
Standing Duct Type
Duct Type Operation Control SystemControl
Operation Optional
System
Accessories
Optional Accessories Remote sensor Rem
BRCS01A-1(4) BRC
Type
No. Item
No. Item Type FXVQ125N FDKS35EA
FDKS25EA FXVQ200N FXVQ250N
FDKS25CA FXVQ400N
FDKS35CA FDKS50C FXVQ500N
FDKS60C For VRV indoorFor
unitVRV
useindoor unit use
11 Insulation kit for high humidity KDT25N32 KAF261M224
KAF261M140 KDT25N50KAF261N450
KAF261M280 KDT25N63
KAF261N560
No.
No. No.
No. Type
Type FXFSQ-A Type FXFSQ-A
Type FXDQ-PD FXDQ-PD
FXDQ-PD FXD
FXFSQ-A FXUQ-A FXUQ-A
FXFQ-A FXFQ-A
FXZQ-M FXZQ-M
FXCQ-M
FXFSQ-A
FXFQ-A FXEQ-A
FXFQ-A
Item
Item Item
Item FXZQ-MFXCQ-A
FXCQ-MFXEQ-A
FXZQ-M FXDQ-SP
FXEQ-A FXCQ-A
FXSQ-PA
FXDSQ-A FXDQ-SP
FXEQ-A
FXMQ-PA FXDQ-SP
FXSQ-PA FXD
FXDSQ-A FXM
2 – KAFSJ9A400 KAFSJ9A560 FXDQ-ND FXDQ-ND
FXDQ-ND
1 Navigation remote controller
1 Navigation remote BRC7M635F
controller
BRC1E63 Note 5 BRC7M635F
BRC1E63 BRC1E63
BRC1E63 5 5 BRC1E63
NoteNote BRC1E63 BRC1F61
BRC1E63 NoteBRC1F61
5 BRC1E63Note 5 BRC1F61
BRC1E63BRC1F61 Note 5
Wall
3
Mounted Type KD-9A140 KD-9A200 KD-9A280 KD-9A400 KD-9A560
2 Simplified remote controller Simplified remote (Fresh
2 Wireless —White)
controller /
Wireless BRC7E531W
(Fresh
BRC7C67—White)BRC2E61
/
BRC4M63
BRC7E531W BRC7C67 BRC2E61
BRC4M63
BRC4C66 — BRC2E61
BRC4C66 —
4 Suction grille KDGF-9A140 KDGF-9A200 KDGF-9A280 KDGF-9A400 KDGF-9A560 1 Remote controller 1 Remote controllerBRC7M635K BRC7M635K
FTKS50F BRC7M635F
(Black) (Fresh White) / BRC7E531WBRC7M635F (Fresh White) /
(Black) BRC7CB59
Type 3 Wireless remote controller 3 Wireless remote controller BRC7E531WBRC4M63
BRC7M66 BRC7CB59BRC4M66BRC7M66 BRC4M63 BRC4C66BRC4M66
Discharge and Suction

FTKJ25N FTKJ35N FTKS25D BRC7M635K (Black) BRC7M635K (Black)


No.
5 KAF-91B200FTKJ50N
KAF-91B280 FTKS60F
FTKS50B KAF-91B560
Item
Filter KAF-91B140
FTKS35DKAF-91B400 FTKS71F Wired —Wired BRC1C62 — — BRC1C62 —
BRC1C62 BRC1C62
chamber for high chamber Replacement 4-1 Adaptor for wiring (operation
4-1 Adaptor status output)
for wiring (operation BRP11B62status output) BRP11B61 BRP11B62 BRP11B61 — — BRP11B61 — BRP
61 Titanium apatite deodorising 65% *1, 3 KAF-92B140 KAF-92B200 KAF-92B280 KAF-92B400 KAF-92B560 2 Navigation remote controller
2 (WiredNavigation
remote controller)
remote controller
BRC1E63(Wired
Note 6 remote controller)
BRC1E63 BRC1E63 Note BRC1F61
6 BRC1E63 BRC1F61 BRC1E63
BRC1E63 Note 7 BRC1E63 BRC1E63 BRC1E63
Note 7 Note 7 BRC1E63 No
for highfilter *1 KAF970A46 KAF952A42 KAF952B42 4-2 Adaptor for wiring 4-2 Adaptor for wiring KRP1C11A KRP1BA57 KRP1C11A — KRP1B61
KRP1BA57 — — KRP1C64
KRP1B61 KRP1B56— —
KRP1C64 KRP
72 Dust collection filter (PM 2.5) with frame 90% *2, 3 KAF-93B140 BAFP046A42
KAF-93B200 KAF-93B280 –
KAF-93B400 KAF-93B560 3 Simplified remote controller
3 Simplified
(Exposed type)
remote controller (Exposed type) — — BRC2C51 BRC2C51
5-1 Wiring adaptor for electrical
5-1 Wiringappendices
adaptor (1)for electrical— appendices (1) KRP2A62 — — KRP2A61
KRP2A62 —— KRP2A61
KRP2A61 KRP2A53 — —
KRP2A61 KRP
3 Dust collection filter (PM 2.5) without frame BAFP046A41 – 4 Remote controller for hotel
4 use Remote
(Concealed
controller
type) for hotel use (Concealed type) — — BRC3A61 BRC3A61
8 Filter chamber *1, 2 KDDF-9A140 KDDF-9A200 KDDF-9A280 KDDF-9A400 KDDF-9A560 5-2 Wiring adaptor for electrical
5-2 Wiringappendices
adaptor (2)for electrical appendices
KRP4AA53(2) KRP4AA53KRP4AA51
KRP4AA53 —
KRP4AA53 KRP4AA51
KRP4AA51 KRP4A54 — —
KRP4AA51 KRP
Note: *1. Filter is a standard accessory. It should be replaced approximately 3 years. 5 Adaptor for wiring 5 Adaptor for wiring KRP1C11A KRP1BA57 KRP1C11A KRP1BA57
KRP1B61 — KRP1B56
KRP1B61 —— KRP1C64 —
KRP1B56 KRP1C6
6 Remote sensor (for indoor 6 temperature)
Remote sensor (for indoor temperature) BRCS01A-1
KRCS01-5B BRCS01A-4 BRCS01A-1
KRCS01-5B BRCS01A-1 BRCS01A-4
BRCS01A-4 BRCS01A-1 BRCS01A-4
BRCS01A-1
9 Plenum chamber *4 KPCJ140A KPC5J KPC8J KPCJ400A KPC15JA 6-1 Wiring adaptor for electrical
6-1 Wiring
appendices
adaptor (1)for KRP2A62
electrical
— appendices
KRP2A62 (1) KRP2A61 —
KRP2A62 —
KRP2A62 KRP2A53
KRP2A61 — — KRP2A53
KRP2A61 — KRP2A6
Note 2, 3 Note 4 Note 2, 3 Note
Note
2, 3
4 Note
Note
3 2, 3 Note 4 Note 3 Note 4
10 KPP9JA 7
6-2 Wiring adaptor
Installation foradaptor
box for electrical
7
6-2 Wiring
PCB appendices
adaptor
Installation box(2)for
foradaptor
electrical PCBappendices (2) KRP4AA51
KRP4AA53 KRP4AA53 —
KRP1BA97 KRP4A54 —— —
KRP4AA51 KRP1BA97 KRP4A54
KRP4AA51 —— — KRP4AA5
Pulley for plenum chamber *4 KPP8JA KPP10JA – KRP1H98A KRP1BA101 KRP1H98A KRP1B96
KRP1BA101 BRP9A90
KRP1B96 KRP1BA101 BRP9A90 KRP1
BP
11 Units
Freshfor Connection
air intake kit to Residential Indoor KD106D10
Units KDFJ906A560 8
7 Remote sensor (for indoor
External control adaptor
7 temperature)
Remote sensor (for
8 for External
outdoor control
unit
indoor temperature)
KRCS01-5B
adaptor for outdoor
Note 2, 3
BRCS01A-1
Note 4, 5
unit
DTA104A62
KRCS01-5B
Note 2, 32, 3
Note
BRCS01A-4

BRCS01A-1
DTA104A62
Note 4, 5
BRCS01A-1
DTA104A61
NoteNote
4, 5 2, 3
BRCS01A-4
— —
Note
BRCS01A-4
BRCS01A-1
DTA104A61
Note
2, 3
4, 5
DTA104A53
Note 2, 3
— —
BRCS01A-
Note 2, 3
DTA
Note
98 Installation
Adaptor box for
for multi tenant98
adaptor PCB
Installation
Adaptor box for
for multi adaptor
tenant PCB
DTA114A61 DTA114A61 — —— — — —
No.
12 Rear suction kit Type KDFJ905B140BPMKS967A2
KDFJ905B200 KDFJ905B280 BPMKS967A3
KDFJ905B400 KDFJ905B560 KRP1H98A KRP1BA101 KRP1B96 KRP1H98A KRP1BA101 KRP1BA101
KRP1B96 KRP4A98
KRP1BA101KRP4A97 KRP4A98 KR
Item
9 External control adaptor
9 for External
outdoor control
unit adaptorDTA104A62
for outdoor unit DTA104A62
DTA104A61 — DTA104A53
DTA104A61 —— DTA104A61 —
DTA104A53 DTA104A
131 REFNET joint
Discharge grille for plenum side KD101A10 KHRP26A22T KD101A20
Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints. 10 10
Adaptor for multi tenant AdaptorType
for multi tenant
DTA114A61 DTA114A61 —
Type — FXLQ-MA
DTA114A61 FXLQ-MA
FXBQ-PDTA114A6
14 Wood base KKWJ9A140 KWF1G5P KWF1G8P KKWJ9A400 KWF1G15 No. No. FXSQ-PA FXMQ-PA FXMQ-M FXMQ-P
FXSQ-PA FXMQ-PA
FXHQ-MA
FXMQ-M
FXHQ-A
FXMQ-P
FXAQ-A
FXHQ-MA FXHQ-A FXVQ-NFXAQ-A FX
Item Item FXNQ-MA FXBPQ-P
FXNQ-MA
15 Vibration isolating frame K-ABSG1406A K-ABSG1407A K-ABSG1408A K-ABSG1409A K-ABSG1410A 1 1
Navigation remote controller NavigationType
remote controller Type BRC1E63 FXLQ-MA
BRC1E63 FXLQ-MA
FXBQ-P
BRC1E63 Note 6, 7 BRC1E63 FXB
BRC
No. No. FXMQ-M FXUQ-A FXMQ-M
FXHQ-MA FXUQ-A
FXAQ-P FXHQ-MA FXAQ-P
FXVQ-N FXVQ-N
Note: 2 Item
Simplified 2
remote controller Item
Simplified remote controller BRC2E61 FXNQ-MA
BRC2E61 FXNQ-MA
FXBPQ-P
BRC2E61 Note 7 BRC2E61 FXB
BRC
3 Wireless remote controller 3WirelessWireless remote controller BRC4C66
BRC4C64 Wireless BRC7CB59 BRC4C64 BRC4C66
BRC4C66 BRC7CB59
BRC4C64
BRC7EA66 BRC7EA66
BRC4C64
BRC7EA619 BRC7M56BRC4C66
BRC7EA66 BRC7M676
BRC4C64 BRC7EA66—
BRC7EA619BRC4C64
BRC7M56BRC4C64
BRC4C64 — BRC7M676 BRC4C64
—BRC4C64BRC
1 Remote controller 1 Remote controller
4-1 Adaptor for wiring (operation
4-1Wired Adaptor
status output)
for wiring (operation Wired status output)
BRP11B62 BRP11B62 BRC1C62
BRP11B62
— BRP11B61
BRP11B62 BRC1C62 — —BRC1C62 BRP11B61
BRP11B62
Note 8 BRC1C62— —BRC1C62 BRP11B62
BRP11B62
Note 8 BRC
*4. Use the plenum chamber and pulley for plenum chamber in combination.
4-22 Navigationfor
Adaptor remote
wiring 4-22 (Wired
controller Navigation
remote controller)
Adaptor remote
for wiring controller
BRC1E63 (Wired remote
KRP1C64 controller)
BRC1E63 Note 6, 7 BRC1E63
KRP1B61 KRP1C13A BRC1E63
KRP1C64BRC1E63 KRP1B61
KRP1BA54
Note 6, 7 KRP1C13A —BRC1E63
BRC1E63 KRP1B61
KRP1BA54
Note 9 KRP1C67—BRC1E63
BRC1E63 KRP1B61
KRP1B61
Note 9 BRC
KR
5-13 Simplified
Wiring remote
adaptor 5-13
controller
for electrical Simplified
(Exposed
Wiring
appendices
adaptorremote
type) BRC2C51
controller
(1)for electricalKRP2A61 (Exposed type)
appendices BRC2C51
(1) KRP2A61 —
KRP2A61 KRP2A62 KRP2A61 ——
BRC2C51 KRP2A61 —
KRP2A62KRP2A61 —BRC2C51
BRC2C51
KRP2A62 KRP2A61 —KRP2A61BRC
KRP2A61 KR
Clean Room Air Conditioner 5-24
65
Wiring
Remote adaptor
Adaptorsensor
Remote
forfor
controller
for wiring
4 useWiring
electrical
hotel
5-2
(for indoor
appendices
Remote adaptor
(Concealed
Adaptorsensor
65 temperature)
Remote
(2)forfor
controller
type)
for wiring
BRC3A61
electrical
hotel
(for KRP1B61
indoor
useappendices
KRP4AA51 (Concealed type)
temperature)
BRCS01A-4 —BRCS01A-1
BRC3A61
(2) KRP4AA51 —
KRP4AA51
KRP1B61
KRP1BA54
BRCS01A-4
BRCS01-6B BRCS01A-1——
KRP4AA52
BRCS01A-1
KRP4AA51 —
BRC3A61
KRP1BA54
KRP1B61
BRCS01A-4
KRP4AA51 —
BRCS01-6B BRCS01A-1 —
KRP4AA51
KRP4AA52
KRP1C67
BRC3A61
BRC3A61
BRCS01A-1
KRP1B61
KRP1B61
BRCS01A-4
— KRP4AA51 —
KRP4AA51BRC
KRP4AA51
KRP1C67 BRCS0 KRP
No. Item Type FXBQ40P FXBQ50P FXBQ63P FXBPQ63P 6-1 6-1
Wiring adaptor for electrical Wiring
appendices
adaptor (1)for
NoteKRP2A61
electrical
2, 3 appendices
Note 2, 3 — (1)NoteKRP2A61
2,KRP2A62
3 Note 2, Note 3—
3 KRP2A61 KRP2A61
Note 3KRP2A62 KRP2A62
3 KRP2A61
Note 2,Note 3 KRP2A61
Note 3KRP2A61 Note 2, 3 KRP2A62 KRP
7 Installation box for adaptor 7 PCB
Installation box for adaptor PCB — — —
6-2 Wiring adaptor for electrical
6-2 Wiring
appendices
adaptor (2)KRP4A98
electricalKRP4A97
forKRP4AA51 appendices
KRP4AA53 (2)KRP4A98
KRP4AA51
KRP4AA52KRP4A97 KRP1CA93
KRP4AA51KRP1D93A
KRP4AA53 KRP4AA51
KRP4AA52 KRP4AA93
KRP1CA93
KRP4AA51
— KRP1D93A
KRP4AA51
KRP4AA51 KRP4AA93 — KRP
1 Outlet unit – BAF82A63
7 Remote sensor (for indoor 7 temperature)
Remote sensor (for indoor temperature)
BRCS01A-1 BRCS01A-4 BRCS01A-1 BRCS01A-4 BRCS01A-1 BRCS01A-1
Note 8 Not
2 Filter BAFH82A50 BAFH82A63 8 External control adaptor 8 for External
outdoor control
unit adaptor DTA104A61
for outdoor unit DTA104A61
DTA104A61 DTA104A62DTA104A61 DTA104A61 DTA104A62 DTA104A61 DTA104A62 DTA104A61
DTA104A61 DTA104A61 DT
Note 3 Note 2, 3 Note 3 Note 2, 3
8 Installation box for adaptor 8 PCB
Installation box for adaptor — PCBKRP1BA97 — KRP1BA97 — —
3 Ceiling intake type BYB82A50C BYB82A63C BYB82A63CP 9 Adaptor for multi tenant 9 Adaptor for multi tenant DTA114A61 — KRP1CA93DTA114A61 KRP4AA93
DTA114A61 —— KRP1CA93 DTA114A61 KRP4AA93
DTA114A61 — — DTA114A61
Panel 10 External control adaptor 10for cooling
External / heating
control adaptor for cooling / heating — — Note 10 KRP6A1 Note 8 — 10
Note KRP
4 Floor-level intake type BYB82A50W BYB82A63W BYB82A63WP 9 External control adaptor 9 for External
outdoor control
unit DTA104A61
adaptor for outdoor — unit DTA104A61
DTA104A62 DTA104A61
— DTA104A61
DTA104A62 DTA104A61 DTA104A61 DTA104A61 DTA104A62 DTA1
11 Remote controller with 11key Remote controller with key — — DTA104A62 KRCB37-1 — KR
5 KDFJ82A80 10 Adaptor for multi tenant 10 Adaptor for multi tenant — —
DTA114A61 —
DTA114A61 —
Note: 1. Installation box is necessary
Note: 1. forInstallation
each adaptor box marked
is necessary
. for each adaptor marked .
External
112. Up to control
2 adaptors adaptor
can be fixed for
112.forUp cooling
External
each
to / heating
control
2installation
adaptors can adaptor
box.be fixed forforeach
cooling / heating
installation box. — — KRP6A1 Note 10 — KRP6A1 Note 10
123. OnlyRemote controller
one installation box with
can 3.key
12be Only Remote
installed controller
one installation
for each box with
indoor can
unit.be installed for each indoor unit. —
key — KRCB37-1 — KRCB37-1
4. Up to 2 installation boxes can4. beUp installed
to 2 installation
for each indoor
boxes canunit.be installed for each indoor unit.
Note: 1. Installation box is necessary
Note: 1.forInstallation
each adaptor box marked
is necessary
. for each adaptor marked .
5. Up
2. Some
to 2functions
adaptorscan canbe
beset only
fixed 5.
2.forSome
via
Up the2functions
each
to wired remote
installation
adaptors can
can be
box.controller
beset only
fixed BRC1E63
via
for the installation
each wired
or BRC1F61.
remote controller
box. They cannot
BRC1E63
be setorvia
BRC1F61.
other remote
Theycontrollers.
cannot be set via other remote controllers.
Please refer to each indoor unit and
Pleaseremote
refer controller
to each indoor
page unit.befunction
unit
for and remote
details.
forcontroller page for function details.

Residential Indoor Units with connection to BP units


3. Only one installation box can be 3. Only
installed
one installation
for each indoor box can installed each indoor unit.
6. Up
4. Since
to 2the control panel
installation is can
boxes equipped
6.
4.
beUpSince as2the
installed
to standard,
control
eachuse
installation
for paneltheisoption
indoor
boxes equipped
can
unit.beofinstalled
BRC1E63
as standard,
for for 2use
each remote
the option
indoor control
unit. ofsystem.
BRC1E63 for 2 remote control system.
7. Installation
5. When usingbox BRC1E63 or BRC2E61,
is necessary 7.
5. When beusing
forInstallation
each surebox
adaptor.BRC1E63
to remove or
theBRC2E61,
is necessary control panel
for eachbeadaptor.
sure
and tosince
remove
BRC1E63
the control
and BRC2E61
panel andcannot
since BRC1E63
be stored and
inside
BRC2E61
the indoor
cannot
unit, be
please
storedplace
inside
it separately.
the indoor unit, please place
8. Remove the group control adaptor
6. Some function can be set only6.via 8. Remove
Some which
wired the
is
function agroup
standard
remotecan control
equipment
controller adaptor
be set BRC1E63. before
which
only via wiredCannotmounting
is a
remote standardKRP6A1
be controllerequipment
set via other and
BRC1E63.DTA104A62.
before mounting
remote controllers.
Cannot be set KRP6A1
Please refer and
via other to DTA104A62.
remote
page controllers.
118 for function
Please
listrefer
details.
to page 118 for function list details.
KRP6A1 and DTA104A62 cannot
7. Auto airflow rate can be set only KRP6A1
7. Autobe mounted
via wired and
airflow DTA104A62
remoteto the
rate can same
controller cannot
indoor
be set BRC1E63. be
unitmounted
at
only via wired the
Cannot same
remoteto the
time.
same
be controller indoor
set via other unit
BRC1E63. at the same
remote controllers. time.
Cannot be set via other remote controllers.
8. Since the control panel is equipped
8. Sinceasthe
standard,
controluse
panel
theisoption
equipped
for 2as
remote
standard,
control
usesystem.
the option for 2 remote control system.
Adaptor
9. When using BRC1E63, be for wiring
sure
9. to
When
remove Adaptor
usingtheBRC1E63, for
control panel
be wiring
sure
and to
since
remove
BRC1E63
the control
cannot
Example: panel
be stored
and since
inside
Interlocking BRC1E63
the Example:
indoor
operation cannot
ofunit,
thebeplease
stored
place
inside
Interlocking
indoor unititoperation
separately.
theventilation
and indoorofunit, please
thefan thatplace
indoor unititand
takes separately.
in fresh
ventilation
air. fan that
Slim Ceiling Mounted Duct Type 10. Remove the group control adaptor
(operation status
10. Remove
KRP6A1 and DTA104A62 cannotKRP6A1
whichthe
output)
is agroup
(operation
be mounted
standard
control
and DTA104A62
equipment
status
adaptorbefore
to the samecannot
which mounting
output)
indoor be
is a standard
unitmounted
at the same
to the
KRP6A1
time.
equipment
and DTA104A62.
before mounting KRP6A1 and DTA104A62.
same indoor unit at the same time.
No. Type FDKS25EA FDKS35EA FDKS25CA FDKS35CA FDKS50C FDKS60C VRV outdoor unit VRV outdoor unit
Item
1 Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63
For residential For
indoor
residential
unit useindoor unit use Ventilation Fan Adaptor Ventilation Fan Adaptor
Indoor Indoor
Type Type UnitUnit
By installing it in the indoor unitBy installing
with a simple
it in the
FDKS-EA, wire
indoor
C(A) connection,
unit with a simpleFTKJ-N
FDKS-EA, wire
C(A)connection, FTKJ-N
FTKS-D,B,F FTKS-D,B,F
No. No.
BRP11B61
Item this adaptor takes out the operating
BRP11B61
Item this adaptor
signals
takesforout
thetheindoor
operating
unit fan
signals for the indoor unit fan
1 and
Remote controller 1Wirelessthe compressor and enables
type controller
Remote and the
thecompressor
interlocking
Wireless type and
of equipment
enables the interlocking of
— Note 1 equipment — Note 1
Wall Mounted Type 2
such as the ventilationNote
Wiring adaptor for time clock/remote
2
Wiring
controller
fan. such as the ventilation fan.
adaptor for2 time clock/remote controller Note 2
KRP413AB1S
Air Conditioning
+ KRP413AB1S
Air Conditioning
+
FTKS50F (Normal open pulse contact/normal (Normal
openopen
contact)
pulse contact/normal open contact) Ventilation Ventilation
Type FTKS25D 3 Remote controller loss 3 prevention
Remotechaincontroller loss prevention
KKF917A4 chain KKF917A4
KKF910A4 KKF910A4
KKF917A4 KKF917A4
No. FTKJ25N FTKJ35N FTKJ50N FTKS50B FTKS60F
Item FTKS35D FTKS71F 4 BRP11B62
Interface adaptor for 4DIII-NET BRP11B62
Interface
use adaptor for DIII-NET use KRP928BB2S KRP928BB2S
1 KAF970A46 KAF971B42
Note: 1. A wireless remote controller
Note:is1.a Astandard
wirelessaccessory.
remote controller is a standard accessory.
2 BAFP046A42 – 2. Time clock and other devices 2.
should
Time beclock
obtained
and other
locally.
devices should be obtained locally.
3 BAFP046A41 –
Note: *1. Filter is a standard accessory. It should be replaced approximately 3 years. For residential For
indoor
residential
unit useindoor unit use
No. No. Type Type
FDKS-EA, C(A) FDKS-EA, C(A)
FTKJ-N FTKJ-N
FTKS-D, B, F FTKS-
Item Item
1 Remote controller 1Wireless type controller
Remote Wireless type — —
BP Units for Connection to Residential Indoor Units Wiring adaptor for time clock/remote
Wiring
controller
adaptorNote
for2 time clock/remote controller Note 2
Note 1 Note 1

2 2 KRP413BB1S KRP413BB1S
No. Type BPMKS967A2 BPMKS967A3 (Normal open pulse contact/normal (Normal
openopen
contact)
pulse contact/normal open contact)
Option
List

Item
3 Remote controller loss3 prevention
Remotechaincontroller loss prevention chain
KKF917A4 KKF917A4KKF910A4 KKF910A4KKF917A4 KKF9
1 REFNET joint KHRP26A22T
4 Interface adaptor for DIII-NET
4 Interface
use adaptor for DIII-NET use KRP928BB2S KRP928BB2S
Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints.
Note: 1. A wireless remote controller
Note:is1.a Astandard
wirelessaccessory.
remote controller is a standard accessory.
2. Time clock and other devices 2.
should
Time beclock
obtained
and other
locally.
devices should be obtained locally.

101 210
96 211
97 211
97 102
Daikin Engineering Supports
em Configuration
System Configuration
No.
Item Model
Item No. Model No. Function Function
VRV Design and Sales Proposal Assistance
• Up to 16 groups of indoor•units
Up to(128
16 groups
units) can
of indoor
be easily
units
controlled
(128 units)
using
canthe
be easily controlled using the
em Configuration
centralSystem Configuration
Note 2 Note 2
Residential remote
1 controller
Residential central remote controller large LCD panel. ON/OFF, temperature
DCS303A51 DCS303A51
large LCD panel.
controlled individually for indoor
controlled
settings
ON/OFF,
and scheduling
temperature
cansettings
units.individually for indoor units.
be and scheduling can be Daikin provides engineering supports for VRV systems. It
No.
Interface adaptor forItem
residential
2 Interface
indoor
adaptor
units forModel
Item No. indoor units KRP928BB2S
residential
KRP928BB2S Model No. Function Function consists of design supports that can assist consultants and
• Adaptors required to connect • Adaptors
productsrequired
other than
to connect the VRVother
those ofproducts System
thantothose of the VRV System to
• Up
the to 16 groups of indoor•units
Up
the to
(128
16 groups
units) can
of indoor
beadopted
easily
units
controlled
for(128
the units)
using
canthe
beadopted
easily controlled using the
Residential central remote
1
3 controller
Residential
Interface adaptor for SkyAir-series central
Note32
Note
remote controller
Interface adaptor forDCS303A51
SkyAir-series
high-speed
large LCD
Note32 DIII-NET communication
Note
panel. ON/OFF,
high-speed
temperature
large LCD
system
panel.
DIII-NET
settings
ON/OFF,
and
communication
scheduling
temperature
VRV
can
system
System.
settings
be and
for the VRV
scheduling can be
System. architects, as well as sales proposal supports for air conditioning
DTA112BA51 DCS303A51
DTA112BA51
controlled individually for indoor
controlled
units.individually for indoor units.
Central control adaptor kit 4For UAT(Y)-K(A),FD-K
Central control adaptor kitDTA107A55
* To use any of the above optional
For UAT(Y)-K(A),FD-K DTA107A55
installed on the
* To controllers,
use any of the
product unit toinstalled
be controlled.
an appropriate
above optional
adaptor
controllers,
must be
on the product unit to be controlled.
an appropriate adaptor must be
engineers and dealers. We at Daikin provide the software, the
Interface
Wiring adaptor
adaptor forfor residential
other2 Interface
indoor
5 air-conditioner
Wiring adaptor
unitsforfor
adaptor residential
KRP928BB2S
other indoor
air-conditioner
DTA103A51 units required
• Adaptors KRP928BB2S
DTA103A51
to connect
• Adaptors
products required
other than
to connect the VRVother
those ofproducts Systemthantothose of the VRV System to
Note 3 the to
• Up high-speed
1024Note 3 DIII-NET
units communication
the to
can be centrally
• Up high-speed
1024
controlledsystem
unitsDIII-NET
in
can64adopted
be communication
different for
centrally the
groups. VRVsystem
controlledSystem.
in 64adopted
differentfor the VRV System.
groups. simulation results, and drawing materials to support the
Interface expander
DIII-NET adaptor for 3
SkyAir-series
adaptor
6 Interface expander
DIII-NET adaptor for SkyAir-series • Wiring restrictions
adaptor
DTA109A51
DTA112BA51 DTA109A51(max. length:
DTA112BA51 • Wiring 1,000m,
restrictions
total wiring
(max. length:
length: 1,000m,
2,000m, total
max.wiring length: 2,000m, max.
*number
To use any of the above
of branches: 16)optional
*number
apply To to
use
controllers,
any
each of the
anabove
of branches:
adaptor. appropriate
16)optional
applyadaptor
tocontrollers,
eachmust an
be appropriate adaptor must be
adaptor. business-information modeling (BIM) currently entering the
Central control adaptor kit 4For UAT(Y)-K(A),FD-K
Central control adaptor kitDTA107A55
For UAT(Y)-K(A),FD-K on DTA107A55
installed control
the product unit toinstalled
bemultiple
controlled.
on the product unit toor
bemultiple
controlled.
• Demand • Demand
of individual or control of individual
systems. systems.
Wiring
External adaptor
controlfor other
adaptor 5
6-1 air-conditioner
Wiring
External adaptor
control for other
adaptor air-conditioner
DTA103A51
DTA104A61 DTA103A51
DTA104A61
• Low noise option for individual • Lowornoise option
multiple for individual or multiple systems.
systems. mainstream in construction industries.
• Up to 1024 units can be centrally
• Up to 1024 controlled
units in
can64be
different
centrally
groups.
controlled in 64 different groups.
DIII-NET expander adaptor
6 DIII-NET expander adaptor
DTA109A51 • When
• Wiring installing DTA109A51,
restrictions
DTA109A51(max. • When
length:
• DTA104A61
Wiring installing
1,000m, into
DTA109A51,
restrictions
totaloutdoor
wiring units
DTA104A61
(max. length:
length: of1,000m,
10 HP (VRV
2,000m, into
max.outdoor
total X) / length:
wiring units of2,000m,
10 HP (VRV
max.X) /
Mounting plate 6-2 Mounting plate BKS26A BKS26A
14 HP (VRV
number A) or larger.
of branches: 16) apply14 HP
number (VRV
to each A) or larger.
of branches:
adaptor. 16) apply to each adaptor.
Mountingbox
Installation plate
for Note:
adaptor Mounting
6-11. Installation
must plate
be obtained
box KRP4A92
forlocally.
adaptor • Fixing plate
must be obtained for DTA109A51
KRP4A92
locally. • Fixing plate for DTA109A51

Design
For residential use only. Cannot
2. Forbe
residential
used withuseother
only.
centralised
Cannot becontrol
used with
equipment.
other centralised control equipment.
Installation box for Note:
adaptor
1. Installation
must be obtained
box for locally.
adaptor must be obtained locally.
No adaptor is required for some
3. No indoor
adaptorunits.
is required for some indoor units.
For residential use only. Cannot
2. Forbe
residential
used withuseother
only.
centralised
Cannot becontrol
used with
equipment.
other centralised control equipment.
No adaptor is required for some
3. No indoor
adaptorunits.
is required for some indoor units.

ding Management
BuildingSystem
Management System For consultants and architects
ding Management
Building
No. Item
System
Management System
Item Model No. Model No. Function Function
No. Item Item Model intelligent
intelligent Touch No. • Air-Conditioning
Touch Model No. • Air-Conditioning
management Function
system that can management Function
be controlledsystem
by a that can be controlled by a
Basic 1 Hardware Controller Basic DCS601C51
Hardware Controller DCS601C51
compact all-in-one unit. • compact all-in-one unit.
intelligent Touch intelligent Touch
intelligent Touch • Air-Conditioning
intelligent Touch management Air-Conditioning
system that can management
be controlledsystem
by a that can be controlled by a
Controller 1
Basic Hardware
Controller Controller
DIII-NET Basic DCS601C51
plus Hardware DIII-NET
Controller plus
compact DCS601C51
all-in-one unit. compact all-in-one unit.
Combines energy efficiency and comfort
intelligent Touch Option intelligent Touch
1-1 Hardware Option Hardware
adaptor Additional 64 groups (10 outdoor
DCS601A52 • DCS601A52 • Additional
units)64isgroups
possible.(10 outdoor units) is possible.
Controller adaptor
Controller DIII-NET
1-1 plus DIII-NET plus
Electrical box withOption
earth
1-2 Hardware
terminal
Electrical
(4 blocks)
box with
adaptor
Option
earth Hardware
DCS601A52
terminal (4 blocks)
KJB411Aadaptor
• Additional 64
• Wall embedded groups
DCS601A52
switch
KJB411A (10 outdoor
• Additional
box.
• Wall units)
embedded64is groups
possible.
switch(10 outdoor units) is possible.
box.
Electrical box withBasic
earth
1-2
2 terminal
Electrical
Hardware(4 intelligent
blocks)
box with Touch
earth
Basic terminal (4 intelligent
blocks)
KJB411A
Hardware Air-conditioning
Touch
• Wall embedded management
switch
KJB411A box. Air-conditioning
system
• Wall embeddedthat can
management
be
switch controlled
box. system
by that can be controlled by
Manager DCM601A51Manager touch screen.DCM601A51 touch screen.
• Air-conditioning management • Air-conditioning
system that can management
be controlledsystem
by that can be controlled by
Basic
2 Hardware intelligent TouchHardware
Basic DCM601A51intelligent Touch
Additional DCM601A51
64 groups (10 outdoorAdditional
units)64isgroups
possible.(10 outdoor units) is possible.
Manager Manager • touch screen. • touch screen.
2-1 Hardware iTM plus adaptorHardware DCM601A52iTM plus Max. 7 iTMDCM601A52
adaptor plus adaptors •can
• Additional 64 groups (10 outdoor
Max.
be 7connected
iTM plus adaptors
Additional
units)64is
to intelligent
groups
possible.(10
can Touch
be connected to intelligent Touch
outdoor units) is possible. CFD simulation to optimise
Manager. Manager. Heat load calculation
2-1 Hardware iTM plus adaptorHardware DCM601A52iTM plusMax. 7 iTMDCM601A52
adaptor
• Manager.
plus adaptors can Max.
be 7connected
• Manager.
iTM plus adaptors
to intelligent
can Touch
be connected to intelligent Touch outdoor unit layouts
iTM power iTM power Power consumption of indoor Power
unitsconsumption
are calculated of based
indooronunits are calculated based on
2-2 proportional DCM002A51 operation status
proportional DCM002A51of the indoor
• Power consumption of indoor
operation
unit andstatus
• Power
outdoorof the
unitindoor
powerunit and outdoor unit power
intelligent Touch iTM
intelligent Touch power iTM powerconsumption measured by kWh units consumption
are calculated
consumption
metre. measured of based
indoor
by kWh on
units are calculated based on
metre.
2-2 distribution distribution
operation status of the indooroperation
unit andstatus
outdoorof the
unitindoor
powerunit and outdoor unit power
Manager Manager proportional DCM002A51proportional DCM002A51
intelligent Touch intelligent Touch
distribution
iTM energy iTM • consumption
distribution
Building
energy energymeasured by• kWh
consumption consumption
metre.
Building
is measured
visualised.
energy by
consumption kWh metre.
is visualised.
2-3 Software
Option Option Software
DCM008A51 DCM008A51 energy
Manager Manager navigator navigator Wasted air-conditioning Wasted can air-conditioning
be found out. energy can be found out.
• Building energy consumption • Building
is visualised.
energy consumption is visualised.
2-3 Software iTM energy
Option Option Software
DCM008A51
iTM energy
DCM008A51
2-4 navigator client
BACnet ®
DCM009A51BACnet
navigator ®Wasted
client air-conditioning
• BACnet ®
equipment
DCM009A51 can be•energy
Wasted
BACnet
managedcan
®
air-conditioning
beintelligent
found can
equipment
by out. energy
Touch
be managedcan by
Manager. beintelligent
found out. Touch Manager.
2-4
2-5 BACnet ®
client
HTTP Interface DCM009A51
DCM007A51BACnet • BACnet
®
equipment
client ® for
HTTP Interface
Interface DCM009A51
DCM007A51 can
intelligent be
• BACnet
Touch managed
Interface
Manager®
equipment
by
forby intelligent
HTTP can
intelligent Touch
be managed
Touch Manager.
Manager by
byintelligent
HTTP Touch Manager.
Design flexibility
2-5
2-6 HTTP Interface DCM007A51
SVMPR2HTTP Interface
• Interface DCM007A51
for
VRV Smartphoneintelligent
SVMPR2 Touch
Control Interface
VRVManager
•System forforby
intelligent
Smartphone HTTP
residence Touch
Control Manager
System by HTTP
for residence
2-7
2-6 Hardware *1 SVM series Hardware
SVMPC2*1 SVM• series
SVMPR2 VRV Smart SVMPC2
SVMPR2
phoneRemote
Smartphone VRV Smart
Control•Controller
System forfor
residence
phone
Smartphone Control Controller
building
Remote System forforresidence
building
2-7
2-8 Hardware *1 SVM series Hardware
SVMPC2 *1 SVM• series
*5 SVMPS1 VRV
TenantSmart SVMPC2
*5Phone
Billing Remote
SVMPS1
System VRV
Controller
with• PPD Smart
Tenant forPhone
Billing building
Remote
System Controller for building
with PPD
VRV Smartphone Control
2-8 VRV Smartphone Control System
2-9 System *5 SVMPS1
SVMPR1 VRV Smartphone
• Tenant *5
BillingSVMPS1
Control
System
SVMPR1 VRV Smartphone
with•System
PPD
Tenant for residence
Billing Control
System with
withDTA116A51.
System
PPD for residence with DTA116A51. Heat load calculation Model selection Drawing materials support
VRV Smart Phone Control VRV Smart Phone Control System
2-9 System SVMPR1 • VRV
*6 Smart
• VRV Phone
SVMPR1
Tablet and Control
Smartphone*6 VRV
• System
• VRVSmart
for residence
Phone
Controller
Tablet and
for Control
smallwithsize
SmartphoneDTA116A51.
System foror
building residence
Controller withsize
for small DTA116A51.
building or
VRV Tablet and Smartphone
2-10 VRV Controller
Tablet and Smartphone Controller
SVMPC1 SVMPC1
VRV Tablet Controller
2-10 VRV Tablet Controller SVMPC1 • VRV residence with DTA116A51.
TabletSVMPC1
Controller • VRV
for small residence
size
Tablet withwith
building DTA116A51.
Controller DTA116A51
for small size building with DTA116A51
Multi
Di unitSite Management
2-11System
2-11 Multi
Di bySite
unit using
Management
SVMPC1 System MSMPN1 MSM
by using SVMPC1
DEC101A51 •• 8 pairscan control
basedMSMPN1
DEC101A51 VRV
on aallpair of •units
• MSM
ON/OFF viacan
8 pairs SVM control
based
input system
and VRV
allpair
on multi
of units
on aabnormality site.
ON/OFFvia SVM
input.inputsystem on multi site.
and abnormality input.
Di unit
Dio unit 2-12 Dio
2-12 Di unit
unit DEC101A51 •• 4
DEC102A51 8 pairs
pairs based
based on a
DEC101A51
on
DEC102A51a pair
pair of
of ••ON/OFF
ON/OFF
8 pairs
4 pairs based
based
input and
input and
on a
on aabnormality
abnormality
pair of
pair of ON/OFF
ON/OFF
input.input
input. input and
and abnormality
abnormality input.
input.
Dio unit 2-13 Dio unit 4 pairs based
DEC102A51 •• Interface unit on
to aallow
DEC102A51 pair of ••ON/OFF
4 pairs based
communications
Interface input
unitandonto aallow
abnormality
betweenpair of ON/OFF
VRV input.
communications
and input and
BMS. abnormality
between input.
VRV and BMS.
*2 Interface
3 for use in BACnet
*2 ®Interface for use in BACnet
DMS502B51 Operation
®
• Interface and monitoring
DMS502B51 Operation
of air-conditioning
andtomonitoringsystems
VRVofand
through
air-conditioning systems through
VRV and
® unit to allow communications
• Interface
® unit between allow communications
BMS. between BMS.
*2 Interface
3 for use in BACnet
*2 Interface for
®
DMS502B51 BACnet
® communication.
use in BACnetOperation DMS502B51
and monitoring OperationBACnet communication.
of air-conditioning
and monitoring systems ofthrough
air-conditioning systems through
• BACnet
Expansioncommunication. BACnet
Expansioncommunication.
® ®
kit, installed on• DMS502B51, kit,toinstalled
provide on2 more
DMS502B51,
DIII-NET to provide 2 more DIII-NET
Optional
3-1 DIII board Optional DIIIDAM411B51
board DAM411B51
communication
• Expansion ports. Not
kit, installed on• usable
communication
DMS502B51,
Expansionindependently. ports. Not
kit,toinstalled
provide on usable
2 more independently.
DMS502B51,
DIII-NET to provide 2 more DIII-NET
Communication Optional Communication
3-1 DIII board Optional DIIIDAM411B51
board DAM411B51
interface interface communication
• Expansion kit, ports. Not
installed on usable
communication
•DMS502B51,
Expansionindependently.
kit,
to ports. Not
installed
provide 16
on usable
more independently.
DMS502B51,
wattmeter to provide 16 more wattmeter

Sales proposals
Optional
3-2 Di board Optional Di board
DAM412B51 DAM412B51
pulse inputkit,
• Expansion points. Noton
installed usablepulse independently.
inputkit,
•DMS502B51,
Expansion points.
toinstalled
provideNot16
onusable
more independently.
DMS502B51,
wattmeter to provide 16 more wattmeter
Optional
3-2 Di board Optional Di board
DAM412B51 DAM412B51
pulse input
• Interface points.
unit Notcommunications
to allow usablepulse independently.
input
• Interface unitpoints.
between Notcommunications
to allow usable
VRV andindependently.
BMS. between VRV and BMS.
Communication Communication
4
*3 Interface for use in LONWORKS
*3 Interface
®
for use in LONWORKS
DMS504B51 Operation
®
• Interface andtomonitoring
DMS504B51
unit Operation
of air-conditioning
allow communications
• Interface andbetween
unit tomonitoring
allowsystems
VRVofandthrough
air-conditioning
communications
BMS. between systems
VRV andthrough
BMS.
interface interface LonWorks ®
communication. LonWorks ®
communication.
4
*3 Interface for use in LONWORKS
*3 Interface
®
for use in LONWORKS
DMS504B51 Operation
® and monitoring Operation
DMS504B51 of air-conditioning
and monitoring
systemsof through
air-conditioning systems through
LonWorks ®
communication.
• Use of the Modbus protocol LonWorks
• Use enables
®
communication.
of the Modbus
the connectionprotocolof enables
the the connection of the For air conditioning engineers and dealers
Home5 Automation InterfaceHomeAdaptorAutomation VRV
Interface*7Adaptor
DTA116A51 • Use system with
DTA116A51
of the Modbusa variety
®
*7VRV
of
protocol home
• Usesystem
of automation
the with
enables the aconnection
Modbus variety
systems
® of home
protocolfrom
of theautomation
enables systems of
the connection from
the
Home5 Automation InterfaceHomeAdaptorAutomation other
Interface Adaptor
DTA116A51 manufacturers.
VRV system
DTA116A51 other
with a variety VRV manufacturers.
of homesystemautomation
with a variety
systemsof home
from automation systems from
Contact/ UnificationContact/
adaptor for computerised
Unification adaptor for computerised other manufacturers. • Interface
• Interface between the central
other manufacturers.
monitoringbetweenboardthe andcentral
central
monitoring
control board and central control
6
analogue signal control analogue signal control DCS302A52 • units. DCS302A52 • units.
When installing DTA116A51 When
into outdoor
installing units
DTA116A51
of 10 HP into
(VRVoutdoor
X) / units of 10 HP (VRV X) /
Mounting
5-1 plate Mounting plateBKS26A BKS26A
14 HP (VRV A) or larger. 14 HP (VRV A) or larger.
HTTP interface (DCM007A51)Note: *1. is HTTP
also required.
interface (DCM007A51) is also required.
Contact/ is a registeredUnification Contact/
ofadaptor for computerised
Unification adaptor for • Interface between the central
computerised • Interface
monitoring
between
boardtheand
central
central
monitoring
control board and central control Heat load calculation Model selection
® ®
BACnet trademark
6 *2. BACnet American
is a registered
Society of
trademark
Heating, ofRefrigerating
American
DCS302A52 Society
and Air-Conditioning
of Heating, Refrigerating
Engineers
DCS302A52 (ASHRAE).
and Air-Conditioning Engineers (ASHRAE).
analogue ® signal
LonWorks is a trademark control
of *3.
Echelonanalogue
LonWorks ®
is signal
Corporationa trademarkcontrol
registeredof in
Echelon
the United
Corporation
States and units.
registered
other countries. units.
in the United States and other countries.
Installation box for adaptor*4. mustInstallation
be obtained box for
locally.
adaptor must be obtained locally.
HTTP interface (DCM007A51)Note: *1. is HTTP
also required.
interface (DCM007A51) is also required.
PPD option
® (DCM002A51) for*5. iTM PPDis also
option
® required.
(DCM002A51) for iTM is also required.
BACnet is a registered trademark of American
*2. BACnet is a registered
Society oftrademark
Heating, ofRefrigerating
American Society
and Air-Conditioning
of Heating, Refrigerating
Engineers (ASHRAE).
and Air-Conditioning Engineers (ASHRAE).
® ®
LonWorks is a trademark of *3. Echelon
LonWorksCorporation
is a trademark
registeredof in
Echelon
the United
Corporation
States and
registered
other countries.
in the United States and other countries.
Option
List

Option
List

Installation box for adaptor*4. must be obtained


Installation locally.
box for adaptor must be obtained locally.
PPD option (DCM002A51) for*5. iTM PPDis also
option
required.
(DCM002A51) for iTM is also required.
Possible to connect at a maximum *6. Possible
of 2 DTA116A51.
to connect at a maximum of 2 DTA116A51.
® ®
Modbus is a registered trademark *7. Modbusof Schneider
is a registered
Electric trademark
S.A. of Schneider Electric S.A.

103 212
98 212
98 99 104
MEMO

Model Selection Software VRV Xpress

VRV Xpress is a flexible design software that optimises equipment selection. It


can empower consultants and air conditioning engineers so they can fully
enhance their equipment selections to design the most effective, optimum
systems possible. The software also allows the choice of outdoor units based on
peak loads rather than the sum of required capacities for each indoor unit. This
fine-tuning feature reduces VRV system sizes and increases efficiency.

CFD Simulation to Optimise Outdoor Unit Layouts DT FLOW II

DT FLOW II is a simulation software that uses computational fluid dynamics


(CFD), aiming to optimise outdoor unit layouts right at the design stage. When
discharged air from the outdoor unit is drawn back into the suction vent, it can
short circuit the system and lead to: decrease in efficiency of cooling operations,
capacity shortages, operation cut-offs, and shorter lifetime for the outdoor unit.
To avoid the need for expensive layout modifications once construction is
complete, Daikin uses the CFD method at the early design stage. This can help
consultants and architects optimise their outdoor unit arrangement.

Heat Load Calculation DACCS-HKGSG and HKGSA

The DACCS program uses a steady-state load calculation method to compute


heat load over a 24-hour period on summer and winter days. The heat load
coming in through outer walls and rooftops from strong summer sunlight can be
substantial, but the DACCS program applies effective temperature differences
based on the effects of heat accumulated in the walls. The program also
accesses 24-hour weather data for all major cities. The standard design data
includes accurate weather information for 140 countries.

Drawing Supports CAD Symbols

Users download CAD symbol drawing materials, including 2D CAD symbols and
3D Revit data, for VRV systems designing. The 3D Revit data contains
specifications for Daikin products, including things like capacities and electric
characteristics to support Business Information Modeling (BIM).