AMINE RECLAIMER SYSTEM

Document Title CABLE SIZING CALCULATION

Document No. D1006-01-EE-CA-0002 / REV.1

Client Document No. 16006-GKPI-ELE-CAL-0002

Contract No. 2170195

1 Issued for Design 30-Jan-18 VM JS SJ

0 Issued for Approval 16-Jan-18 VM JS SJ

Quality
Rev No Revision Details Issue Date Prepared By Checked By Approved By
Review By
Project documents are controlled documents.
Revisions are denoted in right hand margin

GPS Client GPS Project No.


GULF KEYSTONE PETROLEUM INTERNATIONAL LTD
D1006-01
Client Doc No.: 16006-GKPI-ELE-CAL-0002
CABLE SIZING CALCULATION
REV. 1

REVISION SUMMARY

REVISION SECTION DESCRIPTION

0 COMPLETE DOCUMENT ISSUED FOR APPROVAL

1 COMPLETE DOCUMENT ISSUED FOR DESIGN

Page 2 of 4 D1006-01-EE-CA-0002
Client Doc No.: 16006-GKPI-ELE-CAL-0002
CABLE SIZING CALCULATION
REV. 1

GENERAL NOTES:

1) Design ambient air temperature min: -6.20C, max: 45.250C


2) The reference cable manufacturer is Draka
3) All cable shall be routed in ventilated tray.
4) The max. conductor operating temperature is 90 0C and under short circuit condition is 2500C
5) The starting current of motor with DOL starter is 6 times the full load current.
6) Cable description:
S.No Description

a Single core Cable shall be 600/1000 V , stranded plain annealed copper conductor with XLPE
insulation, aluminium wire armour, Flame retardant type cables as per BS5467.

b Multi core Cable shall be 600/1000 V , stranded plain annealed copper conductor with XLPE
insulation, steel wire armour, Flame retardant type cables as per BS5467.

7) The max. steady state and transient operation voltage drop are as below:
S.No Description Permissible Level
a Motor feeder terminals 5% max.
b Others (Heaters, Packages, etc.) 5% unless particular requirement
c Motor starting voltage drop 15% max. at motor terminals
2% avg. with a max. of 8% at to the
d Lighting sub circuits
farthest fittings

ABBREVIATIONS:
C Core
M Meter

AC Alternating Current

HZ Hertz
PC Power Cable

CC Control Cable
PVC Poly Vinyl Chloride
LCS Local Control Station

MCC Motor Control Centre


XLPE Cross Linked Poly Ethylene

BS Bristish Standard

Page 3 of 4 D1006-01-EE-CA-0002
Document No: D1006-01-EE-CA-0002
GULF KEYSTONE PETROLEUM CABLE SIZING CALCULATION
Revision No. 1

Status ISSUED FOR DESIGN


GLOBAL PROCESS SYSTEMS PROJECT: AMINE RECLAIMER SYSTEM
Date 30-Jan-18

Derating Factors Voltage Drop


Sl.No Service From To Load Voltage Load No. of Cable Cable Method of Ambient Air Group Total Derated No.of Cable Cable Rectance Starting Starting Runing Runing
Equipment (kW) (V) Current (A) Cores Size Current Laying Temperature Rating Derating Current Runs Length Resistance /KM Power Power Power Power Steady State During Starting
Tag No. (mm²) Rating (450 C) factor Factor Capacity (m) /KM @ 50Hz Factor Factor Factor Factor Voltage Permissible Voltage Permissible Remarks
(A) @900C (ohms) (Cosθ) (Sinθ) (Cosθ) (Sinθ) Drop Voltage Drop Voltage
(ohms) (% Vd) drop (%) (% Vd) drop (%)

Reclaimer
Switchgear/ Ventilated
1 PC-0001 Feed Pump 3.0 400 5.85 3C 6 54 0.87 1 0.87 46.98 1.00 275 3.9270 0.088 0.79 0.62 0.86 0.51 2.39 5.00 13.15 15
MCC tray
Motor

Reclaimer
PC-0002 Switchgear/ Ventilated
2 Heater 226 400 326.21 3#1C 185 529 0.87 1 0.87 460.23 1.00 30 0.1280 0.085 NA NA 1.00 0.00 0.54 5.00 NA NA
A,B&C MCC tray
Control Panel

Reclaimer
PC-0003 Heater Ventilated
3 Electrical 226 400 326.21 3#1C 185 529 0.87 1 0.87 460.23 1.00 245 0.1280 0.085 NA NA 1.00 0.00 4.43 5.00 NA NA
A,B&C Control Panel tray
Heater

Page 4 of 4