PLANILLAJE DE CIRCUITO - CALCULO DE CARGA

A.- SISTEMA DE BOMBEO ELECTRICO


POT. U VOLTAJE POT. TOTAL D. MAXIMA
NUMERO DESCRIPCION LINEAS CANT. CORRIENTE TOTAL FACTOR.
CIRCUITO [ AMP] DEMANDA
[ KW ] [ VOLT ] [ KW ] [ KW ]

CA1.1 Motor Electrico a Instalar 149.200 460 L1 - L2- L3 1 149.20 324.35 1 149.20

POTENCIA TOTAL [KW] 149.20 149.20

RESUMEN GENERAL DEL SISTEMA DE FUERZA ELÉCTRICA


TRANSFORMADOR
CARGA INSTALADA 149.20 [KW]
DEMANDA MÁXIMA ACTIVA 149.20 [KW]
FACTOR DE POTENCIA 0.8
DEMANDA MÁXIMA APARENTE 186.50 [KVA]
FACTOR DE COINCIDENCIA 1
DEMANDA MÁXIMA ACTIVA COINCIDENTE 149.20 [KW]
DEMANDA MÁXIMA APARENTE COINCIDENTE 186.50 [KVA]
FACTOR DE RESERVA [25%] 46.63 [KVA]
CAPACIDAD CALCULADA DEL TRANSFORMADOR 233.13 [KVA]

POTENCIA COMERCIAL DEL TRANSFORMADOR TRF1 250.00 [KVA]