Sei sulla pagina 1di 1

BATTERY SIZING DONE TO IEEE485 STANDARD

CUSTOMER Date 20-9-2019


Sized by: SYED FIAMM
PROJECT
FIAMM Sizing Tool 2.1.22
DESIGN MINIMUM CELL ELECTROLYTE CELL TYPE:
TEMPERATURE: 20 °C VOLTAGE 1.750 Volt DENSITY 1.27 FLAT PLATE
(1) (2) (3) (4) (5) (6) (7)
PERIOD LOAD CHANGE IN DURATION TIME TO END (3) / (6)
LOAD (Amperes) LOAD OF PERIOD OF SECTION Ah/pos plate
( minutes ) POSITIVE PLATE FOR SECTION
Pos. Values Neg. Values

Section 1
1 A1 = 600.0 A1-0 = 600.0 M1 = 1 M1= 1 108.35 5.54
Sub total 5.54
Total 1.................... 5.54
Section 2
1 A1 = 600.0 A1-0 = 600.0 M1 = 1 M1+M2= 121 27.80 21.58
2 A2 = 180.0 A2-A1= -420.00 M2 = 120 M2= 120 27.96 -15.02
Sub total 21.58 -15.02
Total 2.................... 6.56

Temperature correction = 1.00 Design Margin = 1.30 Aging Factor = 1.30


Uncorrected Size = 6.56 Positive Plates Number of positive plate x Total Correction Factor (1.69) = 11.08 Positive Plates
Required Size = 12 Positive Plates
Capacity = 960 Ah (C10) Number of cells = 64 Cell Type = SDH 25

Requested Load Profile


700

600
600

500

400
(Amperes)

300

180
200

100

0
0 20 40 60 80 100 120 140

MINUTES

All data printed in this document are preliminary and must be confirmed by Fiamm