Comment on drawings / document for JN-23
Sr.no. Document
5
GTP
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
6 GA drawing
7 LV Bus duct
8
GA of marshalling box
9
10
13
14
15
Comment Resolution Sheet-oil Filled Distribution Transformers.-2 no. 2000 KVA,1000 KVA,500 KVA,11/0.433 KV oil filled Transform
Comments Description
Sr. no. 11-Resistance Per phase value to be mentioned.
Sr. no. 18- HV Side Fault Level is 40kA and LV side fault level is 50kA
Please submit painting process as per CBIP Manual and follow painting
clause 5.21.0
WTI & OTI-Dial shall have linear gradation to read atleast every 2 degc and
accuracy shall be 1.5% tor better
Wiring shall be 1100V Grade and 20% spare terminals shall be provided
Two sets of separate potential free contacts shall be provided for each
alarm and trip wired to terminal block
Provide alarm and Trip contacts for the OTI and WTI
Provide signal Transmitter RTD shall be provided as per clause 5.8.0
RCXT-Dual Output
ALL THE COMMENTS PROVIDED FOR 1000KVA TRANSFORMER ARE
APPLICABLE AND TO BE INCORPORATED
Furnish the values of Short time rating for 2 seconds and Permissible over
loading.
Capacitance value.
K-Factor (for Converter duty Transformers).
test voltage(since QAP not annexed, please include the same in
the datasheet itself).
Creepage distance shall be 25mm/kV, instead of 16mm/kV.
Datasheet : Check the current rating of Tap-changing equipment, it is less
than the nominal current.
GA of HV & LV Terminal Box : Furnish the following details,
Current rating and Voltage grade of the bushing.
Make of bushing
Dry power frequency withstand voltage.
Rating plate : Check the followings,
M/s.Wabag please look into the Energy efficiency level of the distribution
Transformers, the specified Energy efficiency rating is very low.
Furnish the design Impedance in Notes.
Actual tested loss values only need to be filled in the rating plate,hence
specify these values in Notes.
Apart from the above, MRPL comments if any will be shared shortly.
Comment on drawings / document for JN-23188 (M/s. VA Tech Wabag Ltd.) 7.5 MVA, 6.6/0.7
Comments
Transformer losses shall be guaranteed for rating with K factor. No load loss
with K factor will be K times rated no load loss and load loss with K factor
will be K ^2 times rated load loss.
All the comments provided for 1000 KVA transformer are applicable and
to be incorporated. (Mentioned below)
Resistance per phase (Ohm) to be specify.
External short circuit withstand capacity (MVA) and duration (sec).
Overfluxing withstand capacity of transformer: 110% continuous & shall
not exceed 1.9 Tesla.
Material of lamination shall be mentioned: CRGO silicon steel shall be H1-B
grade or equivalent.
LV bushing shall be epoxy cast resin.
Specify tank plate thickness.
Refer GA Drawing BOM serial No. 36 , we had already provide 2 nos. 75x10
mm GI flate
Noted.
Already provided Refer Whole 27 no.
Already provided Refer Whole 27 no.
Already provided Refer Whole 27 no.
Noted ,please confirm coments if any from MRPL so that we will check and
incorprate in revised documents in one attempt.
3188 (M/s. VA Tech Wabag Ltd.) 7.5 MVA, 6.6/0.72-0.72 KV
VTL reply dt. 07.08.2019
We have considered HV Fault level -25 kA for 2 sec and LV is 50 kA for 2
sec as per your specification clause no. 7.0.0 page no. 79 of 273 . If any
change in same is required same wiil be subject to feasibility and price
implication.