Improved Digital Control Scheme of Three Phase UPS Inverter

Using Double Control Strategy


Jae-Ho Choi Byoung-Jin Kim

School of Electrical and Electronics Engineering


Chungbuk National University
48 Gaesindong, Cheongju, Chungbuk, South Korea 36 1-763
Tel : (431)61-2425, Fax : (431)276-7217
E-mail : choi@choijae.chungbuk.ac.kr

Abstract - Novel digital control scheme of UPS inverter voltage regulation and compensation to complement the
based on the double control strategy is proposed. This current controller. Although the capacitor current controller
consists of a inner voltage regulated current controller and acts very well, it is hard to compensate the load current
an outer current regulated voltage controller. In order to
on the instant of its change because the feedback
improve the dynamic response, the voltage controller has a
load predictive feedforward loop and the current controller
capacitor current doesn't include any information about
has an output voltage feedforward loop. PI compensators the load change. As a result of load change, the inverter
including in each of the voltage and current controllers are output capacitor voltage is collapsed with the capacitor
used to guarantee the robustness of the system. The mathe- input typed rectifier load.
matical model and the control algorithm of the proposed This paper proposes a digital control scheme of UPS
scheme are described, and the digital simulation and inverter to improve the dynamic response of output
experimental results for 5 kVA prototype are provided to voltage controller. This provides the sinusoidal voltage
verify the validity of the proposed double control strategy. waveform even though the nonlinear load is connected.
And also, this controller keeps the robustness against
I. INTRODUCTION the parameter variations and noises. The proposed control
scheme is based on the conventional current regulated
Uninterruptible Power Supplies(UPS) are used to keep voltage controller, but it is different from the respect of
the high quality power source for the critical loads such the control target and the control strategy, which is that
as computers and communication systems against the the inner current controller in the outer voltage
poor utility system. The most important role of the UPS controller has a voltage regulated current controller. [7,8]
inverter is to regulate the output voltage waveform with In order to improve the dynamic response, a load
constant voltage and constant frequency even though the predictive feedfonvard loop in a voltage controller and a
variations of the line source or loads. output voltage feedfonvard loop in a current controller is
Sinusoidal PWM and optimal PWM techniques have considered. And to guarantee the robustness of the
been used to the UPS inverters to control the RMS system, PI compensators are included in the voltage and
value of the output voltage and to suppress the harmonic current controllers, respectively. By using the conversion
components. These techniques are simple and have good of all system parameters into dq-synchronously rotating
characteristics under the steady state condition, but they reference frame to generate the constant reference value,
operate with poor transient response and the total the natural phase offset of this controller can be avoided.
harmonic distortion factor of the output voltage is high The mathematical model and the control algorithm of
at the condition of nonlinear loads.[l]
Instantaneous feedback control techniques using dead-
beat controller have been applied to improve the transient
response. However, these are sensitive to the parameter
variations and may be unstable with the increase of the L
controller gain to improve the dynamic response, so its 0
control algorithm requires the load parameters estimation A
and all of the disturbances which affect to the control D
performance should be considered.{2,3]
To overcome these drawbacks, a current regulated
voltage controller for a single phase voltage source
inverter was proposed.[4,5,6] In this scheme, the filter
capacitor current is used as the feedback variable to
achieve a sinusoidal capacitor current. An outer voltage
control loop is also incorporated for the filter capacitor
Fig. 1. Three Phase inverter with LC lowpass filter.

0-7803-3704-2/97 $10.00 0 1 997 IEEE 820


the proposed scheme is described, and the digital
simulation and experimental results for 5 kVA prototype
are provided to verify the validity of the proposed
double control strategy.

11. PROPOSED DOUBLECONTROL STRATEGY

1. Mathematical model of UPS inverter

The configuration of main circuit is shown in Fig. 1


and the state equations are derived as followings:

d
i, = C -dt
U, = i,- iL (1)

d
VL = L,- dt i, = U,- vc-v, (2) Fig. 2 . Block diagram of plant with voltage output.
where
i = [ i , i, iW]-'and v = [U, U, uJ1 (3)

U, =
( U,, + vu, + V U Z J (4)
3
Then the dq-transformed state equations can be
described as Eq. ( 5 ) and Eq. (6).

vcd

Fig. 3. Block diagram of plant with current outout.


The system block diagrams of the plant derived from
Eq. ( 5 ) and Eq. (6) are shown in Fig. 2 and Fig. 3.

2. Current regulated voltage controller


where
The reference values of output voltage transformed by
cos(wt) cos(ot-+ 2?r cos(wt++2?r
dq-synchronously rotating reference frame are derived as -
constant value as Eq. (8) when the output voltage
references are given by Eq. (7).
sin(ot) sin(wt--) 2n
3 sin(wt+-)2jr
3 (9)
Esin (wt) 1
27r 2 2
(7)
27r
vcw
Esin(wt+ 3) As shown in Fig. 2, the load currents are working as
the disturbances to the output voltage and the dq-values

82 1
-t
'cd

Fig. 4. Block diagram of plant including voltage controller and feedforward loops.

iaq

.
uK
i ad

Fig. 5. Block diagram of plant including current controller and feedfonvard loops.

of the output voltage are coupled each other. To 3. Voltage regulated current controller
improve the system performance by eliminating the
harmful effects caused by the load current disturbances, Same as the above voltage controller, the voltage
the load current predictive feedforward loops are regulated current controller is established as shown in
established. And the voltage feedforward loops are Fig. 5 . The harmful effects of the plant caused by the
included to decouple the dq voltage values. Fig. 4 output voltage disturbances and the coupled dq-values of
shows the block diagram of the plant with the current the filter inductor currents are also eliminated in this
regulated voltage controller. The load current predictive scheme. In order to get fast responding PI gains, we
feedfonvard loop can be calculated as following Eq. do not consider about eliminated two kinds of
(10). disturbances which affect the system. Fig. 5 gives a
control equation as follows, where the subscripts 'd' and
'9' are omitted for simplification.

822
(i:- i n ) ( k pki+ ~ )1- .
= zu (11)
Ls vboi

No considering disturbances, the inverter voltage can


be expressed as a differential finction of the inductor
current like follows.
I
' I Gatesignal

Compensating inverter voltage for inductor current


error can be calculated from Eq. (12).

1
H
ThIS320

Control board
I

Replacing k, with L,/T,, Eq. (11) is represented Fig. 6. System configuration of UPS inverter and control
as a trasnsfor function and we can design the integral circuit.
gain using pole placement.
Table 1 . System parameters for simulation.
L$+ kiT, Parameters values
_
2, -
-
iz +
TAG' L$+ kiT, (14) Filter inductance
Filter capacitance
l00pH
400 ,u F
Filter ESR 0.02.Q
DC link voltage lO0OV
4. Pulse width calculation Output Voltage 2 1OV(rms)
Sampling frequency 1OkHz
The reference voltage of the inverter(1GBT) in
one sampling time must satisfy Eq. (15). It is converter There are several impotant parameteres for simulation
to Eq. (16) after adding vdc/2 to each terms of Eq. in Table 1. Fig. 6 shows the system configuration of
(15). And it has the proportional relation in one period the UPS inverter and control circuit. The overall Control
interval of Eq. (16). action of inverter is implemented on the digital real time
controller based on full software using TMS320c31 DSP.
The output voltage and load current waveforms from the
simulations are shown in Fig. 7 and Fig. 8 under the
resistor load and the capacitor input typed rectifier load,
respectively. And the experimental results are shown in
Fig. 9 and Fig. 10. The calculation time delay was not
compensated in this experiment. As the results of
simulation and experiment, it is shown that the proposed
control scheme is capable of supplying both linear and
non-linear loads with excellent voltage regulation and
minimum distortion in the UPS inverter output voltage.
From Eq. (IS), the swiching ON time is calculated as
Eq. (19). IV. CONCLUSION

To improve the dynamic response and guarantee the


(19) robustness of the UPS inverter voltage controller, the
novel double control schemes have been developed.
Using these control algorithms, the disturbances of the
plant and the dq-coupling components have been
111. SIMULATION AND EWERIMENTAL RESULTS compensated and decoupled precisely by the feedforward
controllers. The fully digital -control techniques based on

823
25-Jun-96 D I S P L R Y SETUP
7:06:47
pjq
-_z 100 nV jP;ist;rel

J o q

El 2.08 V
Kcb:T
Single

I";z::;:;t1
5 mS BWL
pi;:q
1 . 1 v RC fi 500 h S / s
2 . 2 U RC 3
3 . 5 U DC 4 DC 48mV
D .1 U oc 0 RUTO

Fig. 7. Simulation result of output voltage and load Fig. 9. Experimental result of output voltage and load
current waveforms under resistor load. current waveforms under resistor load.
25-Jun-96 D I S P L R Y SETUP
7:01:17
[pjq
r l 0.50 U /yGist:;ce)

p,sJob1
D 2.00 V
p;iI4;T
T"xi:;:1
5 m5 BWL
p:i;:q
0
!
w'0.050 - 1
2
.1
-2
U
U
RC fi
RC g 506 hS/s
0.068 0.075 0.084 0.092 0.100
3 5 U DC 1 4 DC 8.85 U
.5 v DC 0 RUTO

8. Simulation results of output voltage and load Fig. 10. Experimental result of output voltage and the
current wavefioms under rectifier load. load current waveforms under rectifier load.

TMS320c31 DSP has been used to implement the 2, pp. 196-204, 1995.
proposed control algorithm, and its validity has been 4. R.W.De Doncker and J.P.Lyons, "Control of three
verified from the digital simulation and experimental phase power supplies for ultra low THD," in ConJ
results. The mathematical modeling and analysis will be Rec. IEEE APEC'91, pp. 622-629, 1991.
discussed in detail to investigate the stability of the 5. J.H.Choi, W.K.Min, J.S.Kim, and S.H.Park, "Single
controllers in the final paper. phase microprocessor based instantaneous voltage
control of inverter for UPS," KlIEIE Trans. vol. 6 ,
REFERENCES no. 6, pp. 49-57, 1992.
6. N.Abde1-Rahim and J.E.Quaicoe, "A single-phase
M.Boost and P.D.Ziogas, "State of the art carrier voltage source utility interface system for weak AC
PWM techniques: a critical evaluation," IEEE Trans. network applications," in Conf Rec. IEEE APEC'94,
Ind Appl., vol. 24, no. 2, pp. 271-280, 1988. pp. 93 -99, 1994.
A.Kawamura, T.Haneyoshi, and R.G.Hoft, "Dead beat 7. T.Kawabata, T.Muyashita, and Y.Yamamoto, "Digital
controlled PWM inverter with parameter estimation control of three-phase PWM inverter with LC filter,"
using only voltage sensor," in ConJ Rec. IEEE IEEE Trans. Power Electron., vol. 6, no. 1, pp.62-
PESC'86, pp. 576 - 583, 1986. 72, 1991.
Y .It0 and S.Kawauchi, "Microprocessor-based robust 8. B.J.Kim, J.H.Choi, J.S.Kim, and C.H.Choi, "Digital
digital control for UPS with three- phase PWM control scheme of UPS inverter to improve the
inverter," IEEE Trans. Power Electron., vol. 10, no. dynamic response," in Conf Rec. IEEE CCECEP6,
pp. 318-321, 1996,