No: SEPERATION OF NO LOAD LOSSES IN SINGLE PHASE TRANSFORMER

AIM:-

To separate the iron losses of a single phase transformer into its components
a. Hysteresis losses
b. Eddy current losses

APPARATUS REQUIRED

S.No Apparatus Required Range Quantity


1 Ammeter (0 – 2A)MC
2 (0 – 2A)MI
3 Voltmeter (0 – 300V)MI
4 Wattmeter (300V, 2.5A,
LPF)
5 Rheostat 640Ω, 1.1A,
250Ω, 5A- 2
Nos,
6 Tachometer
7 Connecting Wires

FORMULA
1. Hysteresis Loss Wh = K1f watts
2. Eddy Current Loss We = K2f2 watts

CIRCUIT DIAGRAM:

300V, 2.5A, LPF


5A (0 – 2A)MI
+ 230V 115V
L F A A
A
2x250Ω, 5A, R
D P S T S

f
230V 640Ω, f
D.C 1.1A V (0 – 300V)MI
M N

ff ff
5A
AA Y B 0V 0V
- 2A
+ +A - 230V/115V

(0 – 2A)MC
D P S T S

160V 250Ω,
D.C 2A

2A
MODEL GRAPH:
Wi/f
(Watts/HZ)

K2f

K1

Frequency (HZ)

THEORY:
PROCEDURE
1. Give connection as per the circuit diagram
2. Close the DPST switch
3. Start the motor with the help of starter
4. For each assumed frequency, calculate speed and voltage so as to keep flux
density constant
5. The field rheostat of the motor is adjusted to run the alternator at desired speed
6. The field rheostat of the alternator is adjusted to make the voltmeter reading such
that V/f is constant
7. Repeat the above procedure for different frequencies
8. Draw the graph by taking Wi/f along Y axis and frequency along X axis
9. The Y intercept of the curve gives K1 and the slope gives K2
10. The eddy current and Hysteresis losses are calculated by using formulas

TABULAR COLUMN
No. of Poles P = 120f/N =
For each assumed frequency find N = 120f/P = RPM
VPhase = Line Voltage / √3 = Volts
Vphase/f = Volts/HZ
For each assumed frequency find V = Vphase x assumed frequency/f = Volts
M.F=
Sl. f N V Wattmeter (LPF) Wi/f Wh We
No HZ RPM Volts Reading(Wi) Watts/HZ Watts Watts
Watts
Division Actual

RESULT