Standard: Northern Ireland Electricity (NIE), 6/025 ENA
×
Get Notifications
6. Clearance from Buildings to low, medium & high voltage lines
7. Clearance above ground at the lowest conductor
8. Vertical Clearance at Middle of Span
9. Safety Clearance from Live Part in Outdoor Substation
10. Lying of Telecommunication Cables with Power Cables (>33 kV)
11. Safe approach limits for people
Go to Content ↑
×
Get Notifications
66 KV 2.4 Meter 3 Meter 4.5 Meter 5.4 Meter
132 KV 3 Meter 3 Meter 4.5 Meter 5.4 Meter
220 KV 4.5 Meter 4.5 Meter 4.5 Meter 5.4 Meter
400 KV 4.5 Meter 5.4 Meter 5.4 Meter 5.4 Meter
Go to Content ↑
Over National
KV Ground Clearance
Highway
66 KV 6.1 Meter 8.0 Meter
132 KV 6.1 Meter 8.6 Meter
220 KV 7.0 Meter 9.8 Meter
400KV 8.8 Meter 10.8 Meter
Go to Content ↑
Clearance for Telephone line Crossings Power Line
KV Clearance (Min)
66 KV 2.4 Meter
132 KV 2.7 Meter
220 KV 3.0 Meter
Go to Content ↑
KV Clearance (Min)
×
Get Notifications
66 KV 14 Meter
132 KV 14.6 Meter
220 KV 15.4 Meter
400 KV 17.9 Meter
Go to Content ↑
×
Get Notifications
to any building or part of a
building
Above 33 KV Line passes above or adjacent 3.7+(0.3 for every
to any building or part of a additional 33 KV )
building
Up to 11 KV The horizontal clearance 1.2 Meter
between the nearer conductor
and any part of such building
11 KV to 33 KV The horizontal clearance 2.0 Meter
between the nearer conductor
and any part of such building
Above 33 KV The horizontal clearance 2.0 + (0.3 for
between the nearer conductor every additional
and any part ofsuch building 33 KV )
Go to Content ↑
×
Get Notifications
Go to Content ↑
Go to Content ↑
Go to Content ↑
×
Get Notifications
Cable Min. Distance
Power cable of voltage exceeding 33 kV
Min 1.2 Meter depth
shall be laid
Underground telecommunication cable Min 0.6 Meter Separate
shall be with underground power cable of from Power Cable
voltage exceeding 33 kV.
Go to Content ↑
Go to Content ↑