Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HIT-V(5.8) M8
Return period (service life in years): 50
Item number: 387055 HIT-V-5.8 M8x110 (element) / 2123406
HIT-RE 500 V3 (adhesive)
Gap filling with Hilti Filling Set M8
Effective embedment depth: hef,opti = 64.0 mm (hef,limit = 160.0 mm)
Material: 5.8
Evaluation Service Report: ETA 16/0143
Issued I Valid: 5/14/2019 | -
Proof: SOFA design method + fib (07/2011) - after ETAG BOND testing
Stand-off installation: without clamping (anchor); restraint level (anchor plate): 2.00; eb = 10.0 mm; t = 14.0 mm
2
Hilti Grout: , multipurpose, fc,Grout = 30.00 N/mm
Anchor plate :
R lx x ly x t = 150.0 mm x 264.0 mm x 14.0 mm; (Recommended plate thickness: 13.0 mm)
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
l [mm] aM
21.0 2.00
0 0
NSd / NRd,s 1 - NSd / NRd,s MRk,s [kNm] MRk,s = MRk,s (1 - NSd/NRd,s) [kNm]
0.397 0.603 0.019 0.011
M M
VRk,s = aM * MRk,s / l [kN] gMs,b,V VRd,s [kN] VSd [kN]
1.074 1.250 0.859 0.578
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
Steel without lever arm 0.397 0.078 2.000 17 OK
Steel with lever arm 0.267 0.405 1.000 68 OK
concrete 0.966 0.112 1.500 99 OK
a a
bN + bV <= 1
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• The anchor resistances used for this design are ONLY valid if the Hilti Filling Set will be installed on the jobsite as per IFU when the Seismic
washer was selected.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100, etc.) is the responsibility of the user
• The anchor plate overlaps the concrete plate edges. A local concrete spalling due to compression has to be checked separately!
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999
8.2 Results
Stress distribution s 11
2
16.94 [N/mm ]
2
-70.93 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Stress distribution s 22
2
2.65 [N/mm ]
2
-275.00 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Deformations (z-direction)
2.7 [mm]
0.0 [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
9 Installation data
2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm
2 Anchor type and diameter: HIT-RE 500 V3 + HIT-V(5.8)
M8
Profile: Double flat bar, ; (L x W x T) = 150.0 mm x 62.0 mm x 12.0 mm Item number: 387055 HIT-V-5.8 M8x110 (element) /
2123406 HIT-RE 500 V3 (adhesive)
Hole diameter in the fixture: df = 9.0 mm Installation torque: 10 Nm
Plate thickness (input): 14.0 mm Hole diameter in the base material: 10.0 mm
Recommended plate thickness: 13.0 mm Hole depth in the base material: 64.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
Hilti HIT-V threaded rod with HIT-RE 500 V3 injection mortar with 64 mm embedment h_ef, M8, Steel galvanized, Hammer drilled installation
per ETA 16/0143, with annular gaps filled with Hilti Filling set or any suitable gap solutions
y
75.0 75.0
132.0
132.0
101.0
2 4
x
80.0
132.0
1 3
52.0
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -40.0 -80.0 925.0 1,440.0 - 176.0
2 -40.0 0.0 925.0 1,440.0 - 96.0
3 40.0 -80.0 1,005.0 1,360.0 - 176.0
4 40.0 0.0 1,005.0 1,360.0 - 96.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.49
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CONCRETE STAIRCASE Date: 9/14/2019
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12