Surge arresters POLIM-D..

N / L
Technical data
-For system voltages up to 36 kV rms - Long duration current impulse 250 A / 2000 µs
-Nominal discharge current I n 8/20 µs 10 kA pk - Energy capability, 1 impulse 1.5 kJ / kV of Uc
-High current impulse Ihc 4/10 µs 100 kA pk acc. IEC clause 7.4.2
-Short circuit rating (1) I s 50 Hz 20 kA rms for 0.2s - Energy input with Ihc 3.6 kJ / kV of Uc
-Line discharge class according to 1 acc. IEC clause 7.5.4 4.2 kJ / kV of Uc (L)
IEC 60099-4 - Power frequency up to 62 Hz
- Classification according to distribution - Cantilever strength 250 Nm
IEEE (ANSI) C62.11 heavy duty - Torsional strength 50 Nm
- Service conditions: temperature (2) - 600C up to + 450C - Vertical load 625 N
- Altitude (3) up to 1800 m
(1) Tested value acc. IEC 60099-4.
(2) These values exceed IEC requirements. For installations in higher ambient temperatures, please contact the manufacturer.
(3) This value exceeds IEC requirements. For installations in higher altitudes, please contact the manufacturer.

Application
Protection of medium voltage AC networks against both, multiple atmospheric and switching overvoltages as well as Very Fast
Transients (VFT). Suitable for instance for the protection of overhead lines and distribution transformers (pole mounted) as well
as other medium voltage equipment. For indoor and outdoor installation. The creepage distance of the L-version is increased.

Advantages
- Low residual voltage - Pollution resistant and UV-stable
- Long protection distance - Housing resistant to rough handling
- High energy input capacity - Maintenance free
- Stable U-I characteristics even after multiple strokes - Stable against shock and vibration
- Proof against ageing - High mechanical resistance
- Explosion and shatter-resistant design

Temporary overvoltage capability (TOV) - Power frequency versus time characteristic


- POLIM-D..N during 1 second (a: 1.390 x Uc or b: 1.316 x Uc)
- POLIM-D..N during 3 seconds (a: 1.370 x Uc or b: 1.290 x Uc)
- POLIM-D..N during 10 seconds (a: 1.337 x Uc or b: 1.262 x Uc)

- POLIM-D..L during 1 second (a: 1.400 x Uc or b: 1.350 x Uc)


- POLIM-D..L during 3 seconds (a: 1.380 x Uc or b: 1.330 x Uc)
- POLIM-D..L during 10 seconds (a: 1.350 x Uc or b: 1.310 x Uc)
- a: value tested with a sample that has not been prestressed by any energy input.
- b: value tetsted with a sample that has been prestressed with a prior energy input according to the operating duty test
- The values have been determined with a test sample preheated at 60 degrees Celsius according to IEC 60099-4 and refer to
an ambient temperature up to 45 degrees Celsius.

Guaranteed data for POLIM-D..N


Type UR UC Residual voltage (Ures) in kV pk at a specified impulse current
Continuous
Rated voltage operating Wave 1/.. us Wave 8/20 us Wave 30/60 us
voltage
POLIM-D..N kV rms kV rms 5 kA p k 1 0 kA p k 1 kA p k 2.5 kA pk 5 kA p k 1 0 kA p k 2 0 kA p k 1 2 5 A p k 2 5 0 A p k 5 0 0 A p k
4 5 4 14.5 16.0 11.7 12.4 13.1 14.0 15.9 10.4 10.8 11.1
6 7.5 6 21.7 24.0 17.5 18.5 19.6 21.0 23.9 15.6 16.1 16.6
8 10.0 8 28.9 32.0 23.3 24.7 26.1 28.0 31.8 20.8 21.5 22.2
10 12.5 10 36.1 39.9 29.1 30.8 32.6 35.0 39.8 25.9 26.8 27.7
12 15.0 12 43.3 47.9 34.9 37.0 39.1 42.0 47.7 31.1 32.2 33.2
14 17.5 14 50.5 55.9 40.7 43.2 45.6 49.0 55.7 36.3 37.5 38.8
16 20.0 16 57.7 63.9 46.5 49.3 52.1 56.0 63.6 41.5 42.9 44.3
18 22.5 18 64.9 71.9 52.3 55.5 58.6 63.0 71.6 46.7 48.2 49.8
20 25.0 20 72.1 79.8 58.1 61.6 65.1 70.0 79.5 51.8 53.6 55.3
22 27.5 22 79.4 87.8 64.0 67.8 71.7 77.0 87.4 57.0 59.0 60.9
24 30.0 24 86.6 95.8 69.8 74.0 78.2 84.0 95.4 62.2 64.3 66.4

Guaranteed data for POLIM-D..L


Type UR UC Residual voltage (Ures) in kV pk at a specified impulse current
Continuous
Rated voltage operating Wave 1/.. us Wave 8/20 us Wave 30/60 us
voltage
POLIM-D..L kV rms kV rms 5 kA p k 1 0 kA p k 1 kA p k 2.5 kA pk 5 kA p k 1 0 kA p k 2 0 kA p k 1 2 5 A p k 2 5 0 A p k 5 0 0 A p k
4 5.2 4 14.5 16.0 11.7 12.4 13.1 14.0 15.9 10.4 10.8 11.1
6 7.8 6 21.7 24.0 17.5 18.5 19.6 21.0 23.9 15.6 16.1 16.6
8 10.5 8 28.9 32.0 23.3 24.7 26.1 28.0 31.8 20.8 21.5 22.2
10 13.1 10 36.1 39.9 29.1 30.8 32.6 35.0 39.8 25.9 26.8 27.7
12 15.7 12 43.3 47.9 34.9 37.0 39.1 42.0 47.7 31.1 32.2 33.2
14 18.3 14 50.5 55.9 40.7 43.2 45.6 49.0 55.7 36.3 37.5 38.8
16 21.0 16 57.7 63.9 46.5 49.3 52.1 56.0 63.6 41.5 42.9 44.3
18 23.5 18 64.9 71.9 52.3 55.5 58.6 63.0 71.6 46.7 48.2 49.8
20 26.2 20 72.1 79.8 58.1 61.6 65.1 70.0 79.5 51.8 53.6 55.3
22 28.8 22 79.4 87.8 64.0 67.8 71.7 77.0 87.4 57.0 59.0 60.9
24 31.4 24 86.6 95.8 69.8 74.0 78.2 84.0 95.4 62.2 64.3 66.4
30 37.5 30 108.3 119.7 87.3 92.4 97.8 105.0 119.4 77.7 80.4 83.1
36 45.0 36 130.0 143.7 104.8 110.9 117.4 126.0 143.3 93.3 96.5 99.8

Note: The manufacturer reserves the right to change technical data or design without prior notice 01/00

ABB Power Distribution email: sales.sa@ch.abb.com / phone: +41 (0)56 205 29 11 CHHOS/AR 3257.00E
Surge arresters POLIM-D..N / L
Dimensions (in mm) Minimum clearances
42
M 12 x 23

42
116 M 12 x 23
87

116
H H

M 12 x 20
M 12 x 20
42

Insulation data, dimensions and weight for POLIM-D..N


Creepage Flashover Recommended
Type Height H Weight Insulation withstand voltage of empty housing
distance distance clearances (4)
BIL 1.2/50 µs 50 Hz 60s wet
req.values tested req. values tested
E min F min
acc. to IEC values acc. to IEC values
mm mm mm mm mm kg kV p K kV p K kV rms kV rms
04 153 121 73 100 144 <0.8 18.2 78 8.3 13
06 153 121 96 121 144 <0.8 27.3 78 12.4 13
08 306 170 118 143 191 <1.2 36.4 110 16.6 25
10 306 170 140 165 191 <1.2 45.5 110 20.8 25
12 306 170 162 186 191 <1.2 54.6 110 24.9 25
14 460 217 184 208 239 <1.6 63.7 140 29.1 38
16 460 217 207 230 239 <1.6 72.8 140 33.2 38
18 460 217 229 251 239 <1.6 81.9 140 37.3 38
20 610 264 251 273 286 <2.2 91.0 170 41.4 50
22 610 264 274 295 286 <2.2 100.1 170 45.6 50
24 610 264 296 316 286 <2.2 109.2 170 49.8 50

Insulation data, dimensions and weight for POLIM-D..L


C reepage Flashover Recommended
Type Hei ght H Wei ght Insulati on wi thstand voltage on empty housi ng
di stance di stance clearances (4)
BIL 1.2/50 µs 50 Hz 60s wet
req.values tested req. values tested
E mi n F mi n
acc. to IEC values acc. to IEC values
mm mm mm mm mm kg kV p K kV p K kV rms kV rms
04 248 136 73 100 144 <0.8 18.2 88 8.3 23
06 248 136 96 121 144 <0.9 27.3 88 12.4 23
08 375 182 118 143 191 <1.2 36.4 118 16.6 31
10 506 229 140 165 239 <1.5 45.5 148 20.8 38
12 506 229 162 186 239 <1.6 54.6 148 24.9 38
14 715 283 184 208 286 <1.9 63.7 184 29.1 50
16 715 283 207 230 286 <2.0 72.8 184 33.2 50
18 844 328 229 251 334 <2.4 81.9 213 37.3 56
20 844 328 251 273 334 <2.4 91.0 213 41.4 56
22 1101 420 274 295 429 <3.0 100.1 273 45.6 71
24 1101 420 296 316 429 <3.0 109.2 273 49.8 71
30 1311 514 361 371 518 <4.1 136.5 273 62.3 75
36 1311 514 429 437 518 <4.1 163.8 273 74.8 75

(4) National and local requirements have priority and may be used.

ABB Power Distribution email: sales.sa@ch.abb.com / phone: +41 (0)56 205 29 11 CHHOS/AR 3257.00E