User’s Manual
PAC-E100S(Overcurrent Protection Relay )
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Table of Contents
1. Overview ........................................................................ 6
1.1. Features ........................................................................ 6
1.2. Functional Single line Diagram .................................. 7
2/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
3/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
5/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
1. Overview
1.1 Features
Numerical-type Over Current (OCR), Ground Over Current (OCGR), Thermal
Overload, Under Current, and Negative Phase Sequence Over Current Protections
Auto-Reclosing, Circuit Breaker Failure, Cold Load Pickup, Inrush Detection
Various TC Curves including 4 IEC Curves, 7 ANSI Curves, 2 KEPCO’s Induction-
type Compatible Curves
Digital Indication of Setting and Metering on LCD (2 Lines × 16 Characters)
Self-Diagnosis and Internal Status Monitoring
Operation Blocking of Individual Relay Element by External Contact Inputs during the
Relay Maintenance
Configurable System Frequency (50 / 60Hz)
Easy setting of 4 Contact Outputs and 4 Programmable LED to use Logic
Contact Output: Available Trip and Signaling Contact
Direct Trip/Close Control of 1 CB from Front Panel Locally and SCADA remotely
Event recording up to 127 events and fault waveforms recording up to 20 at 16
samples/cycle.
Useful PC Application (Setting Tool)
: System Configuration, Event list, Fault waveforms analysis, Protection & Logic
Setting, Monitoring & Measurement
Self-Test Function of Contact Output by Manual Trip Emulation
Access Security by Password for Setting Change and CB Control.
Communication Interface
- RS-232C (Front and Rear), RS485C (SCADA Communication)
- Protocol: MODBUS, DNP3.0, IEC60870-5-103
Metering: 3-phase RMS Currents, Sequence Currents, Thermal, Frequency, CB Trip
Count
Free selection of control source voltage (80~300Vdc / 110~240Vac)
EMI/EMC Performance Reinforced.
6/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
46 37 49
52
PAC-E100
7/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
2. Technical Data
General Specifications
2.1.1. Current Input
Rated Current(In) AC 1A/5A (50/60Hz)
Input range 0.01 ~ 50 * In
3 times of rated value: Continuous
Thermal
20 times of rated value: 4 sec
Withstand
40 times of rated value: 2 sec
Capability
100 times of rated value: 1 sec
Burden <0.5VA / phase
2.1.6. Case
Construction Draw-out type
IP Protection Level IP51
Material Steel with Hard-Combustion Plastic Cover
8/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
ANSI/IEEE
-Inverse (ANSI_I)
TC Curve -Short Inverse (ANSI_SI)
-Long Inverse (ANSI_LI)
-Moderately Inverse (ANSI_MI)
-Very Inverse (ANSI_VI)
-Extremely Inverse (ANSI_EI)
-Definite Inverse (ANSI_DI)
ANSI/IEEE
TC Curve -Inverse (ANSI_I)
-Short inverse (ANSI_SI)
-Long inverse (ANSI_LI)
-Moderately inverse (ANSI_MI)
-Very inverse (ANSI_VI)
-Extremely inverse (ANSI_EI)
-Definite inverse (ANSI_DI)
9/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
10/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
11/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
12/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
13/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
14/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
3. Functional Description
× TM (sec )
K
T = L
+ C
G
− 1
GS
Curve K L C
IEC normal inverse (IEC_NI) 0.14 0.02 0.00
IEC very inverse (IEC_VI) 13.50 1.00 0.00
IEC extremely inverse (IEC_EI) 80.00 2.00 0.00
IEC long inverse (IEC_LI) 120.00 1.00 0.00
ANSI inverse (ANSI_I) 8.9341 2.0938 0.17966
ANSI short inverse (ANSI_SI) 0.2663 1.2969 0.03393
ANSI long inverse (ANSI_LI) 5.6143 1 2.18592
ANSI moderately inverse (ANSI_MI) 0.0103 0.02 0.0228
ANSI very inverse (ANSI_VI) 3.922 2 0.0982
ANSI extremely inverse (ANSI_EI) 5.64 2 0.02434
ANSI definite inverse (ANSI_DI) 0.4797 1.5625 0.21359
KEPCO normal inverse (KNI) 0.11 0.02 0.42
KEPCO very inverse (KVI) 39.85 1.95 1.08
T : Trip time in second
K,C,L : Constants
G : Current input
GS : Pickup current setting
TM : Time multiplier
Trip time for G/Gs ≥20 are identical to those for G/Gs = 20.
15/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE 50_PKP_A
50_PKP_OR
50_PKP_B
IA > PICKUP
50_PKP_C
IB > PICKUP
50_OP_B
BLOCK
= Operand
50_OP_C
Operand
FUNCTION =
ENABLE
51_PKP_A
51_PKP_OR
IA > PICKUP
51_PKP_B
51_PKP_C
IB > PICKUP
IC > PICKUP
MULTIPLIE 51_OP_A
51_OP_OR
R
CURVE 51_OP_B
51_OP_C
BLOCK
= Operand
Operand
16/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE 50N_PKP
IN > PICKUP
BLOCK
= Operand
Operand 50N_OP
DELAY
FUNCTION =
ENABLE
51N_PKP
IN > PICKUP
CURVE
BLOCK
= Operand
MULTIPLIE 51N_OP
R
Operand
17/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
[Trip TC Curve]
t Trip time
τ Temperature rise time constant
I Load current
I P Pre-load current
k Setting factor
IN Nominal current
18/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE THERMAL >
Time 49_ALARM
ALARM
Constant
Imax >
K-factor * In
BLOCK
= Operand THERMAL >
49_OP
100%
Operand
19/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE 37_PKP_A
37_PKP_OR
37_PKP_B
IA < PICKUP
37_PKP_C
IB < PICKUP
37_OP_B
BLOCK
= Operand
37_OP_C
Operand
20/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE 46_PKP
I2 > PICKUP
BLOCK
= Operand
Operand 46_OP
DELAY
21/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
- Auto reclosing becomes READY status after Prepare Time delay in case
Prepare Condition is satisfied. For example, when the Prepare Condition
is “CB Closed”, then the reclosing process is into READY status after
Prepare Time set, in case CB is closed.
- After reclosing starts and the first delay is passed, CB is closed. Now,
Discriminating Time and Reclaim Time starts to count, and it checks if CB
is really closed during Discriminating Time. If not, 79_Fail (Reclosing Fail)
is alarmed and no more reclosing is processed.
- If Start Condition remains after the final reclsong, CB is locked out to open
and 79_Fail is alarmed.
22/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Prepare Time
Prepare Condition
Start Condition
Delay 1 Delay 2
CB Close (DI)
Discriminating Time
Reclaim Time
Ready LED
In Progressing LED
23/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Prepare Time
Prepare Condition
Start Condition
Delay 1 Delay 2
CB Close (DI)
Discriminating Time
Reclaim Time
Ready LED
In Progressing LED
24/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Prepare Time
are Condition
Condition
Delay 1 Delay 2
lose (DI)
minating Time
im Time
y LED
ogressing LED
25/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE
50BF_OP
DELAY
TRIP RELAY
= Operated
IA > PICKUP
IB > PICKUP
IC > PICKUP
BLOCK
= Operand
Operand
26/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE COLDLD_PKP
IA < PICKUP
OP COLDLD_OP
DELAY
IB < PICKUP
RESET Reset
IC < PICKUP
DELAY
BLOCK
= Operand
Operand
27/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
FUNCTION =
ENABLE I2/I1_OP
DELAY
BLOCK
= Operand
Operand
28/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
CB OPEN / CLOSE
This function performs trip (open)/close control actions of CB. CB Open or Close button on
the front panel is activated only on the Local mode (“L” LED on). On the Remote mode, only
control command from SCADA through communication is accepted.
Before control command via front panel, SELECT button and Password enter are required
first. SELECT button is the concept to prevent the mal-operation on the front panel and this
concept is the same with SBO (Select Before Operate) concept in communication protocol, i.e.
DNP3.0, where SCADA (master system) selects first the equipment to control remotely before
setting out actual control command to keep other masters from selecting the same equipment so
that control right is granted to that SCADA only. This dedicated concept is adopted equally to
Local control and this is also used for mal-operation prevention of direct open/close command.
After the correct password enter and SELECT button again, then a phrase that CB is selected is
displayed on LCD and SELECT LED is blinking. After while, CB OPEN/CLOSE buttons are
activated for 15 seconds.
29/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Input#1
Input#2
Input#3
Input#4 Reset Type
Input#5
Input#6 = Self Contact Out
Input#7
Input#8 #1 ~ #4
Input#1
Input#2
Input#3
Input#4 0.00 ~ 60.00
Input#5
Input#6
Input#7
Input#8
LED#1~#4
Input#1
Input#2
Reset Type
Input#3
Input#4 = Manual
Input#5
Input#6
Input#7
Input#8
Input#1
S Q
Input#2
Input#3
Input#4
Input#5 R
Input#6
Input#7
Input#8
Logic Annunciator
30/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
31/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
32/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
V+
Trip Contact
52a 52b
i
52
Trip Coil
V-
Example)
V DC : 24V (from System)
V MIN : 16V (from PAC-E100S)
I MIN : 0.0025A (from PAC-E100S)
R TC : 300Ω (from System)
V TC_MAX : 10V (from System)
33/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
24V − 16V
RMAX = − 300Ω = 2.9 KΩ
2.5mA
24V − 10V
RMIN = × 300Ω = 420Ω
10V
2.9 KΩ − 420Ω
R= = 1.24 KΩ
2
The closest standard value of 1.3kΩ is selected; the power is:
2
24V
PR = × 1.3KΩ
1.3KΩ + 0.3KΩ
PR ≥ 0.2925
3.2.7. Communication
1 RS232 Port (19200 BPS, ModBus Protocol)
Front
For maintenance and Setting software (Engineering Tool)
1 RS232 Port (19200 BPS, ModBus Protocol)
For maintenance and Setting software (Engineering Tool)
Rear 1 RS485 Port (300 ~ 38400 BPS, DNP3.0/Modbus/
IEC870-5-103 Protocol)
For SCADA communication
34/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
System Configuration & Set Value Upload to PC and Batch Download to PAC-E100S
Event data Upload to PC and Listing
Fault Waveforms data Upload to PC and Analysis
Set Value & Recorded Data Saving
The manipulation of setting software is explained in more detail on chapter 6 and the
following figure shows protection page of setting program.
35/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4 Operational Description
Screw
Display LCD
Indicators LED
2 Line LCD for indicating
-Run LED metering and setting value
-System Error LED
-Protection Element Pickup LED
-Protection Element Trip LED
4 Configurable LED
Up/Down/Left/Right
Key
Reset Key
CB Control LED
-Local/Remote LED
-Control Select LED Menu Key
-CB Open LED
-CB Close LED Confirm and Change of set value
Enter Key
CB Control Key
-Confirm set value and Password
-Local/Remote Key
-Control Select Key
-CB Open Key
-CB Close Key
RS232 Port for
Local Maintenance
Screw
36/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.1.2. LEDs
4.1.3. Keypad
UP
Menu Move, Value Change
DOWN
ARROW
RIGHT Menu Move, Menu Item Selection
LEFT
Menu Move, Escape to Upper Menu / Cancel Item
RESET Manual Reset of System Error and Trip LED
MENU Enter into Menu Tree Display
ENT Setting Value Enter and Confirm
L/R Local / Remote Control Mode Change
CONTROL SELECT CB Control Selection
(Password) OPEN CB Trip Control
CLOSE CB Close Control
37/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
38/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
39/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
MAIN
DISPLAY STATUS CONTACT INPUT CONT IN#1 ~ 4
Display
CONTACT OUTPUT CONT OUT#1 ~ 4
SELF DIAGNOSIS MEMORY, SETTING, AD CONVERTER,
CALIBRATION, TRIP CIRCUIT
PROTECTION IOC1(50_1), IOC2(50_2), TOC(51),
IOCG1(50N_1), IOCG2(50N_2),
TOCG(51N),
THERMAL(49), UC(37), NSOC(46),
AREL(79), CBFAIL(50BF), COLD LD,
RECORD EVENT INRUSH
WAVEFORM
MEASURE CURR(IA), CURR(IB), CURR(IC), CURR(IN),
SEQ(I0), SEQ(I1), SEQ(I2), THERMAL,
FREQUENCY, TRIP COUNT
SYSTEM INFO. Version Display
40/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
I A : 1 4 0 . 6 7 A
I B : 1 3 9 . 1 2 A
I A : 1 4 0 . 6 7 A ▶D I S P L A Y
MENU
I B : 1 3 9 . 1 2 A
▶S E T T I N G
MENU
▶ C O MM A N D
MENU
41/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶D I S P L A Y ▶D I S P L A Y
ENT
▶S T A T U S
▶D I S P L A Y
▶M E A S U R E
▶D I S P L A Y
▶R E C O R D
▶D I S P L A Y
▶S Y S T EM I NFO .
4.4.1.1. DISPLAY/STATUS
DISPLAY menu is composed of CONTACT INPUT, CONTACT OUTPUT, SELF
DIAGNOSIS, and PROTECTION sub menu.
Each of sub menus shows contact input, contact output, self-diagnosis and operating status
of protection elements.
▶D I S P L A Y ▶S T A T U S
▶S T A T U S ▶C O N T A C T I NPUT
▶S T A T U S
▶C O N T A C T OUT P UT
▶S T A T U S
▶S E L F D I AGNO S I S
▶S T A T U S
▶P R O T E C T I O N
42/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S T A T U S CONT I N# 1 1 / 4
▶C O N T A C T I NPUT : OF F
CONT I N# 2 2 / 4
: OF F
CONT I N# 3 3 / 4
: OF F
CONT I N# 4 4 / 4
: OF F
▶S T A T U S CONT OUT # 1 1 / 4
▶C O N T A C T OUT P UT : DE ENERG I Z ED
CONT OUT # 2 2 / 4
: DE ENERG I Z ED
CONT OUT # 3 3 / 4
: DE ENERG I Z ED
CONT OUT # 4 4 / 4
: DE ENERG I Z ED
43/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S T A T U S ME MO R Y 1 / 5
▶S E L F D I AGNO S I S : OK
S ETT I NG 2 / 5
: OK
AD CONVERT E R 3 / 5
: OK
CAL I BRAT I ON 4 / 5
: OK
TR I P C I RCU I T 5 / 5
: OK
4.4.1.5. DISPLAY/STATUS/PROTECTION
This menu displays picked-up started and operated status of 13 protection elements. Phase
elements show started and operated phases A, B, and C, and ground elements show “PK” and
“OP” symbols, when the fault current is picked up and the relaying element is signaled to
operate.
▶S T A T U S I OC 1 ( 5 0 _ 1 ) 1 / 1 3
▶P R O T E C T I O N PKP : ABC , OP : ABC
I OC 2 ( 5 0 _ 2 ) 2 / 1 3
PKP : ABC , OP : ABC
TOC ( 5 1 ) 3 / 1 3
PKP : ABC , OP : ABC
I OCG 1 ( 5 0 N _ 1 ) 4 / 1 3
PKP : PKP , OP : OP
I OCG 2 ( 5 0 N _ 2 ) 5 / 1 3
PKP : PKP , OP : OP
44/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
TOCG ( 5 1 N ) 6 / 1 3
PKP : PKP , OP : OP
T H E RMA L ( 4 9 ) 7 / 1 3
PKP : PKP , OP : OP
UC ( 3 7 ) 8 / 1 3
PKP : ABC , OP : ABC
N SOC ( 4 6 ) 9 / 1 3
PKP : PKP , OP : OP
ARE L ( 7 9 ) 1 0 / 1 3
R : R , P ROG : P , F : F
C BF ( 5 0 B F ) 1 1 / 1 3
OP : OP
COL D LD 1 2 / 1 3
PKP : PKP , OP : OP
I NRUSH 1 3 / 1 3
OP : OP
4.4.1.6. DISPLAY/MEASURE
This menu displays measurement and metering data of electric values. PAC-E100S has 4
current inputs, and measures phase & earth currents, each sequence values, thermal, frequency,
and trip counter. (Frequency is show according to input value of A-phase current.)
▶D I S P L A Y I A ( R M S , T H D) 1 / 3 8
▶M E A S U R E : 0 . 0 0 A , 1 0 . 0 %
I N ( R M S , T H D) 4 / 3 8
: 0 . 0 0 A , 1 0 . 0 %
CURR ( I A ) 5 / 3 8
: 0 . 0 0 A , < 0 . 0
45/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
…
CURR ( I N ) 8 / 3 8
: 0 . 0 0 A , < 0 . 0
S EQ ( I 0 ) 9 / 3 8
: 0 . 0 0 A , < 0 . 0
S EQ ( I 1 ) 1 0 / 3 8
: 0 . 0 0 A , < 0 . 0
S EQ ( I 2 ) 1 1 / 3 8
: 0 . 0 0 A , < 0 . 0
I A_ H - 1 , 2 12 / 3 8
: 0 . 0 0 A ,
I A_ H -3 , 4 1 3 / 3 8
: 0 . 0 0 A ,
…
I N_ H - 1 1 , 1 2 3 5 / 3 8
: 0 . 0 0 A ,
T H E RMA L 3 6 / 3 8
: 0 . 0 %
FREQUENCY 3 7 / 3 8
: 0 . 0 0H z
TR I P COUNT 3 8 / 3 8
: 6 5 5 3 5
▶D I S P L A Y PAC - E 1 0 0 C
▶S Y S T EM I NFO . V e r : V1 . 0 0
46/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S E T T I N G ▶S E T T I N G
ENT
▶S Y S T EM
▶S E T T I N G
▶P R O T E C T I O N
47/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.1. SETTING/SYSTEM
SYSTEM menu is composed of POWER SYSTEM, WAVEFORM, RTC, CB CONTROL,
COM, DNP3.0, CONTACT INPUT, CONTACT OUTPUT, LED, and PASSWORD. POWER
SYSTEM is used for setting of frequency, frequency tracking, phase CT ratio and ground CT.
WAVEFORM is used for setting of waveform type/trigger source/trigger position, RTC is used
for setting time, and CB CONTROL is used for time setting TRIP and CLOSE PULSE. COM is
used for communication setting. DNP3.0 is used for setting of DNP when communication
method is DNP3.0(DNP 3.0 has no existence when protocol is IEC870-5-103 or Modbus).
CONTACT INPUT / OUTPUT and LED are used for setting contact input/output and
Programmable LED respectively. PASSWORD is used when change password.
▶S E T T I N G ▶S Y S T EM
▶S Y S T EM ▶P OWE R S Y S T EM
▶S Y S T EM
▶W A V E F O R M
▶S Y S T EM
▶R T C
▶S Y S T EM
▶C B CONTROL
▶S Y S T EM
▶C O M
▶S Y S T EM
▶D N P 3 . 0
▶S Y S T EM
▶C O N T A C T I NPUT
▶S Y S T EM
▶C O N T A C T OUT P UT
▶S Y S T EM
▶L E D
▶S Y S T EM
▶ P A S S WO R D
48/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S E T T I N G FREQUENCY 1 / 4
▶P OWE R S Y S T EM : 6 0 H z
PHS CT RAT I O 2 / 4
: 5 : 5
GND CT RAT I O 3 / 4
: 5 : 5
TR I P RELAY 4 / 4
: CONT OUT # 1
Setting
Basic
Item Range Description
step
value
FREQUENCY 50Hz / 60Hz 60Hz Frequency setting
PHS CT RATIO 1 ~ 6000: 5 1 5 Phase CT ratio setting
GND CT RATIO 1 ~ 6000: 5 1 5 Ground CT ratio setting
CONT
TRIP RELAY CONT OUT#1~#4 TRIP RELAY setting
OUT#1
<Table 4.4.2.2.1 POWER SYSTEM Setting Item>
4.4.2.3. SETTING/SYSTEM/WAVEFORM
WAVEFORM is used for setting of waveform type, trigger source, trigger position.
▶S E T T I N G TYPE 1 / 3
▶W A V E F O R M : 1 0 * 1 2 CYCLE S
TR I G . S RC 2 / 3
: L _OF F
TR I G . POS 3 / 3
: 9 9 %
Setting Basic
Item Range Description
Step Value
TYPE 10*12 / 20*6 cycles 10*12 Waveform type setting
Refer to the Waveform trigger source
TRIG.SRC L_OFF
table 3.2.3.3. setting
TRIG.POS 0 ~ 99% 1 50% Trigger position setting
<Table 4.4.2.3. WAVEFORM Setting Item>
49/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.4. SETTING/SYSTEM/RTC
RTC is used for setting the current time.
▶S E T T I N G Y Y Y Y / MM / D D ,
▶R T C h h : mm : s s
Setting Basic
Item Range Description
Step Value
YY 00 ~ 99 1 00 Year setting
MM 01 ~ 12 1 01 Month setting
DD 01 ~ 31 1 01 Day setting
HH 00 ~ 23 1 00 Hour setting
MM 00 ~ 59 1 00 Minute setting
SS 00 ~ 59 1 00 Second setting
mmm 00 ~ 999 1 00 Millisecond setting
50/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S E T T I N G TR I P PUL SE 1 / 2
▶C B CONTROL : 5 . 0 s
CLOS E PUL SE 2 / 2
: 5 . 0 s
Setting Basic
Item Range Description
unit value
TRIP PULSE 0.1 ~ 5.0s 0.1s 5.0s Time setting of CB Trip
CLOSE PULSE 0.1 ~ 5.0s 0.1s 5.0s Time setting of CB Close
4.4.2.6. SETTING/SYSTEM/COM
COM menu is composed of FUNCTION, SLAVE ADDR, BPS, and PROTOCOL and each
menu set up communication function, slave address, BPS and protocol.
▶S E T T I N G FUNCT I ON 1 / 4
▶C O M : D I SABLE
S LAVE ADDR 2 / 4
: 1
BP S 3 / 4
: 3 0 0
P ROTOCOL 4 / 4
: MO D B U S
Setting Basic
Item Range Description
step value
FUNCTION ENABLE/DISABLE DISABLE Setting of use or not
SLAVE ADDR 1 ~ 65534 1 1 Slave address setting
Setting of
BPS 300 ~ 38400 9600
communication speed
MODBUS/IEC870 Protocol setting
PROTOCOL MODBUS
(DNP3.0/MODBUS) (Ordering option)
51/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.7. SETTING/SYSTEM/DNP3.0
DNP3.0 menu is composed of TX DELAY, LINK CONFIRM, LINK RETRY, LINK
TIMEOUT, SBO TIMEOUT, WR TIME INT and COLD RESTART, and each menu set up Tx
delay, Link confirm, Link retry, Link timeout, SBO timeout, Write time interval and Cold restart.
▶S E T T I N G TX DELAY 1 / 7
▶D N P 3 . 0 : 0 m s e c
L I NK C O N F I RM 2 / 7
: NEVER
L I NK RETRY 3 / 7
: 1
L I NK T I ME OU T 4 / 7
: 1 m s e c
S BO T I ME OU T 5 / 7
: 1 m s e c
WR T I ME I NT 6 / 7
: 0 m i n
COL D RE S TART 7 / 7
: D I SABLE
Setting
Item Range Basic value Description
step
TX DELAY 0 ~ 65000msec 1msec 0msec Tx delay setting
NEVER/ALWAYS
LINK CONFIRM NEVER Link confirm setting
/SOMETIMES
LINK RETRY 0~5 1msec 0 Link retry setting
LINK TIMEOUT 1 ~ 65000msec 1msec 1msec Link timeout setting
SBO TIMEOUT 1 ~ 65000msec 1msec 1msec SBO timeout setting
WR TIME INT 0 ~ 65000min 1min 0min Write time interval setting
COLD RESTART ENABLE/DISABLE DISABLE Cold restart setting
52/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S E T T I N G CONT I N# 1 1 / 4
▶C O N T A C T I NPUT : NOT _ CONNE CT ED
CONT I N# 2 2 / 4
: NOT _ CONNE CT ED
CONT I N# 3 3 / 4
: NOT _ CONNE CT ED
CONT I N# 4 4 / 4
: NOT _ CONNE CT ED
Setting
Item Range Basic value Description
step
NOT_CONNECTED/
CB_OPENED/
CB_CLOSED/ Setting of contact
CONT IN #1~#4 1 NOT_CONNECTED
ANNUN_RESET/ input
TCS INPUT/
GENERAL_INPUT
Contact Input
Description
elements
NOT_CONNECTED No effect
CB_OPENED Open CB, when input is logic “1”.
CB_CLOSED Close CB, when input is logic “1”
ANNUN_RESET Operate Annunciator Reset, if there is status change of Input Logic.
Used trip circuit supervision input. When input is logic “0” over 5 min
TCS_INPUT
and TRIP CIRCUIT of protection element is “Fail”.
GENERAL_INPUT Used general Contact Input
53/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶S E T T I N G ▶C O N T A C T OUT P UT
▶C O N T A C T OUT P UT ▶C O N T OUT # 1
▶C O N T A C T OUT P UT
▶C O N T OUT # 2
▶C O N T A C T OUT P UT
▶C O N T OUT # 3
▶C O N T A C T OUT P UT
▶C O N T OUT # 4
I NPUT # 1 2 / 1 1
: L _OF F
I NPUT # 2 3 / 1 1
: L _OF F
I NPUT # 3 4 / 1 1
: L _OF F
I NPUT # 4 5 / 1 1
: L _OF F
I NPUT # 5 6 / 1 1
: L _OF F
I NPUT # 6 7 / 1 1
: L _OF F
54/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
I NPUT # 7 8 / 1 1
: L _OF F
I NPUT # 8 9 / 1 1
: L _OF F
RE S ET TYPE 1 0 / 1 1
: SELF
RE S ET DELAY 1 1 / 1 1
: 6 0 . 0 0 s
Setting Basic
Item Range Description
Step value
OR8/HALF-OR8/
LOGIC OR8 Operator setting
AND8/HALF-AND8
Refer to
INPUT #1~#8 Input setting of Operator
Table 3.2.3.3.
Form of Contact Output
RESET TYPE SELF/MANUAL
setting
Off delay setting (Activated
RESET DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec when RESET TYPE is
“SELF”)
4.4.2.10. SETTING/SYSTEM/LED
PAC-E100S provides 4 Programmable LED for the convenience of user. The setting
method is same with CONTACT OUTPUT.
▶S E T T I N G ▶L E D
▶L E D ▶L E D # 1
▶L E D
▶L E D # 2
▶L E D
▶L E D # 3
▶L E D
▶L E D # 4
55/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
- LED (LED#1 ~ 4)
▶L E D LOG I C 1 / 1 1
▶L E D # 1 : OR 8
I NPUT # 1 2 / 1 1
: L _OF F
I NPUT # 2 3 / 1 1
: L _OF F
I NPUT # 3 4 / 1 1
: L _OF F
I NPUT # 4 5 / 1 1
: L _OF F
I NPUT # 5 6 / 1 1
: L _OF F
I NPUT # 6 7 / 1 1
: L _OF F
I NPUT # 7 8 / 1 1
: L _OF F
I NPUT # 8 9 / 1 1
: L _OF F
RE S ET TYPE 1 0 / 1 1
: SELF
RE S ET DELAY 1 1 / 1 1
: 6 0 . 0 0 s
Setting Basic
Item Range Description
step value
OR8/HALF-OR8/
LOGIC OR8 Operator setting
AND8/HALF-AND8
Refer to the table
INPUT #1~#8 Input setting of Operator
3.2.3.3.
RESET TYPE SELF/MANUAL Form of Contact Output setting
Off delay setting (Activated
RESET DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec when RESET TYPE is
“SELF”)
<Table 4.4.2.10.1. LED Setting Item>
56/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.11. SETTING/SYSTEM/PASSWORD
There are 2 types of passwords for PAC-E100S: Settings modification password and
Control action password. Both passwords are same and 4-digit decimal 0~9 numbers and have
the initial values of “0000” on delivery of PAC-E100S.
▶S Y S T EM N EW P A S S WO R D
▶ P A S S WO R D : * * * *
57/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.12. SETTING/PROTECTION
PROTECTION menu is composed of protection elements, IOC1 (50_1), IOC2 (50_2),
TOC (51), IOCG1 (50N_1), IOCG2 (50N_2), TOCG (51N), THERMAL (49), UC(37),
NSOC(46), AREL(79), CBF(50BF), COLD LD, and INRUS, and is used for setting each of
protection elements.
▶S E T T I N G ▶P R O T E C T I O N
▶P R O T E C T I O N ▶I OC 1 ( 5 0 _ 1 )
▶P R O T E C T I O N
▶I OC 2 ( 5 0 _ 2 )
▶P R O T E C T I O N
▶T O C ( 5 1 )
▶P R O T E C T I O N
▶I OCG 1 ( 5 0 N _ 1 )
▶P R O T E C T I O N
▶I OCG 2 ( 5 0 N _ 2 )
▶P R O T E C T I O N
▶T O C G ( 5 1 N )
▶P R O T E C T I O N
▶T H E RM A L ( 4 9 )
▶P R O T E C T I O N
▶U C ( 3 7 )
▶P R O T E C T I O N
▶N S O C ( 4 6 )
▶P R O T E C T I O N
▶A R E L ( 7 9 )
▶P R O T E C T I O N
▶C B F ( 5 0 B F )
58/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N
▶C O L D LD
▶P R O T E C T I O N
▶I NRU SH
▶P R O T E C T I O N FUNCT I ON 1 / 4
▶I OC 1 ( 5 0 _ 1 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
B LOCK 4 / 4
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation delay time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
59/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 4
▶I OC 2 ( 5 0 _ 2 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
B LOCK 4 / 4
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation delay time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
60/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 5
▶T O C ( 5 1 ) : D I SABLE
CURVE 2 / 5
: I EC_ N I
P I CKU P 3 / 5
: 2 0 . 0 0 A
MU L T I P L I E R 4 / 5
: 1 0 . 0 0
B LOCK 5 / 5
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
IEC_NI/IEC_VI/
IEC_EI/IEC_LI/
ANSI_I/ANSI_SI/
CURVE IEC_NI TC Curve setting
ANSI_LI/ANSI_MI/
ANSI_VI/ANSI_EI/
ANSI_DI/KNI/KVI
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
MULTIPLIER 0.01 ~ 10.00 0.01 10.00 Multiplier setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
61/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 4
▶I OCG 1 ( 5 0 N _ 1 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
B LOCK 4 / 4
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation Delay Time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
62/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 4
▶I OCG 2 ( 5 0 N _ 2 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 6 0 . 0 0 s
B LOCK 4 / 4
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 60.00sec 0.01sec 0.00sec Operation Delay Time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
63/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 5
▶T O C G ( 5 1 N ) : D I SABLE
CURVE 2 / 5
: I EC_ N I
P I CKU P 3 / 5
: 2 0 . 0 0 A
MU L T I P L I E R 4 / 5
: 1 0 . 0 0
LOCK 5 / 5
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
IEC_NI/IEC_VI/
IEC_EI/IEC_LI/
ANSI_I/ANSI_SI/
CURVE IEC_NI TC Curve setting
ANSI_LI/ANSI_MI/
ANSI_VI/ANSI_EI/
ANSI_DI/KNI/KVI
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
MULTIPLIER 0.01 ~ 10.00 0.01 10.00 Multiplier setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
64/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 5
▶T H E R M A L ( 4 9 ) : D I SABLE
K - F ACTOR 2 / 5
: 4 . 0 0
T I ME CON S T 3 / 5
: 9 9 9 . 9 m i n
A L A RM 4 / 5
: 1 0 0 %
B LOCK 5 / 5
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
K-FACTOR 0.10 ~ 4.00 0.01 4.00 Trip Pickup setting
TIME
CONST
1 ~ 999.9min 0.1min 999.9min Multiplier setting
ALARM 50 ~ 100% 1% 100% Alarm Pickup setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
65/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 4
▶U C ( 3 7 ) : D I SABLE
P I CKU P 2 / 4
: 1 . 0 0 A
DELAY 3 / 4
: 1 8 0 . 0 0 s
B LOCK 4 / 4
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.02 ~ 1.00*In 0.01*In 1.00*In Pickup setting
DELAY 0.00 ~ 180.00sec 0.01sec 180.00sec Operation Delay Time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
66/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 4
▶N S O C ( 4 6 ) : D I SABLE
P I CKU P 2 / 4
: 2 0 . 0 0 A
DELAY 3 / 4
: 1 8 0 . 0 0 s
B LOCK 4 / 4
: L _ OFF
Setting
Item Range Basic value Description
step
FUNCTION ENABLE/DISABLE DISABLE Protection Elements setting
PICKUP 0.10 ~ 20.00*In 0.01*In 20.00*In Pickup setting
DELAY 0.00 ~ 180.00sec 0.01sec 180.00sec Operation Delay Time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
67/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 1 2
▶A R E L ( 7 9 ) : D I SABLE
S HOT N UM 2 / 1 2
: 4
PRE CON 3 / 1 2
: L _OF F
S TART CON 4 / 1 2
: L _OF F
PRE T I ME 5 / 1 2
: 2 0 0 . 0 0 s
D I SC T I ME 6 / 1 2
: 5 . 0 0 s
RECL T I ME 7 / 1 2
: 3 5 0 . 0 0 s
1 ST D ELAY 8 / 1 2
: 3 0 0 . 0 0 s
2 ND DELAY 9 / 1 2
: 3 0 0 . 0 0 s
3RD DELAY 1 0 / 1 2
: 3 0 0 . 0 0 s
4 TH DELAY 1 1 / 1 2
: 3 0 0 . 0 0 s
B LOCK 1 2 / 1 2
: L _ OFF
68/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Setting
Item Range Basic Value Description
Step
FUNCTION ENABLE/DISABLE DISABLE Protection elements setting
SHOT NUM 1~4 1 4 Shot number setting
PRE CON Reference table 3.2.3 Prepare condition setting
START CON Reference table 3.2.3 Cycle start condition setting
PRE TIME 0.05~200.00s 0.01s 200.00s Prepare time setting
DISC TIME 0.01~5.00s 0.01s 5.00s Discriminating time setting
RECL TIME 0.01~350.00s 0.01s 350.00s Reclaim time setting
1ST DELAY 0.01~300.00s 0.01s 300.00s 1s t delay time setting
2ND DELAY 0.01~300.00s 0.01s 300.00s 2n d delay time setting
3RD DELAY 0.01~300.00s 0.01s 300.00s 3r d delay time setting
4TH DELAY 0.01~300.00s 0.01s 300.00s 4t h delay time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
<Table 4.4.2.22. AREL(79) Setting Item>
69/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶P R O T E C T I O N FUNCT I ON 1 / 5
▶C B F ( 5 0 B F ) : D I SABLE
TR I P RE LA Y 2 / 5
: T S 1
P I CKU P 3 / 5
: 5 . 0 0 A
DELAY 4 / 5
: 6 0 . 0 0 s
B LOCK 5 / 5
: L _ OFF
Setting
Item Range Basic Value Descirption
Step
FUNCTION ENABLE/DISABLE DISABLE Protection elements setting
Pickup current(CB closed)
PICKUP 0.10 ~ 1.00*In 0.01*In 1.00*In
setting
DELAY 0.00 ~ 60.00sec 0.01sec 60.00sec Operation delay time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
70/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.24. SETTING/PROTECTION/COLD LD
COLD LD is Cold load pickup. It is operated definite time-delayed and reset definite time
delayed.
▶P R O T E C T I O N FUNCT I ON 1 / 5
▶C O L D LD : D I SABLE
P I CKU P 2 / 5
: 2 . 5 0 A
OP DELAY 3 / 5
: 1 0 0 0 s
RE S ET DELAY 4 / 5
: 1 0 0 0 s
B LOCK 5 / 5
: L _ OFF
Setting
Basic
Item Range Description
Step
Value
FUNCTION ENABLE/DISABLE DISABLE Protection elements setting
PICKUP 0.10 ~ 0.50*In 0.01*In 0.50*In Pickup current setting
OP DELAY 0 ~ 1000sec 1sec 1000sec Operation delay time setting
RESET DELAY 0 ~ 1000sec 1sec 1000sec Reset delay time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
<Table 4.4.2.24. COLD LD Setting Item>
71/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
4.4.2.25. SETTING/PROTECTION/INRUSH
INRUSH is Inrush detection. It is operated definite time-delayed according as 2nd
harmonic and minimum current.
▶P R O T E C T I O N FUNCT I ON 1 / 5
▶I NRU SH : D I SABLE
I 2 / I 1 2 / 5
: 1 0 0 %
MI N I 1 3 / 5
: 2 . 5 0 A
DELAY 4 / 5
: 6 0 . 0 0 s
B LOCK 5 / 5
: L _ OFF
Setting
Item Range Basic Value Description
Step
FUNCTION ENABLE/DISABLE DISABLE Protection elements setting
I2/I1 10 ~ 100% 1% 100% 2nd harmonics setting(I2/I1)
MIN I1 0.10 ~ 0.50*In 0.01*In 0.50*InMinimum current setting
DELAY 0.00 ~ 60.00sec 0.01sec 60.00secOperation delay time setting
Ban protection function
Refer to the Banned protection function
BLOCK L_OFF
table 3.2.3.3. when setting data status is
Logic “1”.
<Table 4.4.2.25. INRUSH Setting Item>
72/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶C O M M A N D ▶C O M M A N D
ENT
▶C O N T OUT TE ST
▶C O M M A N D
▶E V E N T CLEAR
▶C O M M A N D
▶W A V E CLEAR
▶C O M M A N D
▶T R I P CNT ED I T
▶C O M M A N D
▶P A N E L TE ST
73/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶C O M M A N D CONT OUT # 1 1 / 4
▶C O N T OUT TE ST : DE ENERG I Z ED
CONT OUT # 2 2 / 4
: DE ENERG I Z ED
CONT OUT # 3 3 / 4
: DE ENERG I Z ED
CONT OUT # 4 4 / 4
: DE ENERG I Z ED
1) Right arrow key from CONT OUT TEST menu in Menu Tree
2) Select test item of 16 contact outputs using Up/Down key and Right key
3) Enter settings modification password if required
4) Execute Energized or DeEnergized test using Up/Down key
”Run/Test” LED blinking green or Error message
5) Left key to escape and Repeat steps 2~4 for other items
74/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▶C O M M A N D
▶E V E N T CLEAR
▶C O M M A N D
▶W A V E CLEAR
▶C O M M A N D
▶T R I P CNT ED I T
75/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
5. Application Example
5.1 Connection and Setting
PAC-E100S A
B
C
5
IA 1
6
IB 2
7
IC 3
8
IN 4
C B A
After SETTING/SYSTEM/POWER SYSTEM set to <Table 5.1>, and inject current to current
input terminals.
76/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
IA
I1
IB
IC
I2
I0
1
Zero phase sequence current, I 0 = ( I A + IB + IC ) :(300/5)*0.57 = 34.2[A], 150.0 o
3
1
Positive phase sequence current, I1 = ( I A + aIB + a 2 Ic) :(300/5)*2 = 120[A], 331.5 o
3
1
Negative phase sequence current, I 2 = ( I A + a 2 IB + aIc) :(300/5)*0.57= 34.2[A], 210.0 o
3
77/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
78/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
AC or DC
SURG PWR PW
-
E + R
28 26 27
Internally
Fused
PAC-E100
79/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
6.3.2. CT Connections
Refer to the Table 6.2.1 Terminal Block Diagram Table in the above
A B C
PAC-E100
5 IA+
1 IA-
6 IB+
2 IB-
7 IC+
3 IC-
A B C
PAC-
5 IA+
1 IA-
6 IB+
2 IB-
7 IC+
3 IC-
8 IN+
4 IN-
<Figure 6.3.2.2 2CT and GCT connection for sensitive ground fault detection>
80/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
A B C
PAC-E100S
5 IA+
1 IA-
6 IB+
2 IB-
7 IC+
3 IC-
8 IN+
4 IN-
+ PAC-E100S
19 TS1_NO
9 TS1_COM
T
C
(Wet)
– 14 DI1_P
24 DI1_N
DC 125V
81/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
PAC-E100C Notebook
PC
1: NA
2: TXD
3: RXD 1 Pin No. 2 & 3 1
4: NA
5: Signal
Ground
5 5
6: NA
7: NA
8: NA 9 Pin RS232
9: NA RS232 D-sub Connector
D-sub Connector
Female
PAC-E100S
SCADA Twisted
ZT (*) Pair 1
2:RS485_DATA+
+ 3:RS485_DATA-
SHIELD
5:RS485_COM
–
Chassis 5
Grounded
only Rear RS485
D-sub Connector
(*) ZT : 120 Ω
(Terminal Resistor)
82/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
83/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
▪Program Menu
Device Selecting
Open Saved Project File Loading
Save Edited Data Saving to File
Report Edited Data Saving to Text File and Printing
COM Communication Port Selection on PC. (Addr: 1 fixed)
Connect RS232 Port Communication Connection and Initialization
84/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
85/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
86/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
87/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
88/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
89/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
7.1.8. Monitor
Monitor display shows status monitoring of PAC-E100S. Elements or status monitoring is
composed of Measurement, Self Diagnosis, Protection Component, LED Output, Breaker and
Contact Input/ Output, and there is “Annun Reset” button on front panel’s left.
Refer to LCD setting menu on chapter 4 Operational Description for more detailed
explanation.
90/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
8. Evaluation Software(EvalTool)
The fault waveforms saved in PC can be analyzed by evaluation software, EvalTool.
EavlTool is customized COMTRADE file viewer for PAC-series relay. The functions
supported by EvalTool are COMTRADE file drawing, the amplitude/angle/THD measuring and
analyzing harmonic components of analog channels, and delta time measuring.
Speedy move
Slow move
Zoom in
Zoom out
91/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
If you click icon, you can find ‘Display Channel Select’ above. The checked channels are
all displayed at monitor.
92/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
8.3. Measuring
EvalTool have the fundamental frequency amplitude and angle measuring function at right-side
window. The reference angle is the first analog channel. And the measured samples are one
cycle before yellow vertical cursor. By moving the yellow cursor, the faulted value can be
displayed.
93/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
EvalTool has harmonic component analyzing function. The harmonic components of each
channel are measured by followed formula.
Ik = I k
* 100(%), I 1 ~ : 1st ~ n th harmonic _ rms
2 2 2 I n
I + I + ... + I
1 2 n
94/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
EvalTool has delta time measuring function. The T1 is yellow cursor time and T2 is green
cursor one ‘delta T’ equals the delta time between T1 and T2.
The yellow and green cursor can be viewed by clicking the left and right button of mouse.
95/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
+ C × TM (sec )
K
T = L
G
− 1
GS
T : Trip time in second
K,C,L,M : Constants
G : Current input
GS : Pickup current setting
TM : Time multiplier
Curve K L C
IEC Normal Inverse 0.14 0.02 0.00
IEC Very Inverse 13.50 1.00 0.00
IEC Extremely Inverse 80.00 2.00 0.00
IEC Long Inverse 120.00 1.00 0.00
ANSI Inverse 8.9341 2.0938 0.17966
ANSI Short Inverse 0.2663 1.2969 0.03393
ANSI Long Inverse 5.6143 1 2.18592
ANSI Moderately Inverse 0.0103 0.02 0.0228
ANSI Very Inverse 3.922 2 0.0982
ANSI Extremely Inverse 5.64 2 0.02434
ANSI Definite Inverse 0.4797 1.5625 0.21359
KEPCO Normal Inverse 0.11 0.02 0.42
KEPCO Very Inverse 39.85 1.95 1.08
Trip time for G/Gs ≥20 are identical to those for G/Gs = 20.
96/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
t : Trip time
τ : Temperature rise time constant
I : Load current
I P : Pre-load current
k : Setting factor
I N : Nominal current
Thermal State Calculation
2
I
Θ m +1 = ⋅ [1 − exp(−t / τ )] + Θ m ⋅ exp(−t / τ )
k ⋅ IN
θ being calculated every 100ms
I means True RMS
97/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
98/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
99/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
100/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
101/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
102/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
103/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
104/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
105/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
106/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
107/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
108/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
109/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
110/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
111/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
< Figure A.15 TC Curve for Thermal Overload Protection: In case of 40%>
112/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
P A C - E 1 0 0 - I P C
2 - Normal Current : 5A
113/114
Overcurrent Protection Relay (PAC-E100S) User’s Manual
Seoul Office
Address 5F, Kwangmyong B/D, #115-3, Bangi-dong, Songpa-gu,
Seoul, 138-050, Korea
Phone 82 2 22408106
Fax 82 2 22408188
Homepage http://www.pnctech.co.kr/
114/114