Produced on 09/18/2019 with Xpress Selection V8.6.4 - database DIL 13.8.

Project name Manulife


Project address -
Philippines
Reference -
Client name -
Client address -
Revision -

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ14AYM 1 Cooling only VRV A(18,20HP single module)
FXMQ140PAVE 1 VRV M-PA - Ceiling Mounted Duct
FXMQ200MVE9 1 VRV M - Ceiling Mounted Duct
KHRP26A72T 1 Refnet branch piping kit
BRC1E63 2 Wired Remote Controller (Navigation Remote
Controller)

2. Indoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
TC Total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
SC Sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
HC Heating capacity
Tdis H Indoor unit discharge air temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
2.2. ACCU-1 - RXQ14AYM
Capacity data at conditions and connection ratio (97%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tmp H Rq HC Max HC Tdis H Airflow
°C kW kW kW kW °C °C °C kW kW °C cfm
FCU-1 FXMQ140PAVE 27.0 / 17.7 n/a 15.6 n/a 14.0 Auto 12.1 n/a n/a n/a n/a 1624
FCU-2 FXMQ200MVE9 27.0 / 17.7 n/a 21.9 n/a 19.5 Auto 10.6 n/a n/a n/a n/a 2048

Required cooling capacity towards the outdoor unit: 37.4kW.

Simultaneous operation calculation


Name FCU Tmp C TC SC Tmp H HC
°C kW kW °C kW
FCU-1 FXMQ140PAVE 27.0 / 17.7 15.6 14.0 n/a
FCU-2 FXMQ200MVE9 27.0 / 17.7 21.9 19.2 n/a n/a
Σ 37.4 n/a

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
FCU-1 43-46 220V 1ph 3.4 1400×300×700 46
FCU-2 45.5-48.5 220V 1ph 9 1380×470×1100 137

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW
ACCU-1 RXQ14AYM 97 35.0 39.0 37.4

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
ACCU-1 RXQ14AYM 7.5 R410A 7.4 n/a

Name Model PS MCA WxHxD Wght


A mm kg
ACCU-1 RXQ14AYM 380V 3ph 26.9 1240×1657×765 215

3.2.1. ACCU-1 - RXQ14AYM


Model Qty Description Material cost Install. cost Subtotal
RXQ14AYM 1 Cooling only VRV A(18,20HP single module)
FXMQ140PAVE 1 VRV M-PA - Ceiling Mounted Duct
FXMQ200MVE9 1 VRV M - Ceiling Mounted Duct
KHRP26A72T 1 Refnet branch piping kit
BRC1E63 2 Wired Remote Controller (Navigation Remote Controller)
Total cost

Piping Limitations
Maximum total length 1000.0m
Maximum longest actual length 165.0m
Maximum longest equivalent length 190.0m
Maximum equivalent length (size up of main pipe required if longer) 89.9m
Maximum length first branch to indoor unit (size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor units 90.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.1m
Maximum height difference between indoor units 30.0m
Connection ratio range 50-130%

Pipe Capacities
Maximum Connection Index Diameters
149.9 ⅜"×⅝"
199.9 ⅜"×¾"
289.9 ⅜"×⅞"
419.9 ½"×1⅛"
> 419.9 ⅝"×1⅛"
Main pipe size up ⅝"×1⅛"

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

CCU
A
X Q1
R
-1
4 A

½ "× 1
YM

⅛"
KH
RP2
⅜ "×
A7 2
6 T
⅝"

F
CU
F
X MQ
- 1
1 4
0 P
AVE
4.1. Piping ACCU-1
⅜ "×
¾"

CU
F - 2

X MQ
F 2 0 M
VE9

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

AC CU-1
R Q1X 4AY M
INF 1,F2
L1, L2, 3,N 2 6.9A 3p h
FCU -1
P 1,P2
F XMQ 140 PAV EL
F1, 2F
BRC 1E6 3

,N 3 .4A 1ph
5.1. Wiring ACCU-1
P 1,P2
FCU -2 1E6 3
F XMQ 20 MV E9
F1, 2F L ,N 9 A1p hBRC

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
6. Device Options

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7