TECHNICAL SPECIFICATION FOR AUXILIARIES EQUIPMENT OF

GE-JENBACHER GAS GENSET 1 x JGS 420-B05


Cont.D no. OES/ENGG. - I/TSAE/420-400V-B05 Rev. Date & month: 1st January 2018 Rev. 00
Prepared by: Enginnering Dpt. -I _Design & Application
OPEN COOLING SYSTEM FOR J/W & A/C CIRCUITS SPECIFICATIONS

COOLING TOWER FOR J/W CIRCUIT


Cooling Capacity : 350 USRT
Flow Rate : 140 m3/hr
Fan motor HP : As per Manufacturer standard
Range : 8C
Approach : 3C
Wet Bulb : 30 C
Water Outlet Temperature : 33 C
Water Inlet Temperature : 41 C
Quantity : 01/ genset

PUMPS FOR J/W CIRCUIT


Type : Centrifugal
Flow Rate : 140 m3/hr
Head : 2 .5 bars approx. (it may vary w.r.t piping route)
Motor Power : As per manufacturer standard
Quantity : 2 Nos. (One for standby)

VENTILATION FAN SPECIFICATIONS


INDUCED DRAFT FAN
Flow : 45,000 CFM
Static Pressure : As per duct routing
Motor Hp : As per manufacturer standard
Fan RPM : As per manufacturer standard
Quantity : 01 No./genset (for more flexibility install 2 x 23,500 CFM fans)

EXHAUST FAN
Flow : 26,000 CFM
Static Pressure : As per duct rounting
Motor HP : As per manufacturer standard
Fan RPM : As per manufacturer standard
Quantity : 01 No./ per genset

LUBE OIL TANK


Lube oil tank should have a volume of 500 liters
LUBE OIL PUMPS SPECIFICATIONS
Type Gear type
Flow Rate 20-30 liters/minute
Motor Power As per manufacturer standard
Quantity 2 Nos./ Power house
One for fresh oil charging in Lube oil tank and the other for draining waste oil from the engine

WATER CHARGING PUMP SPECIFICATIONS


Type : Centrifugal type
Flow Rate : 3 m3/hr
Motor Power : As per manufacturer standard
Quantity : 1 Nos./ Power house

FRESH AIR FILTER SPECIFICATIONS


G3 Class, according to EN 779 and/or a filter degree of 85 % according to
Filtration Class :
ASHRAE is required.
Filter Area : 120 Sqft.
Fixed Type Fresh Air Louvers : 120 Sqft.
TECHNICAL SPECIFICATION FOR AUXILIARIES EQUIPMENT OF
GE-JENBACHER GAS GENSET 1 x JGS 420-B05
Cont.D no. OES/ENGG. - I/TSAE/420-400V-B05 Rev. Date & month: 1st January 2018 Rev. 00
Prepared by: Enginnering Dpt. -I _Design & Application
MOTOR CONTROL CENTER
As per GEJ recommendation and motor ratings requirement.
160 Amp breaker (Adjustable) has to be provided in the MCC for supply to GEJ control panel.
20 A MCB, 2pole breaker has to be provided in the MCC for supply to IS panel.

POWER CABLES (COPPER CONDUCTOR, TYPE XLPE OR PVC/PVC)


7 x1 Core x 300 mm2/phase + 4 x 1 Core x 300 mm2 for neutral conductor + 2 x 1 Core x 300 mm2 for neutral earthing .
CONSUMABLES FOR GENSET
S.No Description Specification Quantity Unit
1 Availability of Gas Continuious supply of gas, 370 m3/hr per engine
2 Battery electrolyte 1.28 Specific Gravity 40 liters
Continuous supply is required for cooling tower make up i.e 3
3 Water 250-300 TDS
m3/hr
4 Lube Oil As per sheet attached 437 (approx.) sump capacity liters

5 Coolant Corr Sheild NT 4201 30 (3-5% of volume of water) Kgs

GEJ POWER PANEL SPECIFICATIONS


3200 Amps, fixed type, Air circuit breaker, triple pole, motorized breaker, short circuit rating=xxx kA, standards:IEC-61439-2, IEC-
1
60204 and ISO-8528-4.
2 Over current and short circuit protection
3 24VDC shunt trip coil, 24VDC Under voltage coil and 24 VDC closing coil, 220 VAC motor charging
4 3 x 3200/5 Amps, current transformer for measurement; 1FS5 and 30VA
5 5 wire copper systems (TN-S) system
6 Cu work for L1, L2, L3, Neutral, PE and PEN Bridge.
7 Terminals with fuses to take generator voltage (from Cable side/ before circuit breaker)
8 Terminal with fuses to take bus bar voltages (from bus bar/ after circuit breaker)

AUXILIARY CONTACTS
1 1NO contact: Command generator circuit breaker ON (Closed=Circuit breaker closed)
2 1NC contact: Command generator circuit breaker OFF (Closed= Circuit breaker open)
3 1NO contact: Command under voltage coil generator circuit breaker (Closed=Energized)
4 1NO contact: Status: Generator Circuit Breaker closed (Closed= Circuit breaker closed)
5 1NO contact: Status: Generator Circuit Breaker open (Closed= Circuit breaker open)
6 1NO contact: Status: Generator overload/ short circuit (open=trip)

NOTES
1 Bus bar works should be done as per site requirements, GEJ standard follows:
Bus Bar Rated for xxxx Amps at 45 Degree Centrigrade
Main Cu bus bar for L1, L2, and L3
Neutral Bus bar
PE bus bar
PEN bridge

2 Standard Panel dimensions


Width: 800 mm
Height: 2000 mm + 200 mm (pedestal)
Depth: 800 mm

3 Coupling of bus bar will as per site requirements


4 Plexiglass for live parts
5 Terminals for control cables
6 Panel Color: RAL-7035
7 Short circuit rating of power panel will be as per system short circuit rating.
8 Other equipment that may be required will be as per customer system design. Above mentioned are manadatory for GEJ
9 Blinds for all piping circuits shall be removed in the presence of pre commissioining team of OES.