Appendix 17.

ENGINEERING REQUIREMENTS FOR CUSTOMER’S


22kV and 6.6 kV MAIN INCOMING SWITCHGEAR

O/C – Overcurrent relay type IDMTL with 3/10 characteristics.


Plug Setting =100%, Time Multiplier=0.1.
E/F – Earth fault relay type IDMTL with 3/10 characteristics.
Plug Setting =20%, Time Multiplier=0.1.
PW – PW main protection relay shall match with the SPPG’s end. The PW relays are typically
Solkor R / RF, HOR4, MHOR unit protection relay (For 22kV connection)
A – Ammeter
CB – Circuit breaker
To circuit breaker trip circuit

Notes (Important):
1. Where there is more than one incoming service, a bus-section breaker shall be provided and
be electrically and mechanically interlocked against parallel operation of the incoming
services.

Notes (Protection):
1. Pilot wire protection CTs shall comply with the following requirements:
a. Rated knee point voltage at maximum secondary turns not less than 80V.
b. Exciting current at the rated knee point voltage not more than 150mA.
c. Resistance of the secondary winding, corrected to 75oC not more than 0.15 ohm.
2. No other auxiliary device shall be connected to the pilot wire protection CTs. Pilot wire
protection CT star-point shall be towards protected line.
Appendix 17.2

ENGINEERING REQUIREMENTS FOR CUSTOMER’S


LV MAIN INCOMING SWITCHGEAR

O/C – Overcurrent relay type IDMTL with 3/10 characteristics or DTL relay. For DTL relay, the
setting shall be 100% of approved load with a time lag of not more than 0.5 sec. For
IDMTL relay, the plug setting shall be 100% of approved load with a time multiplier of 0.1
(or 0.2 for approved load more than 1.5kA and up to 2.2kA and with source from SPPA’s
22kV substation).
E/F – Earth fault relay operating at primary fault current of 20% of approved load subject to a
maximum of 120 Amp with time lag of not more than 0.5 sec.
CT – Current transformer Class 5P10, 15VA or better.
CB – Circuit breaker with adequate breaking capacity and circuit breaker using shunt trip shall
be provided with series trip (Direct acting trip) device that operates with no time delay
under short-circuit condition, or with HRC fuses in series.
To circuit breaker trip circuit.

Notes:
Where there is more than one incoming service, a 4-pole bus-section breaker shall be provided and
be mechanically interlocked against parallel operation of the incoming services.