Sei sulla pagina 1di 54

Ing.

Felipe Vera Condominio Altos de Oro Negro Agosto / 2014


Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

CONDOMINIO ALTOS DE ORO NEGRO


CÁLCULO ESTRUCTURAL
EDIFICIO EN CONCRETO REFORZADO
SALON COMUNAL
ORITO – PUTUMAYO

MEMORIA DE CÁLCULO
DISEÑO ESTRUCTURAL

Ing. Felipe Vera


Especialista Estructural

BOGOTA
Pag. 1 de 54

AGOSTO - 2014

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Tabla de Contenido
CARTA DE RESPONSABILIDAD ....................................................................................................................................... 4
DESCRIPCIÓN ........................................................................................................................................................................ 5
PASO 1 ..................................................................................................................................................................................... 5
PASO 2 ..................................................................................................................................................................................... 5
- CARGAS ................................................................................................................................................. 6
- Carga Muerta de Cubierta ........................................................................................................................ 6
- Carga Viva de cubierta ....................................................................................................................................... 6
- Carga debido a Viento ....................................................................................................................................... 6
PASO 3 .................................................................................................................................................................................. 11
- Materiales........................................................................................................................................................ 12
- Materiales (modelo estructural) ..................................................................................................................... 12
- Método de Análisis de Fuerzas Sísmicas ......................................................................................................... 12
- Coeficiente de Importancia ............................................................................................................................. 12
- Masa del edificio.............................................................................................................................................. 13
PASO 4 .................................................................................................................................................................................. 13
- Perfil de Suelo .................................................................................................................................................. 13
- Espectro elástico de diseño .....................................................................................................................15
- Periodo Fundamental ..............................................................................................................................16
PASO 5 .................................................................................................................................................................................. 17
- Coeficiente Ro................................................................................................................................................. 18
PASO 6 .................................................................................................................................................................................. 18
- Ajuste de sismo (R=1.0) A.5.4.5 ...............................................................................................................18
- Irregularidades ................................................................................................................................................ 19
- Irregularidad en planta .................................................................................................................................... 19
- Irregularidades en altura .........................................................................................................................20
PASO 7 .................................................................................................................................................................................. 20
- Cortante en la base .................................................................................................................................20
PASO 8 .................................................................................................................................................................................. 21
- Coeficiente de Disipación de Energía R ....................................................................................................21
PASOS 9 Y 10 ...................................................................................................................................................................... 21
- Revisión de Derivas .................................................................................................................................21
LISTADOS DEL COMPUTADOR..................................................................................................................................... 23
- Coordenadas de los nudos .............................................................................................................................. 23
- Incidencia de elementos frame ...............................................................................................................24
- Incidencia de elementos Shell .................................................................................................................25
- Asignación de Secciones a Frames. ..........................................................................................................26
- Asignación de Secciones a Shells. .................................................................................................................... 27
- Grados de libertad, en análisis estructural. ..................................................................................................... 27
PASO 11 ............................................................................................................................................................................... 28
- Combinaciones de carga .................................................................................................................................. 29
- Ajustando el sismo de diseño .......................................................................................................................... 31
- Fuerzas internas en los elementos...........................................................................................................31
Pag. 2 de 54

- Elementos tipo Frame ..................................................................................................................................... 31


- Elementos tipo Shell ........................................................................................................................................ 35
PASO 12 ............................................................................................................................................................................... 37
- Diseño de elementos (SAP2000/ACI 318-05 / IBC 2003) ................................................................................. 38
- Acero de Columnas .......................................................................................................................................... 38
- Acero en Vigas ................................................................................................................................................. 39

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

DEFLEXIONES .................................................................................................................................................................... 43
CORREAS DE CUBIERTA ................................................................................................................................................. 43
LOSA MACIZA DE CUBIERTA ........................................................................................................................................ 48
- REACCIONES ............................................................................................................................................48
- ZAPATAS..................................................................................................................................................50
- VIGAS DE CIMENTACION .........................................................................................................................52
CALCULO DE ELEMENTOS NO ESTRUCTURALES ................................................................................................... 52
TARJETA PROFESIONAL ................................................................................................................................................ 54

Pag. 3 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

CARTA DE RESPONSABILIDAD

Bogotá, Agosto 16 de 2014

A QUIEN CORRESPONDA

Yo ANDRÉS FELIPE VERA PÉREZ con Matrícula Profesional No. 19202084481 CERTIFICO que realice los
cálculos estructurales para la estructura de soporte de la edifciación de Salón Comunal, en concreto reforzado, del
Condominio oro Negro, este edificio será de atención a la comunidad, y se localizará en la ciudad de Orito –
Putumayo.

Estos cálculos fueron elaborados de acuerdo a las normas Colombianas de Diseño y Construcción Sismo
Resistente, NSR10.

Cordialmente.

Felipe Vera
MAT 192020-84481CAU
Ing. Calculista.
felipevera@hotmail.com

Pag. 4 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

DESCRIPCIÓN

Se emprende el cálculo y diseño de una estructura en concreto reforzado, soporte de una edificación con 2 niveles
de cubierta, el edificio tendrá un área aproximada de 270m².

Nuestra edificación se localiza en Orito - Putumayo, y de acuerdo al NSR10, por el cual se reglamenta la
zonificación sísmica de Colombia, se localiza en zona de amenaza sísmica alta, y de acuerdo a parámetros
geotécnicos, con un perfil de terreno tipo D.

Zona de amenaza sísmica alta, nuestra estructura se especifica como de capacidad especial de energía, en el
campo inelástico, DES.

A continuación se presentan las memorias de cálculo estructural del proyecto en mención, de acuerdo a
lineamientos y pasos enumerados en el título A.1.3.4 Diseño Estructural, tabla A.1.1-1 del NSR10, pag. A-3, así:

PASO 1

PASO 2

Metodología adoptada: factores de carga y resistencia (LRFD)

Pag. 5 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- CARGAS

- Carga Muerta de Cubierta

DLc = 53Kg/m²

- Carga Viva de cubierta

Pendiente menor al 20%;

LLc= 50 k/m²

- Carga debido a Viento

B.6 NSR10, Método 2, capítulo B.6. del NSR10, pag. B-21, método 2, Procedimiento Analítico, B.6.5.

Pag. 6 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Velocidad básica del viento.

Localización: Orito, V=28m/s

Pag. 7 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Factor de dirección del viento, Kd.

Kd = 0.90, sección transversal prismatica.

De acuerdo al título A.2.5.1.1. – Grupo III, Edificio de atención a la comunidad,

Pag. 8 de 54

I: 1.15

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Rugosidad del terreno B.

Categoría de exposición.

Coeficientes de Velocidad, Kz y Kh

Altura máxima de nuestra estructura, medida desde el terreno, Z=6m, aproximadamente, Luego
Kh = 0.7, y Kz, se calcula, de acuerdo a la anterior nota No. 2.
Pag. 9 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Luego Kz = 2.01(Z/Zg)2α = 2.01(7.6/365.8)(0.5) ; Kz = 0.29, pero debe cumplir, Kz > 1.0

Ante la ausencia de la configuración especificada en FIGURA B.6.5.1 (NSR10), se adopta, Kzt = 1.0

Nuestra estructura presenta un perodo fundamental menor que 1.0sg, por lo cual, de acuerdo a B.6.2, es
una estructura rígida.
(Características dinámicas calculadas con un análisis modal de aceleración bidireccional, teniendo en
cuenta el peso propio y la carga muerta).

Luego nuestra estructura se clasifica como estructura rígida o dinámicamente NO sensible, de acuerdo a
B.6.2. G =0.85, y por B.6.5.10,

Clasificación de cerramiento:

Nuestro edificio se clasifica como cerrado.

Pag. 10 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

GCpi : ±0.18

qz= 0.613(1.0)(1.0)(0.9)(28²)(1.15) = 497N/m², se adopta qz=55kg/m².

Teniendo en cuenta los coeficientes de fuerza y de presión, se establece, Pv = ±50kg/m²

PASO 3

Pag. 11 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Materiales

Sistema de Fundación; f’c : 21MPa


Columnas ; f’c: 21MPa
Vigas de cimentación: f’c: 21MPa
Concreto en placas: f’c:21MPa
Concreto en vigas aereas: f’c:21MPa
Acero de refuerzo; fy:420MPa
Acero Estructural; Gr50

- Materiales (modelo estructural)


General Properties
Material Type SymType TempDepend Color

3000Psi Concrete Isotropic No Red


A572Gr50 Steel Isotropic No Blue
A615Gr60 Rebar Uniaxial No White
A992Fy50 Steel Isotropic No Cyan

Basic Mechanical Properties


Material UnitWeight UnitMass E1 G12 U12 A1
Kgf/m3 Kgf-s2/m4 Kgf/m2 Kgf/m2 1/C
3000Psi 2.4028E+03 2.4501E+02 2135000000 889583333. 0.200000 9.9000E-06
A572Gr50 7.8490E+03 8.0038E+02 2.039E+10 7841930445 0.300000 1.1700E-05
A615Gr60 7.8490E+03 8.0038E+02 2.039E+10 1.1700E-05
A992Fy50 7.8490E+03 8.0038E+02 2.039E+10 7841930445 0.300000 1.1700E-05

Rebar Data
Material Fy Fu EffFy EffFu SSCurveOpt SSHysType SHard SCap
Kgf/m2 Kgf/m2 Kgf/m2 Kgf/m2
A615Gr60 42184177.57 63276266.35 46402595.33 69603892.99 Simple Kinematic 0.010000 0.090000

- Método de Análisis de Fuerzas Sísmicas

Método adoptado, de análisis de fuerzas sísmicas inerciales: Espectral Modal Lineal.

- Coeficiente de Importancia

Nuestro proyecto, tiene como coeficiente de importancia I=1.25, para una estructura de atención a la comunidad,
también el perfil de suelo, se clasifica como Tipo D, de acuedo a estudio de suelos, luego:
Pag. 12 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Masa del edificio

y teniendo en cuenta el peso de cubierta y entrepiso,

La masa de nuestra estructura es, W = 100 + 250x53


W = 113Tons

PASO 4

Pag. 13 de 54

- Perfil de Suelo

Perfil de suelo definido por el perfil estratigráfico del estudio de suelos, PERFIL D.

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Y de acuerdo al NSR10,

Fa : 1.2 ; Aa: 0.3


Fv: 1.8; Av: 0.25

Pag. 14 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Espectro elástico de diseño

De acuerdo a lo anterior, las coordenadas de nuestro espectro de diseño, de acuerdo al NSR10, serán:

Pag. 15 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Periodo Fundamental

T=0.48sg, menor que el periodo corto Tc, por lo cual, adoptamos como Sa = 1.125(g), luego nuestro cortante en
la base será, Vs= (1.125)(113) = Vs =125Tons

El anterior es el periodo fundamenta, dinámico, establecido por el NSR10.A.5.4.5.a, procedimiento


correspondiente al método de fuerzas inerciales adoptado para este estudio.

NSR10.A5.4.5. (a)

Pero en todo caso se debe corroborar que el periodo fundamental, dinámico, producto del análisis modal lineal,
no debe exceder CuTa, donde,

Pag. 16 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Ta = 0.047 (6.10.9) = 0.24 (s)

Cu = 1.75 – 1.2(0.25)(1.8) = 1.21; Cu Ta = 0.29 , Luego T < CuTa,

PASO 5

Pag. 17 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Coeficiente Ro

Ro : 2.0 (Estructura péndulo invertido)

PASO 6

Se define como procedimiento de análisis sísmico, el método dinámico elástico, modal lineal. Y se calculan los
siguientes desplazamientos con las fuezas sísmicas, iguales a un cortante basal igual a 113Tons, magnitud de
cortante en la base para sismo sin reducir, es decir con R=1.0, y al 100%, de la fuerza horizontal equivalente.

- Ajuste de sismo (R=1.0) A.5.4.5

Los desplazamientos y efectos sísmicos, para cálculo y revisión de irregularidades, se calculan con el
sismo sin reducir, con un Vs = 113Tons
Pag. 18 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Irregularidades
- Irregularidad en planta

Debido a que no se presentan diafragmas rígidos, no se revisan las irregularidades torsionales

Para nuestro edificio; no se presentan irregularidad por retrocesos en sus esquinas.


Pag. 19 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

En nuestro edificio no se presentan estas condiciones.

De acuerdo a los anterior p : 1.0

- Irregularidades en altura

No se presentan irregularidades en altura

Debido a que se presenta irregularidad en planta, por retrocesos en las esquinas, -a =1.0, y como -p =0.9, pero
como el sistema estructural, y debido a que nuestra estructura se clasifica como péndulo invertido, requiere un
-r=0.75

PASO 7

Pag. 20 de 54

- Cortante en la base

Las magnitudes de nuestro sismo de diseño, como se define en paso 4, es Vs=113Ton;

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

PASO 8

- Coeficiente de Disipación de Energía R

R = 2.0 x 1.0 x 1.0 x 0.75 = 1.5

PASOS 9 Y 10

- Revisión de Derivas
Pag. 21 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Joint OutputCase U1 U2 i hi i adm


Text Text mm mm mm mm mm mm
16 EX 28 1 28 3800 28 38
16 EY -2 30 30 3800 30 38
16 D+L+EX 28 1 28 3800 28 38
16 D+L+EY -2 30 30 3800 30 38
17 EX 28 0 28 3800 28 38
17 EY -2 27 27 3800 27 38
17 D+L+EX 28 0 28 3800 28 38
17 D+L+EY -2 27 27 3800 27 38
26 EX 30 1 30 3800 30 38
26 EY 2 30 30 3800 30 38
26 D+L+EX 30 1 30 3800 30 38
26 D+L+EY 3 30 30 3800 30 38
27 EX 30 0 30 3800 30 38
27 EY 2 27 27 3800 27 38
27 D+L+EX 30 0 30 3800 30 38
27 D+L+EY 3 27 27 3800 27 38
50 EX 30 -1 30 5100 30 51
50 EY -2 27 27 5100 27 51
50 D+L+EX 31 -1 31 5100 31 51
50 D+L+EY -2 27 27 5100 27 51
51 EX 30 2 30 5100 30 51
51 EY -2 28 28 5100 28 51
51 D+L+EX 31 4 31 5100 31 51
51 D+L+EY -2 30 30 5100 30 51
Pag. 22 de 54

52 EX 30 0 30 5100 30 51
52 EY -2 17 17 5100 17 51
52 D+L+EX 31 0 31 5100 31 51
52 D+L+EY -2 17 17 5100 17 51
55 EX 33 -1 33 5100 33 51
55 EY 2 27 27 5100 27 51
Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

55 D+L+EX 34 0 34 5100 34 51
55 D+L+EY 3 27 27 5100 27 51
56 EX 33 -1 33 5100 33 51
56 EY 2 27 27 5100 27 51
56 D+L+EX 34 0 34 5100 34 51
56 D+L+EY 3 28 29 5100 29 51
57 EX 33 0 33 5100 33 51
57 EY 2 17 17 5100 17 51
57 D+L+EX 34 0 34 5100 34 51
57 D+L+EY 3 17 17 5100 17 51

De acuerdo a lo anterior el edificio responde bien a las solicitaciones dadas, desde el punto de vista de
flexibilidad.

LISTADOS DEL COMPUTADOR

- Coordenadas de los nudos

Joint XorR Y Z Joint XorR Y Z


m m m m m m
1 0.00000 0.00000 0.00000 13 9.00000 9.70000 0.00000
2 5.38000 0.00000 0.00000 14 15.00000 9.70000 0.00000
3 9.00000 0.00000 0.00000 15 21.00000 9.70000 0.00000
4 15.00000 0.00000 0.00000 16 0.00000 0.00000 3.80000
Pag. 23 de 54

5 21.00000 0.00000 0.00000 17 5.38000 0.00000 3.80000


6 0.00000 4.85000 0.00000 18 9.00000 0.00000 3.80000
7 5.38000 4.85000 0.00000 19 15.00000 0.00000 3.80000
8 9.00000 4.85000 0.00000 20 21.00000 0.00000 3.80000
10 21.00000 4.85000 0.00000 21 0.00000 4.85000 3.80000
11 0.00000 9.70000 0.00000 22 5.38000 4.85000 3.80000
12 5.38000 9.70000 0.00000 23 9.00000 4.85000 3.80000

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Joint XorR Y Z Joint XorR Y Z


m m m m m m
25 21.00000 4.85000 3.80000 57 21.00000 9.70000 5.10000
26 0.00000 9.70000 3.80000 58 21.00000 2.70000 5.10000
27 5.38000 9.70000 3.80000 59 1.79333 9.70000 3.80000
28 9.00000 9.70000 3.80000 60 1.79333 10.85000 3.80000
29 15.00000 9.70000 3.80000 61 3.58667 9.70000 3.80000
30 21.00000 9.70000 3.80000 62 3.58667 10.85000 3.80000
31 21.00000 2.70000 0.00000 63 6.58667 9.70000 3.80000
32 0.00000 10.85000 3.80000 64 6.58667 10.85000 3.80000
33 5.38000 10.85000 3.80000 65 7.79333 9.70000 3.80000
34 9.00000 10.85000 3.80000 66 7.79333 10.85000 3.80000
35 -1.15000 0.00000 3.80000 67 1.79333 -1.15000 3.80000
36 -1.15000 4.85000 3.80000 68 1.79333 0.00000 3.80000
37 -1.15000 9.70000 3.80000 69 3.58667 -1.15000 3.80000
38 0.00000 -1.15000 3.80000 70 3.58667 0.00000 3.80000
39 5.38000 -1.15000 3.80000 71 6.58667 -1.15000 3.80000
40 9.00000 -1.15000 3.80000 72 6.58667 0.00000 3.80000
41 -1.15000 -1.15000 3.80000 73 7.79333 -1.15000 3.80000
42 -1.15000 10.85000 3.80000 74 7.79333 0.00000 3.80000
44 21.00000 2.70000 3.80000 75 22.15000 6.46667 3.80000
45 22.15000 4.85000 3.80000 76 21.00000 6.46667 3.80000
46 22.15000 9.70000 3.80000 77 22.15000 8.08333 3.80000
47 22.15000 2.70000 3.80000 78 21.00000 8.08333 3.80000
48 21.00000 10.85000 3.80000 79 0.00000 1.61667 3.80000
49 22.15000 10.85000 3.80000 80 -1.15000 1.61667 3.80000
50 9.00000 0.00000 5.10000 81 0.00000 3.23333 3.80000
51 15.00000 0.00000 5.10000 82 -1.15000 3.23333 3.80000
52 21.00000 0.00000 5.10000 83 0.00000 6.46667 3.80000
53 9.00000 4.85000 5.10000 84 -1.15000 6.46667 3.80000
54 21.00000 4.85000 5.10000 85 0.00000 8.08333 3.80000
55 9.00000 9.70000 5.10000 86 -1.15000 8.08333 3.80000
56 15.00000 9.70000 5.10000

- Incidencia de elementos frame

Pag. 24 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame JointI JointJ Frame JointI JointJ Frame JointI JointJ

32 21 22 91 3 18 130 65 28
33 22 23 92 2 17 131 26 85
42 27 22 93 1 16 132 85 83
43 22 17 94 6 21 133 83 21
44 28 23 95 7 22 134 21 81
45 23 18 96 8 23 135 81 79
56 42 32 97 50 51 136 79 16
57 41 38 98 51 52 137 30 78
58 35 16 99 55 56 138 78 76
59 36 21 100 56 57 139 76 25
60 37 26 101 55 53 140 32 60
61 42 37 102 53 50 141 60 62
62 35 41 103 57 54 142 62 33
63 32 26 104 54 58 143 33 64
64 16 38 105 58 52 144 64 66
65 33 27 106 28 55 145 66 34
66 17 39 107 29 56 146 37 86
67 34 28 110 19 51 147 86 84
68 18 40 111 18 50 148 84 36
70 25 44 112 44 58 149 36 82
71 44 20 114 5 20 150 82 80
73 45 47 116 20 52 151 80 35
74 30 48 117 25 54 152 38 67
75 48 49 118 23 53 153 67 69
76 49 46 119 16 68 154 69 39
77 46 30 120 68 70 155 39 71
78 47 44 121 70 17 156 71 73
79 25 45 122 17 72 157 73 40
82 11 26 123 72 74 158 46 77
83 12 27 124 74 18 159 77 75
84 13 28 125 26 59 160 75 45
85 14 29 126 59 61 161 15 30
87 10 25 127 61 27 162 30 57
88 31 44 128 27 63
90 4 19 129 63 65

- Incidencia de elementos Shell

Pag. 25 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Area NumJoints Joint1 Joint2 Joint3 Joint4 Area NumJoints Joint1 Joint2 Joint3 Joint4

5 4 44 47 45 25 22 4 38 67 68 16
7 4 30 46 49 48 23 4 67 69 70 68
8 4 37 26 32 42 24 4 69 39 17 70
13 4 41 38 16 35 25 4 39 71 72 17
16 4 26 59 60 32 26 4 71 73 74 72
17 4 59 61 62 60 27 4 73 40 18 74
18 4 61 27 33 62 28 4 25 45 75 76
19 4 27 63 64 33 29 4 76 75 77 78
20 4 63 65 66 64 30 4 78 77 46 30
21 4 65 28 34 66
31 4 35 16 79 80
32 4 80 79 81 82
33 4 82 81 21 36
34 4 36 21 83 84
35 4 84 83 85 86
36 4 86 85 26 37

- Asignación de Secciones a Frames.

Frame SectionType DesignSect Frame SectionType DesignSect

32 Rectangular V30x40 87 Rectangular C35x35


33 Rectangular V30x40 88 Rectangular C30x40
42 Rectangular V30x40 90 Rectangular C35x35
43 Rectangular V30x40 91 Rectangular C30x30
44 Rectangular V30x40 92 Rectangular C30x30
45 Rectangular V30x40 93 Rectangular C30x30
56 Rectangular V20x40 94 Rectangular C35x35
57 Rectangular V20x40 95 Rectangular C35x35
58 Rectangular V30x40 96 Rectangular C35x35
59 Rectangular V30x40 97 Rectangular VC30X40
60 Rectangular V30x40 98 Rectangular VC30X40
61 Rectangular V20x40 99 Rectangular VC30X40
62 Rectangular V20x40 100 Rectangular VC30X40
63 Rectangular V30x40 101 Rectangular VC30X40
64 Rectangular V30x40 102 Rectangular VC30X40
65 Rectangular V30x40 103 Rectangular VC30X40
66 Rectangular V30x40 104 Rectangular VC30X40
67 Rectangular V30x40 105 Rectangular VC30X40
68 Rectangular V30x40 106 Rectangular C30x30
70 Rectangular V30x40 107 Circle D40
71 Rectangular V30x40 110 Rectangular C35x35
73 I/Wide Flange IPE160 111 Rectangular C30x30
74 I/Wide Flange IPE160 112 Rectangular C30x40
75 I/Wide Flange IPE160 114 Rectangular C30x30
76 I/Wide Flange IPE160 116 Rectangular C30x30
Pag. 26 de 54

77 I/Wide Flange IPE160 117 Rectangular C35x35


78 I/Wide Flange IPE160 118 Rectangular C35x35
79 I/Wide Flange IPE160 119 Rectangular V30x40
82 Rectangular C30x30 120 Rectangular V30x40
83 Rectangular C30x30 121 Rectangular V30x40
84 Rectangular C30x30 122 Rectangular V30x40
85 Circle D40 123 Rectangular V30x40

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame SectionType DesignSect Frame SectionType DesignSect

124 Rectangular V30x40 144 Rectangular V20x40


125 Rectangular V30x40 145 Rectangular V20x40
126 Rectangular V30x40 146 Rectangular V20x40
127 Rectangular V30x40 147 Rectangular V20x40
128 Rectangular V30x40 148 Rectangular V20x40
129 Rectangular V30x40 149 Rectangular V20x40
130 Rectangular V30x40 150 Rectangular V20x40
131 Rectangular V30x40 151 Rectangular V20x40
132 Rectangular V30x40 152 Rectangular V20x40
133 Rectangular V30x40 153 Rectangular V20x40
134 Rectangular V30x40 154 Rectangular V20x40
135 Rectangular V30x40 155 Rectangular V20x40
136 Rectangular V30x40 156 Rectangular V20x40
137 Rectangular V30x40 157 Rectangular V20x40
138 Rectangular V30x40 158 I/Wide Flange IPE160
139 Rectangular V30x40 159 I/Wide Flange IPE160
140 Rectangular V20x40 160 I/Wide Flange IPE160
141 Rectangular V20x40 161 Rectangular C30x30
142 Rectangular V20x40 162 Rectangular C30x30
143 Rectangular V20x40

- Asignación de Secciones a Shells.

Area Section Area Section Area Section

5 PL15 21 PL15 30 PL15


7 PL15 22 PL15 31 PL15
8 PL15 23 PL15 32 PL15
13 PL15 24 PL15 33 PL15
16 PL15 25 PL15 34 PL15
17 PL15 26 PL15 35 PL15
18 PL15 27 PL15 36 PL15
19 PL15 28 PL15
20 PL15 29 PL15

- Grados de libertad, en análisis estructural.

Table: Active Degrees of Freedom


UX UY UZ RX RY RZ
Yes Yes Yes Yes Yes Yes
Pag. 27 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

PASO 11

Como se determinó anteriormente, para nuestra estructura, R= 1.5

Pag. 28 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Combinaciones de carga

Combinaciones de carga para diseño,

Pag. 29 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

ComboName ComboType CaseName ScaleFactor

1.4DL Linear Add DEAD 1.400000


1.2DL+1.6LL Linear Add DEAD 1.200000
1.2DL+1.6LL LL 1.600000
1.2DL+1.6LL+0.5Wx Linear Add DEAD 1.200000
1.2DL+1.6LL+0.5Wx LL 1.600000
1.2DL+1.6LL+0.5Wx WX 0.500000
1.2DL+1.6LL-0.5Wx Linear Add DEAD 1.200000
1.2DL+1.6LL-0.5Wx LL 1.600000
1.2DL+1.6LL-0.5Wx WX -0.500000
1.2DL+1.6LL+0.5Wy Linear Add DEAD 1.200000
1.2DL+1.6LL+0.5Wy LL 1.600000
1.2DL+1.6LL+0.5Wy WY 0.500000
1.2DL+1.6LL-0.5Wy Linear Add DEAD 1.200000
1.2DL+1.6LL-0.5Wy LL 1.600000
1.2DL+1.6LL-0.5Wy WY -0.500000
1.2DL+1.0LL+1.0Wx Linear Add DEAD 1.200000
1.2DL+1.0LL+1.0Wx LL 1.000000
1.2DL+1.0LL+1.0Wx WX 1.000000
1.2DL+1.0LL-1.0Wx Linear Add DEAD 1.200000
1.2DL+1.0LL-1.0Wx LL 1.000000
1.2DL+1.0LL-1.0Wx WX -1.000000
1.2DL+1.0LL+WY Linear Add DEAD 1.200000
1.2DL+1.0LL+WY LL 1.000000
1.2DL+1.0LL+WY WY 1.000000
1.2DL+1.0LL-WY Linear Add DEAD 1.200000
1.2DL+1.0LL-WY LL 1.000000
1.2DL+1.0LL-WY WY -1.000000
1.2DL+1.0LL+1.0EX+0.3EY Linear Add DEAD 1.200000
1.2DL+1.0LL+1.0EX+0.3EY LL 1.000000
1.2DL+1.0LL+1.0EX+0.3EY EX1 1.000000
1.2DL+1.0LL+1.0EX+0.3EY EY1 0.300000
1.2DL+1.0LL-1.0EX+0.3EY Linear Add DEAD 1.200000
1.2DL+1.0LL-1.0EX+0.3EY LL 1.000000
1.2DL+1.0LL-1.0EX+0.3EY EX1 -1.000000
1.2DL+1.0LL-1.0EX+0.3EY EY1 0.300000
1.2DL+1.0LL+1.0EX-0.3EY Linear Add DEAD 1.200000
1.2DL+1.0LL+1.0EX-0.3EY LL 1.000000
1.2DL+1.0LL+1.0EX-0.3EY EX1 1.000000
1.2DL+1.0LL+1.0EX-0.3EY EY1 -0.300000
1.2DL+1.0LL-1.0EX-0.3EY Linear Add DEAD 1.200000
1.2DL+1.0LL-1.0EX-0.3EY LL 1.000000
1.2DL+1.0LL-1.0EX-0.3EY EX1 -1.000000
1.2DL+1.0LL-1.0EX-0.3EY EY1 -0.300000
0.9DL+1.0WX Linear Add DEAD 0.900000
0.9DL+1.0WX WX 1.000000
0.9DL-1.0WX Linear Add DEAD 0.900000
0.9DL-1.0WX WX -1.000000
0.9DL+1.0WY Linear Add DEAD 0.900000
0.9DL+1.0WY WY 1.000000
Pag. 30 de 54

0.9DL-1.0WY Linear Add DEAD 0.900000


0.9DL-1.0WY WY -1.000000
0.9DL+1.0EX+0.3EY Linear Add DEAD 0.900000
0.9DL+1.0EX+0.3EY EX1 1.000000
0.9DL+1.0EX+0.3EY EY1 0.300000
0.9DL+EX-0.3EY Linear Add DEAD 0.900000
0.9DL+EX-0.3EY EX1 1.000000

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

ComboName ComboType CaseName ScaleFactor

0.9DL+EX-0.3EY EY1 -0.300000


0.9DL-EX+0.3EY Linear Add DEAD 0.900000
0.9DL-EX+0.3EY EX1 -1.000000
0.9DL-EX+0.3EY EY1 0.300000
0.9DL-EX-0.3EY Linear Add DEAD 0.900000
0.9DL-EX-0.3EY EX1 -1.000000
0.9DL-EX-0.3EY EY1 -0.300000

- Ajustando el sismo de diseño

Vs = 113 / 1.5 = 75.3 Tons

- Fuerzas internas en los elementos

Fuerzas internas en los elementos, bajo la condición crítica de cada elemento, con las combinaciones de carga, y
el cortante en la base de diseño, reducido con R=1.5

- Elementos tipo Frame

Frame P V2 V3 T M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
32 -211.55 -1234.90 -4.02 -1.41 -14.91 -2015.62
32 -211.55 626.57 -4.02 -1.41 6.74 -379.19
33 -84.65 -569.85 -32.86 -6.71 -44.87 -269.06
Pag. 31 de 54

33 -84.65 682.67 -32.86 -6.71 74.10 -473.26


42 67.67 -1449.79 17.40 -63.47 43.41 -2705.94
42 67.67 228.31 17.40 -63.47 -40.97 256.14
43 47.20 -266.71 4.74 61.50 11.53 164.56
43 47.20 1411.38 4.74 61.50 -11.45 -2611.27
44 137.51 -1152.94 8.00 -15.17 34.00 -1679.19
44 137.51 525.15 8.00 -15.17 -4.79 -156.80

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame P V2 V3 T M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
45 306.33 -598.89 -3.34 32.13 -23.35 -342.81
45 306.33 1079.20 -3.34 32.13 -7.15 -1507.57
56 -114.40 251.04 3.86 -184.44 1.58 -134.22
56 -114.40 516.31 3.86 -184.44 -2.86 -575.44
57 7.99 249.20 6.704E-02 184.37 0.75 -138.86
57 7.99 514.46 6.704E-02 184.37 0.67 -577.96
58 3.24 543.98 1.74 399.79 -1.35 -270.48
58 3.24 941.88 1.74 399.79 -3.35 -1124.84
59 -61.22 534.34 -9.309E-02 -7.75 1.42 -321.35
59 -61.22 932.24 -9.309E-02 -7.75 1.53 -1164.63
60 133.92 547.38 2.02 -407.63 -2.82 -271.20
60 133.92 945.27 2.02 -407.63 -5.14 -1129.47
61 -107.19 255.31 -3.77 185.02 -1.06 -154.46
61 -107.19 520.58 -3.77 185.02 3.27 -600.59
62 9.71 -521.26 -0.19 -182.76 -0.80 -592.86
62 9.71 -256.00 -0.19 -182.76 -0.58 -145.93
63 100.92 552.74 -2.15 405.96 0.69 -295.81
63 100.92 950.64 -2.15 405.96 3.16 -1160.25
64 -6.29 -951.78 -1.30 -404.03 1.67 -1163.82
64 -6.29 -553.88 -1.30 -404.03 3.17 -298.07
65 -36.81 559.53 -0.23 -51.47 2.33 -305.61
65 -36.81 957.43 -0.23 -51.47 2.59 -1177.86
66 -44.95 -961.87 -0.44 53.24 -6.61 -1179.09
66 -44.95 -563.97 -0.44 53.24 -6.11 -301.74
67 -16.43 451.10 9.678E-02 -336.36 -4.89 -460.16
67 -16.43 849.00 9.678E-02 -336.36 -5.00 -1207.72
68 45.70 -844.65 13.44 306.66 27.04 -1221.76
68 45.70 -446.75 13.44 306.66 11.58 -479.21
70 -286.16 -727.97 -21.02 214.21 51.97 -723.94
70 -286.16 15.93 -21.02 214.21 97.16 41.49
71 295.77 -586.77 124.38 364.50 440.24 -356.93
71 295.77 347.43 124.38 364.50 104.41 -33.81
73 54.42 -38.85 0.11 3.746E-02 -0.34 -42.88
73 54.42 1.86 0.11 3.746E-02 -0.58 -3.12
74 -0.32 -33.16 -5.607E-03 4.683E-02 -0.66 -22.24
74 -0.32 -11.39 -5.607E-03 4.683E-02 -0.66 3.37
75 -0.84 -45.06 -4.172E-03 -7.693E-03 0.66 -12.29
75 -0.84 -23.28 -4.172E-03 -7.693E-03 0.66 27.01
76 0.31 7.66 1.907E-02 -5.847E-02 -0.65 -16.16
76 0.31 29.43 1.907E-02 -5.847E-02 -0.67 -37.49
77 0.89 27.59 2.062E-02 1.955E-02 0.68 -37.72
77 0.89 49.37 2.062E-02 1.955E-02 0.65 -81.97
78 4.95 24.82 -0.21 -2.866E-02 0.91 -11.24
78 4.95 46.59 -0.21 -2.866E-02 1.15 -52.31
79 -10.22 -48.47 -4.080E-02 -4.308E-02 0.82 -57.04
79 -10.22 -26.70 -4.080E-02 -4.308E-02 0.87 -13.82
82 -15466.59 149.07 -118.99 -2.90 -125.32 268.23
82 -14480.49 149.07 -118.99 -2.90 326.82 -298.26
83 -12356.23 207.84 -429.38 0.34 -517.48 343.62
Pag. 32 de 54

83 -11370.13 207.84 -429.38 0.34 1114.18 -446.19


84 -8727.90 133.37 -177.01 2.01 -197.89 250.80
84 -7741.81 133.37 -177.01 2.01 474.74 -255.99
85 -5001.34 215.74 215.45 -8.00 750.51 555.01
85 -3624.49 215.74 215.45 -8.00 -68.19 -264.79
87 -12289.72 -633.14 -55.06 67.86 3.06 -471.85
87 -10947.53 -633.14 -55.06 67.86 212.30 1934.10

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame P V2 V3 T M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
88 -5708.54 111.82 161.02 24.45 -85.58 232.57
88 -4393.75 111.82 161.02 24.45 -697.44 -192.34
90 -4945.80 147.22 247.26 28.01 993.48 378.45
90 -3603.61 147.22 247.26 28.01 53.89 -180.97
91 -8499.38 122.66 226.90 2.45 307.45 212.41
91 -7513.29 122.66 226.90 2.45 -554.75 -253.68
92 -12425.86 167.17 481.79 -0.51 625.89 268.43
92 -11439.77 167.17 481.79 -0.51 -1204.93 -366.82
93 -15419.92 119.04 185.64 -1.07 257.67 208.38
93 -14433.82 119.04 185.64 -1.07 -447.77 -243.96
94 -12202.02 760.92 61.47 -6.54 121.12 1074.30
94 -10859.84 760.92 61.47 -6.54 -112.48 -1817.20
95 -3033.63 139.56 49.31 -0.89 101.11 295.21
95 -1691.44 139.56 49.31 -0.89 -86.29 -235.10
96 -8158.50 146.54 41.30 -14.51 95.74 303.51
96 -6816.31 146.54 41.30 -14.51 -61.18 -253.35
97 684.72 -798.32 -171.71 -95.61 -454.60 -101.30
97 684.72 1277.67 -171.71 -95.61 575.65 -1539.35
98 299.94 -1106.77 113.03 171.94 547.64 -1166.99
98 299.94 969.22 113.03 171.94 -130.55 -754.34
99 1261.44 -745.52 -149.33 -188.44 -404.60 105.48
99 1261.44 1330.48 -149.33 -188.44 491.37 -1649.39
100 945.18 -1062.99 167.22 159.83 499.38 -1104.14
100 945.18 1013.01 167.22 159.83 -503.97 -954.19
101 250.73 -1749.45 95.49 116.50 318.99 -828.17
101 250.73 2227.54 95.49 116.50 -144.15 -1987.54
102 7.75 -2322.89 44.94 -84.98 -36.98 -2171.86
102 7.75 1654.10 44.94 -84.98 -254.93 -550.04
103 -1579.83 -1927.15 -158.69 -271.13 -438.74 -1256.34
103 -1579.83 2049.85 -158.69 -271.13 330.90 -1553.88
104 4.18 -980.12 49.23 181.89 348.47 -603.04
104 4.18 782.88 49.23 181.89 242.63 -391.00
105 -368.84 -1338.90 240.52 421.46 587.69 -689.92
105 -368.84 875.10 240.52 421.46 -61.71 -63.80
106 -2832.32 1165.95 -101.40 85.62 -771.55 1293.75
106 -2494.97 1165.95 -101.40 85.62 -639.73 -221.99
107 -3624.49 215.74 215.45 -8.00 -68.19 -264.79
107 -3153.46 215.74 215.45 -8.00 -348.27 -545.25
110 -3603.61 147.22 247.26 28.01 53.89 -180.97
110 -3144.44 147.22 247.26 28.01 -267.55 -372.36
111 -2789.77 729.66 179.46 199.67 878.94 964.88
111 -2452.42 729.66 179.46 199.67 645.65 16.32
112 -2571.57 373.02 191.29 -345.06 488.24 186.00
112 -2121.77 373.02 191.29 -345.06 239.56 -298.93
114 -3515.19 64.96 39.96 -87.84 88.86 201.22
114 -2529.10 64.96 39.96 -87.84 -63.00 -45.63
116 -2181.67 -59.42 -255.80 -192.26 -96.81 -410.13
116 -1844.32 -59.42 -255.80 -192.26 235.74 -332.88
117 -3489.14 -207.92 -1584.02 -17.58 -1108.38 -723.31
Pag. 33 de 54

117 -3029.97 -207.92 -1584.02 -17.58 950.84 -453.02


118 -5009.61 50.55 242.98 -107.17 131.54 267.20
118 -4550.44 50.55 242.98 -107.17 -184.33 201.48
119 9.21 -1690.92 -0.27 365.60 1.22 -1923.05
119 9.21 -1070.43 -0.27 365.60 1.71 552.96
120 -89.89 -410.60 1.83 149.90 -2.58 767.45
120 -89.89 209.90 1.83 149.90 -5.87 947.41

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame P V2 V3 T M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
121 -186.47 880.57 -0.59 -21.05 -3.053E-02 774.93
121 -186.47 1501.06 -0.59 -21.05 1.03 -1360.60
122 -147.01 -1225.21 1.86 14.53 -9.12 -1193.58
122 -147.01 -807.70 1.86 14.53 -11.37 32.94
123 -53.50 -403.47 -8.78 -223.66 4.21 181.55
123 -53.50 14.03 -8.78 -223.66 14.81 416.52
124 52.62 418.72 11.68 -417.66 -9.84 320.73
124 52.62 836.22 11.68 -417.66 -23.94 -436.42
125 545.03 -1689.84 -4.27 -367.31 -11.52 -1910.51
125 545.03 -1069.35 -4.27 -367.31 -3.86 563.57
126 390.81 -409.17 0.67 -153.42 -3.82 776.98
126 390.81 211.32 0.67 -153.42 -5.01 954.39
127 221.35 881.90 -3.30 18.33 -3.88 780.74
127 221.35 1502.39 -3.30 18.33 2.03 -1357.17
128 218.16 -1186.06 1.58 -25.50 -3.37 -1149.61
128 218.16 -768.56 1.58 -25.50 -5.28 29.68
129 240.47 -365.01 -1.21 206.28 0.23 163.03
129 240.47 52.50 -1.21 206.28 1.69 351.57
130 261.42 458.23 3.22 423.53 -4.65 215.65
130 261.42 875.74 3.22 423.53 -8.53 -589.18
131 364.57 -1582.47 7.03 392.05 13.27 -1986.84
131 364.57 -1023.10 7.03 392.05 1.91 119.33
132 53.11 -444.47 1.18 147.22 -0.75 342.96
132 53.11 114.90 1.18 147.22 -2.66 609.37
133 -274.71 705.12 5.33 -16.13 1.21 479.22
133 -274.71 1264.48 5.33 -16.13 -7.40 -1112.88
134 -364.89 -1282.10 -2.25 22.91 -8.42 -1164.76
134 -364.89 -722.74 -2.25 22.91 -4.78 455.82
135 -208.06 -132.88 -1.57 -150.52 -3.11 598.87
135 -208.06 426.48 -1.57 -150.52 -0.57 361.55
136 -43.71 1005.82 -1.20 -387.70 -3.49 144.75
136 -43.71 1565.19 -1.20 -387.70 -1.55 -1933.49
137 342.32 -1497.40 -0.51 -226.77 -68.82 -1091.80
137 342.32 -938.03 -0.51 -226.77 -67.99 876.84
138 236.73 -249.60 -10.35 27.18 58.76 965.04
138 236.73 309.77 -10.35 27.18 75.48 916.40
139 49.30 1045.78 15.77 232.21 -62.87 774.40
139 49.30 1605.14 15.77 232.21 -88.36 -1368.43
140 -311.77 -1092.39 0.22 -69.78 -1.59 -1021.38
140 -311.77 -678.73 0.22 -69.78 -1.99 566.72
141 -184.59 -275.61 -0.92 -65.41 -2.09 482.48
141 -184.59 138.06 -0.92 -65.41 -0.44 605.81
142 -67.67 548.56 0.12 -55.78 -0.80 682.83
142 -67.67 962.22 0.12 -55.78 -1.01 -671.84
143 -40.01 -690.02 -0.23 101.49 7.996E-02 -527.96
143 -40.01 -411.68 -0.23 101.49 0.36 136.73
144 -58.53 -220.58 0.70 68.42 -1.15 123.84
144 -58.53 57.76 0.70 68.42 -2.00 222.07
145 -74.33 254.91 -0.62 41.02 0.12 291.70
Pag. 34 de 54

145 -74.33 533.24 -0.62 41.02 0.87 -183.82


146 -229.17 -1010.65 0.37 62.66 1.03 -1045.50
146 -229.17 -637.74 0.37 62.66 0.43 286.95
147 11.32 -298.56 1.51 66.19 1.87 202.67
147 11.32 74.35 1.51 66.19 -0.58 383.91
148 243.35 423.61 0.62 74.05 -1.20 437.45
148 243.35 796.52 0.62 74.05 -2.19 -548.82

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame P V2 V3 T M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
149 301.81 -807.80 -0.45 -71.73 -1.65 -566.18
149 301.81 -434.89 -0.45 -71.73 -0.91 438.32
150 184.02 -86.15 -0.46 -66.55 -1.70 376.43
150 184.02 286.76 -0.46 -66.55 -0.95 214.27
151 68.95 626.77 -0.53 -62.04 -0.27 295.31
151 68.95 999.68 -0.53 -62.04 0.59 -1019.40
152 41.39 -1093.11 0.47 68.40 -0.25 -1028.49
152 41.39 -679.45 0.47 68.40 -1.09 560.90
153 109.87 -276.68 -0.14 64.19 0.16 475.92
153 109.87 136.98 -0.14 64.19 0.40 601.18
154 182.76 547.41 0.64 54.87 -1.37 677.41
154 182.76 961.07 0.64 54.87 -2.52 -675.19
155 168.80 -713.69 -2.35 -104.13 -2.183E-02 -537.86
155 168.80 -435.35 -2.35 -104.13 2.81 155.40
156 104.78 -244.51 1.41 -73.91 -2.76 136.88
156 104.78 33.83 1.41 -73.91 -4.46 263.99
157 24.51 232.11 -2.30 -38.12 2.85 306.78
157 24.51 510.45 -2.30 -38.12 5.63 -141.22
158 -19.38 -78.21 -2.433E-02 1.615E-02 0.44 -47.92
158 -19.38 -47.60 -2.433E-02 1.615E-02 0.48 53.77
159 0.59 -13.56 6.353E-02 2.714E-03 -0.47 53.53
159 0.59 17.05 6.353E-02 2.714E-03 -0.57 50.71
160 34.94 53.67 -0.15 1.358E-02 0.45 56.32
160 34.94 84.28 -0.15 1.358E-02 0.70 -55.19
161 -10554.13 -515.92 183.54 19.35 270.03 -574.04
161 -9568.04 -515.92 183.54 19.35 -427.42 1386.45
162 -3277.50 -786.49 1747.06 -65.23 1174.66 -1705.50
162 -2940.15 -786.49 1747.06 -65.23 -1096.51 -683.06

- Elementos tipo Shell

AreaElem Joint F11 F22 F12 M11 M22 M12


Kgf/m Kgf/m Kgf/m Kgf-m/m Kgf-m/m Kgf-m/m
5 44 -576.34 -2905.74 -2569.91 -947.10 -108.30 -220.99
5 47 1395.62 3667.44 4506.57 -45.55 78.99 -246.05
5 45 400.46 3368.89 3197.71 -344.72 -716.65 -362.84
5 25 -1571.50 -3204.29 -3878.77 -1247.65 -907.57 -337.77
7 30 52.31 -3.51 -198.47 -1632.72 -840.64 -270.09
7 46 64.67 37.70 -11.80 -797.26 -878.77 586.66
7 49 -49.21 3.53 175.81 571.57 -8.83 365.26
7 48 -61.57 -37.67 -10.86 -251.63 31.81 -491.49
8 37 899.22 -1265.65 -876.52 -445.95 -1012.26 -587.39
8 26 1723.14 1480.75 -269.31 -1431.88 -1452.84 -475.99
8 32 -1483.02 518.90 -902.46 -982.35 -457.36 -583.20
8 42 -2306.94 -2227.50 -1509.67 -14.34 -33.73 -694.60
13 41 171.70 190.59 -51.38 -17.88 -23.67 691.73
13 38 106.05 -28.24 -97.19 -985.85 -460.07 585.64
Pag. 35 de 54

13 16 14.19 -55.80 -196.11 -1428.08 -1455.05 468.44


13 35 79.84 163.04 -150.30 -442.56 -1001.38 574.53
16 26 6037.48 2775.05 467.15 -2174.49 -1672.52 -651.17
16 59 5574.58 1232.05 698.39 571.00 -344.84 -307.97
16 60 -5052.98 -1956.22 -7.93 1152.39 640.28 -69.64
16 32 -4590.08 -413.21 -239.18 -1578.90 -639.43 -412.84
17 59 3956.17 746.53 -2.00 655.87 -269.69 -174.74

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

AreaElem Joint F11 F22 F12 M11 M22 M12


Kgf/m Kgf/m Kgf/m Kgf-m/m Kgf-m/m Kgf-m/m
17 61 4082.45 1167.48 -10.28 830.41 -267.71 -225.38
17 62 -2924.64 -934.65 507.75 1017.98 493.78 -251.70
17 60 -3050.93 -1355.60 516.03 841.85 497.43 -201.06
18 61 2304.04 633.95 551.61 734.66 -354.79 -128.69
18 27 2207.03 310.57 452.50 -1633.87 -1522.47 177.38
18 33 -1181.14 -705.88 -69.99 -1068.88 -497.83 -40.33
18 62 -1084.13 -382.50 29.11 1282.55 631.51 -346.41
19 27 2173.61 300.55 -125.45 -1485.15 -1483.74 -126.40
19 63 2217.74 447.64 -138.51 -1.98 -505.36 58.80
19 64 -701.55 -428.15 21.95 525.35 503.51 444.26
19 33 -745.68 -575.24 35.01 -942.75 -454.11 259.07
20 63 2451.82 517.86 56.65 34.03 -432.63 268.20
20 65 2458.55 540.30 74.77 224.76 -419.61 269.93
20 66 -986.35 -493.17 -162.17 463.62 379.33 237.75
20 64 -993.08 -515.60 -180.28 278.57 367.55 236.02
21 65 2678.41 606.26 -235.14 150.02 -458.26 459.99
21 28 2691.71 650.57 -219.11 -942.80 -1354.73 645.94
21 34 -1221.89 -523.50 140.73 -435.27 -426.67 234.72
21 66 -1235.18 -567.82 124.71 654.35 452.77 48.77
22 38 631.74 129.46 -298.31 -1589.62 -644.36 409.03
22 67 602.56 32.18 -254.90 1145.41 641.76 63.89
22 68 47.63 -134.30 -1.80 561.69 -345.88 304.78
22 16 76.81 -37.02 -45.21 -2187.54 -1679.72 649.92
23 67 1680.61 355.60 21.66 833.77 498.88 196.77
23 69 1724.87 503.13 7.90 1012.57 495.45 247.54
23 70 -948.02 -298.74 -314.00 824.25 -269.00 220.85
23 68 -992.28 -446.27 -300.24 647.09 -270.87 170.08
24 69 2872.22 847.33 -347.95 1276.22 633.62 342.25
24 39 2735.43 391.38 -321.95 -1072.50 -495.40 38.20
24 17 -2098.40 -1058.77 55.23 -1637.16 -1524.71 -179.91
24 70 -1961.62 -602.82 29.23 728.76 -356.72 124.15
25 39 2515.72 325.47 480.32 -962.50 -457.24 -258.83
25 71 2696.25 927.23 573.95 557.10 508.96 -462.71
25 72 -1503.77 -332.78 -65.03 3.57 -511.49 -82.40
25 17 -1684.30 -934.54 -158.66 -1531.90 -1498.29 121.48
26 71 1688.44 624.89 -239.10 288.74 364.81 -255.19
26 73 1483.13 -59.48 -263.19 525.87 387.26 -256.56
26 74 -727.77 -722.75 656.14 287.62 -411.93 -292.41
26 72 -522.46 -38.39 680.23 44.31 -435.62 -291.04
27 73 219.56 -438.55 539.28 664.80 443.36 -68.30
27 40 529.73 595.34 1365.74 -373.15 -423.24 -194.83
27 18 696.14 645.26 50.13 -798.18 -1324.58 -608.43
27 74 385.97 -388.63 -776.32 241.47 -440.20 -481.90
28 25 -515.35 316.18 2157.24 -1446.32 -1666.89 -448.40
28 45 17.15 2091.20 -1981.90 -492.68 -1112.77 -255.12
28 75 568.06 2256.48 -2612.02 567.00 1290.37 35.21
28 76 35.55 481.45 1527.12 -356.82 744.93 -158.07
29 76 625.65 2448.44 -1534.38 -318.99 752.77 -67.36
29 75 -107.95 3.11 621.20 457.69 1044.27 -53.93
Pag. 36 de 54

29 77 -591.71 -142.02 1091.47 501.34 1107.42 9.84


29 78 141.89 2303.31 -1064.10 -275.87 815.40 -3.59
30 78 474.31 3411.39 88.81 -313.57 831.48 217.90
30 77 -984.84 -1452.47 -212.17 585.23 1245.30 -210.09
30 46 -322.79 -1253.86 -517.06 -886.27 -1102.06 -53.60
30 30 1136.36 3610.00 -216.08 -1816.19 -1525.62 374.40
31 35 359.62 1095.62 -312.50 -620.55 -1591.20 377.90

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

AreaElem Joint F11 F22 F12 M11 M22 M12


Kgf/m Kgf/m Kgf/m Kgf-m/m Kgf-m/m Kgf-m/m
31 16 -103.61 -448.49 -253.30 -1651.23 -2202.38 669.68
31 79 -312.28 -511.09 -230.88 -385.05 183.63 342.80
31 80 150.95 1033.02 -290.07 606.09 782.88 51.01
32 80 694.36 2844.39 -262.78 461.37 463.67 213.16
32 79 -829.71 -2235.85 -273.87 -311.50 265.62 179.14
32 81 -624.07 -2174.16 -276.53 -298.19 506.48 213.37
32 82 900.00 2906.08 -265.45 468.57 706.41 247.40
33 82 1456.25 4760.23 -263.29 587.55 931.36 368.95
33 81 -1117.83 -3820.04 -356.00 -374.61 423.39 90.04
33 21 -1791.30 -4022.08 -257.55 -1459.23 -1453.33 -150.66
33 36 782.78 4558.19 -164.84 -467.61 -930.69 128.25
34 36 506.71 3637.96 237.46 -459.04 -903.72 -148.07
34 21 -1507.39 -3075.70 630.62 -1444.51 -1402.64 130.03
34 83 -771.94 -2855.07 817.38 -370.46 443.06 -87.18
34 84 1242.15 3858.59 424.22 585.22 927.54 -365.29
35 84 146.40 206.08 761.47 471.65 719.02 -245.69
35 83 260.15 585.25 331.30 -297.07 517.66 -208.61
35 85 -323.36 410.20 332.72 -313.80 247.13 -175.27
35 86 -437.11 31.03 762.89 461.27 446.65 -212.35
36 86 -1572.83 -3754.69 334.81 609.48 775.14 -46.90
36 85 657.21 3678.76 1017.96 -388.96 162.16 -342.21
36 26 2553.18 4247.55 693.14 -1671.13 -2255.76 -681.68
36 37 323.15 -3185.90 10.00 -633.10 -1630.64 -386.37

PASO 12

Como software de diseño de los elementos, se adopta el software SAP2000, bajo la normativa del
ACI318-05/ IBC2003, y con los factores parciales de carga y resistencia, ajustados según NSR-10, como
en tabla siguiente.
Pag. 37 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- Diseño de elementos (SAP2000/ACI 318-05 / IBC 2003)

- Acero de Columnas

Frame DesignSect DesignType Status As-Long VMajRebar VMinRebar


mm2 mm2/mm mm2/mm
Pag. 38 de 54

82 C30x30 Column No Messages 4681.271 0.838 0.905


82 C30x30 Column No Messages 3924.975 0.838 0.905
83 C30x30 Column No Messages 4834.956 0.995 0.989
83 C30x30 Column No Messages 5088.888 1.006 0.989
84 C30x30 Column No Messages 4088.885 0.859 0.683
84 C30x30 Column No Messages 3581.913 0.859 0.683
85 D40 Column No Messages 3326.895 0.568 0.333

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame DesignSect DesignType Status As-Long VMajRebar VMinRebar


mm2 mm2/mm mm2/mm
85 D40 Column No Messages 1256.637 0.568 0.333
87 C35x35 Column No Messages 2438.029 0.573 0.749
87 C35x35 Column No Messages 2394.946 0.573 0.749
88 C30x40 Column No Messages 2651.099 0.786 0.449
88 C30x40 Column No Messages 2426.788 0.786 0.449
90 C35x35 Column No Messages 2747.533 0.564 0.292
90 C35x35 Column No Messages 1225.000 0.564 0.292
91 C30x30 Column No Messages 3662.397 0.814 0.689
91 C30x30 Column No Messages 3189.123 0.814 0.689
92 C30x30 Column No Messages 4322.919 0.923 0.983
92 C30x30 Column No Messages 4603.207 0.923 0.983
93 C30x30 Column No Messages 4579.461 0.777 0.911
93 C30x30 Column No Messages 4011.342 0.777 0.911
94 C35x35 Column No Messages 6101.015 1.133 1.391
94 C35x35 Column No Messages 5659.917 1.133 1.391
95 C35x35 Column No Messages 5013.394 1.267 1.117
95 C35x35 Column No Messages 4288.146 1.267 1.117
96 C35x35 Column No Messages 4342.949 1.029 1.009
96 C35x35 Column No Messages 3085.718 1.037 1.009
106 C30x30 Column No Messages 900.000 1.143 1.062
106 C30x30 Column No Messages 959.401 1.138 1.062
107 D40 Column No Messages 1256.637 0.536 0.333
107 D40 Column No Messages 2270.586 0.535 0.333
110 C35x35 Column No Messages 1225.000 0.581 0.292
110 C35x35 Column No Messages 2103.476 0.579 0.292
111 C30x30 Column No Messages 900.000 1.062 1.062
111 C30x30 Column No Messages 900.000 1.062 1.062
112 C30x40 Column No Messages 1200.000 0.834 0.333
112 C30x40 Column No Messages 1200.000 0.834 0.333
114 C30x30 Column No Messages 1587.282 0.332 0.458
114 C30x30 Column No Messages 1480.969 0.332 0.458
116 C30x30 Column No Messages 900.000 0.333 0.706
116 C30x30 Column No Messages 1116.442 0.332 0.706
117 C35x35 Column No Messages 1225.000 0.292 1.120
117 C35x35 Column No Messages 1225.000 0.292 1.120
118 C35x35 Column No Messages 1225.000 0.292 1.507
118 C35x35 Column No Messages 1225.000 0.292 1.500
161 C30x30 Column No Messages 2451.804 0.553 0.439
161 C30x30 Column No Messages 1552.277 0.553 0.477
162 C30x30 Column No Messages 2372.970 1.458 0.952
162 C30x30 Column No Messages 900.000 1.458 0.952

- Acero en Vigas

Frame DesignSect DesignType Status As-Top As-Bottom VRebar TLngArea


mm2 mm2 mm2/mm mm2
32 V30x40 Beam No Messages 862.329 556.567 0.487 0.000
Pag. 39 de 54

32 V30x40 Beam No Messages 544.727 493.147 0.433 0.000


33 V30x40 Beam No Messages 772.418 723.521 0.774 0.000
33 V30x40 Beam No Messages 1052.740 986.311 0.780 0.000
42 V30x40 Beam No Messages 777.497 393.342 0.546 417.571
42 V30x40 Beam No Messages 540.294 570.421 0.441 417.571
43 V30x40 Beam No Messages 542.446 564.529 0.440 417.571

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame DesignSect DesignType Status As-Top As-Bottom VRebar TLngArea


mm2 mm2 mm2/mm mm2
43 V30x40 Beam No Messages 771.090 395.371 0.540 417.571
44 V30x40 Beam No Messages 666.620 435.368 0.470 417.571
44 V30x40 Beam No Messages 539.305 506.888 0.418 417.571
45 V30x40 Beam No Messages 550.810 503.183 0.419 402.103
45 V30x40 Beam No Messages 655.674 438.761 0.461 402.103
56 V20x40 Beam No Messages 69.910 46.303 0.252 291.079
56 V20x40 Beam No Messages 115.516 57.332 0.276 291.079
57 V20x40 Beam No Messages 66.034 41.492 0.241 290.795
57 V20x40 Beam No Messages 112.437 55.815 0.265 290.795
58 V30x40 Beam No Messages 46.416 23.164 0.256 417.571
58 V30x40 Beam No Messages 123.626 61.498 0.291 417.571
59 V30x40 Beam No Messages 94.162 46.899 0.379 325.942
59 V30x40 Beam No Messages 188.169 93.351 0.414 325.942
60 V30x40 Beam No Messages 46.624 23.267 0.258 417.571
60 V30x40 Beam No Messages 124.458 61.910 0.293 417.571
61 V20x40 Beam No Messages 70.095 43.536 0.246 281.373
61 V20x40 Beam No Messages 113.647 56.411 0.270 281.373
62 V20x40 Beam No Messages 112.908 56.047 0.270 282.401
62 V20x40 Beam No Messages 69.299 44.146 0.246 282.401
63 V30x40 Beam No Messages 59.456 29.655 0.290 417.571
63 V30x40 Beam No Messages 140.176 69.682 0.325 417.571
64 V30x40 Beam No Messages 140.573 69.879 0.327 417.571
64 V30x40 Beam No Messages 62.406 31.123 0.292 417.571
65 V30x40 Beam No Messages 42.787 21.356 0.265 390.347
65 V30x40 Beam No Messages 130.493 64.895 0.300 390.347
66 V30x40 Beam No Messages 130.709 65.002 0.300 403.604
66 V30x40 Beam No Messages 42.442 21.184 0.265 403.604
67 V30x40 Beam No Messages 91.164 45.411 0.295 463.125
67 V30x40 Beam No Messages 134.228 66.742 0.330 463.125
68 V30x40 Beam No Messages 135.066 67.157 0.328 417.571
68 V30x40 Beam No Messages 88.001 43.841 0.294 417.571
70 V30x40 Beam No Messages 360.000 298.997 0.593 417.571
70 V30x40 Beam No Messages 360.000 360.000 0.535 417.571
71 V30x40 Beam No Messages 361.722 360.000 0.479 417.571
71 V30x40 Beam No Messages 370.849 362.080 0.461 417.571
97 VC30X40 Beam No Messages 325.000 320.647 0.282 313.034
97 VC30X40 Beam No Messages 458.751 301.803 0.327 313.034
98 VC30X40 Beam No Messages 552.474 357.659 0.367 371.374
98 VC30X40 Beam No Messages 565.646 455.142 0.352 371.374
99 VC30X40 Beam No Messages 348.057 351.217 0.308 333.467
99 VC30X40 Beam No Messages 558.500 325.000 0.363 333.467
100 VC30X40 Beam No Messages 523.856 341.565 0.324 354.239
100 VC30X40 Beam No Messages 455.668 325.000 0.317 354.239
101 VC30X40 Beam No Messages 325.000 263.499 0.354 403.425
Pag. 40 de 54

101 VC30X40 Beam No Messages 359.034 233.948 0.398 403.425


102 VC30X40 Beam No Messages 372.142 242.275 0.412 357.880
102 VC30X40 Beam No Messages 325.000 274.346 0.354 357.880
103 VC30X40 Beam No Messages 289.666 142.887 0.000 530.859
103 VC30X40 Beam No Messages 291.734 143.893 0.000 530.859
104 VC30X40 Beam No Messages 201.203 116.164 0.317 417.571

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame DesignSect DesignType Status As-Top As-Bottom VRebar TLngArea


mm2 mm2 mm2/mm mm2
104 VC30X40 Beam No Messages 176.822 108.540 0.304 417.571
105 VC30X40 Beam No Messages 245.228 134.862 0.011 678.147
105 VC30X40 Beam No Messages 212.305 198.900 0.011 678.147
119 V30x40 Beam No Messages 478.029 309.953 0.424 417.571
119 V30x40 Beam No Messages 206.193 298.994 0.369 417.571
120 V30x40 Beam No Messages 129.811 259.120 0.250 417.571
120 V30x40 Beam No Messages 0.000 103.472 0.250 417.571
121 V30x40 Beam No Messages 1.822 131.714 0.287 0.000
121 V30x40 Beam No Messages 360.000 186.401 0.342 0.000
122 V30x40 Beam No Messages 360.000 191.177 0.422 0.000
122 V30x40 Beam No Messages 85.346 90.238 0.385 0.000
123 V30x40 Beam No Messages 0.000 28.063 0.250 369.316
123 V30x40 Beam No Messages 144.298 219.418 0.250 369.316
124 V30x40 Beam No Messages 281.067 343.709 0.387 417.571
124 V30x40 Beam No Messages 404.557 360.000 0.424 417.571
125 V30x40 Beam No Messages 490.855 318.016 0.430 417.571
125 V30x40 Beam No Messages 216.308 311.621 0.376 417.571
126 V30x40 Beam No Messages 138.683 270.277 0.250 417.571
126 V30x40 Beam No Messages 0.000 104.128 0.250 417.571
127 V30x40 Beam No Messages 1.350 131.918 0.288 0.000
127 V30x40 Beam No Messages 360.000 189.700 0.342 0.000
128 V30x40 Beam No Messages 360.000 210.537 0.419 0.000
128 V30x40 Beam No Messages 87.680 92.430 0.382 0.000
129 V30x40 Beam No Messages 0.000 26.645 0.253 417.571
129 V30x40 Beam No Messages 182.712 247.451 0.250 417.571
130 V30x40 Beam No Messages 345.097 360.000 0.454 417.571
130 V30x40 Beam No Messages 483.278 410.377 0.491 417.571
131 V30x40 Beam No Messages 493.333 319.571 0.453 417.571
131 V30x40 Beam No Messages 200.958 221.629 0.404 417.571
132 V30x40 Beam No Messages 117.010 175.418 0.250 417.571
132 V30x40 Beam No Messages 48.527 151.042 0.250 417.571
133 V30x40 Beam No Messages 166.076 247.714 0.331 417.571
133 V30x40 Beam No Messages 416.809 355.201 0.380 417.571
134 V30x40 Beam No Messages 420.642 352.068 0.384 417.571
134 V30x40 Beam No Messages 167.539 245.524 0.335 417.571
135 V30x40 Beam No Messages 49.155 149.995 0.250 417.571
135 V30x40 Beam No Messages 116.063 177.061 0.250 417.571
136 V30x40 Beam No Messages 199.700 223.843 0.400 417.571
136 V30x40 Beam No Messages 489.413 317.109 0.450 417.571
137 V30x40 Beam No Messages 356.984 175.816 0.363 417.571
137 V30x40 Beam No Messages 48.914 199.686 0.313 417.571
138 V30x40 Beam No Messages 11.984 176.376 0.250 417.571
138 V30x40 Beam No Messages 0.000 140.255 0.250 417.571
139 V30x40 Beam No Messages 20.832 149.777 0.314 373.162
Pag. 41 de 54

139 V30x40 Beam No Messages 341.101 168.110 0.363 373.162


140 V20x40 Beam No Messages 247.600 161.490 0.452 295.047
140 V20x40 Beam No Messages 53.478 151.816 0.415 295.047
141 V20x40 Beam No Messages 98.863 182.829 0.188 0.000
141 V20x40 Beam No Messages 0.000 67.779 0.176 0.000
142 V20x40 Beam No Messages 0.000 103.491 0.287 0.000

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Frame DesignSect DesignType Status As-Top As-Bottom VRebar TLngArea


mm2 mm2 mm2/mm mm2
142 V20x40 Beam No Messages 160.863 79.601 0.324 0.000
143 V20x40 Beam No Messages 117.992 58.551 0.325 0.000
143 V20x40 Beam No Messages 51.661 76.633 0.300 0.000
144 V20x40 Beam No Messages 0.000 21.617 0.239 275.828
144 V20x40 Beam No Messages 122.035 164.090 0.224 275.828
145 V20x40 Beam No Messages 19.357 70.555 0.362 287.456
145 V20x40 Beam No Messages 183.717 153.894 0.387 287.456
146 V20x40 Beam No Messages 237.024 154.744 0.406 271.081
146 V20x40 Beam No Messages 32.838 82.452 0.372 271.081
147 V20x40 Beam No Messages 76.069 111.420 0.210 287.628
147 V20x40 Beam No Messages 38.369 104.753 0.190 287.628
148 V20x40 Beam No Messages 2.745 78.125 0.316 290.602
148 V20x40 Beam No Messages 202.055 104.365 0.350 290.602
149 V20x40 Beam No Messages 203.637 103.194 0.353 291.444
149 V20x40 Beam No Messages 3.311 78.744 0.319 291.444
150 V20x40 Beam No Messages 38.848 103.989 0.189 287.561
150 V20x40 Beam No Messages 75.471 112.458 0.207 287.561
151 V20x40 Beam No Messages 32.350 83.237 0.370 269.983
151 V20x40 Beam No Messages 235.068 153.495 0.404 269.983
152 V20x40 Beam No Messages 240.145 156.736 0.440 295.047
152 V20x40 Beam No Messages 47.999 144.898 0.403 295.047
153 V20x40 Beam No Messages 92.807 175.186 0.182 0.000
153 V20x40 Beam No Messages 0.000 67.347 0.169 0.000
154 V20x40 Beam No Messages 0.000 99.403 0.282 0.000
154 V20x40 Beam No Messages 159.672 79.017 0.319 0.000
155 V20x40 Beam No Messages 110.740 54.979 0.308 0.000
155 V20x40 Beam No Messages 41.729 69.656 0.283 0.000
156 V20x40 Beam No Messages 0.000 20.874 0.217 280.536
156 V20x40 Beam No Messages 96.406 145.367 0.197 280.536
157 V20x40 Beam No Messages 10.091 63.729 0.313 295.047
157 V20x40 Beam No Messages 154.227 132.076 0.338 295.047

Pag. 42 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

DEFLEXIONES

Combinaciones de carga, para revisión de deflexiones;

D+L; encontrando una deflexión máxima de: mm, con un factor de flujo plástico y de largo plazo igual a 2.78

Deflexión calculada = L/460, menor a la admisible; L/180 (No soportar elementos frágiles en voladizos)

CORREAS DE CUBIERTA

Correas que reciben la cubierta, estas correas tienen una luz máxima de 6.0m, y una aferencia para teja
termoacústica de 1.70m, por lo cual, Q=1.2DL+1.6LL+0.5WL = 120Kg/m², luego q=205kg/ml,
Mux:0.9Ton-m, y Muy: 0.08Ton-m

Debido a que las correas se configuran en perfiles conocidos como perlines, perfiles formados a partir
de láminas delgadas, dobladas en frío, esto nos obliga a calcular estos elementos, siguiendo los
lineamientos del título F.4 del NSR10.

Y como perfil correa se decide adoptar, un perfil sencillo en 1 perlin phr160x60x3

¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Material Type: A572 Grade 50, Fy=35.153 kgf/mm^2
Design Parameters:
Lx 6.0000 m Ly 2.0000 m Lt 2.0000 m
Kx 1.0000 Ky 1.0000 Kt 1.0000
Pag. 43 de 54

Cbx 1.0000 Cby 1.0000 ex 0.0000 mm


Cmx 1.0000 Cmy 1.0000 ey 0.0000 mm
Braced Flange: None k 0 kgf
Red. Factor, R: 0 Lm 2.0000 m

Loads: P Mx Vy My Vx

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

(kgf) (kgf-m) (kgf) (kgf-m) (kgf)


Entered 0.0 900.0 0.0 80.0 0.0
Applied 0.0 900.0 0.0 80.0 0.0
Strength 9626.2 1114.7 8536.0 296.8 5049.4

Effective section properties at applied loads:


Ae 885.37 mm^2 Ixe 3366637 mm^4 Iye 413352 mm^4
Sxe(t) 42083 mm^3 Sye(l) 22451 mm^3
Sxe(b) 42083 mm^3 Sye(r) 9939 mm^3

Interaction Equations
(P, Mx, My) 0.000 + 0.807 + 0.270 = 1.077 > 1.0
(P, Mx, My) 0.000 + 0.807 + 0.270 = 1.077 > 1.0
(Mx, Vy) Sqrt(0.457 + 0.000)= 0.676 <= 1.0
(My, Vx) Sqrt(0.065 + 0.000)= 0.254 <= 1.0

¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Axial Compression Strength
(KL/r)x=97.301, (KL/r)y=92.562
x=21.622 kgf/mm^2
y=23.892 kgf/mm^2
t=23.968 kgf/mm^2
Fe=14.585 kgf/mm^2
Fy=35.153 kgf/mm^2
c=1.5525
Fn=12.791 kgf/mm^2
Effective width calculations for part 1: Stiffened Channel
Element 1: Unstiffened, w=11 mm
f1=12.791 kgf/mm^2, f2=12.791 kgf/mm^2
=1
k=0.43
=0.14608
<0.673 (fully effective)
Element 2: Check for lip stiffener reduction
S=51.543
w/t < 0.328S (no lip reduction)
Element 2: Stiffened, w=42 mm
f1=12.791 kgf/mm^2, f2=12.791 kgf/mm^2
=1
k=4
=0.18288
=1
be=42 mm
b1=21 mm
b2=21 mm
b1+b2 > compression width (fully effective)
Element 3: Stiffened, w=142 mm
f1=12.791 kgf/mm^2, f2=12.791 kgf/mm^2
=1
Pag. 44 de 54

k=4
=0.6183
=1
be=142 mm
b1=71 mm
b2=71 mm
b1+b2 > compression width (fully effective)

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Element 5: Unstiffened, w=11 mm


f1=12.791 kgf/mm^2, f2=12.791 kgf/mm^2
=1
k=0.43
=0.14608
<0.673 (fully effective)
Element 4: Check for lip stiffener reduction
S=51.543
w/t < 0.328S (no lip reduction)
Element 4: Stiffened, w=42 mm
f1=12.791 kgf/mm^2, f2=12.791 kgf/mm^2
=1
k=4
=0.18288
=1
be=42 mm
b1=21 mm
b2=21 mm
b1+b2 > compression width (fully effective)

Ae=885.37 mm^2
Pn=11325 kgf
c=1.8, c=0.85

Flexural Strength about X-axis


y=23.892 kgf/mm^2
t=23.968 kgf/mm^2
Cb=1
Fy=35.153 kgf/mm^2
Fe=39.613 kgf/mm^2
Fc=29.431 kgf/mm^2
Effective width calculations for part 1: Stiffened Channel
Element 1: No compressive stress (fully effective)
Element 2: No compressive stress (fully effective)
Element 3: Stiffened, w=142 mm
f1=26.12 kgf/mm^2, f2=-26.12 kgf/mm^2
=1
k=24
=0.36071
=1
be=142 mm
ho=160 mm, bo=60 mm, ho/bo=2.6667
b1=35.5 mm
b2=71 mm
Compression width=71 mm
b1+b2 > compression width (fully effective)
Element 5: Unstiffened, w=11 mm
f1=26.12 kgf/mm^2, f2=22.073 kgf/mm^2
=0.84507
Pag. 45 de 54

k=0.48773
=0.19601
<0.673 (fully effective)
Element 4: Check for lip stiffener reduction
S=34.303
Ia=16.63 mm^4
Is=332.75 mm^4 > Ia (no lip reduction)

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

k=2.869
Element 4: Partially stiffened, w=42 mm
f=28.879 kgf/mm^2, k=2.869
=0.32446
<0.673 (fully effective)

Center of gravity shift: y=0 mm


Sc=42083 mm^3
Mn=1238.5 kgf-m
b=1.67, b=0.9

Distortional buckling for part 1 elements 4 to 5


Af=221.34 mm^2, Ixf=5245.2 mm^4, Iyf=80758 mm^4, Ixyf=-12073 mm^4
Xo=21.773 mm, Yo=2.2482 mm, Cwf=2626.6 mm^6, Jf=664.03 mm^4
hx=-35.264 mm, ho=160 mm
Lcr=392 mm
kfe=1296.8 kgf
kwe=1132 kgf
k=0 kgf
kfg=24.854 mm^2
kwg=2.2139 mm^2
Fd=89.729 kgf/mm^2
Mcrd=3848.2 kgf-m
My=1479.4 kgf-m
=0.62002
Mn=1479.4 kgf-m
b=1.67, b=0.9

Flexural Strength about Y-axis


x=21.622 kgf/mm^2
t=23.968 kgf/mm^2
Ctf=1
Fy=35.153 kgf/mm^2
Fe=64.852 kgf/mm^2
Fc=33.178 kgf/mm^2
Effective width calculations for part 1: Stiffened Channel
Element 1: Unstiffened, w=11 mm
f1=31.981 kgf/mm^2, f2=31.981 kgf/mm^2
=1
k=0.43
=0.23099
<0.673 (fully effective)
Element 2: Stiffened, w=42 mm
f1=25.998 kgf/mm^2, f2=-7.5084 kgf/mm^2
=0.2888
k=10.859
=0.15824
=1
be=42 mm
Pag. 46 de 54

ho=60 mm, bo=20 mm, ho/bo=3


b1=12.771 mm
b2=21 mm
Compression width=32.588 mm
b1+b2 > compression width (fully effective)
Element 3: No compressive stress (fully effective)
Element 5: Unstiffened, w=11 mm

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

f1=31.981 kgf/mm^2, f2=31.981 kgf/mm^2


=1
k=0.43
=0.23099
<0.673 (fully effective)
Element 4: Stiffened, w=42 mm
f1=25.998 kgf/mm^2, f2=-7.5084 kgf/mm^2
=0.2888
k=10.859
=0.15824
=1
be=42 mm
ho=60 mm, bo=20 mm, ho/bo=3
b1=12.771 mm
b2=21 mm
Compression width=32.588 mm
b1+b2 > compression width (fully effective)

Center of gravity shift: x=0 mm


Sc=9939.1 mm^3
Mn=329.76 kgf-m
b=1.67, b=0.9

Compression and Bending Interaction


x=1
y=1

Effective section at applied loads


Effective width calculations for part 1: Stiffened Channel
Element 1: No compressive stress (fully effective)
Element 2: No compressive stress (fully effective)
Element 3: Stiffened, w=142 mm
f1=15.707 kgf/mm^2, f2=-22.253 kgf/mm^2
=1.4168
k=37.065
=0.22508
=1
be=142 mm
ho=160 mm, bo=60 mm, ho/bo=2.6667
b1=32.15 mm
b2=71 mm
Compression width=58.756 mm
b1+b2 > compression width (fully effective)
Element 5: Unstiffened, w=11 mm
f1=26.739 kgf/mm^2, f2=23.798 kgf/mm^2
=0.89003
k=0.46991
=0.20204
<0.673 (fully effective)
Pag. 47 de 54

Element 4: Check for lip stiffener reduction


S=35.286
Ia=10.507 mm^4
Is=332.75 mm^4 > Ia (no lip reduction)
k=2.869
Element 4: Partially stiffened, w=42 mm
f=27.292 kgf/mm^2, k=2.869

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

=0.31542
<0.673 (fully effective)

Losa maciza de cubierta

Momento Mx-x Momento My-y

Momento de diseño: 2.2 Ton-m Momento de diseño: 2.3 Ton-m

Nuestra losa se configura en espesor 15cm, en calidad f’c:24.5MPa, y refuerzo en parrilla, 1No.4@15cm, que nos
arroja una capacidad de 2.7 Ton-m

- REACCIONES

Joint OutputCase F1 F2 F3 M1 M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
1 DEAD -73.14 -81.20 12352.31 0.00 0.00 0.00
1 LL -36.90 -8.56 325.61 0.00 0.00 0.00
1 EX -4958.40 -138.88 -7610.83 0.00 0.00 0.00
Pag. 48 de 54

1 EY 524.40 -5457.41 -8513.93 0.00 0.00 0.00


2 DEAD -94.00 -208.73 10008.42 0.00 0.00 0.00
2 LL -43.85 -23.11 224.99 0.00 0.00 0.00
2 EX -5994.12 -31.82 -2478.79 0.00 0.00 0.00
2 EY 484.08 -4530.57 -5798.38 0.00 0.00 0.00
3 DEAD -79.76 -100.09 6561.12 0.00 0.00 0.00
3 LL -35.45 -26.55 424.20 0.00 0.00 0.00

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Joint OutputCase F1 F2 F3 M1 M2 M3
Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
3 EX -5260.36 63.59 7086.43 0.00 0.00 0.00
3 EY 487.76 -4153.72 -8431.37 0.00 0.00 0.00
4 DEAD -60.07 -21.34 1563.02 0.00 0.00 0.00
4 LL -31.95 -21.42 1885.33 0.00 0.00 0.00
4 EX -4049.52 -41.81 -1939.60 0.00 0.00 0.00
4 EY 288.21 -1111.38 180.01 0.00 0.00 0.00
5 DEAD -10.74 -20.60 2703.95 0.00 0.00 0.00
5 LL -9.95 -27.31 111.34 0.00 0.00 0.00
5 EX -1722.96 33.01 4346.19 0.00 0.00 0.00
5 EY 203.03 -2908.97 -9559.04 0.00 0.00 0.00
6 DEAD -356.15 -30.73 9752.87 0.00 0.00 0.00
6 LL -54.78 -13.03 230.17 0.00 0.00 0.00
6 EX -7891.42 -285.17 -5263.60 0.00 0.00 0.00
6 EY 2.82 -10294.39 1.50 0.00 0.00 0.00
7 DEAD -91.06 -28.20 2488.37 0.00 0.00 0.00
7 LL -52.93 -28.01 -92.85 0.00 0.00 0.00
7 EX -10009.41 1.82 -6827.61 0.00 0.00 0.00
7 EY 4.06 -8300.92 6.73 0.00 0.00 0.00
8 DEAD -98.52 -26.83 5779.47 0.00 0.00 0.00
8 LL -41.81 -37.51 851.08 0.00 0.00 0.00
8 EX -8133.56 179.74 13130.40 0.00 0.00 0.00
8 EY 1.23 -7751.83 -5.50 0.00 0.00 0.00
10 DEAD 384.22 14.86 9228.43 0.00 0.00 0.00
10 LL 6.43 -51.86 920.22 0.00 0.00 0.00
10 EX -2259.99 86.08 -791.55 0.00 0.00 0.00
10 EY -87.56 -5736.91 12656.32 0.00 0.00 0.00
11 DEAD -75.47 48.85 12408.88 0.00 0.00 0.00
11 LL -21.02 -3.79 368.84 0.00 0.00 0.00
11 EX -5257.36 -183.59 -7406.10 0.00 0.00 0.00
11 EY -520.73 -5457.39 8519.50 0.00 0.00 0.00
12 DEAD -97.93 178.50 10004.94 0.00 0.00 0.00
12 LL -26.96 -6.56 264.22 0.00 0.00 0.00
12 EX -6334.00 28.40 -3127.23 0.00 0.00 0.00
12 EY -479.67 -4530.57 5799.39 0.00 0.00 0.00
13 DEAD -76.82 70.09 6707.15 0.00 0.00 0.00
13 LL -17.65 -15.64 534.55 0.00 0.00 0.00
13 EX -5512.26 141.40 7350.65 0.00 0.00 0.00
13 EY -483.75 -4153.62 8429.21 0.00 0.00 0.00
14 DEAD -74.98 -28.90 1549.84 0.00 0.00 0.00
14 LL -23.38 -25.97 1896.45 0.00 0.00 0.00
14 EX -4246.29 35.20 -1099.84 0.00 0.00 0.00
14 EY -290.93 -1095.20 -209.58 0.00 0.00 0.00
15 DEAD 269.94 -83.94 8085.16 0.00 0.00 0.00
15 LL 11.67 -27.31 636.27 0.00 0.00 0.00
15 EX -2182.14 27.35 3976.34 0.00 0.00 0.00
15 EY -194.15 -2931.95 5116.19 0.00 0.00 0.00
31 DEAD 154.48 -61.75 4188.53 0.00 0.00 0.00
31 LL -1.47 -63.36 323.21 0.00 0.00 0.00
31 EX -1687.75 84.68 655.14 0.00 0.00 0.00
Pag. 49 de 54

31 EY 61.19 -7084.72 -8191.05 0.00 0.00 0.00

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- ZAPATAS

Pag. 50 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Pag. 51 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

- VIGAS DE CIMENTACION

CALCULO DE ELEMENTOS NO ESTRUCTURALES

Grado de desempeño.

Ahora bien, realizando el cálculo para muros con columnetas de refuerzo cada 2.0m, y manejando una altura
máxima de muro de 2.5m, y un espesor de 15cm, tenemos,

𝑎𝑥 × 𝑎𝑝 1.25𝑆𝑎 × 2.5
Pag. 52 de 54

Fp = 𝑀𝑝 = 1650 = 970𝐾𝑔
𝑅𝑝 6

Rp=6.0, anclajes dúctiles, epóxicos, RamsetRedHead G5.


Pero Fp ≥ Aa I/2 Mp = (0.25 x 1.25)/2 (1650) = 260Kg.

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

Luego Fp = 970Kg.

Fp
hi
2/3(hi)

De acuerdo a lo anterior cortante en anclajes:


Vua: Fp= 1.0 Tons
Vn: 1.6 Ton (Anclaje de ½”, en concreto de 3000psi, y longitud de anclaje 12cm)
Longitud de anclaje:
8fd = 8(12.7) = 101mm, se adopta 12cm de longitud embebida de anclaje.

Y de acuerdo al fabricante.

Pag. 53 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374
Ing. Felipe Vera Condominio Altos de Oro Negro Agosto / 2014
Mat. 19202084481 CAU Salón Comunal
Orito - Putumayo

TARJETA PROFESIONAL

Pag. 54 de 54

Ing. Felipe Vera - Carrera 13 No. 52 A 16 Of. 602 - Tel: 3860161 - Email: fevera13@gmail.com – Cel: 3104584374