Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
DESIGN CRITERIA
DGCS Vol. 5
2.2.2 Assume slab thickness (Article 14.4.1.1). Unless approved by the Owner, the depth of a concrete deck, excluding
any provisions for grinding, grooving and sacrificial surface, should not be less than 175 mm.
Table 2-1 Traditional Minimum Depths for Constant Depth Superstructures (from Table 10.1.2.6-1)
Superstructure Minimum Depth (Including Deck)
2.2.3 Determine the location of the critical section for negative moment based on the girder top flange width
(11.3.2.1.5)
2.2.4 Determine Dead Load Moments.
• Moment due to self-weight of slab
where:
where:
ωslab = width of slab X thickness of wearing surface X γwearing surface S = clear span
length
2.2.5 Determine Live Load Positive and Negative Moments using Table A11-1.
Figure 2-1 Maximum Live Load Moments per Unit Width, N-mm/mm (from Table A11-1)
Note: Multiple presence factors and the dynamic load allowance are incorporated in the tabulated values.
Interpolation between the listed values may be used for the distances other than those listed in Table A11-1.
For methods of determining live load moments other than the use of Table A11-1, dynamic load allowance (Article
10.8) and multiple presence factors (Article 10.7.2.2) should be incorporated. The dynamic load allowance shall
not be applied to pedestrian loads or to the design lane load.
1 1.20
2 1.00
3 0.85
>3 0.65
Table 2-4 Load Combination and Load Factors (from Table 10.3-1)
DC Use one of these
DD at a time
Load Combination DW LL
EH IM
EV CE
ES WA WS FR TU TG SE
BR
EL EQ BL CT CV
PL
Limit State PS LS
CR
SH
Table 2-5 Load Factors for Permanent Loads, γp (from Table 10.3-2)
Load Factor
Type of Load
Max Min
DC: Component and Attachments 1.25 0.90
Load Factor
Type of Load
Max Min
DW: Wearing Surfaces and Utilities 1.50 0.65
Flexible Buried Structures other than Metal Box Culverts 1.95 0.90
2.2.8 Calculate factored flexural resistance, Mr at points of maximum moment (Article 12.4.3.2).
For conventional construction, resistance factor ɸ is tabulated in Table 2-6.
For sections in which the net tensile strain in the extreme tension steel at nominal resistance, ɛ t, is between the
limits for compression-controlled (ɛt = 0.002) and tension-controlled (ɛt = 0.005), ɸ may be linearly increased
from 0.75 to that for tension controlled sections as ɛ t increases from the compression-controlled strain limit to
0.005.
where:
c = distance from the extreme compression fiber to the neutral axis (mm)
dt = distance from the extreme compression fiber to the centroid of the extreme tension steel element (mm)
2.2.9 Compare factored flexural resistance versus maximum applied factored moment.
2.2.10 Calculate distribution reinforcement parallel to traffic (Article 14.4.3.1). Spacing of distribution
bar shall be:
where:
% distribution =
S = effective span length (in mm)
The area of reinforcement per mm, on each face and in each direction shall be:
2.3.2 Assume girder size based on span length and girder spacing (Table 10.1.2.6-1).
Table 2-7 Traditional Minimum Depths for Constant Depth Structures (from Table 10.1.2.6-1)
Superstructure Minimum Depth (Including Deck)
2.3.3 Determine Dead Load Moments, Shear and Dead Load Analysis using STAAD software or by manual calculation.
• Component and Attachments
- Slab, haunch, girder, diaphragm, post, railing, sidewalk
2.3.4 Determine Live Load Moments and Shear by STAAD Live Load Analysis or manual calculation. Vehicular live
loading on the roadways of bridges or incidental structures, designated HL-93, and shall consist of combination
of the:
or
Figure 2-3 Design Truck and Tandem Loads
2.3.5 Determine Live Load Distribution Factors for Moments (Table 11.3.2.2-5) and for Shear (Table
11.3.2.2-9).
Table 2-8 Common Deck Structures covered in Articles of Distribution Factor Method for Moment and Shear, and
Distribution Factor Method for Shear (from 11.3.2.2-2)
Supporting Components Type of Deck Typical Cross Section
where:
eg = distance between the centers of gravity of the basic beam and deck (mm)
• Determine LL distribution factors for moment (Table 11.3.2.2-5) and shear (Table 11.3.2.29) under single
lane and multi-lane loading.
Table 2-9 Distribution of Live Loads per Lane for Moment in Interior Beams (From Table 11.3.2.2-5)
Applicable
Crosssection from Range of
Type of Superstructure Distribution Factors
Table Applicability
11.3.2.2-2
Concrete Deck, Filled Grid, a, e, k and One Design Lane Loaded: 1100 S 4900
Partially Filled Grid, or also i, j S 0.4 S 0.3 Kg 0.1 110 ts 300
4300 L
Unfilled Grid Deck Composite with Reinforced if sufficientlyconnected to 0.06 Lts3
6000 L 73000
Concrete Slab on Steel or act as a unit Two or More Design Lanes Loaded:
g where: k 2.5 Nb 0.2 1.5 if sufficiently Two or More Design Lanes Loaded: 5 Nb 20
L J
h
displacement
at the interface
Skew 45°
Applicable
Crosssection from Range of
Type of Superstructure Distribution Factors
Table Applicability
11.3.2.2-2
NL
0.05 0.85
Nb N L b
Concrete DeckMultiple Steel BoxGirders on b, c Regardless of Number of Loaded
N
Lanes:0.425 0.5 NL 1.5
Table 2-10 Distribution of Live Load for Shear in Interior Beam (from Table 11.3.2.2-9)
Applicable Cross
One Design Two or More Design Lanes Range of
Type of Superstructure Section from
Lane Loaded Loaded Applicability
Table 11.3.2.2-2
6000 L
76 73000
Unfilled Grid Deck if sufficiently 00 0.2
3600 10700
Composite with Reinforced connected to
Concrete Slab on Steel or act as a unit 110 ts 300
Concrete Deck, Filled Grid, a, e, k and also S 2.0 1100 S 4900 Partially Filled Grid, or i, j 0.36
S S
Nb 4
1800 S 4000
d
6000 L73000
b I
� 5 ≤ N ≤ 20
L J ≥10 10 1010 J
Strength I Limit State: 1.0(dc * MDC + DW * MDW + LL* MLL1+IM) Service I
Limit State: 1.0( 1.0 * MDC + 1.0 * MDW + 1.0*MLL+IM)
Table 2-11 Load Combination and Load Factors (from Table 10.3-1)
DC Use one of these
DD at a time
Load Combination DW LL
EH IM
EV CE
ES WA WS FR TU TG SE
BR
EL EQ BL CT CV
PL
Limit State PS LS
CR
SH
Table 2-12 Load Factors for Permanent Loads, γp (from Table 10.3-2)
Load Factor
Type of Load
Max Min
DC: Component and Attachments 1.25 0.90
Flexible Buried Structures other than Metal Box Culverts 1.95 0.90
Load Factor
Type of Load
Max Min
ES: Earth Surcharge 1.50 0.75
2.3.7 Determine the stress limit immediately prior to transfer in the prestressing strands for the prestressing steel used
(12.6.3)
Figure 2-4 Stress Limits for Prestressing Tendons (from Table 12.6.3-1)
• Anchorage Set
The magnitude of the anchorage set shall be the greater of that required to control the stress in the
prestressing steel at transfer or that recommended by the manufacturer of the anchorage. The magnitude of
the set assumed for the design and used to calculate set loss shall be shown in the contract documents and
verified during construction.
• Friction
Losses due to friction between the prestressing tendons and the duct wall may be taken as:
Losses due to friction between the external tendons across a single deviator pipe may be taken as:
where:
x = length of a prestressing tendon from the jacking end to any point under consideration
Elastic Shortening
2.3.10 Determine stress in strands immediately after transfer as the stress prior to transfer minus instantaneous losses
2.3.11 Determine final stress in strands as stress immediately prior to transfer minus sum of instantaneous loss and
time dependent losses after transfer
2.3.12 Determine compression and tension stress limits at transfer
2.3.13 Determine final compression and tension stress limits at service
2.3.14 Calculate initial service moment stress in the top and bottom of the prestressed girder
2.3.15 Calculate final service moment stress in the top and bottom of the prestressed girder
2.3.16 Design for flexure under Service Limit State (Article 12.2.1).
2.3.17 Design for flexure under Strength Limit State (Article 12.2.3).
• Calculate main reinforcement of girder.
• Calculate factored flexural resistance, Mr at points of maximum moment (Article 12.4.3.2).
For sections in which the net tensile strain in the extreme tension steel at nominal resistance, ɛ t, is between
the limits for compression-controlled (ɛ t = 0.002) and tension-controlled (ɛt = 0.005), ɸ may be linearly
increased from 0.75 to that for tension controlled sections as ɛ t increases from the compression-controlled
strain limit to 0.005.
where:
c = distance from the extreme compression fiber to the neutral axis (mm) d t = distance from the extreme
compression fiber to the centroid of the extreme tension
The current provisions of LRFD eliminate the maximum reinforcement limit. A reduction in the factored
flexural resistance of the section is added instead. It states that below a net tensile strain in the extreme
tension steel of 0.005, as the tension reinforcement quantity increases, the factored resistance of prestressed
and nonprestressed sections is reduced to compensate for decreasing ductility with increasing overstrength.
The amount of non-prestressed tensile reinforcement shall be adequate to develop a factored flexural
resistance, Mr, at least equal to the lesser of:
• 1.33 times the factored moment required by the applicable strength load combination, or
• 1.2�𝑐𝑟 = �1�3𝑓𝑟𝑆𝑐
where:
Sc = section modulus for the extreme fiber of the composite section where tensile stress is caused
by externally applied loads (mm3)
2.3.18 Design for shear under Strength Limit State (Article 12.5).
• Determine bv and dv bv = effective web width taken as the minimum web width (in mm) d v = effective shear
depth
where:
ɸ = resistance factor
The spacing of the transverse reinforcement shall not exceed the maximum permitted spacing, s max,
determined as:
Case 1: If vu<0.125 f’c, smax is equal to lesser of 0.80 dv and 600 mm Case 2: If vu≥0.125
f’c, smax is equal to lesser of 0.40 dv and 300 mm
where:
|� ɸ�
𝑐𝑜𝑡�
The area of skin reinforcement Ask in mm2/m of height on each side face shall satisfy:
where:
• Calculate gross (Ig), cracked (Icr) and effective (Ie) moments of inertia of superstructure
3
where:
Dg = depth of girder
• Obtain immediate deflection at quarter points from STAAD results or manual calculation
• Compute long time deflection
Case 1: If Ig<Ie, long time deflection = 4* (immediate deflection)
NO Is the section
adequate?
YES
NO Is the section
adequate?
YES
BRIDGE SUBSTRUCTURE
7.3 Wingwalls
The wingwalls shall be arranged to support the road approach embankment above the
The wingwalls shall be of sufficient length to retain the roadway embankment to the
dimensions.
PIERS
Bridge piers transmit the load of the superstructure to the foundation material and provide
channel.
Types of Pier
Piers with solid shaft may be used in river crossing wherer debris is present and the
flow of the stream is fast. The foundation may be spread footing or pile type. Long
solid shaft piers may have poor seismic performance and should be avoided.
Piers with two columns may be used in normal bridgs when the river crossing has no
Piiers with single column(T-Bent) may be used to avoid skewed piers or in elevated
highways where the location of the foundation is restricted. The foundation may be
Pier consisting of piles taken up to the superstructure seat may be used for short
span bridges. This type of pier on driven piles(specially one row) should be avoided
when exposed length of pile exceed 2m unless a proper seismic analysis and design
are prepared.
15 FOUNDATIONS
The expected project requirement shall be analyzed to determine the type and
grade separation, support loads from bridge superstructures, provide for dry
Identify areas of geologic concern on the site and potential variability of local
geology.
scour locations.
Develop likely sequence and phases of construction and their effect on the
them
15.4.1 General
15.4.1.1 Application
reasonable cost
At locations where soil conditions would normally permit the use of spread footings
but the potential exists for scour, liquefaction or lateral spreading, in which case
Where right-of-way or other space limitations would not allow the use of spread
footings.
Where existing soil, contaminated by hazardous materials, must be removes for the
Center to center pile spacing should not be less than 762 mm or 2.5 pile
diameters. The distance from the side of any pile to the nearest edge of the pile cap
The tops of piles shall project at least 304.8 mm into to the pile cap after all
damaged materials gas been removed. If the pile is attached to the cap by
embedded bars or stands, the pile shall extend no less than 152.4 mm into the cap.
Where a reinforced concrete beam is cast-in place and used as bent cap supports by
piles, the concrete cover on the sides of the pile shall not be less than 152.4 mm.
cap satisfying the requirement of Article 12.10.4, the projection may be less than
152.4 mm.
select material, which does not obstruct pile penetration to the required depth.
Nominal axial resistance should be specified in the contract, type of pile and size of
Group interaction
Pile quantity estimation from estimated pile penetration required to meet nominal
performance criteria.
Verification of pile drivability to confirm that acceptable driving stresses and blow
counts can be achieved in an available driving system to meet all contact acceptance
criteria.
Ultimate pile capacity can be computed considering the soil resistance to pile during
the process of driving
There are several pile driving formula but almost all were based on the rational pile
formula
Other pile driving formula are the Janbu, Gates, Danish, Canadian national Building
Code.
Pile driving analysis (Hiley formula or similar) of all piles shall be correlated to the
other pile testing for pile driving control.
Modified Hiley’s Formula or any formula from brochures of the equipment used, shall be
adopted when the ratio of the weight of ram or hammer to weight of piles is greater than
one fourth(1/4)