Sei sulla pagina 1di 5

1.4 Electronic vs.

Pneumatic Instruments
H. L. FELDMAN (1969) R. K. KAMINSKI (1985) B. G. LIPTÁK (1995, 2005)

The debate concerning the relative merits of electronic versus of pneumatics. Naturally, when evaluating the advisability of
pneumatic instrumentation took place in the middle of the pneumatics, one must evaluate the options of analog elec-
20th century. As can be seen from the references for this sec- tronics, digital controllers with or without computers, distrib-
tion, most of the arguments were published during that period, uted control systems, and programmable logic controllers.
and little additional knowledge has been obtained in more The relative merits of analog vs. digital controls are covered
recent decades. Although the debate has been concluded, and in Section 1.1 of this volume. In the discussion here, refer-
the process control industry has decisively moved into the elec- ences are provided for further reading on the subject.
tronic and digital age, knowing the arguments — the advantages
and disadvantages of pneumatics versus electronics — can still THE OLD DEBATE
be educational. For this reason, and because pneumatics are
still used in the heating, ventilation, and air conditioning indus- In the debate some decades ago, some authors promoted
try and in the control valve portion of control loops, this section 1–4 5–9
electronics and others pneumatics. Table 1.4b summa-
has not been deleted from this handbook. rizes the views on both pneumatic and electronic instruments
that are expressed in the first nine referenced articles.
1–18
FACTORS TO BE CONSIDERED In the area of maintenance, the referenced literature does
not present convincing evidence that electronics guarantees
The main advantages of pneumatic systems over electronic reduced maintenance costs, but it does suggest that electronic
instruments lies in their safety in hazardous locations and in instrumentation is easier to maintain and that the life of elec-
the availability of qualified maintenance personnel. However, tronic instruments is longer. This is because of the wear on the
electronic systems are favored when computer compatibility, pivot points, the change in spring elasticity and diaphragm
long transmission distances, or very cold ambient conditions stretch in pneumatic designs. Maintenance publications, such
are expected, or when long-term maintenance is to be mini- as those of ISA, have contributed to making maintenance easier
mized (Figure 1.4a). by promoting modular component designs and self diagnostics.
Perhaps “Pneumatics versus High Technology” would The argument that pneumatic instruments need dry, clean
have been a better title for this section. If a process plant uses air but electronic systems do not is not correct because many
digital electronic control, it is very difficult to justify the use electronic control system include I/P (current-to-air) convert-
ers and electro-pneumatic valve positioners, which also require
14
dry and clean air. Deuschle, in his detailed cost comparison,
points out that the capacity required for the air compressor
Signal transmission distance
serving an electronic control system is about 60% of that
required for a pneumatic system. For a specific application,
Maintenance 17
Capital costs
the rating approach proposed by Tompkins can be considered
costs
for comparing the choice of pneumatics versus electronics.
Electronic
or
pneumatic
HVAC DAMPER ACTUATORS
?
Signal
The relative performance of electronic and pneumatic damper
Hazardous or safe
compatibility locations
actuators will be discussed below.

Pneumatic Actuators
Erection and maintenance
labor availability Pneumatic dampers are usually throttled over a 5 PSI spring
FIG. 1.4a range such as from 8 to 13 PSIG. Over this range, the damper
Electronic versus pneumatic systems. will move from the closed to the open position if there is no

41

© 2006 by Béla Lipták


42 General

TABLE 1.4b
Viewpoints Expressed on Electronics versus Pneumatics†
Features Electronics Superior Pneumatics Superior About Equal Remarks

Lower initial hardware cost 11,12,13,14,15,16,17*


Lower installation cost 10, 12, 13, 14 11 Ref. 13: Cost for either
varies all over the map
Lower total installed cost 12, 14, 15, 16*
Simpler system design 13, 15, 16*
Shorter check-out and start-up 11*
Shorter training period 11*
Higher dependability (reliability) 11, 15, 16*
Less affected by corrosive 13, 14, 17* Ref. 14: Air acts as a purge
atmospheres
Lower maintenance 12, 14, 17 11 * Ref. 12 cites
user experience
More compatible with 13, 14, 18*
control valves
Greater accuracy 11, 12, 16*
Superior dynamic response 11, 12, 13, 14, 15, 16, 17, Ref. 13: Normally, the fastest
18* response is not necessary
Better suited for long 11, 12, 13, 14, 15, 17, 18*
transmission distances
Superior computer capability 11, 12, 13, 14, 17, 18* Ref. 13: This is the primary
reason for selecting electronic
instruments

Numbers refer to the references listed at the end of this section.
*
An asterisk marks the preference of this author.

friction and no process load, which resist the movement of (FL ) is, say, 45 lb, that load will shift the throttling range of
the damper. Usually both are present. the damper by 3 PSIG. Depending on the failure position of
the damper, either the lower or the upper limit of the range
Hysteresis will be shifted. Consequently, if the process load (FL ) is 45 lb,
the throttling of a fail closed (FC) damper will not occur
Resistance forces (FR ) are present, not only because there is between 8 and 13 PSIG, but the damper will throttle between
friction between the stem and the hole through which it passes 5 and 13 PSIG. Similarly a fail open (FO) damper will throttle
but because there also is linkage stiffness and axle bind at the between 8 and 16 PSI.
rotary joints. Therefore, because the air is both the control
signal and the power source, its pressure must rise beyond
that required to break free and initiate movement, which Direct Coupled Electronic Actuator
results in overshoot. On the return stroke, the air signal pressure When a 2- to 10-VDC signal, generated by a 4- to 20-mADC
must drop below the spring force (FS ) before the spring will signal passing through a 500-ohm resistor, directly operates
overcome friction and start returning the damper. On an actu- the damper, performance is improved. This is because the
ator with a 4” stroke, this can result in a hysteresis of 1”. direct coupled electronic actuator has a resolution of 160:1,
28
allowing a positioning accuracy that can be as high as 120:1,
Spring Range Shift which is much superior to that of a pneumatic actuator. This
actuator uses an internal potentiometer to verify its position
When a process load (FL ) exists on the damper, it will shift with respect to the control signal. Consequently, it is unaf-
2
the throttling range of the damper. If the actuator area is 15 in. , fected by friction and process load forces and obeys the rela-
each pound of air signal pressure will generate 15 lb of added tionship between control signal and internal potentiometer
force on the diaphragm (FA ). Therefore, if the process load within +/–0.05 VDC.

© 2006 by Béla Lipták


1.4 Electronic vs. Pneumatic Instruments 43

Pneumatic vs. Electronic buses and networks require substantial engineering, partic-
ularly in the area of the interfacing of different suppliers’
If the pneumatic actuator has no positioner, the problems of products.
hysteresis and spring range shift will make its performance The transmission range of the electronic system can be
inferior to that of a direct coupled electronic design. If the a mile or more with no time lag. However, this feature is
pneumatic actuator is furnished with a positioner, its perfor- important only in a minority of control loops.
mance is improved. The amount of improvement depends on With regard to electrical noise, pneumatic instruments
the quality of the positioner, which will determine how close are, of course, immune. Electronic systems do experience
the loop performance will approach that of the electronic problems if shielding and grounding are inadequate. In recent
actuator. In any case, it is not likely that the positioning years, many manufacturers have designed instruments pro-
accuracy of a pneumatic actuator will approach or reach that tected against RFI (radio frequency interference).
of an electronic one.
The relative costs of the installed pneumatic and electronic
actuators are a function of the quality of the pneumatic posi- CONVERTERS
tioner used. If the positioner is of reasonably high quality, the
installed costs will be similar. A pneumatic system does not need additional hardware to
operate an air-operated control valve, whereas an I/P con-
verter must be installed if an electronic loop is to operate a
CONTROL SIGNALS pneumatic control valve. Because many transmitter outputs
are inherently electronic, pneumatic loops also require I/P
Putting together a pneumatic system can be relatively simple. converters for applications involving such transmitters on
The 3- to 15-PSIG (0.2- to 1.0-bar) air pressure signal range temperature, flow, or analytical measurements.
permits the teeing in of different manufacturers’ equipment Electronic systems are superior for data loggers, comput-
with very few problems. Other pressure ranges are seldom ers, distributed control, and/or programmable controller
used, except when there is reason to amplify the range, such applications. The pneumatic system would require I/Ps, P/Is,
as to 6 to 30 PSIG. and pneumatic scanning devices for these applications.
Much has been written about pneumatic transmission
19–23
lags. In this regard the electronic system is superior;
however, pneumatics systems have been successfully oper- ELECTRICAL SAFETY
ated with 250- to 500-ft (75- to 150-m) lines. When boosters
are used, distances of 1000 ft (300 m) and more can be In many process industries, some locations are hazardous
considered.
21, 22
The longer distances can be attained by spec- because of the presence of flammable gases, combustible
ifying such requirements as higher air capacities and the use dusts, and ignitable fibers. Therefore, equipment in hazardous
of volume boosters and 3/8 in. (9.38 mm) OD tubing. In order areas must be designed so that it will not cause a fire or
to reduce transmission distances, field-mounted controllers explosion (see Section 7.1 in Volume 1 of this handbook for
22 details). Manufacturers and users agree that pneumatic instru-
can also be used. According to Buckley, serious limitations
ments are inherently safe to use in installations in hazardous
on performance are caused by:
areas. On the other hand, analog and digital electronic instru-
ments require special protection features if they are to operate
1. Control valves without positioners in a hazardous environment.
2. The use of 1/4 in. (6.25 mm) rather than 3/8 in. (9.38 mm) If the area is Class I explosion-proof, where explosive
OD tubing or ignitable mixtures (in air) of flammable gases or vapors
3. Restrictions in manual/automatic switch blocks and constitute the hazard, the electronics must meet different require-
plug-in manifolds ments. Divisions 1 and 2 are defined below:
4. Inadequate valve positioner air capacities
5. Single-acting (instead of double-acting) positioners on Division 1: Location is likely to have flammable mix-
cylinder operators tures present under normal conditions or the oper-
6. Inadequate field air supplies ating process equipment is likely to require frequent
7. Multiple process lags maintenance
Division 2: Location is likely to have flammable mix-
The most common analog electronic control or trans- tures present only under abnormal conditions
mission signal is 4 to 20 mA DC. Considerable engineering
must go into all-electronic systems because of impedance The initial and installed costs for electronic systems will be
restrictions and polarity, power supply, shielding, and a function of the electrical classifications and of the selected
grounding requirements. In digital control systems, the approaches, which are used to meet the requirements of the

© 2006 by Béla Lipták


44 General

National Electrical Code. The choices include explosion- 21. Buckley, P. S., “Dynamic Design on Pneumatic Control Loops, Part
proof housings, purging, and intrinsically safe designs. For I: Analysis by Segments,” Instrumentation Technology, April 1975,
pp. 33–40.
Division 2, nonincendiary, nonarcing, and hermetically 22. Buckley, P. S., “Dynamic Design of Pneumatic Control Loops, Part
sealed equipment can also be considered. (Refer to Chapter 7 II: Application Principles and Practices,” Instrumentation Technology,
in the Measurement volume and to References 24 to 26 in June 1975, pp. 39–42.
this section for more information.) 23. Shinskey, F. G., Process Control Systems, 2nd ed., New York:
McGraw-Hill, 1979, pp. 38–40.
24. Magison, E. C., Electrical Instruments in Hazardous Locations, 3rd
ed., Research Triangle Park, North Carolina: Instrument Society of
THE MODERN DEBATE America, 1978.
25. Oudar, J., “Intrinsic Safety,” Measurements and Control, October
In selecting a control system one must examine the advan- 1981, pp. 153–160.
27 26. Garside, R., Intrinsically Safe Instrumentation: A Guide, Research
tages and drawbacks of both analog and digital alternatives,
Triangle Park, North Carolina: Instrument Society of America, 1982.
which was the topic of Section 1.1 in this chapter. Digital
27. Kaminski, R. K., “The Basic Control Choice,” Instrumentation Tech-
controls are compatible with computers, distributed control nology, July 1973, p. 41.
systems, programmable controllers, and digital controllers. 28. Belimo Aircontrols Inc., Electronic vs. Pneumatic Actuation, Dan-
bury, CT, 2003.

References
Bibliography
1. Mathewson, C. E., “Advantage of Electronic Control,” Instruments
and Automation, February 1955, pp. 258–269. Bailey, S. J., “Process Control 1979: A Year of Drastic Change, and More
2. “Sun Oil Opts for Electronic Instrumentation,” Canadian Controls To Come,” Control Engineering, October 1979.
and Instrumentation, February 1968, pp. 29–31. Bailey, S. J., “The Programmable Controller Is Finding Its In-Line Niche,”
3. “CPI Swing to Electronic Controls,” Chemical Week, April 13, 1968, Control Engineering, February 1980.
p. 53. Bowron, J., “DCS vs. PLC — Enough Already!” InTech, September 1992.
4. Hileman, J. R., “Practical Aspects of Electronic Instruments,” Instru- Cocheo, S., “How to Evaluate Distributed Computer Control Systems,”
mentation Technology, May 1968, pp. 43–47. Hydrocarbon Processing, June 1981.
5. “A Plug for Pneumatics,” Chemical Week, December 14, 1968, pp. 77 “The Configurations of Process Control: 1979,” Control Engineering,
and 79. March 1979.
6. Maas, M. A. “Pneumatics: It’s Not Dead Yet,” Instruments and Con- D’Abreo, F. A., “Replacing Installed Process Control Computers,” Instru-
trol Systems, November 1974, pp. 47–52. mentation Technology, July 1982.
7. Martin, R. L., “Simple Solutions to Control Problems,” Chemical Dartt, S. R., “Distributed Digital Control — Its Pros and Cons,” Chemical
Engineering, May 22, 1978, pp. 103–111. Engineering, September 6, 1982.
8. Bailey, S., “Pneumatic Process Controls: An Eternal Case of Bor- Giles, R. G., and Bullock, J. E., “Justifying the Cost of Computer Control,”
rowed Time,” Control Engineering, October 1978, pp. 39–42. Control Engineering, May 1976.
9. Farmer, E., “Pneumatics in a Digital World,” Instruments and Control Hall, J., and Kuhfeld, R., “Industry Leaders Look at 1982,” Instruments and
Systems, March 1979, pp. 31–35. Control Systems, January 1982.
10. Teed, J. T., “Comparative Installation Costs for Miniature Pneumatic Hickey, J., “The Interconnect Dilemma,” Instrument and Control Systems,
and Electronic Instruments,” Paper 1-LA61, Fall Instrument-Automa- December 1981.
tion Conference, Instrument Society of America, 1961. Kompass, E. J., “The Long-Term Trends in Control,” Control Engineering,
11. Palmer, O. J., “Instrumentation — Pneumatic Versus Electronic, September 1979.
Which Way To Buy?” Paper 5.4-4-64, 19th Annual Conference, Ledgerwood, B. K., “Trends in Control,” Control Engineering, May 1982.
Instrument Society of America, 1964. McAdams, T. H., “Digital Control at Half the Cost of Analog,” Instruments
12. Savage, H. L., “Electronic vs. Pneumatic Control Systems,” unpub- and Control Systems, April 1977.
lished paper, 1964. McNeil, E. B., “A User’s View of Instrumentation,” Chemical Processing,
13. Lynch, B., “Comparison of Electronic and Pneumatic Control Systems,” October 1982.
Paper presented at the 6th Annual Maintenance Management Sym- Merritt, R., “Large Control Systems: Big Price Tags but Even Bigger
posium, Instrument Society of America, 1971. Returns,” Instrument and Control Systems, December 1981.
14. Deuschle, R., “Pneumatic? Electronic? Which to Buy?” Instruments Miller, T. J., “New PCs Exemplify Trends to Smaller Size and Distributed
and Control Systems, February 1975, pp. 51–54. Network Compatibility,” Control Engineering, January 1983.
15. Lommatsch, E. A., “Pneumatic versus Electronic Instrumentation,” Morris, H. M., “Operator Convenience Is Key as Process Controllers Evolve,”
Chemical Engineering, June 21, 1976, pp. 159–162. Control Engineering, March 1981.
16. Hordeski, M., “When Should You Use Pneumatics, When Electron- Neal, D., “The Datalogger Moves into Control,” Instruments and Control
ics?” Instruments and Control Systems, November 1976, pp. 51–55. Systems, November 1982.
17. Tompkins, J., “Pneumatic or Electronic Instrumentation?” Instru- Pluhar, K., “International Manufacturers Offer Many Choices in Process
ments and Control Systems, January 1979, pp. 55–57. Control Systems,” Control Engineering, January 1980.
18. Marcovitch, M. J., “Whither Pneumatic and Electronic Instrumenta- Rapley, D. E., “How to Select Distributed Control and Data Systems,”
tion?” Chemical Engineering, Deskbook Issue, October 13, 1979, Instrumentation Technology, September 1980.
pp. 45–49. Sheridan, T. B., “Interface Needs for Coming Industrial Controls,” Instru-
19. Harriott, P., Process Control, New York: McGraw-Hill, 1964, mentation Technology, February 1982.
pp. 204–210. Smith, D. R., “Is Your Control Computer Obsolete?” Instruments and Control
20. Warnock, J. D., “How Pneumatic Tubing Size Influences Controlla- Systems, February 1982.
bility,” Instrumentation Technology, February 1967, pp. 37–43. “Special Report on Programmable Controllers,” Plant Services, June 1982.

© 2006 by Béla Lipták


1.4 Electronic vs. Pneumatic Instruments 45

Stanton, B.D., “Designing Distributed Computer Control Systems,” Warenskjold, G. A., “Microprocessor vs. Analog Control for the Nicholasville
Hydrocarbon Processing, June 1981. Water Treatment Facility,” Annual Conference, Instrument Society of
Stanton, B.D., “Reduce Problems in New Control System Design,” America, 1978.
Hydrocarbon Processing, August 1982. Williams, T. J., “Two Decades of Change — A Review of the 20-Year History
Thurston, C. W., “Experience with a Large Distributed Control System,” of Computer Control,” Control Engineering, September 1977.
Control Engineering, June 1979.

© 2006 by Béla Lipták

Potrebbero piacerti anche