FIRE ALARM SYSTEM CAUSE & EFF

ANNUNCIATION NOTIFICATION

ACTIVATION OF VOICE EVACUATION


ALARM INDICATION & BUZZER IN

ACTUATE EVACUATION SIGNAL

DISPLAY/ PRINT CHANGE OF


CAUSE← EFFECT↓

SIGNAL TYPE

STATUS
MFACP
ACTIVATION OF SMOKE DETECTOR FIRE X X X X
ACTIVATION OF SMOKE DETECTOR FIRE X X X X
ACTIVATION OF DUCT DETECTOR FIRE X X X X
ACTIVATION OF DUCT DETECTOR FIRE X X X X
ACTIVATION OF HEAT DETECTOR FIRE X X X X
ACTIVATION OF HEAT DETECTOR FIRE X X X X
ACTIVATION OF MANUAL CALL POINT FIRE X X X X
ACTIVATION OF MANUAL CALL POINT FIRE X X X X
OTHER STATUS
ELECTRIC FIRE PUMP - RUN FAULT X X
LOOP OPEN CIRCUIT FAULT X
LOOP SHORT CIRCUIT FAULT X
MASTER ALARM OPEN CIRCUIT FAULT X
MASTER ALARM SHORT CIRCUIT FAULT X
EARTH FAULT FAULT X
FIRE PUMP SYSTEM LOW BATTERY FAULT X
FIRE PUMP POWER FAILURE FAULT X
FIRE PUMP PHASE REVERSAL FAULT X X
SPRINKLER CONTROL VALVE- LVL. ROOF FAULT X X
SPRINKLER CONTROL VALVE- LVL.1 FAULT X X
SPRINKLER CONTROL VALVE-LVL. GRND FAULT X X
WATER FLOW- LVL. ROOF FAULT X X
WATER FLOW - LVL.1 FAULT X X
WATER FLOW -LVL. GRND FAULT X X

Fire Alarm Sequence of operations


1.The fire alarm system shall operate as follows:
A. Manual Operation - operation of manual fire alarm pull station shall:
1) Identify the individual station on the system control panel and sound the alarm bell at the control panel and remote alarm p
2) Sound audible alarms and actuate strobes
3) Transmit a signal to the central station
B. Activation of area smoke detector, heat detector and flow switch shall cause the following:
1) Provide operation as described for manual call point.
C. Activation of any supervisory circuit shall cause the following actions and indications:
1) Record the occurrence of the event, the time of occurrence and the device initiating the event.
D. Receipt of a trouble signal at the fire alarm control shall cause the following:
1)Display at the control panel and remote annunciator panels alphanumeric LCD display, the origin or the trouble condition rep
2) Activate trouble, audible and visual signals at the fire control panel and remote annunciator.
3) Record the occurrence of the event, the time of occurrence and the device initiating the event.
TRANSMIT FIRE ALARM SIGNAL TO

X
X
X
X
X
SUPERVISING STATION

TRANSMIT SUPERVISORY SIGNAL


NOTIFICATION

X
X
X
X
X
X
TO SUPERVISING STATION

TRANSMIT TROUBLE SIGNAL TO

X
X
X
X
X
X
X
SUPERVISING STATION

X
X
X
X
X
X
X
X
RELEASE ALL SLIDING DOOR

RELEASE MAGNETICALLY HELD

X
X
X
X
X
X
X
X
X
X
X
X
SMOKE DOORS

X
X
X
X
X
X
X
X
X
X
X
X UNLOCK EGRESS

X
X
X
X
X
X
X
X

SHUTDOWN ELEVATORS
SYSTEM CAUSE & EFFECT MATRIX FOR CCCC Housing Camp

CLOSE SMOKE/FIRE DAMPERS IN

X
X
X
RATED WALLS

X
X
X
X
X

ACTUATE SMOKE EXHAUST

ACTUATE SUPPRESSION SYSTEM


REQUIRED FIRE SAFETY CONTROL

PREDISCHARGE ALARMS

INITIATE SUPPRESSING SYSTEM


RELEASING SEQUENCE

ACTUATE GRAPHIC SYSTEM

X
X
X
X
X
X
X
X
X
X
X
X
X

DISPLAY FLOOR MAP


SUPPLEM
l panel and remote alarm panel.

or the trouble condition report.


X
X
X
PRESSURIZE STAIRWELLS

OTHER SYSTEM SHUTDOWN


PROCESS

ACTUATE EXTERIOR STROBE

X
X
X
X
X
X
X
X
X
X
X
SUPPLEMENTARY

RESPONSE POINT

X
X
X
X
X
X
X
X
X
X
X
SHUTDOWN AIR HANDLING UNIT