Sei sulla pagina 1di 53

GRID

ALSTOM Grid GmbH HIGH VOLTAGE PRODUCTS LILIENTHALSTR. 150 POST OFFICE BOX 60491 D-34123 KASSEL PHONE: 0561 502-0 FAX: 0561 502-2758

TYPE HYpact 145kV SBB

DARSTELLUNG:
LEISTUNGSSCHALTER STELLUNG AUS
FEDERENERGIEANTRIEB GESPANNT
STEUERSPANNUNG AUSGESCHALTET
LEISTUNGSSCHALTER DRUCKLOS
TRENNER/ERDER IN STELLUNG AUS

DIAGRAM:
CIRCUIT BREAKER IN OFF POSITION
CLOSING SPRING OF SPRING OPERATING MECHANISM CHARGED
CONTROL VOLTAGE OFF

A =20141610
CIRCUIT BREAKER WITHOUT PRESSURE SF6
DISCONNECTOR/EARTHING-SWITCH IN OFF POSITION

/ A00
=20141610
EN_01

APE2
A00
03.11.2015

SR 201416-10 Date : 03.11.2015


Drawn : Weber
Checked: Schlein
Norm :
DECKBLATT
00 00000 03.11.15 MW.
HYpact
COVER
NO. REVISION DATE NAME HYpact
1 2 3 4 5 6 7 8
COSTOMER- MANUFACTURER'S DRAWING- REVISION- DOCUMENT NUMBER SHEET DESIGNATION
DOCUMENT NUMBER DOCUMENT NUMBER STATE
DRAW.TY. ASSOCIATION SERIAL NO.
SR 201416-10 00 A =20141610 A00 DECKBLATT HYpact
COVER HYpact
A A
SR 201416-10 00 S =20141610 A01 INHALTSVERZEICHNIS HYpact
LEGEND HYpact
SR 201416-10 00 S =20141610 A02 INHALTSVERZEICHNIS HYpact
LEGEND HYpact
SR 201416-10 00 S =20141610 AW1 ÜBERSICHTSPLAN HYpact
LAYOUT PLAN HYpact
SR 201416-10 00 S =20141610 B01 SINGLE LINE DIAGRAM HYpact
SINGLE LINE DIAGRAM HYpact
SR 201416-10 00 S =20141610 D01 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 D02 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
B B
SR 201416-10 00 S =20141610 M01 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 M02 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 R01 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 R02 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 R03 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
Copyright as per DIN 34 to be observed!

SR 201416-10 00 S =20141610 R04 STROMLAUFPLAN HYpact


CIRCUIT DIAGRAM HYpact
C C
SR 201416-10 00 S =20141610 R05 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 X01 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAM HYpact
SR 201416-10 00 S =20141610 ZE1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZF1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZK1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZM1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
D D
SR 201416-10 00 S =20141610 ZQ1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZR1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZS1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZS2 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZS3 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610 ZY1 BETRIEBSMITTELPLAN HYpact
E LIST OF EQUIPMENT HYpact E
SR 201416-10 00 V =20141610 K01 KLEMMENANSCHLUSSPLAN-X2 HYpact
+S1 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 K02 KLEMMENANSCHLUSSPLAN-X2 HYpact
+S1 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 K03 KLEMMENANSCHLUSSPLAN-X2 HYpact
=20141610

+S1 TERMINAL DIAGRAM HYpact


SR 201416-10 00 V =20141610 K04 KLEMMENANSCHLUSSPLAN-X2 HYpact
EN_01

APE2

+S1 TERMINAL DIAGRAM HYpact


A01

SR 201416-10 00 V =20141610 K05 KLEMMENANSCHLUSSPLAN-X2 HYpact


+S1 TERMINAL DIAGRAM HYpact
03.11.2015

SR 201416-10 00 V =20141610 K30 STECKER -X22 ME4 HYpact


F +S1 TERMINAL DIAGRAM HYpact F

Date 03.11.2015 INHALTSVERZEICHNIS S =20141610


Drawn Weber GRID HYpact / A01
00 00000 03.11.15 MW. Checked Schlein LEGEND Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
COSTOMER- MANUFACTURER'S DRAWING- REVISION- DOCUMENT NUMBER SHEET DESIGNATION
DOCUMENT NUMBER DOCUMENT NUMBER STATE
DRAW.TY. ASSOCIATION SERIAL NO.
SR 201416-10 00 V =20141610 Q01 QUERVERBINDUNGSPLAN HYpact
+S1 CROSSCONNECTIONS HYpact
A A
SR 201416-10 00 V =20141610 Q02 QUERVERBINDUNGSPLAN HYpact
+S1 CROSSCONNECTIONS HYpact
SR 201416-10 00 V =20141610 K01 KLEMMENANSCHLUSSPLAN LS HYpact
+S4 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 K02 KLEMMENANSCHLUSSPLAN LS HYpact
+S4 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 K03 KLEMMENANSCHLUSSPLAN LS HYpact
+S4 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 K04 KLEMMENANSCHLUSSPLAN LS HYpact
+S4 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 K05 KLEMMENANSCHLUSSPLAN LS HYpact
+S4 TERMINAL DIAGRAM HYpact
B B
SR 201416-10 00 V =20141610 K10 STECKER -X2 LS HYpact
+S4 TERMINAL DIAGRAM HYpact
SR 201416-10 00 V =20141610 Q10 QUERVERBINDUNGSPLAN HYpact
+S4 CROSSCONNECTIONS HYpact
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610
EN_01

APE2
A02
03.11.2015

F F

Date 03.11.2015 INHALTSVERZEICHNIS S =20141610


Drawn Weber GRID HYpact / A02
00 00000 03.11.15 MW. Checked Schlein LEGEND Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ÜBERSICHTSPLAN
LAYOUT PLAN
A A

+S1 +S4

-Q91/-Q81 -X22 -W02/ 16x1,5mm² -X2

TRENNER/ERDER-ANTRIEB ME4
DISCONNECTOR/EARTHING-SWITCH
B B
Copyright as per DIN 34 to be observed!

C C

-Q0
LEISTUNGSSCHALTER
CIRCUIT BREAKER

D D

+S

WANDLERKASTEN
TERMINAL BOX
E E
=20141610
EN_01

APE2
AW1
03.11.2015

F F

Date 03.11.2015 ÜBERSICHTSPLAN S =20141610


Drawn Weber GRID HYpact / AW1
00 00000 03.11.15 MW. Checked Schlein LAYOUT PLAN Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SINGLE LINE DIAGRAM


A A

B B

+S4

-Q0 M
Copyright as per DIN 34 to be observed!

C C
+S1

-Q81 M -Q91

P1
D
CORE1:800-400-200/5,0.5 ,20VA@800/5,15VA@400/5,10VA@200/5 D
CT 1,2,3 CORE2:800-400-200/5,5P20,20VA@800/5,15VA@400/5,10VA@200/5
CORE3:800-400-200/5,5P20,20VA@800/5,15VA@400/5,10VA@200/5
CORE4:800-400-200/5,5P20,20VA@800/5,15VA@400/5,10VA@200/5
P2

VT 2 Winding 1:110000V:V3/110V:V3, 0.5, 30VA


E HYpact Winding 2:110000V:V3/110V:V3, 3P, 30VA E
=20141610
EN_01

APE2
B01
09.11.2015

F F

Date 03.11.2015 SINGLE LINE DIAGRAM S =20141610


Drawn Weber GRID HYpact / B01
00 00000 03.11.15 MW. Checked Schlein SINGLE LINE DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S4
HEIZUNG MOTORSTEUERUNG LEISTUNGSSCHALTER -Q0
HEATING MOTOR CONTROL CIRCUIT BREAKER -Q0

A A
L1 3L+
230V 50Hz 220V DC

-X1 500 -X1 450

-Q1 1

-F10 1 /ZQ1.1
2
/ZF1.1 -Q1 3
2
B /ZQ1.1 B
4

-X1 480 -X1 481 -X1 482

11
-S10
/ZS2.1 1
12
-S2
Copyright as per DIN 34 to be observed!

/ZS1.1
2
C C

A1
-M1
M
/ZM1.1

1 A2
-R2
/ZR1.1
2
3
-S2
D 1 /ZS1.1 D
-E10
/ZE1.1 4
2

-X1 484 -X1 485 -X1 486

-Q1 5

/ZQ1.1
E 6 E
=20141610

-X1 515 -X1 465


EN_01

APE2
D01

N 3L-
03.11.2015

-X1 PE 220V DC

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / D01
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S1
HEIZUNG MOTORSTEUERUNG TRENNER/ERDER -Q91/-Q81
HEATING MOTORDRIVE DISCONNECT/EARTHING SWITCH -Q91/-Q81
2L+
L1
230V 50HZ 220V DC
A -X2 400 -X2 414 415
A

1
-F2
-F10 1 /ZF1.1
2
/ZF1.1 4
2
-F2
/ZF1.1
3

-X2 900 -X2 901


B 1 1 1 1 B
-K3 -K4 -K1 -K2
/ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1
2 2 2 2

11
-S10
-X2 531
/ZS2.1
12
Copyright as per DIN 34 to be observed!

C 3/BL C
-M1
/ZM1.1
5/SW
1
-R1
/ZR1.1
2
-X2 532

1
-E10
/ZE1.1
2 4 4 4 4
D -K3 -K2 -K4 -K1 D
/ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1
3 3 3 3

-X2 553 -X2 555

6/WE

4/GR
1 2 -X2 533 -X2 534

M
-S7 /ZS3.1
5 5 5 5
-K4 -K1 -K3 -K2

-M1
/ZM1.1
/ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1
E 6 6 6 6 E

5
-F2
=20141610

/ZF1.1
6
EN_01

APE2

-X2 403 -X2 420 421


D02
03.11.2015

N 2L-

220V DC
F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / D02
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S4
EIN 1.AUS 2.AUS SF6-UEBERWACHUNG
CLOSE 1.TRIP 2.TRIP SF6-CONTROL AND MONITORING
+`EIN +`1.AUS +`2.AUS 1L+ 220V DC
-X2 13 220V DC 220V DC 220V DC
-X1 600
A A
-W02 13
-X1 603 -X1 601 600 -X1 602
-X22 13
+S1 -X1 610
-X2 548
13 13 -X1 630 -X1 688 -X1 730 -X1 788
-S4 -S5
21
-K1 /ZS2.1 /ZS2.1
/ZK1.1 14 14
22 1 3 11 9
R
0
22 L -S3 -S3 -S3 -S3
-K2 /ZS2.1 /ZS2.1 /ZS2.1 /ZS2.1
/ZK1.1 2 4 12 10
21
B 21 B
-K3
/ZK1.1
22
22
-K4
/ZK1.1
21
-X2 549

-X22 14 3
Copyright as per DIN 34 to be observed!

21 13 5
-W02 14 -K11 -K11 -S1.1
C /ZK1.1 /ZK1.1 /ZS1.1
1 13 3 15 3
C
22 14 6
-X2 14 11 -S1.1 -S1.1 -F1
P
-S1.1 /ZS1.1 /ZS1.1 /ZF1.1
/ZS1.1 2 14 4 16 4
12 4
A1
-Y4
/ZY1.1
A2 A1 A1
-Y1 -Y2
/ZY1.1 /ZY1.1 -X1 530
9 A2 A2
-S2
/ZS1.1
-X1 541 10 31 61
-K14 -K14
D 21 A1
/ZK1.1 /ZK1.1
A1
D
32 62
-K14 -K11 -K14
/ZK1.1 /ZK1.1 /ZK1.1
22 A2 A2

-X1 539

-X1 540

6 8
-S3 -S3
/ZS2.1 /ZS2.1
E 5 7 E
43
-S4
/ZS2.1
44
=20141610

-X1 625 -X1 645 -X1 745


EN_01

APE2

-X1 606 -X1 607


M01

-`EIN -`1.AUS -`2.AUS


03.11.2015

220V DC 220V DC 220V DC -X1 605

F 1L- 220V DC F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / M01
00 00000 03.11.15 MW. Checked Schlein AGK CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S1 CONTROL CIRCUIT - DISCONNECT/EARTHING SWITCH -Q91/-Q81
TRENNER/DISCONNECTING SWITCH -Q91 1L+ ERDER/EARTHING SWITCH -Q81
220V DC
EIN/CLOSE AUS/OPEN EIN/CLOSE AUS/OPEN
-X2 551 13 -X2 552 13 -X2 446 13 -X2 432 13
-S11 -S12 -S13 -S14
A /ZS2.1 /ZS2.1 /ZS2.1 /ZS2.1 A
14 14 14 14
-X2 890 -X2 892 -X2 894 -X2 896

-X22 1 -X22 3 -X22 4 -X22 6 -X22 7 -X22 9 -X22 10 -X22 12


-W02 1 -W02 3 -W02 4 -W02 6 -W02 7 -W02 9 -W02 10 -W02 12
-X2 1 -X2 3 -X2 4 -X2 6 -X2 7 -X2 9 -X2 10 -X2 12
+S4 -X2 410 411 +S4
-X1 900 -X1 902 -X1 903 -X1 905 -X1 906 -X1 908 -X1 909 -X1 911
25 27 13 15 17 19 21 23

R
0
L

R
0
L
-S3 -S3 -S3 -S3
/ZS2.1 /ZS2.1 /ZS2.1 /ZS2.1
26 28 14 16 18 20 22 24
B -X1 901 -X1 904 -X1 907 -X1 910 B

-X2 2 -X2 5 54 54 54 54 -X2 8 -X2 11


-W02 2 -W02 5 -K3 -K4 -K1 -K2 -W02 8 -W02 11
-X22 2 -X22 5 /ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1 -X22 8 -X22 11
53 53 53 53
-X2 431 -X2 433 -X2 430 -X2 547

A1 A1 A1 A1
-K3 -K4 -K1 -K2
Copyright as per DIN 34 to be observed!

/ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1


A2 A2 A2 A2
61 61 61 61
C -K4 -K3 -K2 -K1 C
/ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1
62 62 62 62
7 3 5 1
-S2 -S2 -S2 -S2
/ZS3.1 /ZS3.1 /ZS3.1 /ZS3.1
8 4 6 2

7 5
-S7 -S7
/ZS3.1 /ZS3.1
8 6

-X22 15 71 71
-K1 -K3
D -W02 15 /ZK1.1 /ZK1.1 D
72 72
-X2 15 72 for voltage interlocking on line side 72
-K2 -K4
+S4 /ZK1.1 /ZK1.1
-X1 81 71 -X2 538 -X2 904 71
-X2 445
16
-S1.3
/ZS1.1 -X2 441
15
-X1 82 95
-F2
/ZF1.1
96
-X2 16
E E
83 83 83 83
-W02 16 -K1 -K2 -K3 -K4
-X22 16 /ZK1.1 /ZK1.1 /ZK1.1 /ZK1.1
84 84 84 84
-X2 442
=20141610
EN_01

APE2

-X2 434 -X2 418 -X2 419


M02

220V DC 1L-
03.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / M02
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S4
MELDUNGEN LEISTUNGSSCHALTER -Q0
SIGNALISATION CIRCUIT BREAKER -Q0

A A

B B

-X1 850 -X1 890 -X1 676 677

-X1 532 -X1 533 -X1 534 -X1 535 -X1 536 -X1 537 -X1 538
Copyright as per DIN 34 to be observed!

C 1 C

1 13 7 21 11 34 36 39 11 5

R
0
L
-F1 -K14 -S2 -Q1 -F10 -S3 -S2
P
/ZF1.1 /ZK1.1 /ZS1.1 /ZQ1.1 /ZF1.1 /ZS2.1 /ZS1.1
2 14 8 22 12 33 35 40 12 6

D D

-X1 870 -X1 872 -X1 873 -X1 874 -X1 878 -X1 880 -X1 884 -X1 892 -X1 894 -X1 896 -X1 678 679
PROTECTIVE MOTOR SWITCHES

CIRCUIT BREAKER HEATING

AUTO RECLOSING LOCKOUT


OPERATING LOCKOUT SF6

CLOSING LOCKOUT DRIVE

E E
FUNKTIONSSPERRE SF6

MOTORSCHUTZSCHALTER

ABSICHERUNG HEIZUNG
EIN-SPERRE ANTRIEB
WARNUNG SF6
ALARM SF6

KU-SPERRE
REMOTE

LOCAL
=20141610

FERN

ORT

AUS
0
EN_01

APE2
R01
03.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / R01
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S4
FREIE HILFSSCHALTERKONTAKTE LEISTUNGSSCHALTER -Q0
FREE CONTACTS OFF AUXILIARY SWITCH CIRCUIT BREAKER -Q0

A A

B B

-X1 10 12 13 22 23 32 33 42 43 52 53 62 63 72 73 83 92 93 112 113 122 123 132 133


Copyright as per DIN 34 to be observed!

C C
9 9 1 11 3 13 5 15 7 9 1 11 3 13 5 7 9 1 11 3 13 5 15 7
-S1.1 -S1.2 -S1.3 -S1.4
/ZS1.1 /ZS1.1 /ZS1.1 /ZS1.1
10 10 2 12 4 14 6 16 8 10 2 12 4 14 6 8 10 2 12 4 14 6 16 8

D D
-X1 19 11 14 21 24 31 34 41 44 51 54 61 64 71 74 84 91 94 111 114 121 124 131 134

E E
=20141610
EN_01

APE2
R02
03.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / R02
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S1

BETRIEBSART ÜBERLAUFSCHUTZ RESERVEKONTAKTE ERDER -Q81


MODE LIMIT SWITCH SPARE CONTACTS EARTHING SWITCH -Q81
A A

-X2 438 107 127 -X2 21 31 41 51 61 71 73 81 83 91 93 101 103 111 113

B B

11
-S7
/ZS3.1
12
Copyright as per DIN 34 to be observed!

C C
10 12 14 16 23 21 31 29 39 37 47 45 55 53 63 61 103 97 111 105 119 113 127 121
-S2
/ZS3.1
9 11 13 15 24 22 32 30 40 38 48 46 56 54 64 62 104 98 112 106 120 114 128 122

1
-S8
D /ZS3.1 D
2

E E

-X2 439 108 118 128 -X2 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114
=20141610
EN_01

APE2
R03
10.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / R03
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S1

RESERVEKONTAKTE TRENNER -Q91


A SPARE CONTACTS DISCONNECTOR SWITCH -Q91 A

-X2 121 131 141 151 161 171 173 181 183 191 193 201 203 211 213

B B
Copyright as per DIN 34 to be observed!

C C
19 17 27 25 35 33 43 41 51 49 59 57 99 101 107 109 115 117 123 125
-S2
/ZS3.1
20 18 28 26 36 34 44 42 52 50 60 58 100 102 108 110 116 118 124 126

D D

E -X2 122 124 132 134 142 144 152 154 162 164 172 174 182 184 192 194 202 204 212 214 E
=20141610
EN_01

APE2
R04
10.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / R04
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
+S1
KONTAKT DIAGRAMM
MELDUNGEN TRENNER/ERDER -Q91/-Q81 HILFSSCHALTER
CONTACT SHEMA
SIGNALISATION DISCONNECTING-/EARTHING SWITCH -Q91/-Q81 AUXILIARY SWITCH
A A

-X2 221 223 231 233 241 243 251 253 -X2 539 -X2 902 ERDER TRENNER
EARTH.-SWITCH DISC.-SWITCH
EIN AUS EIN
CLOSE OPEN CLOSE
B B
HAUPTKONTAKT
MAIN CONTACT
1-2,81-82,89-90

3-4,85-86,93-94

5-6
Copyright as per DIN 34 to be observed!

7-8
C C
9-10,13-14
81 83 85 87 89 91 93 95 97 11
-S2 -F2 -F10
11-12,15-16
/ZS3.1 /ZF1.1 /ZF1.1
82 84 86 88 90 92 94 96 98 12 21-22,29-30,37-38
45-46,53-54,61-62
69-70,77-78

23-24,31-32,39-40
47-48,55-56,63-64
71-72,79-80

D 17-18,25-26,33-34 D
41-42,49-50,57-58
65-66,73-74

19-20,27-28,35-36
43-44,51-52,59-60
67-68,75-76

83-84,91,92

87-88,95-96
-X2 222 224 232 234 242 244 252 254 -X2 898 -X2 903
E E
MOTORSCHUTZ TRENNER/ERDER
PROTECTIVE MOTOR SWITCH

CIRCUIT BREAKER HEATING


=20141610

ABSICHERUNG HEIZUNG
EN_01

APE2
R05
03.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / R05
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
FREIE KLEMMEN/STECKERKONTAKTE
FREE TERMINALS/PLUG CONTACTS

A A
TRENNER/ERDERANTRIEB LS-ANTRIEB
DISCONNECTOR/EARTHING SWITCH CIRCUIT BREAKER
-Q91/-Q81 -Q0
+S1 +S4

PE
-X2 538 PE PE
B B

-X1 451 466 516 608 609 611

-X1 626 631 646 750 700 731


904
-X1 746 705 501 483 604

-X1 898
-X2 PE PE
Copyright as per DIN 34 to be observed!

PE
C C

-X1 PE

PE

D D
-X2 PE
-X2 PE -X2 PE

-X22 PE

E E
=20141610
EN_01

APE2
X01
05.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610


Drawn Weber GRID HYpact / X01
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

2 LAMPE
LAMP
MANUF. :
ORD.NR. :
TYPE:11W/E14

A A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

2
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
BELEUCHTUNG -Q0 LIGHTING -Q0 +S4 -E10 /D01.3
BELEUCHTUNG-Q91/-Q81 LIGHTING -Q91/-Q81 +S1 -E10 /D02.3

B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610
EN_01

APE2
ZE1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZE1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 SF6-DICHTEWAECHTER
SF6-DENSIMETER
MANUF. : WIKA
ORD.NR. :
TYPE:233.52.100

A A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 3
P
2 4
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
SF6-UEBERWACHUNG SF6-CONTROL +S4 -F1 /R01.2 /M01.7

1 UEBERLASTRELAIS
OVERLOADRELAY
MANUF. : ALLEN BRADLEY
ORD.NR. :
TYPE:193-TA
B B
1 3 5 95 97

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

2 4 6 96 98

APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION


Copyright as per DIN 34 to be observed!

MOTORSCHUTZ MOTOR PROTECTION -Q91/-Q81 +S1 -F2 /D02.7 /D02.7 /D02.7 /M02.2 /R05.4

C C

2 SICHERUNGSAUTOMAT
FUSE
MANUF. : GE
ORD.NR. :
TYPE:EP61

16A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 12 14

D 2 11 D
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
HEIZUNG -Q91/-Q81 HEATING -Q91/-Q81 +S1 -F10 /D02.2 /R05.5
HEIZUNG -Q0 HEATING -Q0 +S4 -F10 /D01.2 /R01.3

E E
=20141610
EN_01

APE2
ZF1
05.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZF1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 SCHUETZ
CONTACTOR
MANUF. : ALLEN BRADLEY
ORD.NR. :
TYPE:700-K22Z

A A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

A1 13 21 31 43

A2 14 22 32 44
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
PUMPVERHINDERUNG -Q0 ANTI-PUMPING -Q0 +S4 -K11 /M01.2 /M01.2 /M01.2

B 1 SCHUETZ
CONTACTOR
MANUF. : ALLEN BRADLEY
ORD.NR. :
TYPE:700-K22Z+100-KFA22 B

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

A1 13 21 31 43 53 61 71 83

A2 14 22 32 44 54 62 72 84
Copyright as per DIN 34 to be observed!

APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION


FU-SPERRE SF6 -Q0 OPERATION LOCKOUT SF6 -Q0 +S4 -K14 /M01.7 /R01.2 /M01.2 /M01.5 /M01.6 .
C C
4 SCHUETZ
CONTACTOR
MANUF. : ALLEN BRADLEY
ORD.NR. :
TYPE:100-K09+100-KFA22

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

A1 1 3 5 21 53 61 71 83

A2 2 4 6 22 54 62 72 84
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
D D
ERDERSTEUERUNG -Q81 EARTH SWITCH CONTROL -Q81 +S1 -K1 /M02.5 /D02.7 /D02.7 /D02.4 /M01.1 /M02.4 /M02.6 /M02.2 /M02.5
ERDERSTEUERUNG -Q81 EARTH SWITCH CONTROL -Q81 +S1 -K2 /M02.6 /D02.7 /D02.4 /D02.7 /M01.1 /M02.5 /M02.5 /M02.2 /M02.6
TRENNERSTEUERUNG-Q91 DISCONNECTOR CONTROL -Q91 +S1 -K3 /M02.2 /D02.6 /D02.4 /D02.7 /M01.1 /M02.4 /M02.3 /M02.5 /M02.6
TRENNERSTEUERUNG-Q91 DISCONNECTOR CONTROL -Q91 +S1 -K4 /M02.3 /D02.6 /D02.7 /D02.4 /M01.1 /M02.4 /M02.2 /M02.5 /M02.6

E E
=20141610
EN_01

APE2
ZK1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZK1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 MOTOR
MOTOR
MANUF. : GROSCHOPP
ORD.NR. :
TYPE:KE70-40

A 1000W A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER
A1
M
A2
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
FEDERKRAFTANTRIEB SPRING OPERATING -Q0 +S4 -M1 /D01.6

1 MOTOR
MOTOR
MANUF. : GROSCHOPP
ORD.NR. :
TYPE:KE50-30
B B
250W

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER
4 3
M
6 5
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
Copyright as per DIN 34 to be observed!

MOTORANTRIEB MOTORDRIVE ME4 -Q91/-Q81 +S1 -M1 /D02.5 /D02.7

C C

D D

E E
=20141610
EN_01

APE2
ZM1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZM1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 MOTORSCHUTZSCHALTER MANUF. : GE
ORD.NR. :
TYPE:Mbs25

A PROTECTIVE MOTOR SWITCHES A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 3 5 13 21

2 4 6 14 22
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
MOTORSCHUTZSCHALTER PROTECTIVE MOTOR SWITCHES-Q0 2A +S4 -Q1 /D01.6 /D01.6 /D01.6 /R01.3

B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610
EN_01

APE2
ZQ1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZQ1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

2 HEIZPATRONE
HEATING COIL
MANUF. : JEKA
ORD.NR. :
TYPE:16x250

A 80W A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER
1

2
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
HEIZUNG ANTRIEB HEATING DRIVE -Q0 +S4 -R2 /D01.2
HEIZUNG ANTRIEB HEATING DRIVE -Q91/-Q81 +S1 -R1 /D02.2

B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610
EN_01

APE2
ZR1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZR1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 HILFSSCHALTER
AUXILIARY SWITCH
MANUF. : ALSTOM
ORD.NR. :
TYPE:CR90V

A A
DC 220V 2A 20ms
AC 220V 15A : :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 3 5 7 9 11 13 15

2 4 6 8 10 12 14 16
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
SCHALTERSTEUERUNG BREAKER CONTROL -Q0 +S4 -S1.1 /M01.5 /M01.6 /M01.3 . /R02.2 /M01.2 /M01.5 /M01.6

4 HILFSSCHALTER
AUXILIARY SWITCH
MANUF. : ALSTOM
ORD.NR. :
TYPE:CR90V
B B

DC 220V 2A 20ms
AC 220V 15A : :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 3 5 7 9 11 13 15

2 4 6 8 10 12 14 16
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
Copyright as per DIN 34 to be observed!

SCHALTERSTEUERUNG BREAKER CONTROL -Q0 +S4 -S1.2 /R02.2 /R02.2 /R02.3 /R02.3 /R02.2 /R02.2 /R02.3 /R02.3
SCHALTERSTEUERUNG BREAKER CONTROL -Q0 +S4 -S1.3 /R02.3 /R02.4 /R02.4 /R02.4 /R02.3 /R02.4 /R02.4 /M02.1
C C
SCHALTERSTEUERUNG BREAKER CONTROL -Q0 +S4 -S1.4 /R02.5 /R02.5 /R02.5 /R02.6 /R02.5 /R02.5 /R02.5 /R02.5
MOTORABSTEUERSCHALT. MOTOR CONTROL SWITCH +S4 -S2 /D01.6 /D01.6 /R01.7 /R01.2 /M01.2 /R01.6 . .

D D

E E
=20141610
EN_01

APE2
ZS1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZS1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 UMSCHALTER
CHANGE-OVER-SWITCH
MANUF. : K&N
ORD.NR. :
TYPE:CH10
A A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39

R
0
L
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION

/M01.2

/M01.2

/M01.2

/M01.2

/M01.5

/M01.4

/M02.3

/M02.3

/M02.5

/M02.6

/M02.6

/M02.7

/M02.2

/M02.3

/R01.5

/R01.5

/R01.6
B FERN-ORT-UMSCHALTER REMOTE-LOCAL-SWITCH +S4 -S3 B

6 TASTER
PUSH BUTTON
MANUF. : GE
ORD.NR. :
TYPE:BFDGO
Copyright as per DIN 34 to be observed!

C C
: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

13 21 31 43

14 22 32 44
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
TASTER EIN Q0 P.BUTTON CLOSING Q0 +S4 -S4 /M01.2 /M01.2
TASTER AUS Q0 P.BUTTON TRIPPING Q0 +S4 -S5 /M01.4
TASTER EIN Q91 P.BUTTON CLOSING Q91 +S1 -S11 /M02.3
TASTER AUS Q91 P.BUTTON TRIPPING Q91 +S1 -S12 /M02.3

D TASTER EIN Q81 P.BUTTON CLOSING Q81 +S1 -S13 /M02.6


D
TASTER AUS Q81 P.BUTTON TRIPPING Q81 +S1 -S14 /M02.7

2 KONTAKTELEMENT
CONTACT MODULE
MANUF. : MARQUARDT
ORD.NR. :
TYPE:BR1117.201

E : : E
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

11

12
=20141610

APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION


BELEUCHTUNG -Q0 LIGHTING -Q0 +S4 -S10 /D01.3
EN_01

APE2

BELEUCHTUNG-Q91/-Q81 LIGHTING -Q91/-Q81 +S1 -S10 /D02.3


ZS2
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZS2
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 HILFSSCHALTER
AUXILIARY SWITCH
MANUF. :
ORD.NR. :
TYPE:RXD10R

A A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION

101
103
105
107
109
111
113
115
117
119
121
123
125
127
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
85
87
89
91
93
95
97
99
3
1

7
9
5

B B

100
102
104
106
108
110
112
114
116
118
120
122
124
126
128
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
4
2

8
6
/M02.6
/M02.3
/M02.5
/M02.2
/R03.1
/R03.2
/R03.2
/R03.2
/R04.3
/R04.3
/R03.3
/R03.3
/R04.3
/R04.3
/R03.4
/R03.3
/R04.4
/R04.4
/R03.4
/R03.4
/R04.4
/R04.4
/R03.5
/R03.4
/R04.5
/R04.5
/R03.5
/R03.5
/R04.5
/R04.5
/R03.6
/R03.5

/R05.1
/R05.1
/R05.2
/R05.2
/R05.2
/R05.2
/R05.3
/R05.3
/R03.6
/R04.5
/R04.6
/R03.6
/R03.6
/R04.6
/R04.6
/R03.6
/R03.7
/R04.6
/R04.7
/R03.7
/R03.7
/R04.7
/R04.7
/R03.7
.
.
.
.
.
.
.
.
STEUERUNG CONTROL ME4 -Q91/-Q81 +S1 -S2
Copyright as per DIN 34 to be observed!

1 HILFSSCHALTER
AUXILIARY SWITCH
MANUF. :
ORD.NR. :
TYPE:RUS20
C C

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER
1 3 5 7 9 11 13 15 17 19 21 23 25 27

2 4 6 8 10 12 14 16 18 20 22 24 26 28

APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION

STEUERUNG CONTROL ME4 -Q91/-Q81 +S1 -S7 /D02.5 . /M02.5 /M02.2 /R03.1

D D

1 ENDSCHALTER
LIMIT SWITCH
MANUF. : GESSMANN
ORD.NR. :
TYPE:SO 1.10

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

E E
2
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
STEUERUNG CONTROL ME4 -Q91/-Q81 +S1 -S8 /R03.2
=20141610
EN_01

APE2
ZS3
05.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZS3
00 00000 03.11.15 MW. Checked Schlein LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

3 SPULE
COIL
MANUF. : ALSTOM
ORD.NR. :
TYPE:49.102.110-XX

A 340W A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

A1

A2
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
AUSLOESESPULE 1.AUS TRIP COIL 1.OFF +S4 -Y1 /M01.5
AUSLOESESPULE 2.AUS TRIP COIL 2.OFF +S4 -Y2 /M01.6
AUSLOESESPULE EIN CLOSE COIL ON +S4 -Y4 /M01.2
B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610
EN_01

APE2
ZY1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610


Drawn Weber GRID HYpact / ZY1
00 00000 03.11.15 MW. Checked Schlein AGK LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X2 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/X01.3 PE
/R03.3 Q -S2 21 21
/R03.3 -S2 24 22
/R03.3 -S2 22 24
/R03.3 Q -S2 29 31
/R03.3 -S2 32 32
/R03.4 -S2 30 34
B /R03.4 Q -S2 37 41 B
/R03.4 -S2 40 42
/R03.4 -S2 38 44
/R03.4 Q -S2 45 51
/R03.4 -S2 48 52
/R03.5 -S2 46 54
/R03.5 Q -S2 53 61
Copyright as per DIN 34 to be observed!

/R03.5 -S2 56 62
C /R03.5 -S2 54 64 C
/R03.5 -S2 63 71
/R03.5 -S2 64 72
/R03.6 -S2 61 73
/R03.6 -S2 62 74
/R03.6 -S2 103 81
/R03.6 -S2 104 82
/R03.6 -S2 97 83
D /R03.6 -S2 98 84 D

/R03.6 -S2 111 91


/R03.6 -S2 112 92
/R03.6 -S2 105 93
/R03.6 -S2 106 94
/R03.7 -S2 119 101
/R03.7 -S2 120 102
/R03.7 -S2 113 103
E /R03.7 -S2 114 104 E

/R03.1 Q -S2 10 107


/R03.1 -S2 9 108
=20141610+S1

/R03.7 -S2 127 111


/R03.7 -S2 128 112
EN_01

APE2

/R03.7 -S2 121 113


K01

/R03.7 -S2 122 114


05.11.2015

/R03.2 -S2 11 118


F /R04.3 Q -S2 17 121
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X2 V =20141610


Drawn Weber GRID HYpact +S1 / K01
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X2 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/R04.3 -S2 20 122
/R04.3 -S2 18 124
/R03.2 Q -S2 14 127
/R03.2 -S8 2 128
/R04.3 Q -S2 25 131
/R04.3 -S2 28 132
/R04.3 -S2 26 134
B /R04.4 Q -S2 33 141 B
/R04.4 -S2 36 142
/R04.4 -S2 34 144
/R04.4 Q -S2 41 151
/R04.4 -S2 44 152
/R04.4 -S2 42 154
/R04.5 Q -S2 49 161
Copyright as per DIN 34 to be observed!

/R04.5 -S2 52 162


C /R04.5 -S2 50 164 C
/R04.5 -S2 59 171
/R04.5 -S2 60 172
/R04.5 -S2 57 173
/R04.5 -S2 58 174
/R04.5 -S2 99 181
/R04.5 -S2 100 182
/R04.6 -S2 101 183
D /R04.6 -S2 102 184 D

/R04.6 -S2 107 191


/R04.6 -S2 108 192
/R04.6 -S2 109 193
/R04.6 -S2 110 194
/R04.6 -S2 115 201
/R04.6 -S2 116 202
/R04.7 -S2 117 203
E /R04.7 -S2 118 204 E

/R04.7 -S2 123 211


/R04.7 -S2 124 212
=20141610+S1

/R04.7 -S2 125 213


/R04.7 -S2 126 214
EN_01

APE2

/R05.1 -S2 81 221


K02

/R05.1 -S2 82 222


05.11.2015

/R05.1 -S2 83 223


F /R05.1 -S2 84 224
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X2 V =20141610


Drawn Weber GRID HYpact +S1 / K02
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X2 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/R05.2 -S2 85 231
/R05.2 -S2 86 232
/R05.2 -S2 87 233
/R05.2 -S2 88 234
/X01.2 PE

B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610+S1
EN_01

APE2
K03
05.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X2 V =20141610


Drawn Weber GRID HYpact +S1 / K03
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X2 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/X01.2 PE
/R05.2 241 -S2 89
/R05.2 242 -S2 90
/R05.2 243 -S2 91
/R05.2 244 -S2 92
/R05.3 251 -S2 93
/R05.3 252 -S2 94
B /R05.3 253 -S2 95 B
/R05.3 254 -S2 96
/D02.2 400 -F10 1
/D02.2 403 -X2 553
/M02.4 410 -K4 54 Q
/M02.4 411
/D02.7 414 -F2 1
Copyright as per DIN 34 to be observed!

/D02.7 415
C /M02.5 418 -K4 84 Q C
/M02.6 419
/D02.7 420 -F2 6
/D02.7 421
/M02.5 -X22 8 430 -K1 A1 Q
/M02.2 -X22 2 431 -K3 A1 Q
/M02.6 432 -X22 10
/M02.3 -X22 5 433 -K4 A1 Q
D /M02.2 434 -F2 96 Q D

/R03.1 438 -S7 11


/R03.1 439 -S7 12
/M02.2 441 -F2 95
/M02.1 442 -X22 16
/M02.2 -X22 15 445 -K2 71 Q
/M02.5 446 -X22 7
/D02.7 Q -K1 2 531 -M1 3/BL
E /D02.7 Q -K1 4 532 -M1 5/SW E

/D02.5 -S7 2 533 -M1 6/WE


/D02.6 Q -K1 3 534 -M1 4/GR
=20141610+S1

/M02.4 Q -K2 71 538 -X2 904


/R05.4 539 -F2 97
EN_01

APE2

/M02.6 Q -K2 53 547 -X22 11


K04

/M01.1 -X22 13 548 -K1 21


05.11.2015

/M01.1 -X22 14 549 -K4 21


F /M02.2 551 -X22 1
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X2 V =20141610


Drawn Weber GRID HYpact +S1 / K04
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X2 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/M02.3 552 -X22 4
/D02.2 -X2 403 553 -R1 2
/D02.2 555 -E10 2
/M02.3 -X22 3 890 -S11 14
/M02.3 -X22 6 892 -S12 14
/M02.6 -X22 9 894 -S13 14
/M02.7 -X22 12 896 -S14 14
B /R05.4 898 -F2 98 B
/D02.2 -F10 2 900 -R1 1
/D02.2 901 -S10 11
/R05.5 902 -F10 11
/R05.5 903 -F10 12
/M02.4 -K4 71 904 -X2 538
/X01.2 PE -X22 PE
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610+S1
EN_01

APE2
K05
05.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X2 V =20141610


Drawn Weber GRID HYpact +S1 / K05
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X22 STANDARD: Harting 16 polig

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS OBERTEIL POT NR DESTINATIONS UNTERTEIL CABLE CORE REMARKS A
/X01.2 PE -X2 PE
/M02.2 -W02 1 +S4 -X2 1 1 -X2 551
/M02.2 -W02 2 +S4 -X2 2 2 -X2 431
/M02.3 -W02 3 +S4 -X2 3 3 -X2 890
/M02.3 -W02 4 +S4 -X2 4 4 -X2 552
/M02.3 -W02 5 +S4 -X2 5 5 -X2 433
/M02.3 -W02 6 +S4 -X2 6 6 -X2 892
B /M02.5 -W02 7 +S4 -X2 7 7 -X2 446 B
/M02.5 -W02 8 +S4 -X2 8 8 -X2 430
/M02.6 -W02 9 +S4 -X2 9 9 -X2 894
/M02.6 -W02 10 +S4 -X2 10 10 -X2 432
/M02.6 -W02 11 +S4 -X2 11 11 -X2 547
/M02.7 -W02 12 +S4 -X2 12 12 -X2 896
/M01.1 -W02 13 +S4 -X2 13 13 -X2 548
Copyright as per DIN 34 to be observed!

/M01.1 -W02 14 +S4 -X2 14 14 -X2 549


C /M02.1 -W02 15 +S4 -X2 15 15 -X2 445 C
/M02.1 -W02 16 +S4 -X2 16 16 -X2 442

D D

E E
=20141610+S1
EN_01

APE2
K30
05.11.2015

F F

Date 03.11.2015 STECKER -X22 ME4 V =20141610


Drawn Weber GRID HYpact +S1 / K30
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
= Change Main Loc. = Change Subloc. = Change Column Or Sheet = Change Main Loc. = Change Subloc. = Change Column Or Sheet
ø
net destination con. mat.
ø
[mm²]
color reference net destination con. mat.
[mm²]
color reference

-E10 1 =20141610/D02.3 -S2 2 =20141610/M02.6


A A
-S10 12 =20141610/D02.3 -S2 6 =20141610/M02.5

-F2 2 =20141610/D02.7 -S7 5 =20141610/M02.5

-F2 4 =20141610/D02.7 -S2 4 =20141610/M02.3

-F2 3 =20141610/D02.7 -S2 8 =20141610/M02.2

-K1 1 =20141610/D02.7 -S7 7 =20141610/M02.2

-K2 1 =20141610/D02.7 -K4 62 =20141610/M02.2


-K3 1 =20141610/D02.6 -S2 7 =20141610/M02.2
B -K4 1 =20141610/D02.6 -K3 62 =20141610/M02.3 B
-F2 5 =20141610/D02.7 -S2 3 =20141610/M02.3
-K1 6 =20141610/D02.4 -K2 62 =20141610/M02.5
-K2 6 =20141610/D02.7 -S2 5 =20141610/M02.5
-K3 6 =20141610/D02.7
-K1 62 =20141610/M02.6
-K4 6 =20141610/D02.4
-S2 1 =20141610/M02.6
-K1 5 =20141610/D02.4
-K1 71 =20141610/M02.2
Copyright as per DIN 34 to be observed!

-K2 3 =20141610/D02.4
-S7 8 =20141610/M02.2
C -K3 3 =20141610/D02.4 C
-K3 71 =20141610/M02.5
-K4 5 =20141610/D02.4
-S7 6 =20141610/M02.5
-S7 1 =20141610/D02.5
-K1 72 =20141610/M02.2
(ext)
-X2 531 =20141610/D02.7
-K2 72 =20141610/M02.2
-K1 2 =20141610/D02.7
-K2 2 =20141610/D02.7 -K3 72 =20141610/M02.5

-K3 2 =20141610/D02.6 -K4 72 =20141610/M02.5

-K4 2 =20141610/D02.6 -K3 A2 =20141610/M02.2


D D
-K4 61 =20141610/M02.2
(ext)

-X2 532 =20141610/D02.7


-K1 4 =20141610/D02.7 -K4 A2 =20141610/M02.3

-K2 4 =20141610/D02.4 -K3 61 =20141610/M02.3

-K3 4 =20141610/D02.4 -K1 A2 =20141610/M02.5


-K4 4 =20141610/D02.7 -K2 61 =20141610/M02.5
(ext)

-X2 534 =20141610/D02.6 -K2 A2 =20141610/M02.6


-K1 3 =20141610/D02.7 -K1 61 =20141610/M02.6
5

(int)
E -K2 =20141610/D02.7 -X2 410 =20141610/M02.4 E
-K3 5 =20141610/D02.7 -K4 54 =20141610/M02.4
-K4 3 =20141610/D02.7 -K3 54 =20141610/M02.4
=20141610+S1

-K2 21 =20141610/M01.1 -K2 54 =20141610/M02.5


-K3 21 =20141610/M01.1 -K1 54 =20141610/M02.4
EN_01

22 -S11 13 =20141610/M02.3
APE2

-K1 =20141610/M01.1
Q01

-K2 22 =20141610/M01.1 -S12 13 =20141610/M02.3


03.11.2015

-K3 22 =20141610/M01.1 -S13 13 =20141610/M02.6


F
-K4 22 =20141610/M01.1 -S14 13 =20141610/M02.7 F

Date 03.11.2015 QUERVERBINDUNGSPLAN V =20141610


Drawn Weber GRID HYpact +S1 / Q01
00 00000 03.11.15 MW. Checked Schlein CROSSCONNECTIONS Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
= Change Main Loc. = Change Subloc. = Change Column Or Sheet = Change Main Loc. = Change Subloc. = Change Column Or Sheet
ø
net destination con. mat.
ø
[mm²]
color reference net destination con. mat.
[mm²]
color reference

(int)
-X2 418 =20141610/M02.5 -S2 47 =20141610/R03.4
A A
84

(ext)
-K4 =20141610/M02.6 -X2 61 =20141610/R03.5
-K3 84 =20141610/M02.6 -S2 53 =20141610/R03.5
-K2 84 =20141610/M02.6 -S2 55 =20141610/R03.5
-K1 84 =20141610/M02.5

(ext)
-X2 107 =20141610/R03.1

(int)
-X2 430 =20141610/M02.5 -S2 10 =20141610/R03.1
-K1 A1 =20141610/M02.5 -S2 12 =20141610/R03.2
-K1 53 =20141610/M02.4

(ext)
-X2 127 =20141610/R03.2

(int)
B -X2 431 =20141610/M02.2 -S2 14 =20141610/R03.2 B
-K3 A1 =20141610/M02.2 -S2 16 =20141610/R03.2
-K3 53 =20141610/M02.4

(ext)
-X2 121 =20141610/R04.3

(int)
-X2 433 =20141610/M02.3 -S2 17 =20141610/R04.3
-K4 A1 =20141610/M02.3 -S2 19 =20141610/R04.3
-K4 53 =20141610/M02.4

(ext)
-X2 131 =20141610/R04.3

(int)
-X2 434 =20141610/M02.2 -S2 25 =20141610/R04.3
Copyright as per DIN 34 to be observed!

-F2 96 =20141610/M02.2 -S2 27 =20141610/R04.3


C -K1 83 =20141610/M02.5 C

(ext)
-X2 141 =20141610/R04.4
-K2 83 =20141610/M02.6
-S2 33 =20141610/R04.4
-K3 83 =20141610/M02.6
-S2 35 =20141610/R04.4
-K4 83 =20141610/M02.6

(ext)
(int) -X2 151 =20141610/R04.4
-X2 445 =20141610/M02.2
-S2 41 =20141610/R04.4
-K2 71 =20141610/M02.2
-S2 43 =20141610/R04.4
(ext) (ext)

-X2 538 =20141610/M02.4

(ext)
-X2 161 =20141610/R04.5
D
-X2 547 =20141610/M02.6
-S2 49 =20141610/R04.5 D
-K2 53 =20141610/M02.5
-S2 51 =20141610/R04.5
-K2 A1 =20141610/M02.6

-S2 13 =20141610/R03.2
-S2 15 =20141610/R03.2
-S8 1 =20141610/R03.2
(ext)

-X2 21 =20141610/R03.3
-S2 21 =20141610/R03.3
E -S2 23 =20141610/R03.3 E
(ext)

-X2 31 =20141610/R03.3
-S2 29 =20141610/R03.4
=20141610+S1

-S2 31 =20141610/R03.3
(ext)

-X2 41 =20141610/R03.4
EN_01

APE2

-S2 37 =20141610/R03.4
Q02

-S2 39 =20141610/R03.4
03.11.2015

(ext)

-X2 51 =20141610/R03.4
F F
-S2 45 =20141610/R03.5
Date 03.11.2015 QUERVERBINDUNGSPLAN V =20141610
Drawn Weber GRID HYpact +S1 / Q02
00 00000 03.11.15 MW. Checked Schlein CROSSCONNECTIONS Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K 1,5MM2
sw -X1 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/X01.6 PE
/R02.2 -S1.1 9 10
/R02.2 -S1.2 10 11
/R02.2 -S1.2 9 12
/R02.2 -S1.2 1 13
/R02.2 -S1.2 2 14
/R02.2 -S1.1 10 19
B /R02.2 -S1.2 12 21 B
/R02.2 -S1.2 11 22
/R02.2 -S1.2 3 23
/R02.2 -S1.2 4 24
/R02.3 -S1.2 14 31
/R02.3 -S1.2 13 32
/R02.3 -S1.2 5 33
Copyright as per DIN 34 to be observed!

/R02.3 -S1.2 6 34
C /R02.3 -S1.2 16 41 C
/R02.3 -S1.2 15 42
/R02.3 -S1.2 7 43
/R02.3 -S1.2 8 44
/R02.3 -S1.3 10 51
/R02.3 -S1.3 9 52
/R02.3 -S1.3 1 53
/R02.3 -S1.3 2 54
D /R02.4 -S1.3 12 61 D

/R02.4 -S1.3 11 62
/R02.4 -S1.3 3 63
/R02.4 -S1.3 4 64
/R02.4 -S1.3 14 71
/R02.4 -S1.3 13 72
/R02.4 -S1.3 5 73
/R02.4 -S1.3 6 74
E /M02.1 -S1.3 16 81 -X2 15 E

/M02.1 -S1.3 15 82 -X2 16


/R02.4 -S1.3 7 83
=20141610+S4

/R02.4 -S1.3 8 84
/R02.5 -S1.4 10 91
EN_01

APE2

/R02.5 -S1.4 9 92
K01

/R02.5 -S1.4 1 93
03.11.2015

/R02.5 -S1.4 2 94
F /R02.5 -S1.4 12 111
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN LS V =20141610


Drawn Weber GRID HYpact +S4 / K01
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K 1,5MM2
sw -X1 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/R02.5 -S1.4 11 112
/R02.5 -S1.4 3 113
/R02.5 -S1.4 4 114
/R02.5 -S1.4 14 121
/R02.5 -S1.4 13 122
/R02.5 -S1.4 5 123
/R02.5 -S1.4 6 124
B /R02.5 -S1.4 16 131 B
/R02.5 -S1.4 15 132
/R02.6 -S1.4 7 133
/R02.6 -S1.4 8 134
/X01.6 -X2 PE PE
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610+S4
EN_01

APE2
K02
03.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN LS V =20141610


Drawn Weber GRID HYpact +S4 / K02
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K 1,5MM2
sw -X1 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/X01.6 PE
/D01.6 450 -Q1 1
/X01.6 451
/D01.6 465 -Q1 6
/X01.6 466
/D01.2 -R2 1 480 -F10 2
/D01.2 481
B /D01.3 -S10 11 482 B
/X01.6 483
/D01.2 -R2 2 484 -X1 515
/D01.2 485
/D01.3 -E10 2 486
/D01.2 500 -F10 1
/X01.6 501
Copyright as per DIN 34 to be observed!

/D01.2 515 -X1 484


C /X01.6 516 C
/M01.7 -F1 4 -F1 4 530 -K14 A1
/R01.2 -F1 1 -F1 1 532 -X1 850
/R01.2 533 -K14 13
/R01.2 534
/R01.2 535 -S2 7
/R01.3 536 -Q1 21
/R01.3 537
D /R01.3 538 -F10 11 D

/M01.2 -X2 13 539 -K11 A2 Q


/M01.2 540 -S3 6
/M01.1 541 -X2 14
/M01.7 600 -F1 3 -F1 3
/M01.7 601 -S4 13 Q
/M01.7 602
/M01.6 603
E /X01.6 604 E

/M01.7 605
/M01.7 606 -K14 A2 Q
=20141610+S4

/M01.7 607
/X01.6 608
EN_01

APE2

/X01.6 609
K03

/M01.2 610 -S3 1


03.11.2015

/X01.6 611
F /M01.2 625 -S3 5
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN LS V =20141610


Drawn Weber GRID HYpact +S4 / K03
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K 1,5MM2
sw -X1 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/X01.6 626
/M01.5 630 -S3 9
/X01.6 631
/M01.5 645 -K14 32
/X01.6 646
/R01.6 676 -S2 11
/R01.7 677 -S2 5
B /R01.6 678 -S2 12 B
/R01.7 679 -S2 6
/M01.5 688 -S1.1 13
/X01.6 700
/X01.6 705
/M01.6 730 -S1.1 3
/X01.6 731
Copyright as per DIN 34 to be observed!

/M01.6 745 -K14 62


C /X01.6 746 C
/X01.6 750
/M01.6 788 -S1.1 15
/R01.2 850 -X1 532
/R01.2 870 -F1 2 -F1 2
/R01.2 872 -K14 14
/R01.2 873
/R01.2 874 -S2 8
D /R01.3 878 -Q1 22 D

/R01.3 880
/R01.3 884 -F10 12
/R01.5 890 -S3 34
/R01.5 892 -S3 33
/R01.5 894 -S3 35
/R01.6 896 -S3 40
/X01.6 898
E /M02.2 -X2 1 900 -S3 25 E

/M02.2 -X2 2 901 -S3 26


/M02.3 -X2 3 902 -S3 27
=20141610+S4

/M02.3 -X2 4 903 -S3 13


/M02.3 -X2 5 904 -S3 14
EN_01

APE2

/M02.3 -X2 6 905 -S3 15


K04

/M02.5 -X2 7 906 -S3 17


03.11.2015

/M02.5 -X2 8 907 -S3 18


F /M02.6 -X2 9 908 -S3 19
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN LS V =20141610


Drawn Weber GRID HYpact +S4 / K04
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K 1,5MM2
sw -X1 STANDARD: PHOENIX PT4/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/M02.6 -X2 10 909 -S3 21
/M02.6 -X2 11 910 -S3 22
/M02.7 -X2 12 911 -S3 23
/D01.3 PE
/X01.6 PE -F1 PE -F1 PE

B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610+S4
EN_01

APE2
K05
03.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN LS V =20141610


Drawn Weber GRID HYpact +S4 / K05
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 sw -X2 STANDARD: Harting 16 polig

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS OBERTEIL POT NR DESTINATIONS UNTERTEIL CABLE CORE REMARKS A
/X01.6 PE -X1 PE
/M02.2 -W02 1 +S1 -X22 1 1 -X1 900
/M02.2 -W02 2 +S1 -X22 2 2 -X1 901
/M02.3 -W02 3 +S1 -X22 3 3 -X1 902
/M02.3 -W02 4 +S1 -X22 4 4 -X1 903
/M02.3 -W02 5 +S1 -X22 5 5 -X1 904
/M02.3 -W02 6 +S1 -X22 6 6 -X1 905
B /M02.5 -W02 7 +S1 -X22 7 7 -X1 906 B
/M02.5 -W02 8 +S1 -X22 8 8 -X1 907
/M02.6 -W02 9 +S1 -X22 9 9 -X1 908
/M02.6 -W02 10 +S1 -X22 10 10 -X1 909
/M02.6 -W02 11 +S1 -X22 11 11 -X1 910
/M02.7 -W02 12 +S1 -X22 12 12 -X1 911
/M01.1 -W02 13 +S1 -X22 13 13 -X1 539
Copyright as per DIN 34 to be observed!

/M01.1 -W02 14 +S1 -X22 14 14 -X1 541


C /M02.1 -W02 15 +S1 -X22 15 15 -X1 81 C
/M02.1 -W02 16 +S1 -X22 16 16 -X1 82

D D

E E
=20141610+S4
EN_01

APE2
K10
03.11.2015

F F

Date 03.11.2015 STECKER -X2 LS V =20141610


Drawn Weber GRID HYpact +S4 / K10
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
= Change Main Loc. = Change Subloc. = Change Column Or Sheet = Change Main Loc. = Change Subloc. = Change Column Or Sheet
ø
net destination con. mat.
ø
[mm²]
color reference net destination con. mat.
[mm²]
color reference

-E10 1 bl =20141610/D01.3 -K11 22 bl =20141610/M01.2


A A
-S10 12 =20141610/D01.3 -S1.1 11 =20141610/M01.2

-Q1 2 bl =20141610/D01.6 -K14 31 bl =20141610/M01.5


-Q1 3 =20141610/D01.6 -Y1 A2 =20141610/M01.5

-Q1 4 bl =20141610/D01.6 -K14 61 bl =20141610/M01.6


-S2 1 =20141610/D01.6 -Y2 A2 =20141610/M01.6

(int)
-Q1 5 bl =20141610/D01.6 -X1 539 bl =20141610/M01.2
-S2 4 =20141610/D01.6 -K11 A2 " =20141610/M01.2
B -M1 A1 bl =20141610/D01.6 -K14 22 =20141610/M01.2 B

(int)
-S2 2 =20141610/D01.6 -X1 601 bl =20141610/M01.7

-M1 A2 bl =20141610/D01.6 -S4 13 " =20141610/M01.2

-S2 3 =20141610/D01.6 -S5 13 =20141610/M01.4

(int)
-S1.1 2 bl =20141610/M01.5 -X1 606 bl =20141610/M01.7

-S1.1 14 " =20141610/M01.5 -K14 A2 " =20141610/M01.7

-Y1 A1 =20141610/M01.5 -S4 44 =20141610/M01.2


Copyright as per DIN 34 to be observed!

C -S3 3 bl =20141610/M01.2 -S3 36 bl =20141610/R01.5


C
-S4 14 =20141610/M01.2 -S3 39 =20141610/R01.6

-S1.1 4 bl =20141610/M01.6
-S1.1 16 " =20141610/M01.6
-Y2 A1 =20141610/M01.6

-S3 7 bl =20141610/M01.2
-S4 43 =20141610/M01.2

-S2 9 bl =20141610/M01.2
D D
-Y4 A2 =20141610/M01.2

-S3 10 bl =20141610/M01.5
-S1.1 1 =20141610/M01.5

-S3 11 bl =20141610/M01.4
-S5 14 =20141610/M01.4

-S1.1 12 bl =20141610/M01.2
-Y4 A1 =20141610/M01.2

E -K11 13 bl =20141610/M01.2 E
-K11 21 " =20141610/M01.2
-S3 2 " =20141610/M01.2
=20141610+S4

-S1.1 5 =20141610/M01.3

-K11 14 bl =20141610/M01.2
EN_01

A1
APE2

-K11 " =20141610/M01.2


Q10

-S1.1 6 =20141610/M01.3
03.11.2015

-K14 21 bl =20141610/M01.2
F F
-S2 10 =20141610/M01.2

Date 03.11.2015 QUERVERBINDUNGSPLAN V =20141610


Drawn Weber GRID HYpact +S4 / Q10
00 00000 03.11.15 MW. Checked Schlein CROSSCONNECTIONS Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
GRID
ALSTOM Grid GmbH HIGH VOLTAGE PRODUCTS LILIENTHALSTR. 150 POST OFFICE BOX 60491 D-34123 KASSEL PHONE: 0561 502-0 FAX: 0561 502-2758

TYPE HYpact 145


CT/VT ARRANGEMENT

A =20141610T
=20141610T

/ A00
EN_01

APE2
A00
03.11.2015

SR 201416-10 Date : 03.11.2015


Drawn : Weber
Checked: Schlein
Norm :
DECKBLATT
00 00000 03.11.15 MW.
HYpact
COVER
NO. REVISION DATE NAME HYpact
1 2 3 4 5 6 7 8
COSTOMER- MANUFACTURER'S DRAWING- REVISION- DOCUMENT NUMBER SHEET DESIGNATION
DOCUMENT NUMBER DOCUMENT NUMBER STATE
DRAW.TY. ASSOCIATION SERIAL NO.
SR 201416-10 00 A =20141610T A00 DECKBLATT HYpact
COVER HYpact
A A
SR 201416-10 00 S =20141610T A01 INHALTSVERZEICHNIS HYpact
LEGEND HYpact
SR 201416-10 00 S =20141610T T01 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAMM HYpact
SR 201416-10 00 S =20141610T T02 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAMM HYpact
SR 201416-10 00 S =20141610T T04 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAMM HYpact
SR 201416-10 00 S =20141610T T06 STROMLAUFPLAN HYpact
CIRCUIT DIAGRAMM HYpact
SR 201416-10 00 S =20141610T ZF1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
B B
SR 201416-10 00 S =20141610T ZR1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 S =20141610T ZT1 BETRIEBSMITTELPLAN HYpact
LIST OF EQUIPMENT HYpact
SR 201416-10 00 V =20141610T K80 KLEMMENANSCHLUSSPLAN-X410 HYpact
+S TERMINAL DIAGRAM -X410 HYpact
SR 201416-10 00 V =20141610T K81 KLEMMENANSCHLUSSPLAN-X410 HYpact
+S TERMINAL DIAGRAM -X410 HYpact
SR 201416-10 00 V =20141610T K90 KLEMMENANSCHLUSSPLAN-X450 HYpact
+S TERMINAL DIAGRAM -X450 HYpact
Copyright as per DIN 34 to be observed!

SR 201416-10 00 V =20141610T K100 KLEMMENANSCHLUSSPLAN-X211 HYpact


+S TERMINAL DIAGRAM -X211 HYpact
C C

D D

E E
=20141610T
EN_01

APE2
A01
03.11.2015

F F

Date 03.11.2015 INHALTSVERZEICHNIS S =20141610T


Drawn Weber GRID HYpact / A01
00 00000 03.11.15 MW. Checked Schlein LEGEND Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

STROMWANDLER 1,2,3 KERN 1 STROMWANDLER 1,2,3 KERN 2


CURRENT TRANSFORMER 1,2,3 CORE 1 CURRENT TRANSFORMER 1,2,3 CORE 2

+E01
A A

1S1 1S1 1S1 2S1 2S1 2S1


-T1/1 1S2 -T1/2 1S2 -T1/3 1S2 -T1/1 2S2 -T1/2 2S2 -T1/3 2S2
/ZT1.1 /ZT1.1 /ZT1.1 /ZT1.1 /ZT1.1 /ZT1.1
1S3 1S3 1S3 2S3 2S3 2S3
1S4 1S4 1S4 2S4 2S4 2S4
HS- ANLAGE
HV-STATION

B B
Copyright as per DIN 34 to be observed!

C C

D D

+S

-X410 113 112 111 110 123 122 121 120 133 132 131 130 -X410 213 212 211 210 223 222 221 220 233 232 231 230

E -X410 170 171 172 173 -X410 270 271 272 273 E
WANDLERKASTEN
TERMINAL BOX
=20141610T
EN_01

APE2
T01
03.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610T


Drawn Weber GRID HYpact / T01
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAMM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

STROMWANDLER 1,2,3 KERN 3 STROMWANDLER 1,2,3 KERN 4


CURRENT TRANSFORMER 1,2,3 CORE 3 CURRENT TRANSFORMER 1,2,3 CORE 4

+E01
A A

3S1 3S1 3S1 4S1 4S1 4S1


-T1/1 3S2 -T1/2 3S2 -T1/3 3S2 -T1/1 4S2 -T1/2 4S2 -T1/3 4S2
/ZT1.1 /ZT1.1 /ZT1.1 /ZT1.1 /ZT1.1 /ZT1.1
3S3 3S3 3S3 4S3 4S3 4S3
3S4 3S4 3S4 4S4 4S4 4S4
HS- ANLAGE
HV-STATION

B B
Copyright as per DIN 34 to be observed!

C C

D D

+S

-X410 313 312 311 310 323 322 321 320 333 332 331 330 -X410 413 412 411 410 423 422 421 420 433 432 431 430

E -X410 370 371 372 373 -X410 470 471 472 473 E
WANDLERKASTEN
TERMINAL BOX
=20141610T
EN_01

APE2
T02
03.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610T


Drawn Weber GRID HYpact / T02
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAMM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPANNUNGSWANDLER 2 WICKLUNG 1 SPANNUNGSWANDLER 2 WICKLUNG 2


VOLTAGE TRANSFORMER 2 WINDING 1 VOLTAGE TRANSFORMER 2 WINDING 2
+E01
A A

1N 2N
-T5/2 -T5/2
/ZT1.1 /ZT1.1
HS-ANLAGE 1A 2A

B B

+S
-X450 110 -X450 210
Copyright as per DIN 34 to be observed!

-X450 170 -X450 270


C C
-X450 171 -X450 271

D 1 1
D
-F151 -F251
/ZF1.1 /ZF1.1
2 2

-X450 113 134 -X450 213 234

E E
215514
=20141610T
EN_01

APE2
T04
04.11.2015

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610T


Drawn Weber GRID HYpact / T04
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAMM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+E01
A A

HS-ANLAGE

B B

+S -X211 401 402 403 404 -X211 610


L1
Copyright as per DIN 34 to be observed!

-X410 900
C C

13 21 13 21 1
-F151 -F251 -F1/T5
P 1
/ZF1.1 /ZF1.1 /ZF1.1
14 22 14 22 2 -R3
/ZR1.1
2

PE
D PE PE D
2

PE PE PE

-X450 PE PE PE

-X211 414 415 416 417 -X211 611 -X450 PE PE


-X410 901
-X211 PE
N -X410 PE PE PE

E E
215514

SICHERUNGSAUTOMAT VT/WINDUNG 1

SICHERUNGSAUTOMAT VT/WINDUNG 2
CIRCUIT BREAKER VT/WINDING 1

CIRCUIT BREAKER VT/WINDING 2


=20141610T
EN_01

APE2
T06
04.11.2015

WARNUNG SF6
ALARM SF6

F F

Date 03.11.2015 STROMLAUFPLAN S =20141610T


Drawn Weber GRID HYpact / T06
00 00000 03.11.15 MW. Checked Schlein CIRCUIT DIAGRAMM Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 SF6-DICHTEWAECHTER
SF6 DENSIMETER
MANUF. : WIKA
ORD.NR. :
TYPE:233.52.100

A A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER

1 3
P
2 4
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
SF6-UEBERWACHUNG SF6-CONTROL +S -F1/T5 /T06.5

B B

2 AUTOMAT SPGS.-WANDL. MANUF. : SIEMENS


ORD.NR. :
TYPE:5SL6103-7
ST3010
Copyright as per DIN 34 to be observed!

: :
C TECHNICAL COMPONENTS TYPE ORDERING NUMBER C

1 13 21

2 14 22
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
SICHERUNG T5 WICKL.1 PROTECTION T5 WIND.1 +S -F151 /T04.2 /T06.2 /T06.3
SICHERUNG T5 WICKL.2 PROTECTION T5 WIND.2 +S -F251 /T04.5 /T06.3 /T06.3

D D

E E
215514
=20141610T
EN_01

APE2
ZF1
04.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610T


Drawn Weber GRID HYpact / ZF1
00 00000 03.11.15 MW. Checked Schlein LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

1 HEIZUNG
HEATING
MANUF. : DALE
ORD.NR. :
TYPE:RH-50

A 25W A

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER
1

2
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
HEIZUNG CT HEATING CT +S -R3 /T06.7

B B
Copyright as per DIN 34 to be observed!

C C

D D

E E
215514
=20141610T
EN_01

APE2
ZR1
03.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610T


Drawn Weber GRID HYpact / ZR1
00 00000 03.11.15 MW. Checked Schlein LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PART DESCRIPTION, DESIGN, TECHNICAL DATA,MANUFACTURER, TYPE, ORDERING DATA COMPLETE DEVICE REPRESANTATION OR REFERENCE
NUMBER APPLICATION SET. VALUES LOCATION ITEM DESIGNATION WITH REFERENCE TO DETAIL DRAWINGS (CIRCUIT DIAGRAM, SHEET, CURRENT PATH) REMARKS

3 STROMWANDLER
CURRENT TRANSFORMER
MANUF. :
ORD.NR:
TYPE:

A A

: :
TECHNICAL COMPONENTS TYPE OPDERING NUMBER
800-400-200/5,0.5 ,20VA@800/5,15VA@400/5,10VA@200/5
800-400-200/5,5P20,20VA@800/5,15VA@400/5,10VA@200/5
800-400-200/5,5P20,20VA@800/5,15VA@400/5,10VA@200/5
800-400-200/5,5P20,20VA@800/5,15VA@400/5,10VA@200/5

1S1
1S2
1S3
1S4

2S1
2S2
2S3
2S4

3S1
3S2
3S3
3S4

4S1
4S2
4S3
4S4
APPLICATION SETTING VALUES LOCATION ITM DESIGNATION

STROMWANDLER CURERNT TRANSF. +E01 -T1/1 /T01.2 /T01.5 /T02.2 /T02.5


STROMWANDLER CURERNT TRANSF. +E01 -T1/2 /T01.3 /T01.6 /T02.3 /T02.6
STROMWANDLER CURERNT TRANSF. +E01 -T1/3 /T01.4 /T01.7 /T02.4 /T02.7
B B

1 SPANNUNGSWANDLER
VOLTAGE TRANSFORMER
MANUF. :
ORD.NR. :
TYPE:

: :
TECHNICAL COMPONENTS TYPE ORDERING NUMBER
Winding 1:110000:V3/110:V3,0.5, 30VA
Winding 2:110000:V3/110/V3,3P,30VA
Copyright as per DIN 34 to be observed!

C 1A 1N 2A 2N C
APPLICATION SETTING VALUES LOCATION ITEM DESIGNATION
SPANNUNGSWANDLER VOLTAGE TRANSFORMER +E01 -T5/2 /T04.2 /T04.5

D D

E E
=20141610T
EN_01

APE2
ZT1
10.11.2015

F F

Date 03.11.2015 BETRIEBSMITTELPLAN S =20141610T


Drawn Weber GRID HYpact / ZT1
00 00000 03.11.15 MW. Checked Schlein LIST OF EQUIPMENT Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
4 MM2 sw -X410 STANDARD: PHOENIX PT6/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/T06.8 PE
/T01.2 -X410 170 110 +E01 -T1/1 1S1
/T01.2 111 +E01 -T1/1 1S2
/T01.2 112 +E01 -T1/1 1S3
/T01.2 113 +E01 -T1/1 1S4
/T01.3 -X410 171 120 +E01 -T1/2 1S1
/T01.3 121 +E01 -T1/2 1S2
B /T01.3 122 +E01 -T1/2 1S3 B
/T01.3 123 +E01 -T1/2 1S4
/T01.4 -X410 172 130 +E01 -T1/3 1S1
/T01.4 131 +E01 -T1/3 1S2
/T01.4 132 +E01 -T1/3 1S3
/T01.4 133 +E01 -T1/3 1S4
/T01.2 -X410 110 170
Copyright as per DIN 34 to be observed!

/T01.3 -X410 120 171


C /T01.4 -X410 130 172 C
/T01.5 173 ERDE
/T01.6 -X410 270 210 +E01 -T1/1 2S1
/T01.5 211 +E01 -T1/1 2S2
/T01.5 212 +E01 -T1/1 2S3
/T01.5 213 +E01 -T1/1 2S4
/T01.7 -X410 271 220 +E01 -T1/2 2S1
/T01.7 221 +E01 -T1/2 2S2
D /T01.6 222 +E01 -T1/2 2S3 D

/T01.6 223 +E01 -T1/2 2S4


/T01.8 -X410 272 230 +E01 -T1/3 2S1
/T01.8 231 +E01 -T1/3 2S2
/T01.7 232 +E01 -T1/3 2S3
/T01.7 233 +E01 -T1/3 2S4
/T01.6 -X410 210 270
/T01.7 -X410 220 271
E /T01.8 -X410 230 272 E

/T01.8 273 ERDE


/T02.2 -X410 370 310 +E01 -T1/1 3S1
=20141610T+S

/T02.2 311 +E01 -T1/4 3S2


/T02.2 312 +E01 -T1/4 3S3
EN_01

APE2

/T02.2 313 +E01 -T1/1 3S4


K80

/T02.3 -X410 371 320 +E01 -T1/2 3S1


04.11.2015

/T02.3 321 +E01 -T1/5 3S2


F /T02.3 322 +E01 -T1/5 3S3
F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X410 V =20141610T


Drawn Weber GRID HYpact +S / K80
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM -X410 Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
4 MM2 sw -X410 STANDARD: PHOENIX PT6/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/T02.3 323 +E01 -T1/2 3S4
/T02.4 -X410 372 330 +E01 -T1/3 3S1
/T02.4 331 +E01 -T1/6 3S2
/T02.4 332 +E01 -T1/6 3S3
/T02.4 333 +E01 -T1/3 3S4
/T02.2 -X410 310 370
/T02.3 -X410 320 371
B /T02.4 -X410 330 372 B
/T02.5 373 ERDE
/T02.6 -X410 470 410 +E01 -T1/1 4S1
/T02.5 411 +E01 -T1/4 4S2
/T02.5 412 +E01 -T1/4 4S3
/T02.5 413 +E01 -T1/1 4S4
/T02.7 -X410 471 420 +E01 -T1/2 4S1
Copyright as per DIN 34 to be observed!

/T02.7 421 +E01 -T1/5 4S2


C /T02.6 422 +E01 -T1/5 4S3 C
/T02.6 423 +E01 -T1/2 4S4
/T02.8 -X410 472 430 +E01 -T1/3 4S1
/T02.8 431 +E01 -T1/6 4S2
/T02.7 432 +E01 -T1/6 4S3
/T02.7 433 +E01 -T1/3 4S4
/T02.6 -X410 410 470
/T02.7 -X410 420 471
D /T02.8 -X410 430 472 D

/T02.8 473 ERDE


/T06.7 900 -R3 1
/T06.7 901 -R3 2
/T06.8 PE
/T06.8 PE
/T06.8 PE
/T06.8 PE
E /T06.8 PE E
=20141610T+S
EN_01

APE2
K81
04.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X410 V =20141610T


Drawn Weber GRID HYpact +S / K81
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM -X410 Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
2,5 MM2 -X450 STANDARD: PHOENIX PT6/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/T06.8 PE
/T04.2 +E01 -T5/2 1A 110 -F151 1
/T04.2 -F151 2 113
/T04.2 134
/T04.2 +E01 -T5/2 1N 170
/T04.2 171 ERDE
/T04.5 +E01 -T5/2 2A 210 -F251 1
B /T04.5 -F251 2 213 B
/T04.5 234
/T04.5 +E01 -T5/2 2N 270
/T04.5 271 ERDE
/T06.8 PE
/T06.8 PE
/T06.8 PE
Copyright as per DIN 34 to be observed!

/T06.8 PE
C C

D D

E E
=20141610T+S
EN_01

APE2
K90
04.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X450 V =20141610T


Drawn Weber GRID HYpact +S / K90
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM -X450 Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
INSTALLATION/INSTRUCTIONS LINE MATERIAL TERMINAL-TYPE
STANDARD: H07V-K
1,5 MM2 -X211 STANDARD: PHOENIX PT6/USLKG10

REFE- LINE( IN MM2) LINE( IN MM2)


A RENCE CABLE CORE DESTINATIONS POT NR DESTINATIONS CABLE CORE REMARKS A
/T06.8 PE
/T06.2 -F151 13 401
/T06.3 -F151 21 402
/T06.3 -F251 13 403
/T06.3 -F251 21 404
/T06.2 -F151 14 414
/T06.3 -F151 22 415
B /T06.3 -F251 14 416 B
/T06.3 -F251 22 417
/T06.5 -F1/T5 1 -F1/T5 1 610
/T06.5 -F1/T5 2 -F1/T5 2 611
/T06.8 -F1/T5 PE -F1/T5 PE PE
Copyright as per DIN 34 to be observed!

C C

D D

E E
=20141610T+S
EN_01
K100
APE2
04.11.2015

F F

Date 03.11.2015 KLEMMENANSCHLUSSPLAN-X211 V =20141610T


Drawn Weber GRID HYpact +S / K100
00 00000 03.11.15 MW. Checked Schlein TERMINAL DIAGRAM -X211 Sheet
State Revision Date Name Norm Origin: Sub.f.: Rpl.by: HYpact SR 201416-10 Sh.
1 2 3 4 5 6 7 8

Potrebbero piacerti anche