Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
3.3 Motors......................................................................................................................................... 12
1
4.1 System Boundaries...................................................................................................................... 15
2
AUXILIARY FEED WATER SYSTEM
The Auxiliary Feed water System (AFW) is a key component in pressurized water reactor
designs. The AFW performs several functions within the reactors, however the primary function
is, provision of feedwater to the steam generators in order to maintain a heat sink. This is usually
in the event of, loss of the reactors main feedwater, loss of offsite power as a result of a reactor
The AFW system performs safety-related functions within the reactor. The system supplies
feedwater to the steam generators at high-pressure, in-order to provide a balance of the water
inventory that is required to remove heat energy from the reactor coolant system through
secondary side steam release [2]. This feedback system is usually used in the event of
inoperability or unavailability of the main feed water system. During such accidents, the AFW
system automatically starts and delivers adequate feedwater flow that maintains steam generator
levels thereby preventing the main steam safety valves from opening. This mechanism also helps
achieve cold shutdown conditions during accidents that require rapid reactor coolant system
cooldowns.
The AFW system also performs functions related to regulatory commitments within the reactor.
In scenarios of total blackout, the system automatically supplies sufficient feedwater that
removes decay heat from the units for up to one hour without reliance on AC power [2].
3
2 AFW System components
An ideal AFW system is configured with two separate mechanical divisions, independent of each
other with and with separate initiation and control functions designed to feed all the steam
generators. One of the divisions may consist of two electric motor-driven pumps whereas the
The common design configurations of AFW systems are four-steam and two-steam generator
plants. In a four-steam generator plant, each of the electric-motor driven pump train has the
capacity to supply two steam generators whereas the turbine driven pump is capable of supplying
four steam generators. In a two-division two-train plants setup, both the pumps are aligned and
Each of the steam generators is fed water through flow control valves. The valves regulate the
steam generator levels by open or closing to release feedwater. The flow control valves are
controlled either manually or automatically from the control rooms. The water supply to the
AFW system provides for redundancy, with the primary source being water from the condensate
storage tanks while the secondary feed is from the plant water system that are powered by diesel
generators. The condensate tanks will each have their water levels monitored to a capacity that
allows for up to 6 hours of system operation. The switchover in water supply from the primary to
the secondary source is initiated by conditions such as; low-suction pressure or power failure.
Each of the turbines is fitted with a hydraulic governor control valve and a trip and throttle valve
with motor reset capabilities. The governor valves open the steam isolation valve(s) that activate
4
the turbines to the required operation speed. In order to maintain the turbine’s speed to match the
pump rated speeds, the governor modulates the control valves to meet the required speeds. The
governor controlled turbine speeds are either adjusted remotely from the control room or
manually at the governor. The throttle valves are used to stop the turbines, this is usually done
automatically from the control room or the remote shutdown panel. In instances where the
turbine speeds get to 115% of the rated speeds, the throttle valves are electrically tripped.
5
2.2 AFW System Diagram
6
2.3 List of Components
Globe
valve
AF
Insolatio
n
Valve(G
ate
valve)
Steam
insolatio
n/Steam
Globe
valve
Gate V1006A, V1005A,V1002A,
Valve V1001A, V1601, V1626, V1184,
V1185,
V105D,V1200,V1201,V1605,V1
610,V1700,V1220,V1205A,V120
4A/B,V1201A,V1603/V1616,V1
151
Governo V3011 E/H Operated
r Globe
Valve(E
/H)
Trip and V3009 Motor-operated by
Throttle demand
Valve
7
Butterfl V1208
y Valve
Demi
Water
Storage
Tank
AF
Storage
Tank
A/B
Raw
Water
Storage
Tank
Condens
ate
Storage
Tank A
TKO1
Condens
ate
Storage
Tank B
TKO2
AF TDP PP01A/B, MDP PP02A/B
Pump
Pump PP31(A), PP31(B)
AF V0035,V0037
Modulat
ing
Valve
Gate V105 Motor operated, Fall
Valve locked
(Motor
Operate
d)
Gate V1623, V1627, V1621,V1622 Manual operated, All
Valve modes
(Manual
Operate
d)
Turbine AF Pump Turbine A TA01A All models
Orifice V1015, V1017
8
Steam PT 1013A, PT1013B, PT1013C,
Generat
or 1/2
Steam
Generat
or 2
3.1 Valves
Valves are an integral part of the AFW system’s architecture, their main functionality being
control or stopping liquid flow along a pipe. The components of a valve include; the seat and
disk that function together to throttle system flow, the valve has a body that acts as a pressure
boundary and a bonnet that contains the packaging and provides support to the stem [3].
Valves are often positioned using a variety of methods based on their operation modes, this
include; hydraulic operated, manual operated, air operated and motor operated valves. To
identify direction of flow within valves, there are usually external markings on the valve’s body
There are different valve designs each with different functionalities, this include; gate valves,
globe valves, butterfly valves, ball valves and check valves among others.
Check valves are designed to allow flows only in one direction. There is minimal resistance of
flow when the valve is open and they automatically close when system flow reverses.
9
There are different designs of check valves such as lift check valves and stop check valves, the
Gate valves are often used for isolation. They can be operated either in fully open or fully closed
modes. In a fully closed mode, the gate exerts force on the seat thereby creating a tight seal
whereas in the fully open mode the gate is out of the flow path.
Globe valves are primarily used in regulation or throttling flow, but then can also be used for
isolation. They have a rounded disk and tapered seat. The seat and disks of the globe valves are
usually not as damaged compared to gate valves when the valves are used to regulate flow.
Globe valves are typically configured as either Angle globe valves or Needle glove valves, the
former designed to serve both as an isolation, throttle valve and a 90 degree piping elbow.
Needle glove valves on the other hand are used for fine flow control in small diameter pipes,
they have sharp pointed conical disk and matching seats that make that a possibility.
Butterfly valves are used for isolation, they are light weight and are commonly used in low
pressure low flow systems with large diameter piping (Agency, 2019, p. 35). The valves are
usually unable to seal tightly if there are high pressure differences across the valve’s disk.
10
Butterfly valves perform a 90-degree operation, for the disk to position from a fully open to fully
Similar to Butterfly valves, Ball valves are also used for isolation, and they perform a 90-degree
operation. They are commonly used in high pressure systems (Agency, 2019, p. 36).
The trip and throttle valve is designed to control steam flow and prevent catastrophic failure, it is
therefore a critical safety device on a steam turbine. When operating as throttle valves, they
regulate flow of steam and gas in large high-pressure pipe lines, whereas when operating as trip
The trip throttle valve can be remotely shutdown from the control room to stop the turbine. The
valves are automatically tripped if the turbines over speed to a tune of 115% of the rated speed.
These valves are used to prevent system pressure from exceeding specific defined values, this in
A relief valve maintains pressure by gradually opening as pressure exceeds a defined setpoint
and gradually closing as the pressure drop below the particular setpoint. (Agency, 2019, p. 37).
11
3.3 Motors
Motors are instrumental in the operation of many equipment within the AFW system, including
pumps, fans, compressors and valves. They convert electrical energy either from AC or Dc to
Motors have temperature and vibration detection systems, cooling and lubricating systems,
bearings and other support systems that must operate optimally for motors to perform their
intended functions.
3.4 Pumps
Pumps are mechanical devices that are used to move fluids, either liquid or gas. Most pumps are
motor-driven, but in some cases they are powered by either steam turbines or diesel engines.
Pumps have support systems such as temperature and vibration detection systems, cooling and
lubricating systems that must operate correctly for pumps to perform their intended functions.
(Agency, 2019, p. 38). Within the AFW system, there are two types of pumps; Motor-Driven
The motor-driven pumps are multistage, horizontal, centrifugal pumps, they supply up to 440
gpm at discharge pressure of about 1300 psig. The motor-driven pumps are powered by 4.16-
12
Low-low water level in any single steam generator
Loss of one main feed pump (MFP) if power is greater than 80 percent
The turbine driven pumps are multistage, horizontal, centrifugal pumps capable of delivering 880
The automatic start signals for the turbine driven auxiliary feed pumps include;
The condensate storage tanks provide water to the suctions of the auxiliary feedwater pumps for
supplying AFW to the Steam Generators. The tanks also provide usable water volume for plant
start-up including transient demands. The tanks always have water capacity required for safe
shutdown of the plant, this level always maintained by the height of the tank penetrations.
13
The condensate storage tank has a capacity of 480,000 gallons, and it is designed to maintain a
minimum level of 66% (340,000 gallons). The minimum water level satisfies the grade cold
shutdown capability that enables the plant to operate in the hot standby mode for 4 hours
followed by a 5 hour orderly plant cooldown ("NRC: Auxiliary Feedwater (AFW) System," n.d.)
14
4 AFW System Fault Analysis
Variations in components boundaries are considered one of primary reasons for susceptibility to
failures. Individual component boundaries highly influence failure rates depending on particular
components and system designs. Each component has a boundary and points of interference with
other systems.
A system can be broken down into their subsystems and components for fault analysis, an
failure events that may result into entire system failures. It is common that systems that function
dynamically are more prone to failure that static system components (Lee & McCormick, 2012,
p.143).
This refers to any failure that could possibly occur on components. All modes is used in
instances where detailed data for a particular failure mode is unavailable, thereby implying that
the particular component should be taken out of service under normal operation conditions.
4.2.1.2 Degraded
This refers to any failure that causes a component not to perform their function accurately, in the
expected capacity.
15
4.2.1.3 Failure to Change position
This refers to instances where components fail to move to a new required position. It is common
to components that perform their functions by moving from one state to another such as valves
and breakers.
This refers to instances where components fail to remain in a required position, it is applicable to
components that operate by changing state between two positions. Failure typically causes
move to a new, closed position. Used where components operate by moving from one position to
Also a subset of failure to change position mode, characterized by a components failure to move
to a new, open position. Applicable to components whose performance are subjective to moving
This failure mode is applicable to components that do not move in order to perform their
when demanded. This failure mode is also applicable as a composite failure mode for a pump not
16
4.2.1.8 Short to Ground
The short to ground failure mode characterizes ground connections of any component where
unable to perform their functions when isolation to ground is broken and a power to ground
circuit formed.
4.2.1.11 Plug/Rupture
This is a failure mode unique to piping that is characteristic of rupture to a pipe segment that
This refers to a component failing to continue operation (rotational movement) when required. It
Refers to component fail to start when demanded, applicable to all the components that operate
17
4.2.1.14 Spurious Function
Refers to failure of components to retain their current status, such as change state without any
trigger to dos so. It is used for components that perform their functions by existing in a particular
4.2.1.15 Rupture
Rupture characterizes inability to retain liquid boundaries. It is applicable to all components that
18
4.3 Classification of Failure Events
primary/secondary/command failures or failures due to human errors (Lee & McCormick, 2012,
p.144).
This are faults that arise when a system components perform their intended functions but fail due
to basic mode events such as structural faults. Primary faults often occur as a result of wear; high
performance systems experience primary faults arise from wear due to improper maintenance of
replacement of components or component part. Wears can also arise from poor designs or
fabrications, however this is common in lower performance systems (Lee & McCormick, 2012,
p.144).
environment other than the one it was designed for. Such faults are known as Secondary faults.
Command faults on the other hand arise from components operating at the wrong place or time,
an example is a pressure vessel failing because of an operator incorrectly closing a valve. (Lee &
Common cause failures (CCF) are described as failures that result from two or more component
failures arising from the same inherent flaw in design, manufacture, operation or maintenance of
the components. Common cause failures occurring on multiple system components significantly
19
In order to classify an event as resulting from a common cause failure, the following conditions
The component failures or degradations must result from a single shared cause
time.
Two or more individual components must fail or be degraded during demand, in-
service testing or from deficiencies that would have resulted in a failure had the demand
The component failures are not due to the failure of equipment outside the
Common cause failures often result from concurrent existence of two factors; components
susceptibility to failure due to a particular cause of failure and a coupling factor that results into a
condition where multiple components are affected by the same cause (Lee & McCormick, 2012,
p.147).
Human errors can be generally classified into either omission errors or errors of commission in
human reliability analysis. Omission errors refer to scenarios where operators do not take any
action or where action taken does not make any significant difference with lack of action (Lee &
McCormick, 2012, p.148), whereas errors of commission refer to actions taken that significantly
20
Human interaction with the nuclear plant are majorly during routine operations, testing, and
maintenance and plant safety issues. Human response to accidents are mostly always under
21
References
Lee, J. C., & McCormick, N. J. (2012). Risk and Safety Analysis of Nuclear Systems.
https://nrcoe.inl.gov/resultsdb/SysStudy/AFW.aspx
22