Sei sulla pagina 1di 1

NOTE

ALL DIMENSIONS IN MM

LEGEND & NOTES ON MECHANICAL DRAWINGS ALL DISCREPANCIES SHOULD BE REPORTED


TO THE ARCHITECT

GENERAL NOTES
LEGEND All dispensers either shall be installed on a concrete foundation and installed
in accordance with manufacturer's instructions to ensure protection against
DATE REVISION SIGN

physical damage.
SYMBOL DESCRIPTION
All vapor vents shall be terminated at least 12 feet above grade, 5 feet from
P1 Ø 2" SCH - 40 G.I. PMS PIPE property lines and 5 feet from building openings.

P2 Ø 2" SCH - 40 G.I. PMS PIPE All vent pipings shall be installed so they will drain toward the tank without traps in
which liquids can collect. The vent shall not be subject to physical damage or
Ø 2" SCH - 40 G.I. PMS PIPE vibration. Installation shall be in accordance to NFPA 30, Section 4.2.5.1.2.
P3
CLIENT
All tanks shall be top-loaded tanks, and metallic fill pipe shall be installed to
P4 Ø 2" SCH - 40 G.I. DIESEL PIPE
minimize the generation of static electricity by terminating the pipe within 150mm
of the bottom of the tank, and shall be installed in such a manner that avoids
EJILINK - KU NIG. LTD.
P5 Ø 2" SCH - 40 G.I. DIESEL PIPE
excessive vibration.
PV Ø1 1/2" SCH - 40 G.I. VAPOR RECOVERY PIPE
All piping between storage tanks and dispensers shall be installed to slope PROJECT
backwards to the storage tanks.
PK 2" SCH - 40 G.I. KEROSENE PIPE
PROPOSED PETROL STATION
All tanks shall be equipped with overfill prevention to prevent being filled in excess UMUEZEMA VILLAGE, OJOTO,
PGS Ø2" SCH - 40 G.I. PMS SUPPLY (INLET) PIPE
of 95 % of its capacity. IDEMILI SOUTH L. G. A
PIPE FITTING (ELBOW) ANAMBRA STATE
All tanks shall be provided with a spill container having a capacity of not less than
25 L for each tank fill connection. the spill containers shall be non-combustible and
PIPE FITTING (STRAIGHT TEE) M & E CONSULTANT
shall be fixed to the tank and equipped with a manual drain valve.
PIPE FITTING (CROSS)
Storm water drainage system shall provide for oil/water separator to collect storm
water before discharge to public drain system.
PIPE FITTING (45 DEG. BEND)
PLOT 26 DBS ROAD, ASABA, DELTA STATE.
PIPE FITTING (BEND 90 DEG. DOWN)
E-mail: awandgnresources@gmail.com
STORAGE TANK DIMENSIONS
0803-091-6984, 0808-470-7466
VV VAPOR VENT
TANK No. COMPART. CAPACITY PRODUCT Ø (m) LENGTH
TR1, TR2, ... TR6 CONCRETE PIPE TRENCH BELOW GRADE T-1 02 19,000 L. PETROL 2.40 4.2m
DESIGN TEAM
Engr. Godwin E. Iweka
MH TANK INSPECTION MANHOLE T-2 02 19,000 L. PETROL 2.40 4.2m Engr. Stanley Ogum
T-3 03 28,000 L. PETROL 2.40 6.5m Engr. Engr. Agboro Broadman
P1, P2, ...P9 FUEL DISPENSERS Wilson Odu
T-4 02 19,000 L. DIESEL 2.40 4.2m
T1, T2, ... T7 UNDERGROUND STORAGE TANKS AND CONNECTION PIPES
T-5 02 19,000 L. DIESEL 2.40 4.2m
FHR FIRE HOSE REEL
T-6 02 19,000 L. KEROSENE 2.40 4.2m

OWT OVERHEAD WATER STORAGE TANK 02 19,000 L. SPARE 2.40 4.2m


DWG TITLE DWG. No.
T-7
SITE PLAN M 01

PROJECT No.
DATE
ACM/0319 MARCH, 2019