DESIGN CRITERIA A member of Building Code Compliance Association
#E00001
CODE REFERENCE BUILDING CODE 2012 INTERNATIONAL BUILDING CODE
DESIGN STANDARDS AISC 13TH EDITION, ACI 318 APPENDIX D
IBC 1603.1.1 LIVE LOAD 5 PSF LATERAL
OP-01 DISTRIBUTED WALL LOAD 107 PLF

TOTAL WALL WEIGHT 2220 LBS

MAXIMUM CONCENTRATED LOAD


IBC TABLE 1607.1 1110 LBS
PER DROP

MATERIAL SPECIFICATIONS

MATERIAL STRENGTH SPECIFICATIONS NOTES

FLOOR CONCRETE USED FOR CONNECTION IN THIS DESIGN IS 1


ASSUMED TO BE MIN. 4" THICK WITH A MINIMUM IN-SITU COMPRESSIVE
STRENGTH OF 4,000 PSI. CONCRETE, REINFORCEMENT OR
CONCRETE
STRUCTURAL METAL DECK THAT IS VISIBLY DETERIORATED OR
DAMAGED SHALL BE BROUGHT TO THE ATTENTION OF THE
STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.
HOT ROLLED STEEL SHAPES SHALL BE SIZES NOTED ON PLANS AND 2
STRUCTURAL STEEL
DETAILS AND GRADES AS NOTED BELOW.
ANCHOR BOLTS ANCHORS SHALL BE HILTI KWIK BOLT TZ-CS 3

WELDED CONNECTIONS SHALL BE SHIELDED METAL ARC WELDING 4


(SMAW) WITH E70 ELECTRODES OR METAL INERT GAS WELDING (MIG)
WELDS WITH ER70S-6 WIRE. ULTRASONIC TEST TO BE PERFORMED
LVL 2 FOR THE THICKNENESS OF THE STRUCTURAL MEMBER EXCEEDING 5/16
INCHES.
OP-01 CONNECTION BOLTS SHALL BE 3/4" DIAMETER A325 BEARING TYPE 'N' 6
LVL 1 CONNECTION BOLTS
UNLESS NOTED OTHERWISE.

CPH 063-233 (TRW PO# 11449IA)


ALIGHT SOLUTIONS
1. TAKE PRECAUTION TO NOT DAMAGE EXISTING BEAM OR SLAB REINFORCING WHILE DRILLING FOR ANCHORS-TYP. IT IS RECOMMEND TO XRAY
MEMBERS FOR REINFORCEMENT LOCATIONS PRIOR DRILLING.

8770 NEW TRAILS DRIVE


2. UNLESS NOTED OTHERWISE ON PLAN, STRUCTURAL STEEL GRADES SHALL BE AS FOLLOWS:

THE WOODLANDS, TX
2.1. BEAMS ASTM A992
2.2. ANGLES ASTM A36
2.3. ROLLED COLUMNS ASTM A992
2.4. PIPE COLUMNS ASTM A53
2.5. TUBE SECTIONS ASTM A500
2.6. BASE PLATES ASTM A36
3. ANCHOR DESIGN INCLUDES MAX SHEAR 1,000 PSI AND MAX TENSION 2,500 PSI.
4. ALL WELDS SHALL BE 3/16" IN SIZE AND 3" IN LENGTH U.N.O.
5. MAXIMUM CONCENTRATED LIVE LOADS ARE LIMITED TO 2,000 LBS AS REQUIRED BY IBC TABLE 1607.1 FOR OCCUPANCY OFFICE BUILDING.
6. IMPACT TO THE STRUCTURE HAS NOT BEEN EVALUATED FOR THIS LOAD AND SHOULD BE PERFORMED BY THE BUILDING STRUCTURAL ENGINEER.
7. CPH ENGINEERING IS RESPONSIBLE ONLY FOR THE STRUCTURAL DESIGN OF THE MOVABLE PARTITION SUPPORT SYSTEM. CPH ENGINEERING IS
NOT THE ENGINEER OF RECORD (E.O.R) FOR THE STRUCTURE IN WHICH THIS WALL IS BEING INSTALLED. THIS ENGINEERED DESIGN IS INTENDED
TO BE SUBMITTED TO THE E.O.R. FOR APPROVAL.

NOTE: ALL DIMENSIONS SHOWN ON THE PLAN ARE TO BE FIELD VERIFIED.

FRAMING PLAN OP-01


1 Scale: 1/4" = 1'-0"

CONSTRUCTION 08/XX/2019
REVISION/ISSUE DATE

Sheet Name:

FRAMING PLAN

Sheet No.:

S-1