Current and Voltage Sensors

7.0 Introduction
EVT Series VoltageWatch
Product Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-2
7
7.1 EVT Series VoltageWatch Voltage Sensors 7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-5
7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-6

7.2 ECS Series CurrentWatch Current Switches


7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-8 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-9

7.3 ECSJ Series CurrentWatch Current Switches


7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-11 7
ECSJ Series CurrentWatch Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-12
Current Switch 7
7.4 ECS7 Series CurrentWatch Current Switches
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-15 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-16
7
7.5 ECSTD Series CurrentWatch Current Switches
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-19 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-20
7
7.6 ECSD Series CurrentWatch Current Switches
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-23 7
EACR Series CurrentWatch
Current Sensor
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-24
7
7.7 EAC Series CurrentWatch Current Sensors
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-26
7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-27 7
7.8 EACR Series CurrentWatch Current Sensors
7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-30
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-31 7
7.9 EDC Series CurrentWatch Current Sensors 7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-33
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-34 7
7.10 EGF Series CurrentWatch Current Sensors 7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-37
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-38 7
7.11 EGFL Series CurrentWatch Current Sensors 7
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-42
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-43
7
Unless otherwise noted, the products contained in this section should not
7
be used for functional safety applications. These products were not designed
or tested to IEC 60947-5-3 or recommended for functional safety. 7
7
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-1


7.0 Current and Voltage Sensors
Introduction

Product Selection Guide


7
7 EVT Series VoltageWatch
Voltage Sensors
ECS Series CurrentWatch
AC Current Switches
ECSJ Series CurrentWatch
AC Current Switches
ECS7 Series CurrentWatch
AC Current Switches

7
7
7
7
7
Page V8-T7-5 Page V8-T7-8 Page V8-T7-11 Page V8-T7-15
7 Overview Overview Overview Overview

7 Eaton’s VoltageWatch™ sensor is a high-


performance, true RMS sensor for sensing
AC current switches for detecting
overcurrent condition.
Jumper selectable AC switches with
solid-state output.
Self-calibrating AC current switch with
solid-state outputs.
voltage in single- and three-phase
7 installations.

Applications Applications Applications Applications


7 Detect below normal or “brown out” voltage Electronic proof of flow—current operated Electronic proof of flow—current operated Conveyors—use current overload models to

7
conditions; protect against possible motor switches eliminate the need for multiple switches eliminate the need for multiple detect conveyor jams caused by scenarios
overheating pipe or duct penetrations and are more pipe or duct penetrations and are more such as side-by-sides
Identify phase-loss conditions by detecting reliable than electro-mechanical pressure or reliable than electro-mechanical pressure or Electronic proof of flow—more reliable than
7 voltage reduction in one or more phases of a
three-phase motor
flow switches
Conveyors—detect jams and overloads
flow switches
Conveyors—detect jams and overloads
electro-mechanical pressure or flow
switches, with no need for pipe or duct

7 Monitor overvoltage conditions associated Lighting circuits—easier to install and more Lighting circuits—easier to install and more penetrations
with regenerative voltage to help in accurate than photocells accurate than photocells Pump protection—provides overload (jams)
diagnosing/avoiding motor drive issues and underload (suction loss) indication
7
Fans, pumps and heating elements—faster Fans, pumps and heating elements—faster
Detect voltage conditions that may cause response than temperature sensors response than temperature sensors
stress in or damage to soft starter Critical motors Critical motors
7 components (SCRs)
Ancillary equipment Ancillary equipment

7 Product Features Product Features Product Features Product Features

True RMS output—allows for use in Universal outputs—NO or NC solid-state Choice of NO or NC solid-state outputs— Self-powered and self-calibrating—
7 situations where power supplied is switch for control circuits up to 240 Vac/dc, 1A at 240 Vac reduces installation costs
non-sinusoidal compatible with most automation systems 0.15A at 30 Vdc Status monitoring, overload and operating
7 Standard 4–20 mA loop powered output—
industry standard output works easily and
Self-powered—cuts installation and
operating costs
15A at 120 Vac
3A at 120 Vac
window options—choose the operating
style that matches your application
reliably with existing controllers 0.15A at 30 Vdc, dual contact
7 Input/output isolation—input and output
Easily adjustable setpoint—increases
application flexibly and speeds start-up Self-powered—cuts installation and
operating costs
Universal output—AC or DC compatibility
with any automation system
circuitry is electrically isolated for improved Solid- or split-core housings—versions
7 safety tailored for each type of installation Easily adjustable setpoint—speeds
start-up and reduces inventory
Compact DIN rail mount enclosure— space- LED indication—provides quick visual
7 saving 35 mm wide enclosure mounts
quickly for an attractive installation
indication of contact status Solid- or split-core housings—choose the
appropriate version for your application
Built-in mounting feet—simple, two-screw
LED indication—provides quick visual
7 panel mount or attach with optional din-rail
mounting kit accessory indication of output contact status
Built-in mounting feet—provide for a secure
7 installation

7 Voltage Range Current Range Current Range Current Range

120, 240, 480V Fixed or adjustable set point, 1–150A Adjustable set point, 1.75–200A Self-calibrating set point, 1.5–150A

7 Approvals Approvals Approvals Approvals

7
UL® UL Listed UL Listed UL Listed
CE (Pending) cUL® Listed cUL Listed cUL Listed
RoHS Compliant cULus cULus cULus
7 CE CE CE

7 (Pending)

V8-T7-2 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
Introduction
7.0
ECSTD Series CurrentWatch ECSD Series CurrentWatch EAC Series CurrentWatch EACR Series CurrentWatch
AC Current Switches DC Current Switches AC Current Sensors RMS Current Sensors 7
7
7
7
7
7
Page V8-T7-19 Page V8-T7-23 Page V8-T7-26 Page V8-T7-30

Overview Overview Overview Overview 7


AC current switches with time delay. DC switch with solid-state or mechanical
relay output.
AC current sensor with analog outputs and
power supply options.
True RMS AC current sensing with
4–20 mA output. 7
7
Applications Applications Applications Applications

Motor protection—serves as an electronic Electronic proof of flow—current operated Automation equipment—analog current VFD controlled loads—monitoring Vdc
7
proof-of-operation; detects current draw switches eliminate the need for multiple reading for remote monitoring and software output indicates how the motor and
changes in motors when they encounter
problems such as pumps running dry or
pipe or duct penetrations alarms attached load are operating 7
Welders—Instant indication of equipment Data loggers—self-powered sensor helps SCR controlled loads—accurate
pending bearing failure; non-intrusive and
less expensive to install than differential
status conserve data logger batteries measurement of phase angle fired or burst
fired (time proportioned) SCRs, with faster
7
pressure flow sensors or thermal switches Large drive motors—provide monitoring for Panel meters—simple connection displays
current measurement than temperature
High inrush or temporary overload
current—adjustable start-up/delay timer
field loss protection
Power supplies—detect and signal over-
power consumption
sensors 7
current condition before equipment damage Switching power supplies and electronic
7
allows 0–15 second delay to eliminate ballasts—true RMS sensing is the most
nuisance trips from high inrush or short UPS—monitors battery output accurate way to measure power supply or
overload conditions ballast input power
Ancillary equipment
7
Product Features Product Features Product Features Product Features 7
Adjustable start-up/delay timer—field Choice of mechanical relay or Highly accurate—factory matched and True RMS output—true RMS technology is
adjustable from 0–15 seconds to eliminate
nuisance alarms due to start-up inrush or
solid-state outputs—
SPDT (Form C) relay, 5.0A at 240 Vac
calibrated single-piece sensor is more
accurate than traditional two-piece, field-
accurate on distorted waveforms like VFD or
SCR outputs
7
7
temporary overcurrent conditions or 30 Vdc installed solutions Jumper-selectable ranges—reduces
Choice of NO/NC AC or universal outputs— Solid-state, NO, 0.15A at 240 Vac/dc Average responding—“average inventory and eliminates zero and span
contact ratings of 1.0A at 240 Vac or Easily adjustable setpoint—speeds start-up responding” algorithm gives an RMS output
7
Isolation—output is magnetically isolated
universal outputs of 0.15A at 240 Vac/dc and reduces inventory on pure sine waves, perfect for constant from the input for safety and elimination of
(NO models) and 0.2A at 135 Vac/dc (NC Compact, one-piece design—easily fits in speed (linear) loads insertion loss (voltage drop)
models) for use with most standard motor
control systems
crowded control panels
Input isolation—safer than shunt/relay
Jumper selectable ranges—the ability to
change input ranges reduces inventory and 7
Improved ease of installation and use— eliminates zero and span
7
combinations
self-powered, split-core models simplify Isolation—output is magnetically isolated
installation, 1.0A AC rating eliminates need Adaptive hysteresis—hysteresis is five
percent of setpoint, allowing closer control from the input for safety and elimination of
for time delay relay, and status LED provides
visual indication of setpoint trip and than fixed-hysteresis switches insertion loss (voltage drop)
7
contact action Solid-core housings
7
Current Range Current Range Current Range Current Range

Adjustable set point, 1.5–200A Varies by model 0–200A 0–200A true RMS
7
Approvals Approvals Approvals Approvals 7
UL Listed UL Listed UL Listed UL Listed
cUL Listed cUL Listed cUL Listed cUL Listed 7
CE CE cULus (except EACP models) cULus
CE marked (except EACP models) CE
7
(Pending) 7
(ECSTD401 and 4025C—No approval) (EACP models not listed)
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-3


7.0 Current and Voltage Sensors
Introduction

EDC Series CurrentWatch EGF Series CurrentWatch EGFL Series CurrentWatch


7 DC Current Sensors Ground Fault Sensors Ground Fault Sensors

7
7
7
7
7
Page V8-T7-33 Page V8-T7-37 Page V8-T7-42

7 Overview Overview Overview

7 Current sensing for DC loads up to 300A


with analog outputs.
Ground fault sensors with solid-state or
mechanical relay outputs.
Ground fault sensors with mechanical
relays.

7 Applications Applications Applications

7 Battery banks—monitors load current,


monitors charging current and verifies
Personnel protection (typically 5 mA)—
detects sensitive ground fault conditions,
Personnel protection (typically 5 mA)—
detects sensitive ground fault conditions,
operation which could cause injury to people, and which could cause injury to people
7 Transportation—measures traction power functions as a sensor and alarm trigger
when applied as an input to an overall
Equipment protection (typically 10 or
or auxiliary loads 30 mA)—for applications where personnel
7 Electric heating elements—monitors heater
ground fault protection system
Equipment protection (typically 10 or
protection is not the primary concern, higher
setpoint capability helps eliminate nuisance
loads with a faster response time than
30 mA)—for applications where personnel tripping
7 temperature sensors
protection is not the primary concern, higher
setpoint capability helps eliminate
Regulatory—meets requirements as
stipulated by governmental and industrial
7 nuisance tripping while still providing
adequate ground fault detection to protect
regulatory groups for ground fault sensing
machine electronics
7
Product Features Product Features Product Features
7 Jumper-selectable ranges—reduces Broad range of options to meet application Broad range of options to meet application
inventory and eliminates zero or span pots needs—NO or NC, solid-state or needs—mechanical relays, normally
7 Isolation—output is magnetically isolated
from the input for safety, also eliminating
mechanical relays, normally energized or
normally de-energized contacts
energized or normally de-energized contacts
Setpoint options maximize ease-of-use and

7
insertion loss (voltage drop) Setpoint options maximize ease-of-use and application flexibility—field selectable 5, 10
Internal power regulation—cuts installation application flexibility—field selectable 5, 10 or 30 mA setpoints on the EGFL “tri-set”
costs and works well, even with or 30 mA setpoints on the EGF “Tri-set” models make user adjustments fast, sure
7 unregulated power models make user adjustments fast, sure
and convenient
and convenient
Compatible with standard equipment—
Split core design and built-in mounting
7 brackets—makes installation quick and Compatible with standard equipment— application on single- and three-phase
easy application on single- and three-phases systems, ideal for use with shunt trip
systems, ideal for use with shunt trip breakers, and magnetically isolated from
7 breakers, and magnetically isolated from
monitored circuit and control power
monitored circuit and control power

7 Current Range Current Range Current Range

7 0–400A Fixed or adjustable 5/10/30 mA trip Tri-Set Adjustable, 5, 10 or 30 mA

Approvals Approvals Approvals


7 UL Listed (Pending) UL Recognized UL Approved
CE CE cULus
7 CE

7
7
7
7
7

V8-T7-4 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
VoltageWatch EVT Series
7.1
Contents
EVT Series VoltageWatch Voltage Sensors
Description Page
7
EVT Series VoltageWatch Voltage Sensors 7
Standards and Certifications . . . . . . . . . . . . . . V8-T7-6
Catalog Number Selection . . . . . . . . . . . . . . . . V8-T7-6 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-6
Technical Data and Specifications . . . . . . . . . . V8-T7-7 7
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-7 7
7
7
7
7
7
EVT Series VoltageWatch Voltage Sensors 7
Product Description Application Description 7
Eaton’s VoltageWatch™ True RMS Voltage Monitoring Example Application—Phase Loss
sensor is a high-performance, ● Detect below normal or 7
true RMS sensor for sensing “brown out” voltage
voltage in single- and three- conditions; protect against
PLC
24 Vdc Supply
20 mA Transducer Output
7
phase installations. possible motor overheating
– +
500 Vac

7
19.36 mA Transducer Output
Applicable on nominal circuits ● Identify phase-loss VTR 480 Vac
AC Voltage
Phase to Phase
of 120V, 240V and 480V, this conditions by detecting VTR 460 Vac
18.72 mA Transducer Output
voltage sensor provides a
7
VTR
voltage reduction in one or Motor
fully isolated analog output more phases of a three- Control
Signal Zero Vac 4 mA Transducer Output
proportional to rated nominal
voltage in both sinusoidal and

phase motor
Monitor overvoltage
Motor
Starter
7
non-sinusoidal (variable
frequency) situations. It is
housed in a slim, compact,
conditions associated with
regenerative voltage to 7
help in diagnosing/avoiding
easy-to-install DIN rail mount
enclosure. motor drive issues 7
● Detect voltage conditions
Ideal for situations where that may cause stress in or Features 7
power quality is of interest or damage to soft starter
True RMS Output— Input/Output Isolation—
7
● ●
concern, the VoltageWatch components (SCRs)
sensor facilitates monitoring Allows for use in situations Input and output circuitry is
of supply voltage levels, where power supplied is electrically isolated for
identifying undervoltage or non-sinusoidal, such as improved safety 7
overvoltage conditions, and VFD applications, poor ● Compact DIN Rail Mount
helping to protect critical power quality installations
or other electrically harsh/
Enclosure—Space-saving 7
motors and electronics. 35 mm wide enclosure
Designed with an industry-
standard 4–20 mA output, ●
challenging environments
Standard 4–20 mA Loop
mounts quickly for an
attractive installation
7
VoltageWatch is easily
coupled to a data logger,
Powered Output—
Industry standard output 7
panel meter or PLC to enable works easily and reliably
basic trending of operational with existing controllers, 7
status of low voltage circuits data loggers and SCADA
up to real-time monitoring equipment 7
and reporting of supply
voltage levels. 7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-5


7.1 Current and Voltage Sensors
VoltageWatch EVT Series

Standards and Certifications


7 ● UL
DANGER
THIS SENSOR IS NOT A
7 CE (Pending)

SAFETY DEVICE AND IS NOT
● RoHS Compliant INTENDED TO BE USED AS A
7 SAFETY DEVICE. This sensor
is designed only to detect
7
(Pending)
and read certain data in an
electronic manner and
perform no use apart from
7 that, specifically no safety-
related use. This sensor
7 product does not include
self-checking redundant
7 circuitry, and the failure of
this sensor product could
7 cause either an energized
or de-energized output
condition, which could result
7 in death, serious bodily
injury, or property damage.
7
7
Catalog Number Selection
7 VoltageWatch EVT Series—Top Terminal Current Sensors
7 EVT 1 - 420 - 24L
7
Standard Family Name Nominal Range Output Type Supply Voltage
7 EVT = VoltageWatch sensor 1 = 120V 420 = 4–20 mA 24L = 24V Loop powered
3 = 240V
7 4 = 480V

7
7 Product Selection

7 EVT Series VoltageWatch EVT Series—Top Terminal Current Sensors


Power Supply Output Signal Nominal Voltage Catalog Number
7 24 Vdc loop powered 4–20 mA 120 EVT1-4120-24L

7 240 EVT3-4420-24L

7 480 EVT4-4420-24L

7
7
7
7
7
7
7
7

V8-T7-6 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
VoltageWatch EVT Series
7.1
Technical Data and Specifications Wiring Diagram
7
VoltageWatch EVT Series VoltageWatch EVT Series
Description Specification 24 Vdc Power 7
Load
Power supply
Input
24 Vdc loop-powered
120V, 240V, 480V
(–)(+) (+) Controller
(–) Meter, etc.
7
Input over-range +15% of nominal range
- +
7
Output 4–20 mA proportional; capped at 24 mA maximum
Response time 250 ms (to 90% value) Output 7
Accuracy <1%
Linearity <0.5%
7
Loading <500 ohms
7
Isolation voltage 2500 Vac
Frequency range 40 Hz–5 kHz 7
Operating temperature –22° to 140°F (–30° to 60°C)
Mounting DIN rail compatible 7
7
Case UL 94 V0 flammability rated; noncorrosive thermoplastic
Environmental 14° to 122°F (–10° to 50°C), 0–95% RH noncondensing
EMC/immunity EN50081-1, EN50082-2 Line Voltage
(120, 240, 480) 7
Ripple <1% (peak to peak)
Listings UL/cUL and CE pending 7
7
Dimensions
Approximate Dimensions in Inches (mm)
7
Complete Unit 7
7
7
7
2.66 (67.6)
7
1.77
(45.0)
7
7
2.39 (60.7) 7
7
3.53 (89.7) 1.40 (35.6)
7
7
7
7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-7


7.2 Current and Voltage Sensors
CurrentWatch ECS Series

Contents
7 ECS Series CurrentWatch Current Switches
Description Page
7 ECS Series CurrentWatch Current Switches
Standards and Certifications . . . . . . . . . . . . . . . V8-T7-9
7 Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-9
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-9
7 Technical Data and Specifications . . . . . . . . . . V8-T7-10
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-10
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-10

7
7
7
7
7
7 ECS Series CurrentWatch Current Switches
7 Product Description Example Application—
The CurrentWatch™ ECS Any change in current can be Pump Jam and Suction Loss Protection
7 Series from Eaton’s electrical sensed with the ECS Series.
Jam

AMPS
sector is a family of solid- A change in current may Overload Setpoint
B/I Card

7 state adjustable current


switches, ideal for providing
indicate motor failure, belt
loss/slippage or mechanical PLC
Motor
Off

7 status information on failure. Any of these events Digital Normal Operation


Input
electrical equipment. The can cause the current to drop Motor
ECS is excellent for new significantly, tripping the Control
7 installations, where the switch and notifying the Signal Time

conductors run through the controller.


7 housing, requiring no cutting.
These switches are also ideal
Motor
7 for retrofits, since split-core
models can be opened to fit Application Description Starter

around existing conductors.


7 The current switch is
Typical Applications Current Switch

accurate, reliable and easy


● Electronic Proof of
7 to install. Flow—Current operated
switches eliminate the
Features
7 The ECS can sense
continuous currents from
need for multiple pipe or
duct penetrations and are ● Universal Outputs—NO ● Solid- or Split-Core
1 to 150A and does not more reliable than electro-
7
or NC solid-state switch for Housings—Versions
require any supply voltage, mechanical pressure or control circuits up to 240 tailored for each type of
as the power required is flow switches Vac/dc, compatible with installation
7 induced from the monitored
conductor. The output is a
● Conveyors—Detect jams most automation systems ● LED Indication—Provides
and overloads ● Self-Powered—Cuts quick visual indication of
7 non-polarity-sensitive solid-
state contact for switching
● Lighting Circuits—Easier installation and operating contact status
to install and more costs ● Built-In Mounting Feet—
AC and DC circuits up to
7 240 Vac/dc. This switch also
accurate than photocells ● Easily Adjustable Simple, two-screw panel
includes an LED indicating
● Fans, Pumps and Heating Setpoint—Increases mount or attach with
7 two states: on and below trip Elements—Faster
response than temperature
application flexibly and
speeds start-up
optional DIN-rail mounting
kit accessory
point, and above trip point
7 with contacts energized. All
ECS Series switches carry an ●
sensors
Critical Motors
7 unconditional five-year
warranty.
● Ancillary Equipment

7 For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),


in Canada call 1-800-268-3578.
For the most current information
7 on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184.

V8-T7-8 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECS Series
7.2
Standards and Certifications
● UL Listed
DANGER 7
THIS SENSOR IS NOT A
cUL Listed
7

SAFETY DEVICE AND IS NOT
● CE Certified INTENDED TO BE USED AS A
SAFETY DEVICE. This sensor
is designed only to detect
7
and read certain data in an
electronic manner and
7
perform no use apart from
that, specifically no safety- 7
related use. This sensor
product does not include 7
self-checking redundant
circuitry, and the failure of
this sensor product could
7
cause either an energized
or de-energized output 7
condition, which could result
in death, serious bodily 7
injury, or property damage.
7
Product Selection
7
ECS Series CurrentWatch Current Switches

Top Terminal Current Switches


7
Power Supply Aperture Size Output Signal Setpoint and LED Configuration Catalog Number 7
Solid-Core Housing Solid-Core Housing
Self powered 0.74 in (19 mm) Normally open Adjustable 1–150A setpoint with LED ECSNOASC 7
(no external power needed)
7
Fixed 1.0A setpoint no LED ECSNOFSC
Fixed 5.5A setpoint no LED ECSNOFSCY1
Normally closed Adjustable 1–150A setpoint with LED ECSNCASC
7
Fixed 1.0A setpoint no LED ECSNCFSC
Split-Core Housing Split-Core Housing 7
Self powered 0.85 in (21.6 mm) Normally open Adjustable 1.75–150A setpoint with LED ECSNOASP
(no external power needed)
Fixed 1.5A setpoint no LED ECSNOFSP
7
Normally closed Adjustable 1.75–150A setpoint with LED ECSNCASP 7
Fixed 1.5A setpoint no LED ECSNCFSP
7
7
Accessories
7
DIN Rail
Mounting Kit
ECS Series CurrentWatch
Current Switches 7
Description Catalog Number
7
DIN rail mounting kit 1 EDINKIT

7
7
Note 7
1 Sensor pictured for reference and not included in kit.

7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-9


7.2 Current and Voltage Sensors
CurrentWatch ECS Series

Technical Data and Specifications


7
7
ECS Series CurrentWatch Current Switches
Description Specification Description Specification

7 Power supply Self-powered—no power supply needed Overload Fixed setpoint, NO models: 6 sec. at 500A; 1 sec. at 1000A
All other models: 6 sec. at 400A; 1 sec. at 1000A
Output Magnetically isolated solid-state switch
Maximum continuous Amps: 250A
7 Output rating NO version: 0.15A at 240 Vac/dc
Isolation voltage UL listed to 1270 Vac, tested to 5000 Vac
NC version: 0.2A at 135 Vac/dc
7 Models ending Y1: 5.0A, 125 Vac, 30 Vdc Frequency range 6–100 Hz
Off-state leakage <10 μA Sensing aperture Solid-core housings: 0.74 in (19 mm)

7 Response time 120 ms


Housing
Split-core housings: 0.85 in (21.6 mm)
UL94 V0 flammability rated
Setpoint range Solid-core housings: 1–150A
7 Split-core housings: 1.75–150A Environmental Operating temperature: –58° to 122°F (–50° to 50°C)
Humidity: 0–95% RH, non-condensing
Hysteresis 5% of setpoint
7
7 Wiring Diagram

7 ECS Series CurrentWatch Current Switches


Normally open (NO) models shown
7
AC or DC AC or DC
7 Power Load

7
7 Monitored Wire

7 Current Switch

7
7 Dimensions
7 Approximate Dimensions in Inches (mm)
Solid-Core Housing Split Core Housing
7 3.03 3.04 0.19 Dia.
(77.0) (77.2)
7
(4.8)

0.93
7 (23.6) 1.19
(30.2)

7 0.19 Dia.
(4.8) 2.40
(61.0) 3.53
7 0.74 Dia.
(89.7)
2.40
(19)
7
(61)
2.18

7
(55.4)

7 2.25
(57.2) 0.85 (21.6)

7
3.50
(88.9)

7 0.85 (21.6)

7
7

V8-T7-10 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECSJ Series
7.3
Contents
ECSJ Series CurrentWatch Current Switches
Description Page
7
ECSJ Series CurrentWatch Current Switches 7
Standards and Certifications . . . . . . . . . . . . . . V8-T7-12
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-12 7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-13
Technical Data and Specifications . . . . . . . . . . V8-T7-13 7
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-14
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-14 7
7
7
7
7
7
ECSJ Series CurrentWatch Current Switches 7
Product Description Application Description 7
The CurrentWatch ECSJ Typical Applications Example Application—
Series current operated ● Electronic Proof of Pump Jam and Suction Loss Protection 7
switches from Eaton’s Flow—Current operated Jam
7

AMPS
electrical sector provide the switches eliminate the B/I Card Overload Setpoint
same dependable indication need for multiple pipe or Motor
of status offered by the
CurrentWatch ECS Series,
duct penetrations and are PLC
Digital Normal Operation
Off 7
more reliable than electro- Input
but with the added benefit of
increased setpoint precision.
mechanical pressure or
flow switches
Motor
Control
Time
7
Signal
A choice of three, jumper-
selectable input ranges
● Conveyors—Detect jams
and overloads
7
allows the ECSJ Series to be
tailored to an application, ● Lighting Circuits—Easier
to install and more Motor 7
providing more precise Starter
accurate than photocells
control through improved
setpoint resolution. Self- ● Fans, Pumps and Heating 7
Current Switch
powering, isolated solid-state Elements—Faster
outputs, 1–6A, 6–40A and response than temperature 7
40–200A input ranges, and a sensors
choice of split- or solid-core ● Critical Motors Features 7
enclosures are standard. ● Ancillary Equipment ● Choice of NO or NC ● Solid- or Split-Core
For typical applications of the
Solid-State Outputs— Housings—Choose the 7
● 1A at 240 Vac appropriate version for your
CurrentWatch ECSJ Series,
see listing on this page. ● 0.15A at 30 Vdc application 7
● 15A at 120 Vac
● LED Indication—Provides
● 3A at 120 Vac
quick visual indication of
output contact status
7
● 0.15A at 30 Vdc, dual
contact
● Built-In Mounting Feet—
Provide for a secure 7
● Self-Powered—Cuts installation
installation and operating ● UL, cUL and CE 7
costs Approved—Accepted
● Easily Adjustable worldwide 7
Setpoint—Speeds start-up
and reduces inventory 7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-11


7.3 Current and Voltage Sensors
CurrentWatch ECSJ Series

Standards and Certifications


7 ● UL Listed
DANGER
THIS SENSOR IS NOT A
7 cUL Listed

SAFETY DEVICE AND IS NOT
● CE Certified INTENDED TO BE USED AS A
7 ● UL 508 Industrial Control
Equipment (USA and
SAFETY DEVICE. This sensor
is designed only to detect
7 Canada) and read certain data in an
electronic manner and
perform no use apart from
7 that, specifically no safety-
related use. This sensor
7 product does not include
self-checking redundant
7 circuitry, and the failure of
this sensor product could
7 cause either an energized
or de-energized output
condition, which could result
7 in death, serious bodily
injury, or property damage.
7
Product Selection
7 ECSJ Series CurrentWatch Current Switches
7 Front and Top Terminal Switches

7 Power Supply Aperture Size Output Type, Voltage and Rating Setpoint and LED Configuration Catalog Number
Solid-Core Housing Solid-Core Housing with Front Terminal
7
with Front Terminal
Self-powered 0.55 in (14 mm) Normally open, 1A at 240 Vac Adjustable 1–6, 6–40 or 40–175A ECSJ400SC
(no external power needed) setpoint with LED

7 Normally open, 15A at 120 Vac,


10A at 240 Vac
Adjustable 1–6, 6–40 or 40–175A
setpoint with LED
ECSJ406SC 1

7 Normally closed, 1A at 240 Vac Adjustable 1–6, 6–40 or 40–175A


setpoint with LED
ECSJ401SC

7 Normally closed, 15A at 120 Vac,


10A at 240 Vac
Adjustable 1–6, 6–40 or 40–175A
setpoint with LED
ECSJ407SC 1

7 Dual contact, NO and NC,


0.15A at 30 Vdc
Adjustable 1–6, 6–40 or 40–175A
setpoint without LED
ECSJ430SC 1

7 Normally open, 0.15A at 30 Vdc Adjustable 1–6, 6–40 or 40–175A


setpoint with LED
ECSJ420SC

7
Adjustable 1–6, 6–40 or 40–175A ECSJ424SC
setpoint without LED
Normally closed, 0.15A at 30 Vdc Adjustable 1–6, 6–40 or 40–175A ECSJ421SC
7 setpoint with LED
Solid-Core Housing Solid-Core Housing with Top Terminal
7 with Top Terminal
Self-powered 0.74 in (19 mm) Normally open, 3A at 120 Vac Adjustable 1–6, 6–40 or 40–175A ECSJ404SC
(no external power needed) setpoint with LED
7
7
Normally closed, 3A at 120 Vac Adjustable 1–6, 6–40 or 40–175A ECSJ405SC
setpoint with LED

7 Split-Core Housing Split-Core Housing

7 Self-powered
(no external power needed)
0.85 in (21.6 mm) Normally open, 1A at 240 Vac Adjustable 1.75–6, 6–40 or 40–200A
setpoint with LED
ECSJ402SP

7
Normally closed, 1A at 240 Vac Adjustable 1.75–6, 6–40 or 40–200A ECSJ403SP
setpoint with LED
Normally open, 0.15A at 30 Vdc Adjustable 1.75–6, 6–40 or 40–200A ECSJ422SP
7 setpoint with LED
Normally closed, 0.15A at 30 Vdc Adjustable 1.75–6, 6–40 or 40–200A ECSJ423SP
7 setpoint with LED

7
Note
1 Unit features built-in heatsink that adds to height. See dimension drawings on Page V8-T7-14 for details.

V8-T7-12 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECSJ Series
7.3
Accessories
7
ECSJ Series CurrentWatch
DIN Rail
Mounting Kit Current Switches 7
7
Description Catalog Number
DIN rail mounting kit 1 EDINKIT

7
7
7
Technical Data and Specifications 7
ECSJ Series CurrentWatch Current Switches 7
Description AC Solid-State Output Specification DC Solid-State Output Specification
Power supply Self-powered—no power supply needed Self-powered—no power supply needed
7
Output
Output rating
Isolated solid-state switch Isolated solid-state switch
7
Standard models 1.0A at 240 Vac 0.15A at 30 Vdc
7
High current ECSJ404SC and ECSJ405SC: 3.0A at 120 Vac ECSJ430SC: 0.15A at 30 Vdc, dual contact, NO and NC
switching models
7
Very high current ECSJ406SC and —
switching models
Off-state leakage
ECSJ407SC: 15A at 120 Vac, 10A at 240 Vac
NO models: <10 μA NO models: <10 μA
7
7
NC models: 2.5 mA NC models: 2.5 mA
Response time 40–120 ms 40–120 ms
Setpoint range (adjustable) Solid-core models: 1–6, 6–40 and 40–175A
Split-core models: 1.75–6, 6–40 and 40–200A
Solid-core models: 1–6, 6–40 and 40–175A
Split-core models: 1.75–6, 6–40 and 40–200A
7
Hysteresis Low: 6%; mid: 4%; high: 3% Low: 6%; mid: 4%; high: 3%
7
Isolation voltage UL listed to 1270 Vac, tested to 5000 Vac UL listed to 1270 Vac, tested to 5000 Vac
Frequency range 6–100 Hz 6–100 Hz 7
Sensing aperture Solid-core, front terminal models: 0.55 in (14 mm) Solid-core, front terminal models: 0.55 in (14 mm)
Solid-core, top terminal models: 0.74 in (19 mm)
Split-core models: 0.85 in (21.6 mm) sq.
Solid-core, top terminal models: 0.74 in (19 mm)
Split-core models: 0.85 in (21.6 mm) sq.
7
Housing UL94 V0 flammability rated UL94 V0 flammability rated
7
Environmental Operating temperature: –58° to 122°F (–50° to 50°C) Operating temperature: –58° to 122°F (–50° to 50°C)
Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing
7
Overload Ratings
7
Maximum Amperes 7
Housing Range Six Seconds One Second
Solid-core 1–6A 400A 600A 7
6–40A 500A 800A
40–175A 800A 1200A 7
Split-core 1.75–6A
6–40A
400A
500A
600A
800A
7
40–200A 800A 1200A 7
Note
1 Sensor pictured for reference and not included in kit. 7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-13


7.3 Current and Voltage Sensors
CurrentWatch ECSJ Series

Wiring Diagrams 12
7
All Normally Open (NO) Models ECSJ430SC (Dual Contact, NO and NC)
7
7 Output
Range Jumper
Output
Range Jumper
None R None R

7 Setpoint LOW MID HIGH SmartLED Setpoint LOW MID HIGH SmartLED

7 All Normally Closed (NC) Models

7
Output
7 Range Jumper
None R
Setpoint LOW MID HIGH SmartLED
7
7 Dimensions
Approximate Dimensions in Inches (mm)
7 All Solid-Core Models with Front Terminals
Except ECSJ406SC and ECSJ407SC All Solid-Core Models with Top Terminals
7 2.75 3.03
(69.9) (77.0)
7 0.93
0.92 (23.4)
(23.6)
7
0.19
(4.8)
Dia. 0.19 Dia.
7 2.16
(54.9)
(4.8) 2.40
(61.0)

7 0.55
0.74 Dia.
(19)
(14)

7 Dia. 2.18
2.18 (55.4)
(55.4)

7
7 3.30
(83.8)
3.50
(88.9)

7 ECSJ406SC and ECSJ407SC Solid-Core


Models with Front Terminals All Split-Core Models
7 3.04 0.19 Dia.
2.75
(77.2)
7
(69.9) (4.8)

0.92

7
(23.4) 1.19
0.19 (30.2)
(4.8)

7
dia.
2.16 3.53
(54.9) (89.7)

7 2.40
(61)
0.55

7 2.49
(63.2) 2.18
(14.0)
dia.
(55.4)

7 2.25
(57.2) 0.85 (21.6)
7 Heatsink

3.30
7 (83.8)
0.85 (21.6)

7 Notes
1 Terminals are #6 screws.

7 2 DC contacts are polarity sensitive.

V8-T7-14 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECS7 Series
7.4
Contents
ECS7 Series CurrentWatch Current Switches
Description Page
7
ECS7 Series CurrentWatch Current Switches 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-16
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-16 7
Technical Data and Specifications . . . . . . . . . . V8-T7-17
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-18 7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-18
7
7
7
7
7
7
ECS7 Series CurrentWatch Current Switches 7
Product Description Application Description Features Standards and Certifications 7
The CurrentWatch ECS7 Typical Applications ● Self-Powered and Self- ● UL Listed
Series load monitoring ● Conveyors—Use current Calibrating—Reduces ● cUL Listed 7
switches from Eaton’s overload models to detect installation costs ● CE Certified
electrical sector are designed conveyor jams caused by ● Status Monitoring, ● UL 508 Industrial Control 7
for overload, underload or scenarios such as side-by- Overload and Operating Equipment (USA and
operating window
applications. Upon sensing an
sides Window Options— Canada) 7
● Electronic Proof of Choose the operating style
average operating current,
the ECS7 Series self-learns
Flow—More reliable than that matches your
application
7
electro-mechanical
and establishes a limit-alarm Universal Output—AC
7

pressure or flow switches,
trip point based on ±15% of or DC compatibility with
with no need for pipe or
the average expected current any automation system
draw. The ECS7 Series is

duct penetrations
Pump Protection— ● UL, cUL and CE 7
available in solid- or split-core DANGER
Provides overload (jams) Approved—Accepted
housing styles.
and underload (suction worldwide THIS SENSOR IS NOT A 7
For typical applications of the loss) indication SAFETY DEVICE AND IS NOT
CurrentWatch ECS7 Series, INTENDED TO BE USED AS A 7
see listing on this page. SAFETY DEVICE. This sensor
is designed only to detect 7
and read certain data in an
electronic manner and
perform no use apart from
7
that, specifically no safety-
related use. This sensor 7
product does not include
self-checking redundant 7
circuitry, and the failure of
this sensor product could
cause either an energized
7
or de-energized output
condition, which could result 7
in death, serious bodily
injury, or property damage. 7
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-15


7.4 Current and Voltage Sensors
CurrentWatch ECS7 Series

Product Selection
7
ECS7 Series CurrentWatch Current Switches
7
Front and Top Terminal Switches
7 Power Supply Output Type Aperture Size Intelligent Logic Catalog Number

7
Solid-Core Housing Solid-Core Housing
Self-powered Normally open 0.74 in (19 mm) Over/underload, 1.5–150A self-calibrating ECS701SC 1

7
(no external power needed)
Overload only, 1.5–150A self-calibrating ECS700SC

7 Underload only, 1.5–150A self-calibrating ECS702SC

7 Split-Core Housing Split-Core Housing

7
Self-powered Normally open 0.85 in (21.6 mm) Over/underload, 2.8–150A self-calibrating ECS711SP 1
(no external power needed)

7
Overload only, 2.8–150A self-calibrating ECS710SP

7
Underload only, 2.8–150A self-calibrating ECS712SP

7
7 Accessories

7 DIN Rail
Mounting Kit
ECS7 Series CurrentWatch
Current Switches

7 Description Catalog Number


DIN rail mounting kit 2 EDINKIT
7
7
7
Notes
7 1 Output is closed when current is within ±15% window.
2 Sensor pictured for reference and not included in kit.

7
7
7
7
7
7
7
7
7
7
7
7

V8-T7-16 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECS7 Series
7.4
Technical Data and Specifications
7
ECS7 Series CurrentWatch Current Switches
Description Specification 7
Power supply
Output
Self-powered—no power supply needed
Magnetically isolated solid-state switch
7
Output rating Normally open (NO) models: 0.3A at 135 Vac/dc
Not polarity sensitive
7
Off-state leakage <10 μA
7
Response time 200 ms
Setpoint range Solid-core models: 1.5 to 150A 7
Split-core models: 2.8 to 150A
Setpoint Overload models: +15% of load
Underload models: –15% of load
7
7
Operating window: ±5% of setpoint
Hysteresis 5% of setpoint
Overload 500A at 6 sec., 1000A at 1 sec.
7
Isolation voltage UL listed to 1270 Vac, tested to 5000 Vac
Frequency range 6–100 Hz 7
Sensing aperture Solid-core models: 0.74 in (19 mm) dia.
Split-core models: 0.85 in (21.6 mm) sq. 7
Housing UL94 V0 flammability rated
Environmental Operating temperature: –58° to 122°F (–50° to 50°C) 7
Humidity: 0–95% RH, non-condensing
7
Current Switch Operation
7
Underload Only Models Overload Only Models
7
(LED Slow)
7
Output Open (LED Fast) Output Closed
115% of Calibration Point

7
Amps

Amps

Calibration Point Calibration Point


(LED Fast)
Output Closed (LED Slow)

Output Open (LED Off)


Output Open 7
(LED Off)
7
Over/Underload Models 1 7
Output Closed
(LED Slow)
115% of Calibration Point
7
Output Open (LED Fast) 7
Amps

Output Closed
85% of Calibration Point 7
(LED Slow)
(LED Off) 7
Note
7
7
1 Output is closed when current is within ±15% window.

7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-17


7.4 Current and Voltage Sensors
CurrentWatch ECS7 Series

Wiring Diagram
7
ECS7 Series CurrentWatch Current Switches
7
7
AC or DC AC or DC
Power Load

7
7 Monitored Wire

7 Current Switch

7
7 Dimensions
7 Approximate Dimensions in Inches (mm)
Solid-Core Housing Split-Core Housing
7 3.03 3.04 0.19 Dia.
7
(77.0) (77.2) (4.8)

0.93
7 (23.6) 1.19
(30.2)

7 0.19 Dia.
(4.8) 2.40
(61.0) 3.53
7 0.74 Dia.
(89.7)
2.40
(19)
7 2.18
(61)

7 (55.4)

7 2.25
(57.2) 0.85 (21.6)

7 3.50
(88.9)

7 0.85 (21.6)

7
7
7
7
7
7
7
7
7
7
7

V8-T7-18 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECSTD Series
7.5
Contents
ECSTD Series CurrentWatch Current Switches
Description Page
7
ECSTD Series CurrentWatch Current Switches 7
Standards and Certifications . . . . . . . . . . . . . . V8-T7-20
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-20 7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-21
Technical Data and Specifications . . . . . . . . . . V8-T7-21 7
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-22
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-22 7
7
7
7
7
7
ECSTD Series CurrentWatch Current Switches 7
Product Description Application Description 7
The CurrentWatch ECSTD Typical Applications Example Application—
Series from Eaton’s electrical ● Motor Protection— Isolated Alarm System Interfacing 7
sector is a family of high Serves as an electronic
performance current- proof-of-operation; detects ECSTD Series Current Switch I
n New
7
operated switches with field- current draw changes in p Alarm
adjustable time delay to help
minimize nuisance trips
motors when they
u
t
s
System 7
encounter problems such
during start-up and operation.
Designed for motor status
as pumps running dry or
pending bearing failure;
7
applications where setpoint
accuracy and repeatability are
non-intrusive and less
expensive to install than Existing
7
critical, the ECSTD Series differential pressure flow Audible
7
Alarm
offers a linear setpoint sensors or thermal System Alarm
characteristic and constant switches; much quicker
hysteresis. Standard features
include self-powering,
response time than Class 7
10 overload relays Features
jumper-selectable ranges and
a choice of outputs and
● High Inrush or ● Adjustable Start-Up/ ● Improved Ease of 7
Temporary Overload Delay Timer—Field Installation and Use—
housing styles.
For typical applications of the
Current—Adjustable start-
up/delay timer allows 0–15
adjustable from 0–15
seconds to eliminate
Self-powered, split-core
models simplify
7
second delay to eliminate
CurrentWatch ECSTD Series,
see listing on this page. nuisance trips from high
nuisance alarms due to
start-up inrush or
installation, 1.0A AC rating
eliminates need for time 7
inrush or short overload temporary overcurrent delay relay, and status LED
conditions conditions provides visual indication 7
● Choice of NO/NC AC or of setpoint trip and contact
Universal Outputs— action 7
Contact ratings of 1.0A at ● Industrial Grade
240 Vac or universal Performance—Constant 7
outputs of 0.15A at 240 hysteresis and linear
Vac/dc (NO models) and
0.2A at 135 Vac/dc (NC
response characteristics
enhance setpoint accuracy
7
models) for use with most
standard motor control
● Agency Approved—UL
Listed, CE pending
7
systems
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-19


7.5 Current and Voltage Sensors
CurrentWatch ECSTD Series

Standards and Certifications


7 ● UL Listed
DANGER
THIS SENSOR IS NOT A
7 cUL Listed

SAFETY DEVICE AND IS NOT
● CE (Pending) INTENDED TO BE USED AS A
7 ● UL 508 Industrial Control
Equipment (USA and
SAFETY DEVICE. This sensor
is designed only to detect
7 Canada) and read certain data in an
electronic manner and
perform no use apart from
7 (Pending) that, specifically no safety-
related use. This sensor
7 product does not include
self-checking redundant
7 circuitry, and the failure of
this sensor product could
7 cause either an energized
or de-energized output
condition, which could result
7 in death, serious bodily
injury, or property damage.
7 Product Selection
7 ECSTD Series CurrentWatch Current Switches

7 AC Output Switches (NO/NC 1A at 240 Vac)

7 Solid-Core Housing
Power Supply Aperture Size Output Type Setpoint Options Catalog Number
Solid-Core Housing

7 Self powered
(no external power needed)
0.75 in (19 mm) Normally open Adjustable setpoints: 1.5–12, 12–55 or 50–175A ECSTD401SC

7 Normally closed Adjustable setpoints: 1.5–12, 12–55 or 50–175A ECSTD402SC

7
Split-Core Housing Split-Core Housing
7 Self powered 0.85 in (21.6 mm) Normally open Adjustable setpoints: 2–12, 12– 55 or 50–200A ECSTD404SP
(no external power needed)
7
Normally closed Adjustable setpoints: 2–12, 12–55 or 50–200A ECSTD405SP
7
7
7 AC/DC Output Switches (NO 0.15A at 240 Vac/dc, NC 0.2A at 135 Vac/dc) 1
Power Supply Aperture Size Output Type Setpoint Options Catalog Number

7 Solid-Core Housing Solid-Core Housing


Self powered 0.75 in (19 mm) Normally open Adjustable setpoints: 1.5–12, 12–55 or 50–175A ECSTD406SC
7 (no external power needed)

7 Normally closed Adjustable setpoints: 1.5–12, 12–55 or 50–175A ECSTD407SC

7 Split-Core Housing Split-Core Housing

7
Self powered 0.85 in (21.6 mm) Normally open Adjustable setpoints: 2–12, 12– 55 or 50–200A ECSTD408SP
(no external power needed)

7 Normally closed Adjustable setpoints: 2–12, 12–55 or 50–200A ECSTD409SP

7
Note
7 1 Preferred for PLC inputs.

V8-T7-20 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECSTD Series
7.5
Accessories
7
ECSTD Series CurrentWatch
DIN Rail
Mounting Kit Current Switches 7
7
Description Catalog Number
DIN rail mounting kit 1 EDINKIT

7
7
7
Technical Data and Specifications 7
ECSTD Series CurrentWatch Current Switches 7
Description Specification
Power supply Self-powered—no power supply needed
7
Output
Output rating
Magnetically isolated solid-state switch
AC output models: NO/NC 1A at 240 Vac
7
Off-state leakage
AC/DC output models: NO 0.15A at 240 Vac/dc; NC 0.20A at 135 Vac/dc
<10 μA
7
Response time Adjustable 0.2 to 15 sec. 7
Setpoint range Solid-core: 1.5–12, 12–55 or 50–175A
Split-core: 2–12, 12–55 or 50–200A (jumper selectable)
7
Hysteresis 5% (constant)
Isolation voltage 5000 Vac (tested) 7
Frequency range 50–100 Hz
Sensing aperture Solid-core models: 0.75 in (19 mm) dia. 7
Split-core models: 0.85 in (21.6 mm) sq.
Housing UL94 V0 flammability rated 7
7
Environmental Operating temperature: 5° to 122°F (–15° to 50°C)
Humidity: 0–95% RH, non-condensing

7
Overload Ratings
Maximum Amperes 7
Housing Range Continuous Six Seconds One Second
Solid-core 1.5–175A 175A 400A 1000A
7
Split-core 2–200A 200A 400A 1000A
7
LED Indication/Output Status
7
Output 7
Monitored Amps NO NC Smart-LED (If Present)
None or minimum Open Closed Off 7
Below trip level Open Closed Slow (2 sec.)
Above trip level Closed Open Fast (0.5 sec.) 7
Note 7
1 Sensor pictured for reference and not included in kit.

7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-21


7.5 Current and Voltage Sensors
CurrentWatch ECSTD Series

Wiring Diagram
7
ECSTD Series CurrentWatch Current Switches
7 Normally open (NO) models shown

7 AC or DC AC or DC
Power Load
7
7 Output Signal

7
7
To Monitored Wire
7
7
7
7
7 Dimensions
7 Approximate Dimensions in Inches (mm)
Solid-Core Housing Split-Core Housing
7 2.43 0.19
(61.8) (4.83)
7 1.18
(30) Dia.

7
0.75
(19) 3.04
Dia. 2.18 (77.2)
7 (55.4) 3.53
(89.7)
0.967 0.45
7 0.125
(24.56) 2.40
(31)
(11.4)

(3.2) 1.51 0.17


7 (38.3) 3.53 (4.5 Int. Dia.)
Typical of 2 0.85
(89.7) 0.85
(21.6)
7 0.931 LED
(21.6)

(23.7) 2.25

7 1.5
(57.2)

7
(39) 3.08 0.6
(78) (15)

7
7
7
7
7
7
7
7

V8-T7-22 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECSD Series
7.6
Contents
ECSD Series CurrentWatch Current Switches
Description Page
7
ECSD Series CurrentWatch Current Switches 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-24
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-24 7
Technical Data and Specifications . . . . . . . . . . V8-T7-24
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-25 7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-25
7
7
7
7
7
7
ECSD Series CurrentWatch Current Switches 7
Product Description Application Description Features Standards and Certifications 7
The CurrentWatch ECSD Typical Applications
● Choice of Mechanical ● UL Listed
Series current operated ● Electronic Proof of
Relay or Solid-state ● cUL Listed 7
switches from Eaton’s Outputs ● CE
Flow—Current operated
electrical sector provides the switches eliminate the
● SPDT (Form C) relay, 7
same dependable indication need for multiple pipe or 5.0A at 240 Vac or 30
of status offered by the
CurrentWatch ECS Series,
duct penetrations and are

Vdc
Solid-state, NO, 0.15A at
7
more reliable than
but with the added benefit of
increased setpoint precision.
electromechanical
pressure or flow switches
240 Vac/dc
7
A choice of three jumper- ● Easily Adjustable
selectable input ranges allow ● Welders—Instant Setpoint—Speeds start-up DANGER 7
the ECSD Series to be indication of equipment and reduces inventory
THIS SENSOR IS NOT A
tailored to an application, status ● Compact, One-Piece
Design—Easily fits in
SAFETY DEVICE AND IS NOT 7
providing more precise INTENDED TO BE USED AS A
● Large Drive Motors—
control through improved
setpoint resolution. Features Provide monitoring for field ●
crowded control panels
Input Isolation—Safer
SAFETY DEVICE. This sensor 7
loss protection is designed only to detect
such as isolated solid-state or
mechanical relay outputs; 4- ● Power Supplies—Detect
than shunt/relay
combinations
and read certain data in an
electronic manner and
7
20A, 10-50A, and 20-100A and signal over-current Adaptive Hysteresis— perform no use apart from
7

input ranges are standard. condition before Hysteresis is five percent that, specifically no safety-
equipment damage of setpoint, allowing closer related use. This sensor
For typical applications of the
CurrentWatch ECSD Series, ● UPS—Monitors battery
control than fixed- product does not include 7
see the listing on this page. hysteresis switches self-checking redundant
output
● Solid-Core Housings circuitry, and the failure of 7
● Ancillary Equipment ● LED Indication—Provides this sensor product could
quick visual indication of cause either an energized
or de-energized output
7
output contact status
condition, which could result
● Built-In Mounting Feet— in death, serious bodily 7
Provide for a secure injury, or property damage.
installation 7
7
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-23


7.6 Current and Voltage Sensors
CurrentWatch ECSD Series

Product Selection
7
ECSD Series CurrentWatch Current Switches
7
Top Terminal Switches
7 Power Supply Aperture Size Output Type, Voltage and Rating Setpoint and LED Configuration Catalog Number

7
Solid-Core Housing Solid-Core Housings with Top Terminal
with Top Terminal
12 Vac/dc 0.74 in (19 mm) Solid-state, normally open, 0.15A at 240 Vac/dc Adjustable: 4–20, 10–50, 20–100A ECSD112SC

7 Mechanical relay, SPDT (Form C), 5.0A at 240 Vac, 30 Vdc ECSD212SC

7 24 Vac/dc 0.74 in (19 mm) Solid-state, normally open, 0.15A at 240 Vac/dc Adjustable: 4–20, 10–50, 20–100A ECSD124SC

Mechanical relay, SPDT (Form C), 5.0A at 240 Vac, 30 Vdc ECSD224SC
7
7
Accessories
7
ECSD Series CurrentWatch
7
DIN Rail Mounting Kit
Current Switches
Description Catalog Number
7 DIN rail mounting kit 1 EDINKIT

7
7
7
7 Technical Data and Specifications
ECSD Series CurrentWatch Current Switches
7 Description Solid-State Output Models Mechanical Relay Models

7 Power supply 12 Vac/dc (operates from 10–18 Vac/dc)


24 Vac/dc (operates from 20–28 Vac/dc)
12 Vac/dc (operates from 10–18 Vac/dc)
24 Vac/dc (operates from 20–28 Vac/dc)

7 Output Isolated solid-state contact Mechanical relay (SPDT)


Output rating 0.15A at 240 Vac/dc 5.0A at 240 Vac
7 Normally open 5.0A at 30 Vdc
Off-state leakage <10 μA —

7 Response time 100 ms at 10% above setpoint


20 ms at 100% above setpoint

7 Setpoint range Adjustable: 4–20, 10–50, 20–100A —


Hysteresis 5% of setpoint —
7 Overload 1000% of range for 5 sec. —
Isolation voltage 3 kV —
7 Frequency range DC to 400 Hz —

7 Sensing aperture Solid-core, 0.74 in (19 mm) —


Housing UL94 V0 flammability rated —

7 Environmental Operating temperature: –40° to 140°F (–40° to 60°C)


Humidity: 0–95% RH, non-condensing
Operating temperature: –4° to 122°F (–20° to 50°C)
Humidity: 0–95% RH, non-condensing

7 Note
1 Sensor pictured for reference and not included with kit.

7
7
7
7

V8-T7-24 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch ECSD Series
7.6
Wiring Diagrams
7
Solid-State Output Models Mechanical Relay Models
Power Supply Solid-State Power Supply Mechanical 7
12 Vac/dc or 24 Vac/dc Output 12 Vac/dc or 24 Vac/dc Relay Output
7
7
1 2 1 2

7
Setpoint Setpoint 7
7
Dimensions
Approximate Dimensions in Inches (mm) 7
Solid-Core Models 7
0.40 in.
(10.2 mm)
7
7
ø
0.75 in.
(19.1 mm) 7
2.50 in.
(63.5 mm)
7
7
3.88 in. (98.4 mm)
7
0.20 in.

7
ø (5 mm)

7
3.38 in. (86 mm)
7
7
7
7
7
7
7
7
7
7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-25


7.7 Current and Voltage Sensors
CurrentWatch EAC Series

Contents
7 EAC Series CurrentWatch Current Sensors
Description Page
7 EAC Series CurrentWatch Current Sensors
Standards and Certifications . . . . . . . . . . . . . . V8-T7-27
7 Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-27
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-28
7 Technical Data and Specifications . . . . . . . . . . V8-T7-28
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . V8-T7-29
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-29

7
7
7
7
7
7 EAC Series CurrentWatch Current Sensors
7 Product Description Application Description
The CurrentWatch EAC Typical Applications Example Application—
7 Series from Eaton’s electrical ● Automation Preventative Maintenance of a Critical Lighting System
sector combines a current Equipment—Analog
7 transformer and signal current reading for remote
Signal to
Lighting Current
Change
conditioner into a single monitoring and software Controller Sensor
in
7
Current is controlled
package. The EAC Series has alarms Current to extend lamp life
jumper-selected current input ● Data Loggers—Self-
7 ranges and industry standard
outputs: 4–20 mA, 0–5 Vdc or
powered sensor helps
conserve data logger
0–10 Vdc. This family of
7 sensors is designed for
batteries
Lamp Fall
Time

application on “linear” or ● Panel Meters—Simple


7 sinu-soidal AC loads. connection displays power
consumption
Available in split-core or solid- Features
7 core housings. ● Highly Accurate—Factory
matched and calibrated
● Jumper Selectable
Ranges—The ability to
For typical applications of the
7 CurrentWatch EAC Series, single-piece sensor is
more accurate than
change input ranges
reduces inventory and
see listing on this page.
traditional two-piece, field- eliminates zero and span
7 installed solutions ● Isolation—Output is
● Average Responding— magnetically isolated from
7 “Average Responding” the input for safety and
algorithm gives an RMS elimination of insertion loss
7 output on pure sine waves, (voltage drop)
perfect for constant speed ● UL, cUL and CE
7 (linear) loads Approved—Accepted
worldwide
7
7
7
7
7 For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
For the most current information
7 on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184.

V8-T7-26 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EAC Series
7.7
Standards and Certifications 1
● UL Listed
DANGER 7
THIS SENSOR IS NOT A
cUL Listed
7

SAFETY DEVICE AND IS NOT
● CE Certified INTENDED TO BE USED AS A
● UL 508 Industrial Control
Equipment (USA and
SAFETY DEVICE. This sensor
is designed only to detect
7
7
Canada) and read certain data in an
electronic manner and
perform no use apart from
that, specifically no safety- 7
related use. This sensor
product does not include 7
self-checking redundant
circuitry, and the failure of
this sensor product could
7
cause either an energized
or de-energized output 7
condition, which could result
in death, serious bodily 7
injury, or property damage.
7
Product Selection
EAC Series CurrentWatch Current Sensors
7
Top Terminal Current Sensors 7
Power Supply Aperture Size Output Signal Current Range Catalog Number
7
Solid-Core Housing Solid-Core Housings
Self-powered
(no external power needed)
0.74 in (19 mm) 0–5 Vdc 10, 20 or 50A EAC105SC 7
100, 150 or 200A EAC205SC
0–10 Vdc 10, 20 or 50A EAC110SC 7
7
100, 150 or 200A EAC210SC
24 Vdc loop-powered 4–20 mA 2 or 5A EAC0420SC
10, 20 or 50A EAC1420SC
7
100, 150 or 200A EAC2420SC
Split-Core Housing Split-Core Housings—Self-Powered and 24 Vdc 7
Self-powered 0.85 in (21.6 mm) 0–5 Vdc 10, 20 or 50A EAC105SP
(no external power needed)
100, 150 or 200A EAC205SP 7
0–10 Vdc 10, 20 or 50A
100, 150 or 200A
EAC110SP
EAC210SP
7
24 Vdc loop-powered 4–20 mA 2 or 5A EAC0420SP 7
10, 20 or 50A EAC1420SP
100, 150 or 200A EAC2420SP 7
Split-Core Housing
7
Split-Core Housings—120 Vac and 24 Vac/dc
120 Vac 0.85 in (21.6 mm) 4–20 mA 2 or 5A EACP0420120SP 2
10, 20 or 50A EACP1420120SP 2
7
100, 150 or 200A EACP2420120SP 2
24 Vac/dc 4–20 mA 2 or 5A EACP042024USP 2 7
10, 20 or 50A EACP142024USP 2
100, 150 or 200A EACP242024USP 2 7
Notes
1 EACP models not listed.
7
7
2 Not UL listed.

7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-27


7.7 Current and Voltage Sensors
CurrentWatch EAC Series

Accessories
7
7 DIN Rail EAC Series CurrentWatch Current Sensors
Mounting Kit Description Catalog Number

7 DIN rail mounting kit 1 EDINKIT

7
7
7
7 Technical Data and Specifications

7 EAC Series CurrentWatch Current Sensors


Models with 0–5 Vdc Output Models with 0–10 Vdc Output Models with 4–20 mA Output EACP Series Only
7 Description Specification Specification Specification Specification
Power supply Self-powered—no power supply needed Self-powered—no power supply needed 12–40 Vdc loop-powered Models ending -0SP: 120 Vac
7 Models ending -USP: 24 Vac/dc
(40V maximum)

7 Output signal
Output limit
0–5 Vdc
8.2 Vdc
0–10 Vdc
15 Vdc
4–20 mA
23 mA
4–20 mA
22.4 mA

7 Accuracy 1.0% FS 1.0% FS 1.0% FS 1% FS


Response time 100 ms 100 ms 300 ms 100 ms
7 Frequency range 50–60 Hz 50–60 Hz 20–100 Hz 40–100 Hz
Loading 1M ohm minimum rated accuracy 1M ohm minimum rated accuracy See power supply above 50 kohms minimum
7 100 kohms, add 1.3% error 100 kohms, add 1.3% error 500 kohms maximum
Isolation voltage UL listed to 1270 Vac (tested to 5kV) UL listed to 1270 Vac (tested to 5kV) UL listed to 1270 Vac (tested to 5kV) UL listed to 1270 Vac (tested to 5kV)
7 Input ranges Field selectable ranges from 0–200A 3 Field selectable ranges from 0–200A 3 Field selectable ranges from 0–200A 3 0–200A jumper selectable

7 Sensing aperture Solid-core: 0.74 in (19 mm) dia.


Split-core: 0.85 in (21.6 mm) sq.
Solid-core: 0.74 in (19 mm) dia.
Split-core: 0.85 in (21.6 mm) sq.
Solid-core: 0.74 in (19 mm) dia.
Split-core: 0.85 in (21.6 mm) sq.
0.85 in (21.6 mm)

7
Housing UL94 V0 flammability rated UL94 V0 flammability rated UL94 V0 flammability rated UL94 V0 flammability rated
Environmental Operating temperature: Operating temperature: Operating temperature: Operating temperature:

7
–4° to 122°F (–20° to 50°C) –4° to 122°F (–20° to 50°C) –4° to 122°F (–20° to 50°C) –4° to 122°F (–20° to 50°C)
Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing

7 Notes
1 Sensor pictured for reference and not included in kit.
2 Does not apply to EACP series.

7 3 Additional custom ranges available from factory.

7
7
7
7
7
7
7
7
7
7

V8-T7-28 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EAC Series
7.7
Wiring Diagrams
7
EACP Models All Other Models 1
24 Vdc Power Load (Controller, Meter, etc.) 7
Power Supply (–) (+) (+)
(24 Vac/dc or 120 Vac) 4–20 mA Option (–) 7
(–) Load Range Jumper 1(–) 2(+) 7
Output
(+) (Controller, Meter...)
1M ohm Recommended 7
1 2 3 (–) 4 (+)
0–5/10 Vdc Option 100 kohms Acceptable
7
7
Power Output Range Jumper 1(–) 2(+)
Output

7
Dimensions
Approximate Dimensions in Inches (mm)
7
Solid-Core Housing EACP Series 7
7
3.03 0.19
(77.0) (4.8)
1.18 Dia.
0.93
(23.6)
(30)
7
3.04

0.19 Dia. 3.53


(77.2) 7
(4.8) 2.40 (89.7)
(61.0) 7
0.45
0.74 Dia.
(19)
2.40
(61)
(11.4)
7
7
2.18
(55.4) 0.85
(21.6) 0.85
(21.7)
2.25
7
(57.2)
3.50 7
(88.9)
7
All Other Models Note
1 Pressure plate screw terminals.
7
3.04 0.19 Dia. 12–22 AWG solid or stranded.
(77.2) (4.8) Field adjustable setpoint. 7
1.19 7
(30.2)
7
7
3.53
(89.7)
2.40
(61) 7
7
2.25 7
(57.2) 0.85 (21.6)
7

0.85 (21.6)
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-29


7.8 Current and Voltage Sensors
CurrentWatch EACR Series

Contents
7 EACR Series CurrentWatch Current Sensors
Description Page
7 EACR Series CurrentWatch Current Sensors
Standards and Certifications . . . . . . . . . . . . . . V8-T7-31
7 Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-31
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-31
7 Technical Data and Specifications . . . . . . . . . . V8-T7-32
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-32
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-32

7
7
7
7
7
7 EACR Series CurrentWatch Current Sensors
7 Product Description Application Description
The CurrentWatch EACR Typical Applications Example Application—
7 Series current sensor family ● VFD Controlled Loads— Current Sensing for Non-Linear AC Loads
from Eaton’s electrical sector Monitoring VFD output
7 combines a current sensor indicates how the motor 137.2A
and a “True RMS” signal and attached load are
7 conditioner into a single
package. The EACR Series
operating Two-Wire Installation
Is Fast and Easy
● SCR Controlled Loads—
7 provides True RMS output on
distorted waveforms found
Accurate measurement of Controller

phase angle fired or burst


on VFD or SCR outputs, and Field
7 on linear loads in “noisy”
fired (time proportioned)
SCRs, with faster current
True RMS Output
even on VFDs or SCRs
Selectable
Ranges
power environments.
7 Available in solid- or split-core
measurement than
temperature sensors L 54.7Hz
housings.
Switching Power I
7

Motor
N
For typical applications of the Supplies and Electronic E VFD
CurrentWatch EACR Series, Ballasts—True RMS
7 see listing on this page. sensing is the most
accurate way to measure
7 power supply or ballast
input power
7 Features
● True RMS Output—True ● Isolation—Output is
7 Why “True RMS”?
RMS technology is magnetically isolated from
The current waveform of a integrates the actual accurate on distorted the input for safety and
7 typical linear load is a pure
sine wave. In VFD and SCR
waveform over time. The
output is the amperage
waveforms like VFD or elimination of insertion loss
SCR outputs (voltage drop)
7 applications, however, output
waveforms are rough
component of the true power
(heating value) of the AC
● Jumper-Selectable ● UL, cUL and CE
Ranges—Reduces Approved—Accepted
approximations of a sine current waveform. True RMS
7 wave. There are numerous is the only way to accurately
inventory and eliminates
zero and span
worldwide
spikes and dips in each cycle. measure distorted AC
7 The CurrentWatch EACR waveforms. Select the EACR
Series current sensors use a Series sensors for nonlinear
7 mathematical algorithm called
“True RMS” which
loads in “noisy” power
environments.
7 For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
For the most current information
7 on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184.

V8-T7-30 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EACR Series
7.8
Standards and Certifications
● UL Listed
DANGER 7
THIS SENSOR IS NOT A
cUL Listed
7

SAFETY DEVICE AND IS NOT
● CE Certified INTENDED TO BE USED AS A
● UL 508 Industrial Control
Equipment (USA and
SAFETY DEVICE. This sensor
is designed only to detect
7
7
Canada) and read certain data in an
electronic manner and
perform no use apart from
that, specifically no safety- 7
related use. This sensor
product does not include 7
self-checking redundant
circuitry, and the failure of
this sensor product could
7
cause either an energized
or de-energized output 7
condition, which could result
in death, serious bodily 7
injury, or property damage.
7
Product Selection
EACR Series CurrentWatch Current Sensors
7
Top Terminal Current Sensors 7
Power Supply Aperture Size Output Signal Current Range Catalog Number
7
Solid-Core Housing Solid-Core Housing
24 Vdc loop-powered 0.74 in (19 mm) 4–20 mA 2 or 5A EACR0420SC 7
10, 20 or 50A EACR1420SC 7
100, 150 or 200A EACR2420SC 7
Split-Core Housing Split-Core Housing 7
24 Vdc loop-powered 0.85 in (21.6 mm) 4–20 mA 2 or 5A EACR0420SP
7
10, 20 or 50A EACR1420SP
7
100, 150 or 200A EACR2420SP
7
7
Accessories
7
DIN Rail EACR Series CurrentWatch Current Sensors
Mounting Kit Description Catalog Number 7
7
DIN rail mounting kit 1 EDINKIT

7
7
Note
1 Sensor pictured for reference and not included in kit.
7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-31


7.8 Current and Voltage Sensors
CurrentWatch EACR Series

Technical Data and Specifications


7
EACR Series CurrentWatch Current Sensors
7 Description Specification

Power supply 24 Vdc loop-powered, 40 Vdc maximum


7 Output signal 4–20 mA

7 Output limit 23 mA
Accuracy 1.0% FS

7 Response time 600 ms (to 90% step change)


Frequency range 10–400 Hz
7 Isolation voltage UL listed to 1270 Vac (Tested to 5 kV)

7
Input ranges Field selectable ranges from 0–200A 1
Sensing aperture Solid-core: 0.74 in (19 mm) dia.
Split-core: 0.85 in (21.6 mm) sq.
7 Housing UL94 V0 flammability rated

7 Environmental Operating temperature: –4° to 122°F (–20° to 50°C)


Humidity: 0–95% RH, non-condensing

7
Wiring Diagram
7 EACR Series CurrentWatch Current Sensors 2

7 24 Vdc Power Load (Controller, Meter, etc.)


(−) (+) (+)
7 (−)

7 Low Mid High 1(−) 2(+)


Output
7
Range Switch

7 Dimensions
7 Approximate Dimensions in Inches (mm)
Solid-Core Housing Split-Core Housing
7 3.03 0.19
(77.0) (4.83)
7 1.18
(30) Dia.
0.93
7 (23.6)
3.04
(77.2)
7 0.19 Dia.
(4.8) 2.40
3.53
(89.7)
(61.0) 0.45
7 0.74 Dia.
2.40
(31)
(11.4)

(19)
7 2.18 0.85
0.85
(55.4)
7
(21.6)
(21.6)
2.25
7 (57.2)

7
3.50
(88.9)

7
7 Notes
1 Additional custom ranges available from factory.

7
2 Deadfront captive screw terminals (split-core housing models only).

12–22 AWG solid or stranded.


Observe polarity.
7

V8-T7-32 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EDC Series
7.9
Contents
EDC Series CurrentWatch Current Sensors
Description Page
7
EDC Series CurrentWatch Current Sensors 7
Standards and Certifications . . . . . . . . . . . . . . V8-T7-34
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-34 7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-35
Technical Data and Specifications . . . . . . . . . . V8-T7-35 7
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-36
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-36 7
7
7
7
7
7
EDC Series CurrentWatch Current Sensors 7
Product Description Application Description 7
The CurrentWatch EDC Typical Applications Example Application—Battery Charging System
Series from Eaton’s electrical ● Battery Banks—Monitor
7
sector combines a hall effect Charging
load current, monitor Load
sensor and signal conditioner charging current and verify
System
7
into a single package for use operation
7
Unipolar
in DC current applications up 100% (Magnitude Only)
● Transportation—
to 300A. The EDC Series has
Measures traction power
jumper-selected current input
ranges and industry standard
or auxiliary loads 50% 7
outputs: 4–20 mA, 0–5 Vdc or ● Electric Heating
0–10 Vdc. Available in split- Elements—Monitor 0% 7
core models for quick and heater loads with a faster
– Amps 0 + Amps
easy installation. response time than
temperature sensors
7
For typical applications of the
CurrentWatch EDC Series, 7
see listing on this page.
Features 7
● Jumper-Selectable ● Internal Power
Ranges—Reduce Regulation—Cuts 7
inventory and eliminate installation costs and


zero or span pots
Isolation—Output is
works well, even with
unregulated power
7
magnetically isolated from
the input for safety, also
● Split Core Design and
Built-In Mounting 7
eliminating insertion loss Brackets—Make
(voltage drop) installation quick and easy 7
● UL and CE Approved
7
7
7
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-33


7.9 Current and Voltage Sensors
CurrentWatch EDC Series

Standards and Certifications


7 ● UL Listed
DANGER
THIS SENSOR IS NOT A
7 cUL Listed

SAFETY DEVICE AND IS NOT
● CE Certified INTENDED TO BE USED AS A
7 ● UL 508 Industrial Control
Equipment (USA and
SAFETY DEVICE. This sensor
is designed only to detect
7 Canada) and read certain data in an
electronic manner and
perform no use apart from
7 that, specifically no safety-
related use. This sensor
7 product does not include
self-checking redundant
7 circuitry, and the failure of
this sensor product could
7 cause either an energized
or de-energized output
condition, which could result
7 in death, serious bodily
injury, or property damage.
7
Product Selection
7 EDC Series CurrentWatch Current Sensors
7 Top Terminal Current Sensors

7 Power Supply Aperture Size Output Signal Current Range Catalog Number
Split-Core Housing Split-Core Housing—Uni-Polar Output, see Output Graph on Page V8-T7-35
7 24 Vac/dc 0.85 in (21.6 mm) 0–5 Vdc 50, 75 or 100A EDC205SP
100, 150 or 200A EDC305SP
7 150, 225 or 300A EDC405SP

7 0–10 Vdc 50, 75 or 100A


100, 150 or 200A
EDC210SP
EDC310SP

7 150, 225 or 300A EDC410SP


4–20 mA 50, 75 or 100A EDC2420SP
7 100, 150 or 200A EDC3420SP
150, 225 or 300A EDC4420SP
7 Split-Core Housing Split-Core Housing—Bidirectional Output, see Output Graph on Page V8-T7-35

7 24 Vac/dc 0.85 in (21.6 mm) –10 to +10 Vdc 0–100A EDCB100SP

0–200A EDCB200SP
7
0–300A EDCB300SP
7 0–400A EDCB400SP

7 Solid-Core Housing Solid-Core Housing—Single-Polarity Output, see Output Graph on Page V8-T7-35

7
24 Vac/dc 0.75 in (19 mm) 4–20 mA 5, 10 or 20A EDC1420SC

7
7
7
7
7
7

V8-T7-34 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EDC Series
7.9
Accessories
7
CurrentWatch EDC Series
DIN Rail
Mounting Kit Description Catalog Number
7
DIN rail mounting kit 1 EDINKIT 7
7
7
7
Technical Data and Specifications 7
EDC Series CurrentWatch Current Sensors 7
Models with 0–5 Vdc Output Models with 0–10 Vdc Output Models with 4–20 mA Output
Description Specification Specification Specification 7
Power supply 24 Vac/dc (22–38 Vac/dc) 2 VA maximum 24 Vac/dc (22–38 Vac/dc) 2 VA maximum 24 Vac/dc (22–38 Vac/dc) 2 VA maximum
Output signal 0–5 Vdc 0–10 Vdc 4–20 mA 7
7
Output limit 5.75 Vdc 11.5 Vdc 23 mA
Accuracy Solid-core models: 1% FS Solid-core models: 1% FS Solid-core models: 1% FS
Split-core models: 2% FS Split-core models: 2% FS Split-core models: 2% FS
300A models: 1.5% FS 300A models: 1.5% FS 300A models: 1.5% FS 7
Response time Solid-core models: 20 ms (to 90% of step change) Solid-core models: 20 ms (to 90% of step change) Solid-core models: 20 ms (to 90% of step change)
Split-core models: 100 ms (to 90% of step change) Split-core models: 100 ms (to 90% of step change) Split-core models: 100 ms (to 90% of step change) 7
Frequency range DC DC DC
Loading 25 kohms minimum 50 kohms minimum 650 ohms maximum 7
7
Isolation voltage 3 kV (monitored line to output) 3 kV (monitored line to output) 3 kV (monitored line to output)
Linearity 0.75% FS 0.75% FS 0.75% FS
Current ranges Field selectable ranges from 0–300A Field selectable ranges from 0–300A Field selectable ranges from 0–300A
7
Sensing aperture Solid-core housings: 0.75 in (19 mm) dia. Solid-core housings: 0.75 in (19 mm) dia. Solid-core housings: 0.75 in (19 mm) dia.
Split-core housings: 0.85 in (21.6 mm) sq. Split-core housings: 0.85 in (21.6 mm) sq. Split-core housings: 0.85 in (21.6 mm) sq.
7
Environmental Operating temperature: –4° to 122°F (–20° to 50°C) Operating temperature: –4° to 122°F (–20° to 50°C) Operating temperature: –4° to 122°F (–20° to 50°C)
Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing
7
Output Graphs
7
Uni-Poler Output for
Split-Core
Bidirectional Output for
Split-Core
Standard Analog Output for
Solid-Core
7
100% +10 Vdc 100% 7
50% 0 50% 7
0% –10 Vdc 0% 7
– Max. 0 + Max.
– Amps 0 + Amps Amps Amps – Amps 0 + Amps
7
Note
1 Sensor pictured for reference and not included in kit.
7
7
7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-35


7.9 Current and Voltage Sensors
CurrentWatch EDC Series

Wiring Diagram
7
EDC Series CurrentWatch Current Sensors
7 24 Vac/dc
Output is powered
7 by EDC Sensor.

7 Range
1(–) 2(+) 3(–) 4(+)
7
Jumper
Power Output

7
7 Dimensions
Approximate Dimensions in Inches (mm)
7 Split-Core Housing Solid-Core Housing

7 0.19
(4.8)
3.87
(98.3)
1.18 Dia. 3.38

7 (30) (85.9)

3.04
7 3.53
(77.2) 1.50
(38.1)
(89.7)
7 2.90
0.45 (73.7)
7 2.40
(61)
(11.4)
0.80
(20.3)
7 0.85
(21.6) 0.85
7
0.75 Dia.
(21.7) 0.45 (19.1)
2.25 (11.4)
(57.2)
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7

V8-T7-36 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EGF Series
7.10
Contents
EGF Series CurrentWatch Current Sensors
Description Page
7
EGF Series CurrentWatch Current Sensors 7
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-38
Standards and Certifications . . . . . . . . . . . . . . V8-T7-38 7
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-38
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-39 7
Technical Data and Specifications . . . . . . . . . . V8-T7-40
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-41 7
7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-41

7
7
7
7
EGF Series CurrentWatch Current Sensors 7
Product Description Application Description 7
The CurrentWatch EGF Typical Applications Example Application—Insulation Breakdown Monitoring
Series from Eaton’s electrical ● Personnel Protection
7
sector is a family of ground (Typically 5 mA)—Detects
7
Ground Fault Sensor
fault (earth leakage) sensors. sensitive ground fault
Ground fault sensors help conditions, which could
protect people, products and
processes from damage by
cause injury to people, and 7
functions as a sensor and
ground fault conditions by
monitoring all current-carrying
alarm trigger when applied
as an input to an overall
7
conductors in grounded single-
7
ground fault protection Circuit Interruption Device Leakage
and three-phase delta or wye system Shunt Trip Breaker to Ground
For example, Contactor
systems.
Equipment Protection
7

The EGF Series with solid- (Typically 10 or 30 mA)—


state outputs offers the For applications where
benefit of reliable, long- personnel protection is not 7
lasting solid-state switches. the primary concern,
Solid-state design provides higher setpoint capability ”Zero Sequence” Operating Principle 7
unlimited switch operating helps eliminate nuisance
In three-phase delta and wye soon as current leaks to
life, superior resistance to
shock and vibration, zero off-
tripping while still providing
adequate ground fault
systems, under normal ground (fault condition), the 7
conditions, current in the two currents become
detection to protect
state leakage, high switch
speeds and high input-output machine electronics
“hot” leg of a two-wire load
is equal in magnitude but
imbalanced and a net
magnetic field results. The
7
isolation. ● Regulatory—Meets
The EGF Series with
requirements as stipulated
opposite in sign to the current
in a neutral leg. As a result,
CurrentWatch EGF Series
sensors monitor this field and 7
by governmental and the electromagnetic fields trip the contacts when the
mechanical relay outputs
is available in solid-core
industrial regulatory groups surrounding these two leakage rises above the 7
for ground fault sensing conductors cancel, producing setpoint.
housings with a choice of
NO or NC SPST latching relays a “zero sum current.” As 7
and a SPDT Form C relay with
auto-reset. 7
7
7
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
7
For the most current information
on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184. 7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-37


7.10 Current and Voltage Sensors
CurrentWatch EGF Series

Features Standards and Certifications


7 ● Broad Range of Options ● Compatible with ● UL 1053, Class 1
DANGER
to Meet Application Standard Equipment— Recognized THIS SENSOR IS NOT A
7 Needs—NO or NC, solid- Application on single- and ● CE SAFETY DEVICE AND IS NOT
state or mechanical relays, three-phases systems, INTENDED TO BE USED AS A
7 normally energized or ideal for use with shunt trip SAFETY DEVICE. This sensor
normally de-energized breakers, and magnetically is designed only to detect
7 contacts isolated from monitored
circuit and control power
and read certain data in an
electronic manner and
● Setpoint Options
perform no use apart from
7 Maximize Ease-of-Use
and Application
● Agency Approved—UL
and CE Certified, accepted that, specifically no safety-
related use. This sensor
7 Flexibility—Field worldwide
selectable 5, 10 or 30 mA product does not include
setpoints on the EGF “tri- self-checking redundant
7 set” models make user circuitry, and the failure of
this sensor product could
adjustments fast, sure and
7 convenient cause either an energized
or de-energized output
condition, which could result
7 in death, serious bodily
injury, or property damage.
7 Product Selection
7 EGF Series CurrentWatch Current Sensors

7 Solid-State Output Sensors

7
AC Solid-State DC Solid-State
Power Supply Setpoint Output Output Contacts Catalog Number
Solid-Core Housing

7
Solid-Core Housings
120 Vac Fixed, 50 mA Solid-state, NO, 1A at 240 Vac — Normally energized EGF1NOACNE050

7 Normally de-energized EGF1NOACDE050


Solid-state, NC, 1A at 240 Vac — Normally energized EGF1NCACNE050
7 Normally de-energized EGF1NCACDE050
— Solid-state, NO, 0.15A at 30 Vdc Normally energized EGF1NODCNE050
7 Normally de-energized EGF1NODCDE050

7 — Solid-state, NC, 0.15A at 30 Vdc Normally energized


Normally de-energized
EGF1NCDCNE050
EGF1NCDCDE050

7 120 Vac Fixed, 100 mA Solid-state, NO, 1A at 240 Vac — Normally energized EGF1NOACNE100
Normally de-energized EGF1NOACDE100
7 Solid-state, NC, 1A at 240 Vac — Normally energized EGF1NCACNE100
Normally de-energized EGF1NCACDE100
7 — Solid-state, NO, 0.15A at 30 Vdc Normally energized EGF1NODCNE100

7 — Solid-state, NC, 0.15A at 30 Vdc


Normally de-energized
Normally energized
EGF1NODCDE100
EGF1NCDCNE100

7 Normally de-energized EGF1NCDCDE100


120 Vac Tri-set adjustable, Solid-state, NO, 1A at 240 Vac — Normally energized EGF3NOACNET3
7 5, 10 or 30 mA
Normally de-energized EGF3NOACDET3

7
Solid-state, NC, 1A at 240 Vac — Normally energized EGF3NCACNET3
Normally de-energized EGF3NCACDET3

7 — Solid-state, NO, 0.15A at 30 Vdc Normally energized EGF3NODCNET3


Normally de-energized EGF3NODCDET3
7 — Solid-state, NC, 0.15A at 30 Vdc Normally energized EGF3NCDCNET3
Normally de-energized EGF3NCDCDET3
7
7
7

V8-T7-38 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EGF Series
7.10
Mechanical Relay Output Sensors
Power Supply Setpoint Mechanical Relay Output Contacts Catalog Number
7
Solid-Core Housing Solid-Core Housings
7
120 Vac Fixed, 50 mA Mechanical relay, NO SPST relay, Form A (1A at 120 Vac) Latching relay EGF1NOLA050
Mechanical relay, NC SPST relay, Form B (1A at 120 Vac) Latching relay EGF1NCLA050 7
Mechanical relay, SPDT Form C, auto-reset (1A at 120 Vac) Normally energized EGF1SPDTNE050
Normally de-energized EGF1SPDTDE050 7
Fixed, 100 mA Mechanical relay, NO SPST relay, Form A (1A at 120 Vac)
Mechanical relay, NC SPST relay, Form B (1A at 120 Vac)
Latching relay
Latching relay
EGF1NOLA100
EGF1NCLA100
7
Mechanical relay, SPDT Form C, auto-reset (1A at 120 Vac) Normally energized EGF1SPDTNE100 7
Normally de-energized EGF1SPDTDE100
Tri-set adjustable, Mechanical relay, NO SPST relay, Form A (1A at 120 Vac) Latching relay EGF1NOLAT3 7
5, 10 or 30 mA
Mechanical relay, NC SPST relay, Form B (1A at 120 Vac) Latching relay EGF1NCLAT3
Mechanical relay, SPDT Form C, auto-reset (1A at 120 Vac) Normally energized EGF1SPDTNET3
7
Normally de-energized EGF1SPDTDET3
7
24 Vac/dc Fixed, 50 mA Mechanical relay, NO SPST relay, Form A (2A at 30 Vdc) Latching relay EGF2NOLA050
Mechanical relay, NC SPST relay, Form B (2A at 30 Vdc) Latching relay EGF2NCLA050 7
Mechanical relay, SPDT Form C, auto-reset (2A at 30 Vdc) Normally energized EGF2SPDTNE050
Normally de-energized EGF2SPDTDE050 7
7
Fixed, 100 mA Mechanical relay, NO SPST relay, Form A (2A at 30 Vdc) Latching relay EGF2NOLA100
Mechanical relay, NC SPST relay, Form B (2A at 30 Vdc) Latching relay EGF2NCLA100
Mechanical relay, SPDT Form C, auto-reset (2A at 30 Vdc) Normally energized EGF2SPDTNE100
7
Normally de-energized EGF2SPDTDE100
Tri-set adjustable, Mechanical relay, NO SPST relay, Form A (2A at 30 Vdc) Latching relay EGF2NOLAT3 7
5, 10 or 30 mA
Mechanical relay, NC SPST relay, Form B (2A at 30 Vdc) Latching relay EGF2NCLAT3
Mechanical relay, SPDT Form C, auto-reset (2A at 30 Vdc) Normally energized EGF2SPDTNET3 7
Normally de-energized EGF2SPDTDET3
7
7
Accessories
7
DIN Rail EGF Series CurrentWatch Current Sensors
Mounting Kit Description Catalog Number 7
7
DIN rail mounting kit 1 EDINKIT

7
7
Note
1 Sensor pictured for reference and not included in kit.
7
7
7
7
7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-39


7.10 Current and Voltage Sensors
CurrentWatch EGF Series

Technical Data and Specifications


7
EGF Series CurrentWatch Current Sensors
7 Solid-State Output Models Mechanical Relay Output Models
Description Specification Specification
7 Power supply 120 Vac (55–110% of nominal voltage) 120 Vac (55–110% of nominal voltage)
24 Vac/dc (± 20%) 24 Vac/dc (± 20%)
7 Output contact type Isolated dry contact Mechanical relay

7
Output rating (switching AC output switching models: 1A at 240 Vac Auto reset models, SPDT relay:
current and switching DC output switching models: 0.15A at 30 Vdc 1A at 120 Vac; 2A at 30 Vdc
voltage) Latching models, SPST relay:
7 Off-state leakage NO models: <10 μA
1A at 120 Vac; 2A at 30 Vdc
None

7 Response time
NC models: <2.5 mA
200 ms at 5% above trip point 200 ms at 5% above trip point

7
60 ms at 50% above trip point 60 ms at 50% above trip point
15 ms at 500% above trip point 15 ms at 500% above trip point
Frequency range 50–400 Hz (monitored circuit) 50–400 Hz (monitored circuit)
7 Loading 2 VA maximum 2 VA maximum

7 Isolation voltage 5000 Vac (tested) 5000 Vac (tested)


Sensing aperture 0.74 in (19 mm) diameter 0.74 in (19 mm) diameter

7 LED indicator Green LED for power ON status;


red LED for contact status
Green LED for power ON status;
red LED for contact status

7 Housing UL94 V0 flammability rated UL94 V0 flammability rated


Environmental Operating temperature: –4° to 122°F (–20° to 50°C) Operating temperature: –4° to 122°F (–20° to 50°C)
7 Humidity: 0–95% RH, non-condensing Humidity: 0–95% RH, non-condensing

7 Output Tables
7 Protection from faults and control power loss.
Normally Energized Models
7 Control Power Applied

7
No Power No Fault Fault
Normally open models Open Closed Open

7 Normally closed models Closed Open Closed

7
Normally De-Energized Models
7 Control Power Applied
No Power No Fault Fault
7 Normally open models Open Open Closed
Normally closed models Closed Closed Open
7
7 Latching (Mechanical Relay Output) Models
Latching models power up The output will remain
7 initially in the rest (normal)
mode. If there is a fault
latched regardless of whether
the fault is cleared or control
7 condition or the test button is
pushed, the output contacts
power is removed. To reset
the output, apply a
will change state and latch. momentary contact across
7 “reset” terminals.

7
7
7
7

V8-T7-40 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EGF Series
7.10
Wiring Diagrams
7
Solid-State Output Models Mechanical Relay Output Models
All Models Latching Models 7
External Reset
Switch
7
Power Output 1 2 3 4 5 6 G
Power
R
Status
7
Power Output
7
Test
R G

Power Output
1Ø Power
1Ø Load
Jumper Location 7
of Tri-set Models
HOT
NEUT EGF Series
Power
Interupt 7
Auto Reset Models
7
3Ø Wye Power
Power Output
3Ø Load
ØA 1 2 3 4 5 6 G R
ØB
7
Power
Interupt
ØC Power Status
EGF Series
ØN Power Output

Power
3Ø Delta Power 7
Output
3Ø Load
ØA
ØB
Power
Interupt
Jumper Location
of Tri-set Models
7
ØC EGF Series

Power Output
3Ø Power
1Ø Load 7
ØA
ØB EGF Series
Power
Interupt 7
7
Dimensions 7
Approximate Dimensions in Inches (mm)
7
Solid-State Output Models Mechanical Relay Models
2.25 Latching
7
Auto Reset (57.2) (7 Terminals)
TEST
1.50
(38)
(6 Terminals) 1.88
(47.6) 7
0.20
(5.1) 2.90 0.44
7
0.75 Dia
Dia. (11.2)
7
(73.7) (19.1)
3.38
(86) 2.50

7
(63.5)

0.75
(19.1)
Dia. 3.88
7
2.50 (98.6)
(63)
0.20 Dia 7
(5.1)
TEST 7
2.90
(73.7)
7
3.38
(85.9) 7
7
7
7
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-41


7.11 Current and Voltage Sensors
CurrentWatch EGFL Series

Contents
7 EGFL Series CurrentWatch Current Sensors
Description Page
7 EGFL Series CurrentWatch Current Sensors
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-43
7 Standards and Certifications . . . . . . . . . . . . . . V8-T7-38
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V8-T7-43
7 Technical Data and Specifications . . . . . . . . . . V8-T7-43
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . V8-T7-44
7 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V8-T7-44

7
7
7
7
7
7 EGFL Series CurrentWatch Current Sensors
7 Product Description Application Description
The CurrentWatch EGFL Typical Applications Example Application—Insulation Breakdown Monitoring
7 Series from Eaton’s electrical ● Personnel Protection
sector is a family of ground (Typically 5 mA)—Detects
7
Ground Fault Sensor
fault (earth leakage) sensors. sensitive ground fault
Ground fault sensors help conditions, which could
7 protect people, products and
processes from damage by
cause injury to people, and
functions as a sensor and
7 ground fault conditions by
monitoring all current-carrying
alarm trigger when part of
an overall ground fault
conductors in grounded
7 protection system Circuit Interruption Device Leakage
single- and three-phase delta Shunt Trip Breaker to Ground
● Equipment Protection For example, Contactor
or wye systems. For more
7 information, see “Zero
(Typically 10 or 30 mA)—
For applications where
Sequence” Operating ”Zero Sequence” Operating Principle
personnel protection is not
7 Principle on this page. The
EGFL Series is available with
the primary concern, In three-phase delta and wye soon as current leaks to
higher setpoint capability systems, under normal ground (fault condition), the
either solid-state or
7 mechanical relay outputs.
helps eliminate nuisance conditions, current in the
“hot” leg of a two-wire load
two currents become
imbalanced and a net
tripping while still providing
7 The EGFL Series with
mechanical relays are
adequate ground fault
detection to protect
is equal in magnitude but
opposite in sign to the current
magnetic field results. The
CurrentWatch EGFL Series
machine electronics in a neutral leg. As a result, sensors monitor this field and
7 available in solid-core
housings with a choice of NO ● Regulatory—Meets the electromagnetic fields trip alarm contacts when the
or NC SPST latching relays requirements as stipulated surrounding these two leakage rises above the
7 and a SPDT Form C relay with by governmental and conductors cancel, producing setpoint.
auto-reset. All mechanical industrial regulatory groups a “zero sum current.” As
7 models can be ordered with a for ground fault sensing
fixed setpoint or with a “tri-
7 set” option, which provides
three factory-set, field
adjustable setpoints.
7
7
7
7 For Customer Service in the U.S. call 1-877-ETN CARE (386-2273),
in Canada call 1-800-268-3578.
For the most current information
7 on this product, visit our Web site:
www.eaton.com
For Application Assistance in the U.S. and Canada
call 1-800-426-9184.

V8-T7-42 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com


Current and Voltage Sensors
CurrentWatch EGFL Series
7.11
Features Standards and Certifications
● Broad Range of Options ● Compatible with ● UL Approved
DANGER 7
to Meet Application Standard Equipment— THIS SENSOR IS NOT A
UL 1053, Class 1
7

Needs—Mechanical Application on single- and Recognized SAFETY DEVICE AND IS NOT


relays, normally energized three-phase systems, ideal INTENDED TO BE USED AS A
CE
7

or normally de-energized for use with shunt trip SAFETY DEVICE. This sensor
contacts breakers, and magnetically
● cULus is designed only to detect
● Setpoint Options isolated from monitored
circuit and control power
and read certain data in an
electronic manner and
7
Maximize Ease-of-Use
perform no use apart from
and Application
Flexibility—Field
● Agency Approved—UL
and CE Certified, accepted that, specifically no safety- 7
worldwide related use. This sensor
selectable 5, 10 or 30 mA
setpoints on the EGFL “tri- product does not include 7
set” models make user self-checking redundant
adjustments fast, sure and circuitry, and the failure of
this sensor product could
7
convenient
cause either an energized
or de-energized output 7
condition, which could result
in death, serious bodily 7
injury, or property damage.
Product Selection 7
EGFL Series CurrentWatch Current Sensors 7
Mechanical Relay Sensors 7
Power Supply Setpoint Output Type Contacts Catalog Number
Solid-Core Housing Solid-Core Housings 7
120 Vac Tri-set adjustable, 5, 10 or 30 mA Mechanical relay, NO SPST relay, Form A
Mechanical relay, NC SPST relay, Form B
Latching relay
Latching relay
EGFL1NOLAT3
EGFL1NCLAT3
7
Mechanical relay, SPDT Form C, auto-reset Normally energized EGFL1SPDTNET3 7
Normally de-energized EGFL1SPDTDET3
24 Vac/dc Tri-set adjustable, 5, 10 or 30 mA Mechanical relay, NO SPST relay, Form A Latching relay EGFL2NOLAT3 7
Mechanical relay, NC SPST relay, Form B Latching relay EGFL2NCLAT3
Mechanical relay, SPDT Form C, auto-reset Normally energized EGFL2SPDTNET3
7
Normally de-energized EGFL2SPDTDET3
7
Technical Data and Specifications 7
EGFL Series CurrentWatch Current Sensors
Description Specifications
7
Power supply 120 Vac (55–110% of nominal voltage)
24 Vac/dc (± 20%)
7
Output signal Mechanical relay 7
Output rating Auto reset models, SPDT relay: 1A at 125 Vac; 2A at 30 Vdc
Latching models, SPST relay: 1A at 125 Vac; 2A at 30 Vdc
7
OFF-state leakage None
Response time 200 ms at 5% above trip point
60 ms at 50% above trip point
7
Frequency range
15 ms at 500% above trip point
50–400 Hz (monitored circuit)
7
Loading 2VA max. 7
Isolation voltage 5000 Vac (tested)
Sensing aperture 1.83 in (46.5 mm) diameter 7
LED indicator Green LED for power ON status
Red LED for contact status 7
Housing UL94 V0 flammability rated
Environmental Operating temperature: –4° to +122°F (–20° to +50°C) 7
Humidity: 0–95% RH, non-condensing
7

Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com V8-T7-43


7.11 Current and Voltage Sensors
CurrentWatch EGFL Series

Output Tables Latching Models


7 Protection from faults and control power loss. Latching models power up initially in the rest (normal) mode. If
there is a fault condition or the test button is pushed, the output
7 Normally Energized Models
contacts will change state and latch. The output will remain
Control Power Applied latched regardless of whether the fault is cleared or control
7 No Power No Fault Fault power is removed. To reset the output, apply a momentary
Normally open models Open Closed Open contact across “reset” terminals.
7 Normally closed models Closed Open Closed

7 Normally De-Energized Models


Control Power Applied
7 No Power No Fault Fault
Normally open models Open Open Closed
7 Normally closed models Closed Closed Open

7 Wiring Diagrams
7 General Wiring Diagram for Ground Fault Sensors Latching Models
1Ø Power
7 Power Output
1Ø Load
External Reset Switch

HOT
7
Power
Interupt 1 2 3 4 5 6 G R
NEUT EGF Series

3Ø Wye Power Power Status

7 3Ø Load
Power Output

Power Output
ØA TEST
ØB Power

7
Interupt
ØC EGF Series
ØN

7 Power Output
3Ø Delta Power
3Ø Load
Jumper Location for Tri-Set Models

7
ØA
ØB
Power
Interupt
Auto Reset Models
ØC EGF Series

3Ø Power
7 Power Output
1Ø Load 1 2 3 4 5 G R
ØA Power Status
7
Power
Interupt
ØB EGF Series
Power Output
TEST
7
7 Jumper Location for Tri-Set Models

7
Dimensions
7 Approximate Dimensions in Inches (mm)
7 Mechanical Relay Models

7
2.99 (75.9) 1.50 (38.1)

7 1.83 (46.5)

7
7 4.20
(106.7)

7
7 1.42
(36.1)

7 3.25 (82.6)

V8-T7-44 Volume 8—Sensing Solutions CA08100010E—August 2012 www.eaton.com