TEST CERTIFICATE OF CABLE HV AKSHAR ELECINFRA PVT. LTD.

Client ADANI POWER (JHARKHAND) LTD., GODDA Tested On 10/02/2019


Plant GODDA THERMAL POWER PROJECT (2X800 MW) Tested By DEBOJYOTI
Location SS -4 Comp. Code

1.0 DETAILS OF H.T CABLE UNDER TEST :


FROM FEEDER NUMBER-11 TO SS-4
SIZE OF CABLE 3CX185 SQMM VOLTAGE GRADE 11KV
LENGTH 1529MTR TYPE OF CABLE XLPE
MAKE HAVELLS INDIA LTD

2.0 INSULATION RESISTANCE TEST BEFOR HI-POT TEST: AT 5KV DC (Test For 1 min)
Megger Used : 5 KV Range : 0 - 1 T-
R-Y Y-B R-B R-E Y-E B-E
MEASURED VALUE 273GΩ 297GΩ 264GΩ >1.0TΩ 797GΩ >1.0TΩ

2.1 D. C. HIGH VOLTAGE TEST :


VOLTAGE APPLIED MEASUREMENT OF LEAKAGE CURRENT

18 KV DC(%80 OF 2N+1) (milli - AMPS)


PHASE AFTER 5 MINUTES
R-(Y+B+Earth) 0.05
Y-(B+R+Earth) 0.04
B-(R+B+Earth) 0.05

2.2 INSULATION RESISTANCE TEST AFTER HI-POT: AT 5KV DC (Test For 1min)
Megger Used : 5 KV Range : 0 - 1 T-
R-Y Y-B R-B R-E Y-E B-E
MEASURED VALUE 288GΩ 379GΩ 395GΩ >1.0TΩ >1.0TΩ >1.0TΩ

3.0 CONTINUITY CHECK : OK.


3.1 REMARKS : TESTED OK