Proposed Disposition
Use as is
Rework
Replace
Repair
Date of
Reference Number Scope Location Description Contractor Date issued Date cleared Status NCR canceled Causes
Proposition
1 MNC-ACT-BBI-NCR-FON-001 D-wall P22 to P24 Execution of the guide wall was not according to the proposed sections BSV 11-Jun-08 20-Mar-09 7-Apr-09 Closed NCR BBI 001 Method Statement Implementation
3 MC-BBI-Q+-NC-BA-FON-003 D-wall P26 Un-appropriate excavation during excavation along house No.3 Ham Nghi BSV 12-Jun-08 4-Jul-08 Closed Shop drawings conformity
Minimun distance of 4 meters between crane and edge of Guide wall during
5 MC-BBI-Q+-NC-BA-FON-005 D-wall In front of Panel 1 BSV 16-Sep-08 10-Mar-08 Closed Method Statement Implementation
D-wall excavation not follow MOS
6 MNC-ACT-BBI-NCR-FON-002 D-wall Next to P20-P09-P47 Non-protected Inclinometer and Piezometer Pipes IBST 15-Sep-08 20-Mar-09 7-Apr-09 Closed NCR BBI 006 Method Statement Implementation
P11-P08-P43-P02-P09-
P10-P16-P04-P33-P28-
23 MC-BBI-Q+-NC-BA-FON-022 D-wall P49-P26-P34-P15-P29- D-wall concrete casting level is higher than required BSV 7-Nov-08 10-Mar-09 Closed Method Statement Implementation
P30-P25-P35-P42-P31-
P24-P41-P13-P39-P36
Non conformance of Sonic Test results with the ratings Criteria on Method
24 MNC-ACT-BBI-NCR-FON-019 D-wall Panels P48 BSV 4-Nov-08 25-Apr 25-Apr-09 Closed Undeterminated
statement
Non conformance of Sonic Test results with the ratings Criteria on Method
25 MNC-ACT-BBI-NCR-FON-020 D-wall Panels P30 BSV 11-Nov-08 25-Apr 25-Apr-09 Closed Undeterminated
statement
Non conformance of Sonic Test results with the ratings Criteria on Method Waiting for completion of the
26 MNC-ACT-BBI-NCR-FON-021 D-wall Panels P06 BSV 11-Nov-08 26-Mar-09 Undeterminated
statement work
Non conformance of Sonic Test results with the ratings Criteria on Method
27 MNC-ACT-BBI-NCR-FON-022 D-wall Panels P38 BSV 18-Nov-08 25-Apr-09 25-Apr-09 Closed Undeterminated
statement
Non conformance of Sonic Test results with the ratings Criteria on Method
28 MNC-ACT-BBI-NCR-FON-024 D-wall Panels P42 BSV 18-Nov-08 25-Apr-09 25-Apr-09 Closed undeterminated
statement
Non conformance of Sonic Test results with the ratings Criteria on Method Waiting for completion of the
29 MNC-ACT-BBI-NCR-FON-023 D-wall Panels P35 BSV 3-Dec-08 26-Mar-09 Undeterminated
statement work
Non conformance of Sonic Test results with the ratings Criteria on Method
30 MNC-ACT-BBI-NCR-FON-026 D-wall Panels P37 BSV 1-Dec-08 26-Mar-09 7-Apr-09 Closed undeterminated
statement
Non-conformance of depth of excavation based on the approved drawings.
31 MNC-ACT-BBI-NCR-FON-027 Bored Pile BP142 BVN 30-Dec-08 20-Mar-09 26-Mar-09 Closed Method Statement Implementation
Excavtion exceede 2.5m
Non conformance of Sonic Test results with the ratings Criteria on Method
32 MNC-ACT-BBI-NCR-FON-025 D-wall Panels P13 BSV 19-Jan-09 26-Mar-09 7-Apr-09 Closed undeterminated
statement
Pouring Concrete inside Steel Stanchions without prior inspection od NDT
33 MNC-ACT-BBI-NCR-FON-028 Bored Pile BP106 BVN 14-Jan-09 20-Mar-09 26-Mar-09 Closed Method Statement Implementation
or welded joints
Defective Hollow Sections 300x300x16m m not conforming on the quality Waiting for approval of the
34 MNC-ACT-BBI-NCR-FON-029 Stanchion 300x300 C&T 16-Jan-09 23-May-09 Quality of Material
base on the UT conducted proposed disposition
35 MNC-ACT-BBI-NCR-FON-030 Bored Pile BP 43 Pouring without Stanchions BVN 27-Feb-09 20-Mar-09 26-Mar-09 Closed Method Statement Implementation
41 MC-BBI-Q+-NC-BA-FON-023 Bored Pile BP 141 139 144 142 Non conformance of steel cages top level BVN 7-May-09 16-Jun-09 16-Jun-09 Closed Method Statement Implementation
43 MC-BBI-Q+-NC-BA-FON-025 Bored Pile BP 146 Shaft grouting work not as per design, tube No 7, 1 and 6 BVN 28-May-09 10-Aug-09 14-Sep-09 Closed Method Statement Implementation
44 MC-BBI-Q+-NC-PO-GEN-026 Capping Beam CB 12 & CB 11 16 starters bars located on the top of the d-wall are broken HBC 15-Jun-09 17-Jun-09 11-Aug-09 Closed Method Statement Implementation
Some rebars are not aligned with the rest and are coming out of the frame
46 MC-BBI-Q+-NC-PO-GEN-028 Transfer cap TC 20,21 HBC 25-Jun-09 25-Jun-09 11-Aug-09 Closed Method Statement Implementation
of 5 to 8 cm because the reinforcement bars were too long.
Two missing column hooks at first layer and hooks reference 32 not closed
48 MC-BBI-Q+-NC-PO-GEN-030 Transfer Cap TC 10 HBC 7-Jul-09 22-Jul-09 7-Aug-09 Closed Workmanship
properly.
Hooks HA 16 reference 25 are not installed properly: one side of the hooks
49 MC-BBI-Q+-NC-PO-GEN-031 Transfer cap TC 9 HBC 7-Jul-09 10-Jul-09 11-Aug-09 Closed Workmanship
is not bent into the column.
50 MC-BBI-Q+-NC-PO-GEN-032 Transfer cap TC 10 Formwork was not closed properly. Tie rods missing HBC 7-Jul-09 22-Jul-09 7-Aug-09 Closed NCR ACT 049 Workmanship
51 MC-BBI-Q+-NC-PO-GEN033 Transfer cap G106/ TC10 Installation of starter bars for G106 without ACT Approval BBI 11-Jul-09 14-Jul-09 7-Aug-09 Closed NCR ACT 048 Method Statement Implementation
Update: 14-Sep-09
Edit by: SHo
NON-CONFORMANCE REGISTER
Proposed Disposition
Use as is
Rework
Replace
Repair
Date of
Reference Number Scope Location Description Contractor Date issued Date cleared Status NCR canceled Causes
Proposition
53 MC-BBI-Q+-NC-PO-GEN-035 Transfer cap TC 23 core 1 Uneven surface of concrete - poor installation of formwork. HBC 17-Jul-09 29-Jul-09 14-Sep-09 Closed NCR ACT 050 & 51 Method Statement Implementation
55 MC-BBI-Q+-NC-PO-GEN-037 Transfer cap TC 15 The installed starter bar of ground beam G84 from TC 15 is too high HBC 18-Jul-09 31-Jul-09 Closed NCR ACT 053 Shop Drawings Conformity
One water stop was not poured inside CB 11. Incorect installation of
56 MC-BBI-Q+-NC-PO-GEN-038 Capping Beam CB 11 HBC Pending proposed disposition Method Statement Implementation
formwork
57 MC-BBI-Q+-NC-PO-GEN-039 Transfer cap TC 18 Column hooks not closed properly at layers 11 to 17 at reference 24. HBC 20-Jul-09 5-Aug-09 11-Aug-09 Closed Shop drawings conformity
58 MC-BBI-Q+-NC-PO-GEN-040 Transfer cap Tc 10 Bar reference 15 not installed in first casting HBC 20-Jul-09 3-Aug-09 7-Aug-09 Closed NCR ACT 057 Shop drawings conformity
59 MC-BBI-Q+-NC-BA-FON-041 Stanchion S40 Starter bars were cut HBC 21-Jul-09 22-Jul-09 11-Aug-09 Closed Workmanship
61 MC-BBI-Q+-NC-PO-GEN-043 D-wall D'wall P01 P02 & P09 Broken bars during straightening up HBC 30-Jul-09 1-Aug-09 17-Aug-09 Closed Workmanship
Concrete pouring of Ground Floor Slab 1.1 not conforming with Waiting for approval of the
62 MNC-ACT-BBI-NCR-FON-052 GFL Slab Slab 1.1 HBC 17-Jul-09 Method Statement Implementation
insufficient cleaning and improper installation of hydrophilic joints proposed disposition
63 MNC-ACT-BBI-NCR-FON-055 GFL Slab P 09 piezometer P. 09 does not confirm with Method statement HBC 23-Jul-09 Pending proposed disposition Method Statement Implementation
Surface of P05 is not aligned with adjacent one and theoritical position of
65 MC-BBI-Q+-NC-BA-FON-044 D-wall P05 BSV 1-Aug-09 6-Aug-09 14-Sep-09 Closed Workmanship
CB, the deviation is about 50mm comparing to the outer concrete surface.
The installed starter bar of the beam G95 from transfer cap TC05 are
66 MC-BBI-Q+-NC-PO-GEN-045 Transfer cap TC 05 HBC 1-Aug-09 3-Aug-09 17-Aug-09 Closed Workmanship
wrong position (235mm fronm the side of the beam)
81 MNC-ACT-BBI-NCR-FON-062 GFL Slab Slab 1.4 Long Crack on surface of Slab 1.4 HBC 28-Aug-09 Pending proposed disposition Undeterminated
82 MNC-ACT-BBI-NCR-FON-063 Column TC 15 Lightning Reinforcement rod is out of column position HBC 28-Aug-09 10-Sep-09 14-Sep Closed Workmanship
83 MNC-ACT-BBI-NCR-FON-064 GFL Slab Slab 1.3 Long crack on surface of slab 1.3 HBC 31-Aug-09 Pending proposed disposition Undeterminated
Construction Joint between slab 1.3 a nd slab 2.5 does not conform with
84 MNC-ACT-BBI-NCR-FON-065 GFL Slab Slabs 1.3 / 2.5 HBC 31-Aug-09 Pending proposed disposition Undeterminated
requirement
85 MNC-ACT-BBI-NCR-FON-066 GFL Slab Slab 1.1 Long crack on soffit of slab 1.1 HBC 31-Aug-09 Pending proposed disposition Undeterminated
86 MC-BBI-Q+-NC-PO-GEN-056 GFL Slab C 18 C19 Starter bars misplaced HBC 5-Sep-09 8-Sep-09 14-Sep Closed Shop drawings conformity
87 MC-BBI-Q+-NC-PO-GEN-057 GFL Slab C24,25,26,27 Starter bars too short HBC 5-Sep-09 8-Sep-09 14-Sep Closed Shop drawings conformity
Waiting for approval of the
88 MC-BBI-Q+-NC-PO-GEN-058A Core wall W19 Starter bar installation not as per the design HBC 6-Sep-09 8-Sep-09 Shop drawings conformity
proposed disposition
The bars HA20 reference 36 were not installed in the first casting of
89 MC-BBI-Q+-NC-PO-GEN-059 Capping Beam CB 3 HBC 7-Sep-09 9-Sep-09 14-Sep Closed Document
Capping Beam CB3.
Waiting for approval of the
90 MC-BBI-Q+-NC-PO-GEN-060 Column C10 and 32 Starter bars of the coulumn are too short HBC 9-Sep-09 12-Sep-09 Shop drawings conformity
proposed disposition
91 MNC-ACT-BBI-NCR-FON-067 Column C28 Segregation of concrete HBC 5-Sep-09 Pending proposed disposition Undeterminated
93 MNC-ACT-BBI-NCR-FON-068 Core wall W11 Cavity in core Wall 11 under Beam G86 HBC 11-Sep-09 Pending proposed disposition