Sei sulla pagina 1di 19

OWNER CONTRACTOR

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)


PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 1 of 19

SPECIFICATION FOR HIGH VOLTAGE


SWITCHGEAR

0 Issued for Construction 03/09/2007 ARS SN ShS LiuXG

A Issued for Approval 17/07/2007 ARS SN ShS LiuXG

Rev Description Date Prepared Checked Approved Client Owner


OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 2 of 19

CONTENTS

SPECIFICATION FOR HIGH VOLTAGE SWITCHGEAR 1


1 SCOPE 3
1.1 Introduction................................................................................................................3
1.2 Vendor Responsibilities..............................................................................................3
1.3 Scope of Supply.........................................................................................................3
1.4 Conflict of Documentation..........................................................................................4
1.5 Exceptions to Specifications / Compliance Statement................................................4
1.6 Quality System........................................................................................................... 4
2 GENERAL REQUIREMENTS 5
2.1 Codes and Standards.................................................................................................5
2.2 Data Sheets............................................................................................................... 6
2.3 Certification................................................................................................................6
3 SITE CONDITIONS 6
3.1 Environmental............................................................................................................6
3.2 Hazardous Area Classification...................................................................................6
3.3 Safety......................................................................................................................... 6
4 DESIGN AND CONSTRUCTION REQUIREMENTS 7
4.1 System Voltage and Frequency.................................................................................7
4.2 General...................................................................................................................... 7
4.3 Construction............................................................................................................... 7
4.4 Controls and DC Control Circuit Philosophy...............................................................9
4.5 Bus-Bars.................................................................................................................. 10
4.6 HV Circuit Breakers..................................................................................................10
4.7 Potential Transformers (PTs)...................................................................................11
4.8 Current Transformers (CTs).....................................................................................12
4.9 Trip Circuit Supervision............................................................................................12
4.10 Protective Relays...................................................................................................12
4.11 Instruments............................................................................................................ 13
4.12 Auxiliary Switches, Devices and Wiring..................................................................14
4.13 Terminals............................................................................................................... 15
5 ACCESSORIES 15
5.1 DC Power................................................................................................................. 16
5.2 Marking and Finishing..............................................................................................16
5.3 Inspection and Testing.............................................................................................17
5.4 Factory Acceptance Testing (FAT)...........................................................................18
5.5 Certificates of Acceptance........................................................................................19
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 3 of 19

1 SCOPE

1.1 Introduction

This specification covers the design, construction and supply of a High Voltage
Switchgear assembly (HV Switchgear).

1.2 Vendor Responsibilities

Vendor shall be responsible for the complete design, engineering, manufacture, supply,
inspection, testing, documentation and preparation for shipment of the HV Switchgear, in
full compliance with all applicable design Codes and Standards, including those listed in
Section 2 of this document and the requirements of the certifying authority, if applicable.

Purchaser’s approval of the Vendor’s drawings/documents does not in any way affect
Vendor’s full responsibility to supply strictly in accordance with Project specification,
codes and standards.

This specification shall not relieve the Vendor of any responsibility to provide equipment
and services that are suitable for the intended duty.

1.3 Scope of Supply

The Vendor shall supply the following:

• Factory design, fabrication, assembly, factory acceptance testing, packaging and


preparation for shipment, shipment to the site of the specified HV Switchgear
• DC System consisting of batteries, chargers and Distribution Board for protection,
control and indication circuits of the HV Switchgear
• Design drawings and data including Single Line Diagrams, Schematics, Wiring
Diagrams, Termination Diagrams, Bill of Materials, Protection Schematics and
General Arrangement Drawings
• Completed Data Sheets
• “As Constructed” drawings
• Installation, Operation, Maintenance and Commissioning Manuals
• Manufacturer’s Data Report (MDR) Manual
• Erection, testing and commissioning supervision services.

Each unit shall be a self-contained package inclusive of all equipment necessary for
placing the units into immediate service.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 4 of 19

The review and approval of any drawings, procedures or documents referred to in this
Specification shall only indicate acceptance of general requirements and shall not relieve
the Vendor of its obligations to comply with the requirements of the Purchase Order.

Compliance by the Vendor with the provisions of this Specification does not relieve him
of the responsibility of furnishing equipment of proper design, electrically and
mechanically suited, to meet the operating requirements under the specified service
conditions.

1.4 Conflict of Documentation

In the event of a conflict between this specification and any other documentation, the
Purchaser shall be made aware for clarification, before commencement of design or
fabrication.

1.5 Exceptions to Specifications / Compliance Statement

Deviations to the requirements of this Specification and the associated standards and
documents to which the equipment shall be manufactured and tested; must be stated by
Vendor in writing at the bid stage.

In the absence of such a statement, it is considered that the requirements of the


Specification are met without exception.

Any shortcomings that are identified during or on the completion of fabrication shall be
corrected by Vendor at the Vendor’s expense.

1.6 Quality System

A quality control program shall be submitted to the Purchaser for review and approval
prior to commencement of the work. The quality program shall include all
Subcontractors.

The Vendor shall maintain an effective program for quality assurance and quality control,
planned and developed in conjunction with all manufacturing, storage and application
functions necessary to meet the requirements of the Purchase Order and this
Specification.

The Quality Plan shall ensure that quality requirements are determined prior to
commencement of the work and subsequently satisfied throughout.

The Supplier‘s quality system and quality control procedures shall generally conform to
the requirements of ISO 9000/9001/9002; whichever is applicable.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 5 of 19

2 GENERAL REQUIREMENTS

2.1 Codes and Standards

The design and installation shall comply with the following Standards and Codes of
Practice:

IEC 60044 Instrument Transformers


IEC 60056 High-voltage alternating-current circuit breakers
IEC 60129 Alternating current disconnectors and earthing switches
IEC 60186 Voltage transformers
IEC 60255 Electrical Relays
IEC 60265 High Voltage Switches
IEC 60282 High Voltage Fuses
IEC 60298 AC metal-enclosed switchgear and control gear for rated voltages
above 1 kV and up to and including 52 kV
IEC 60332-1 Tests for electric cables under fire conditions
IEC 60420 High Voltage alternating current switch – fuse combinations
IEC 60470 High-voltage alternating current contactors and contactor-based
motor-starters
IEC 60427 Synthetic testing of high voltage alternating current circuit breakers
IEC 60529 Degrees of protection provided by enclosures (IP Code).
IEC 60632 High Voltage Motor Starters
IEC 60694 Common Specifications for High-Voltage Switchgear and
Controlgear Standards
Where the standard consists of multiple parts, the Vendor shall conform to each and
every part.

Where there is no applicable code or standard as mentioned above, codes or standards


published by the following international organisations shall be used:

• International Electro-technical Commission (IEC)


• Harmonised European Standards (EN)

• British Standards Institute (BSI)


OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 6 of 19

2.2 Data Sheets

Purchaser’s equipment Data Sheets shall form a part of this Specification. The
equipment shall comply with all the requirements of the Data Sheets DS-00-E-0017.
The Vendor shall complete all information requested on the Data Sheets.

2.3 Certification

The HV Switchgear shall be fully type tested by ASTA or KEMA or other recognised
independent certification organization (subject to Purchaser’s approval) for adequate
short circuit withstand and allowable temperature rise. The HV Switchgear shall
preferably be type tested for arc fault containment. The requirement for arc fault
containment shall become mandatory when called for on the Data Sheet.

Vendor shall furnish details of certification with copy of the type test certificates
demonstrating compliance with the latest revision of applicable standards for
Purchaser’s approval.

3 SITE CONDITIONS

3.1 Environmental

Refer to the Specification for Environmental Design Conditions Doc No. SP-00-M-0020.

3.2 Hazardous Area Classification

The HV Switchgear will be installed indoors in an unclassified (non-hazardous) location.

3.3 Safety

The HV Switchgear shall conform to the following requirements:

• The switchboard enclosures shall comply with IEC60298, Annexure AA with regard to
mechanical strength and ability to contain an arc fault. The test condition shall be in
conformity with accessibility Type A, and the switchgear shall meet assessment
criteria 1 to 6 inclusive.
• Switchgear and control equipment shall be designed to minimize risk due to internal
short circuits and to ensure personnel safety during all operating conditions,
inspections and maintenance.
• To minimize fire hazards, halogen-free, flame-retardant materials shall be used
where appropriate.
• Toxic materials (such as asbestos, polychlorinated biphenyls (PCBs), mercury, and
the like), shall not be used.
• Operation of the switchgear shall be carried out with the cubicle door closed. This
shall include racking in and out of the circuit breaker and contactor trucks, and
application of the earth switch.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 7 of 19

4 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 System Voltage and Frequency

4.1.1 System Voltage


WAPDA: 11000V, 3 Phase, 3 Wire, 50 Hz

4.1.2 Steady state variations


Steady state (long-term) voltage variation: +5%, -10%

Steady state (long-term) frequency variation: +/-2%

4.1.3 Transient state variations


Transient voltage variation: +/-20%

4.2 General

The HV Switchgear shall have bus bar configuration as shown on single line diagram.
The design shall allow for the future extension of the busbar and addition of new panels
at both ends of the switchgear.

4.3 Construction

The switchgear shall be metal clad enclosed, free standing, dead-front, indoor type, dust
and vermin-proof, standardised to form a single assembly with a common bus-bar and
shall incorporate vacuum breakers/contactors.

Enclosures shall have a minimum degree of protection IP41 as defined in the IEC 60529
without using the floor as part of the enclosure.

The design shall allow for personnel to work safely within an empty switching device
compartment, or one which has the control device assembly removed, with the bus
energised. The main bus and risers shall be fully segregated and plug-in contacts for
the devices shall have minimum openings.

Incoming and outgoing sections shall be supplied with air insulated main power cable
terminating compartments, arranged for bottom cable entry unless specified otherwise
on the Data Sheets. All covers for the switchgear shall be sealed with gaskets (including
back & side covers). Gaskets shall be non-deteriorating rubber or neoprene material.

The switchgear shall be provided with hinged front panel doors. The compartment doors
shall be attached with at least two fixings. Doors and covers of HV compartments which
may be opened without the use of tools shall be provided with mechanical interlock and
padlocking facilities. It shall be possible to gain safe access to breaker / control circuit
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 8 of 19

compartments while HV circuits are live. No LV components and associated LV wiring


shall be located in HV compartment. The following padlocking facilities shall be provided:

• All circuit breakers and contactors in the “OFF” and “TEST” positions
• All busbar and circuit earthing switches.

The structure shall be provided with internal barriers to prevent spreading the damage
between panels when faults occur. These barriers shall also segregate power and
control compartments to confine electrical disturbances and faults.

The switchgear shall be factory assembled in one section or as otherwise required by


shipping limitations and shall be arranged for a minimum of field assembly. The
switchgear shall be suitable for future addition of units on each end.

Suitable means, properly interlocked, shall be provided for earthing as follows:

• Earthing of the line side of the main incoming feeder.


• Earthing of the load side of the outgoing feeder breakers and motor starters.
• Earthing of bus bars.

Any of the following earthing systems is acceptable:

• A fault rated earth switch mechanically interlocked with the circuit breaker / contactor
to prevent inadvertent earthing when the circuit breaker / contactor is closed.
• An adequately rated circuit breaker able to select an earth position.
• A suitable draw out type fault rated earthing truck replacing the circuit breaker.

All earthing switches shall be fault rated to the same fault level as the switchgear.

The switchgear shall be provided with a common copper ground bus. The ground bus
shall extend through the entire length of the composite switchgear and shall be provided
with facilities for connection to Purchaser’s copper earth system.

All equipment shall be interlocked to ensure safe operation. Warning notices shall be
mounted on all devices that may be damaged or cause harm to personnel or equipment
if operated incorrectly.

The switchgear shall be mechanically and electrically interlocked to prevent:

• Removal of the circuit breaker from its normal operating position when the breaker is
in its closed position.
• Switching of earth switch when circuit breaker is in service operation.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 9 of 19

• Disconnecting of Low Voltage (LV) or auxiliary system when circuit breaker is in


operation.
• Switching ON circuit breaker when earth switch is in closed position.
• Insertion of the circuit breaker into its normal position when the earthing switch is in
its closed position.
• Closing of the earth switch when in service position.
• Closing of the circuit breaker, unless the primary disconnecting devices are in full
contact, or separated by a safe distance.

Grounded metal safety shutters shall be provided to automatically cover all bus bar
contacts and insulating spouts or isolating contacts whenever circuit breakers are
withdrawn. The opening and closing of the shutters shall be by positive mechanical
means whilst racking-in or out the circuit breaker or contactor.

All sections shall be designed and arranged for lifting from the top, which may utilise
removable lifting brackets. Provisions shall be made for lifting the switchgear assembly
and bolting it into position.

All items of equipment shall be arranged in a logical manner to facilitate ease of


operation, maintenance and repair.

All metallic non-current carrying parts, not inherently bonded together, shall be bonded
together and connected to the earth bus.

Arc containment barriers shall be provided by means of internally enclosed chambers.

Hinged and draw out type compartment doors shall be effectively earthed through a
flexible connection or a wiping contact.

Proper clamps and supports shall be provided inside the cable and connection cubicle
for fixing and supporting incoming and outgoing cables with suitable clearances.

4.4 Controls and DC Control Circuit Philosophy

Vendor shall supply DC System and DC Distribution Board as part of HV Switchgear.

a) The “close” and “trip” circuits of the HV circuit breakers and contactors shall be
supplied from DC distribution board supplied with the switchgear. DC control circuits
for all incomers and outgoing feeders shall be supplied directly from the distribution
board (one DC circuit per feeder). Each panel shall have separate “trip” and “close”
circuits. Each circuit shall be protected separately by MCB (all MCBs shall be
equipped with auxiliary contacts wired to the terminal strip).

b) It shall be possible to isolate either the “trip” or “close” circuit in any panel, without
affecting any subsequent panels. The sub-circuit for the DC spring charging motor
shall be fuse protected. Protection shall be coordinated with the closing circuit MCB.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 10 of 19

c) Vendor shall size and supply DC battery charger, batteries, battery rack and DC
distribution board. The battery bank shall be sized to support the switchboard DC
System for a duration stated in Section 5.1.

Vendor shall provide clamps and supports inside the cable connection cubicle for fixing
and supporting incoming and outgoing cables with suitable clearances.

4.5 Bus-Bars

The bus-bars shall be hard-drawn high conductivity copper with high-pressure bolted
type connections.

The busbar system (main and droppers) shall be fully insulated throughout. The busbar
insulation shall be continued into the main switching device compartment as far as
practicable. Insulation material shall be epoxy coating type material, flame-retardant,
non-hygroscopic and non-tracking type. Tapered bus-bars shall not be acceptable.
Factory supplied HV rated insulating tape shall be utilised for busbar joints on site.

All bus-bars, including plug-in stubs and insulation, shall withstand thermal and magnetic
effects of the specified short-circuit current imposed on the electrical system for the
period stated in the Data Sheets.

The main earth bus-bar shall be sized to withstand the thermal and dynamic stresses of
a bolted earth fault equal to the switchgear rating for the period stated in the Data
Sheets.

Where allowance for thermal expansion is required, bus-bars shall be joined by double
bolted connections with flexible joints.

Bus-bar ends shall be drilled and finished for future extensions at both ends.

The bus-bars and taps of feeder circuits shall be rated to carry the maximum rating of
the circuit breaker.

Bus-bar droppers shall have the same cross section for their full length.

The sequence of the busbars shall be red-white-blue, top to bottom, left to right and
back to front, all relative to the front of the switchboard.

4.6 HV Circuit Breakers

The circuit breakers shall be motor operated spring charged vacuum circuit breakers (as
specified on the Data Sheet) withdrawout type construction. Circuit breakers shall be
suitable for uninterrupted duty, short circuit breaking capacity (including DC component)
and withstand over-voltage transients when interrupting running currents of small motors
or the magnetising current of the transformers.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 11 of 19

All HV circuit breakers shall be fully removable without the need for handling trucks or
the manual disconnection of wire plugs or sockets. Direct driven mechanical indication
of the switching device position shall be visible from the switchgear front. Indication Light
Emitting Diodes (LEDs) shall also be provided.

Control supply voltage of the circuit breaker shall be DC Voltage mentioned in the Data
Sheet.

Each circuit breaker shall be mechanically and electrically trip-free and have a provision
for manual closing and tripping.

All circuit breakers of identical current rating shall be interchangeable.

Circuit breakers shall have surge arrestors on the outgoing feeders, only if
recommended by the Vendor.

Mechanical counters shall be provided for all circuit breakers.

The circuit breakers shall include all necessary auxiliary switch contacts and shall have
the following contacts, wired to accessible terminal blocks for Purchaser's use:

• Minimum four (4) normally open contacts


• Minimum four (4) normally closed contacts

The circuit breakers shall have an anti-pumping feature and manually reset lockout
relays to prevent circuit breaker re-closing when tripped by protective devices.

Mechanical indications shall be provided on the circuit breakers to indicate operating


position of the breaker.

4.7 Potential Transformers (PTs)

Potential transformers shall be of epoxy resin or butyl rubber moulded type and shall
have the same insulation level as the switchgear. The accuracy shall be Class 1 for
metering PTs as per IEC 60186 or as per equivalent AS. The accuracy class for
protection PTs shall be 3P as per IEC 60186 or as per equivalent AS. Vendor shall
provide PTs with better accuracy class where required for specific applications.

Each potential transformer shall be protected with current limiting primary and secondary
fuses.

Each set of potential transformers, and its protective fuses shall be assembled in a
separate compartment, and so arranged that the unit can be readily withdrawn from the
operating position. In the withdrawn position, the potential transformer and fuses shall
be completely disconnected from service and all exposed parts visibly grounded.

All live parts shall be inaccessible to personnel, or so interlocked that these shall be
accessible only in the de-energised condition.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 12 of 19

4.8 Current Transformers (CTs)

4.8.1 General
Insulation of current transformers shall be of epoxy resin or butyl rubber moulded type
and shall have the same insulation level as the switchgear. The transformers shall
comply with the requirements stated in IEC 60044 or equivalent AS. The accuracy class
shall be Class 1 for metering CTs as per IEC 60044 or equivalent AS. The accuracy
class for protection CTs shall be 5P20 as per IEC 60044 or equivalent AS. Vendor shall
provide CTs with better accuracy class where required for specific applications

The current transformers shall be suitable for withstanding the stresses corresponding to
the thermal and dynamic short-circuit currents imposed on the electrical system for the
time rating of the Switchgear.

All current transformers shall have rating as shown on the single line diagram. The
Vendor shall state the ratio, burden and accuracy class of all CTs.

CT secondaries shall be provided with shorting links facility.

Current transformers used for unit protection system, shall be similar in characteristics at
both ends of the system, and shall be selected in accordance with the relay
manufacturer's recommendations.

4.8.2 CTs for Differential Protection


Vendor shall mount one set of the CTs in the HV switchgear and shall supply the second
set loose for installation on the protected equipment (e.g. generator, motor, transformer).
Purchaser will supply information regarding the mounting details, diameter of the CTs
etc. for the equipment end, required by the Vendor, after placement of the order.

4.9 Trip Circuit Supervision

Trip circuit supervision relays along with indicating LEDs shall be provided for all circuit
breakers and contactor starters/feeders.

4.10 Protective Relays

4.10.1 General
The HV switching devices shall be equipped with the type of protection indicated on the
single-line diagram.

Protective relays shall be flush mounted draw-out type preferably with built-in test
facilities.

Any protective relays without built-in test facilities shall be provided with separate test
terminal blocks mounted on the front panel of the switchgear.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 13 of 19

Each protective relay shall be fitted with a flag indicator, which can be reset externally.

Under-voltage relays shall be fed from potential transformer located in the bus section
and shall be wired to the trip circuit of the motor starters. The under-voltage circuit shall
not be connected to lockout relays.

All incomers and feeders shall be provided with micro processor based protection relays.

4.10.2 Protective Relay Co-ordination


If specified, vendor shall provide recommended settings for each of the relay being
supplied as part of HV Switchgear, based on the following information to be supplied to
Vendor after placement of order:

(i) Maximum and minimum fault level


(ii) Information on Transformer
(iii) Information on time current characteristics of downstream LV Switchgear/MCC
protections.

Vendor shall request all relevant system information and information for downstream LV
system required by Vendor for protective relay co-ordination.

Vendor shall provide complete calculations and graphs showing time current
characteristics of relays for recommended settings to show how co-ordination has been
achieved. The co-ordination gaps shall be clearly visible on all graphs.

4.10.3 Relay Programming


Vendor shall supply all relays pre-programmed (for required outputs, inputs, logic etc)
and set to work in accordance with the settings calculated. Vendor shall test protection
settings at Vendor’s works. In addition Vendor shall supply the required software for
down loading of all required settings to all relays.

Prior to commencement of construction Vendor shall submit details of the relay


programming together with detailed drawings of the switchgear for approval by
Purchaser.

4.11 Instruments

The instruments shall be flush mounted, taut band switchboard type, and wide angle
with a scale deflection not less than 240° back connected and with an accuracy of 1.5%
of Full Scale Deflection. An external “zero” adjustment shall be provided.

Watt-hour meters shall have cyclometric registers and shall normally be of 2-element
type.

The requirements for instruments shall be as shown on the single-line diagrams.


OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 14 of 19

Ammeter scales shall indicate full-load current at approximately 60% of full scale.

4.12 Auxiliary Switches, Devices and Wiring

Internal wiring (excluding main HV power circuits) shall be moisture resistant PVC, 600V
grade, flexible, tinned copper stranded type conductor (minimum 30 strands is required).
The wiring shall be flame retardant to IEC 60332-1.

Conductor ends shall be fitted with a crimped termination device with an insulated
shank. When more than two conductors need to be connected together, terminals which
utilise permanent solid links, shall be provided.

Terminals for different AC voltages shall be separated from each other using barriers
and completely segregated from DC circuits. All terminals on door mounted equipment /
devices that normally remain energised when the circuit breaker is withdrawn shall be
fully shrouded. Terminals for connection of 240V AC and above shall also be shrouded.

Wiring terminal blocks shall be arranged and positioned to afford easy access for
cabling, testing, inspection and maintenance. For current and voltage transformer
secondary circuits, terminals with facilities for measuring, isolating or short circuiting as
necessary shall be provided.

Each switchgear cubicle shall be equipped with an anti-condensation heater, a manual


control switch and a pilot LED with identifiable indication. All internal heaters and
thermostats shall be completely internally wired

A separate DC control power bus, complete with terminals for an incoming feeder, shall
be furnished for each bus section.

Each panel shall be equipped with the following indication LEDs:

• Circuit breaker closed: Red


• Circuit breaker open: Green
• Trip circuit healthy: White
• Fault trip: Amber
• DC Failure: Blue

Separate circuit breakers (MCBs) shall be provided for control power for each unit.
Tripping of control circuit MCB shall be annunciated as a fault.

Fuses and/or MCBs shall be used for protecting voltage circuits of metering supplies and
auxiliary equipment e.g. space heaters.

The minimum size of control wiring shall be 1.5mm² except for CT secondaries, which
shall have 2.5mm² wiring.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 15 of 19

Internal wiring shall be run in ducts to facilitate safe insertion and removal of individual
wires.

The inter-panel wiring shall be terminated on terminal blocks at shipping breaks.

Local trip buttons located on switchgear shall operate independent of remote trip
buttons.

All internal wiring shall be ferruled with the respective wire number, clearly and durably
marked in black on the white background.

4.13 Terminals

The switchgear shall be equipped with a set of relays for remote annunciation of faults.

The switchgear shall be supplied complete with an air insulated main power cable-
terminating compartment.

Removable un-drilled brass gland plates of a minimum thickness of 5mm shall be


provided for both power and control cables. Terminal blocks shall be placed at least
200mm away from gland plates.

Klippon or similar terminal blocks shall be supplied for outgoing control cable
terminations. The outgoing cable terminal blocks shall have the Vendor's standard wire
numbering on the equipment side of the terminal block and the incoming cable and core
numbers on the outgoing side of the block. Shrouded terminals shall be provided for
240V and above AC connections. Terminals of different voltages shall be segregated.

Terminals for power cable shall be sized for the cable specified on the Data Sheets and
single-line diagrams. All other terminals shall be sized for 2 x 2.5mm².

Vendor shall furnish all terminals including 20% extra terminals as spare.

5 ACCESSORIES

The switchgear shall include the following accessories as a minimum:

• Lifting lugs
• Touch-up paint
• Standard accessories and special tools.

A complete set of standard accessories for the switchgear, including test jumpers, test
rack and a set of special tools necessary for the erection, commissioning, maintenance,
and operation shall be provided. They shall be contained in a suitable box or container
with locking facility.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 16 of 19

5.1 DC Power

The DC Power System shall be 24V DC unless stated otherwise on the Data Sheets.
The DC power supply system shall consist of:

 One (1) battery charger


 One (1) battery bank
 One (1) DC distribution board.

Battery charger shall be capable of supplying the maximum load that can occur on the
DC system (e.g. spring charging of circuit breakers and contactors after tripping of all of
them, maximum simultaneous tripping load and additional 20% spare capacity) in
addition to the boost (equalising) charging of the battery bank.

Battery charger shall be equipped with set of contacts for remote alarm “charger failure”.

Recharged battery shall maintain the system during mains power supply failure for a
minimum duration of 1 hours at maximum loading of controls and indications.

Battery shall be sized to adequately satisfy switchgear requirements with 20% spare
capacity.

The module-isolating switch for battery and battery charger shall be a miniature circuit
breaker. The front panel of battery charger shall be fitted with two indicator LEDs and
an analogue meter scaled to read DC output volts. One LED shall indicate primary
circuit healthy and the second LED shall indicate battery charger failure.

5.2 Marking and Finishing

5.2.1 Nameplates / Labels


Machine engraved nameplates/labels with full text shall be installed to designate the
purpose of all circuits, instruments, meters, relays and fuses. Circuit identification
nameplates/labels shall be labels on the back as well as on the front of each
compartment. All nameplates / labels shall be adjacent to the devices and not mounted
directly on the devices. All labels shall be of non-corrodible type, engraved or printed in
English, and shall be of sufficient size to provide easy reading from normal operating
and maintenance positions.

Nameplates/labels shall be manufactured from laminated plastic, showing black lettering


on a white background.

Each cubicle on the switchgear shall have labels on doors, switches, shutters, or where
necessary to caution, warn, or indicate safety precautions, and any other information
deemed necessary for personnel protection.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 17 of 19

Nameplates shall be securely mounted with machine screws such that they may be
easily changed or replaced.

Labels shall be securely fixed to the equipment using not less than two fastenings bolts.
Nuts and washes shall be zinc or cadmium plated. Fastenings shall not loosen due to
vibration.

The main switchboard labels with switchboard details shall be mounted using bolts nuts
and washers as per specification. All other labels such as for individual drives etc. shall
be mounted using adhesives.

Warning and danger labels shall have red lettering on a white background.

5.2.2 Finish
All metal parts shall be protected from rust and corrosion by plating or painting. Painted
parts shall be to Vendor standard painting procedure.

Vendor shall submit painting specifications and procedure to the purchaser for approval.

All other parts, such as handles, levers, and fasteners that are not stainless steel shall
be cadmium, nickel or chrome-plated.

A minimum of 300 ml can of matching touch-up paint shall be furnished with each three-
(3) vertical sections of switchboard cubicle line-up or fraction thereof.

The fully assembled panels shall be mould and vermin-proof and shall be treated to
provide a lasting durability under the specified service conditions.

5.2.3 Site Storage


A set of recommendations, based on the project environmental conditions and detailing
measures to preserve the quality/integrity of the switchgear during a 12 months ‘site
storage in the open’, shall be provided by the Vendor.

5.2.4 Erection and Special Tools


Special tools and equipment, including circuit-breaker-handling trolley's if they are
required, for erection, commissioning, maintenance and testing shall form part of the
order and be shipped together with the assembly.

5.3 Inspection and Testing

The switchgear shall be fully assembled, wired and tested at the factory and subjected to
rigorous QA and testing at all stages of manufacture.

The tests shall be carried out by the Vendor at his works, in accordance with relevant
Standards in Section 2 and the requirements of this specification, unless agreed
otherwise.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 18 of 19

All formal testing will be conducted in accordance with a written test procedure. The
Vendor’s test procedures shall be submitted to the Purchaser prior to the factory
acceptance test for approval. Each formal acceptance test must be signed by the
Vendor’s and the Purchaser’s representatives at the successful completion of the test.

The Vendor shall ensure that adequate notice (a minimum of 15 working days) is given
in writing to the Purchaser prior to the factory acceptance testing.

The Vendor shall afford full facilities to the Inspector during the course of manufacture
and shall arrange access to any Sub-vendor’s works where necessary. Details of this
requirement shall be resolved in pre-inspection meetings.

The acceptance of the work by the Inspector and its release for shipment shall in no way
relieve the Vendor from any responsibility for carrying out all of the provisions of this
specification and relevant documentation, nor does the Purchaser, by such approval and
release, assume any responsibility for such provisions.

All test and inspection data shall be legible, including the name and signature of the
Vendor and, where applicable, the Inspector.

All defects in materials detected during testing shall be repaired or replaced by the
Vendor at no cost to the Purchaser. If the correction of any error or defect involves
serious alterations requiring replacement of parts, the approval of the Purchaser shall be
obtained before proceeding. If the correction of the error requires witnessing by the
Inspector, the Inspector shall sign the correction. Retesting of repaired or replaced
materials shall be mandatory.

If any part of the equipment is damaged after tests have been completed, retesting of
the affected parts is mandatory. The method of repair shall be in accordance with the
Vendor’s standard procedures and approval of the Purchaser.

The Vendor shall supply supervision, specialist personnel and all necessary materials to
support the inspection and testing.

All test equipment shall be in good working condition and shall have been calibrated by
an endorsed laboratory. Copies of calibration certificates shall be provided to the
purchaser prior to the commencement of testing.

Testing shall be carried out by the Vendor and will be witnessed by the Purchaser or his
nominated Inspector at various stages of manufacture and assembly.

5.4 Factory Acceptance Testing (FAT)

The FAT shall be conducted in accordance with the Vendor’s standard QA procedures.
The Vendor’s standard procedures shall be submitted to the purchaser at least two (2)
months prior to testing for approval.
OWNER CONTRACTOR
KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS)
PROJECT

SPECIFICATION FOR HIGH VOLTAGE


Document Title:
SWITCHGEAR

Date: 03/09/2007 Document No: SP-00-E-0012 Rev: 0 Class: I Sheet 19 of 19

The Vendor shall be responsible for generating the FAT procedures. A 100% correct
performance is required. The scope and manner of routine testing shall be in
accordance with IEC 60298.

The FAT shall include as a minimum the following:

• Visual inspection to prove conformity with the approved drawings and the order.
• Spot checks to verify the degree of protection; reliability of operating mechanisms,
interlocks and safety features; insulation levels; creepage distances; earthing;
labelling and interchangeability.
• Main and auxiliary cable circuits checked against approved schematic circuit
diagrams.
• Insulation resistance tests.
• Ductor testing of all bus-bar connections.
• Dielectric tests on all main, control and auxiliary circuits.
• Primary and secondary injection tests.
• Phase sequence and polarity tests
• Full functional testing of circuits for correct mechanical and electrical operation,
including the operation of their control, communications, interlocking, alarming and
protective devices.

Following the above tests, the switchgear and their components shall be examined for
any damage and to ensure that all parts are in satisfactory operating condition.

Complete records of the above inspection and tests shall be compiled into one
inspection document by the Vendor.

On completion of the FAT the switchgear shall be checked and shipped to the
nominated destination.

5.5 Certificates of Acceptance

On satisfactory completion of the FAT, the Vendor shall provide an appropriate


certificate of equipment acceptance.

Attached to these certificates shall be all test records and other relevant documentation.
These shall form part of the Manufacturer’s Data Report (MDR).

The Purchaser will review and approve these certificates.

Final acceptance of the Switchgear/MCC shall be on satisfactory completion of the


Warranty period.

Potrebbero piacerti anche