Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Legal note
Although we have tried to make this technical guide as accurate as possible, we are not liable for any inaccuracies in its content. In-
formation concerning equipment levels and specifications are subject to modification. The equipment features described in this tech-
nical guide are non-binding regarding the specification of the final product. Due to our policy of continually improving our products,
some features may have subsequently been changed or even removed. Please consult your local dealer for information about the
very latest equipment features. The images in this technical guide are for reference only. The illustrations also contain installation
components, accessories and special equipment that do not form part of the standard delivery.
Specification
Dimensions in the diagrams are in millimetres unless stated otherwise. Pressure figures may be stated in pascals (MPa, hPa, kPa)
or in bars (bar, mbar). The details of threaded connections are given in accordance with ISO 228. Fuse types and sizes are stated in
accordance with VDE. Output details apply to new appliances with clean heat exchangers.
WPL 10 I/WPL 10 IK 3
WPL 08-28 Trend
WPL 34/47/57
WPL 10 AC(S)
WPL cool
WPL HT
WPL E
Ideal for the following:
Single-family and two-family houses • • • • • • • • • •
Apartment buildings • • • • •
Non-residential buildings •
Appliance installation
Outdoor installation • • • • • • • • • • •
Indoor installation • • • •
Compact indoor installation • • •
Split design • •
Little installation effort, compact • • • • • •
»» Inverter technology: Variable speed compressor for perfectly Heat is extracted from the outdoor air via the heat exchanger
matched heating output (evaporator) on the air side across its entire operating range.
»» Compact outdoor unit can be combined with internal modules The heating water is heated to the flow temperature in the heat
thus reducing the amount of space required in the installation exchanger on the water side (condenser) using electrical ener-
room gy (compressor). At low air temperatures, the humidity in the air
precipitates as hoarfrost on the evaporator fins. This hoarfrost is
»» Low operating noise thanks to infinitely adjustable fan speed automatically defrosted. The accumulating water flows out of the
and encapsulated refrigerant circuit appliance via the condensate drain in the floor of the appliance
»» ABC design –"anti-block condensate" prevents the condensate and seeps away into the gravel bed. The energy required for de-
drain from becoming blocked, which could result in the evap- frosting is drawn from the heating system. The heat pump auto-
orator freezing matically reverts to heating mode at the end of the defrost cycle.
»» Can be integrated into a home network and controlled via The heat pump manager and output control function match the
smartphone heat pump heating output variably to the actual heat demand.
In cooling mode, heat is extracted from the heating water via the
»» High DHW convenience with large amount of mixed water due heat exchanger on the heating side. The refrigerant is heated fur-
to high flow temperature ther by electrical energy (compressor) and gives off this heat to
»» Straightforward hydraulic connection due to integral anti-vi- the outdoor air via the heat exchanger on the air side.
bration mounts
Safety and quality
Heat is extracted from the outdoor air via the heat exchanger
(evaporator) on the air side across its entire operating range.
The heating water is heated to the flow temperature in the heat
exchanger on the water side (condenser) using electrical ener-
gy (compressor). At low air temperatures, the humidity in the air
Required accessories precipitates as hoarfrost on the evaporator fins. This hoarfrost is
238686 WK 1.1 automatically defrosted. The accumulating water flows out of the
appliance via the condensate drain in the floor of the appliance
236693 SK 2 and seeps away into the gravel bed. The energy required for de-
frosting is drawn from the heating system. The heat pump auto-
Additional accessories matically reverts to heating mode at the end of the defrost cycle.
185579 FE 7 The heat pump manager and output control function match the
220193 FEK heat pump heating output variably to the actual heat demand.
In cooling mode, heat is extracted from the heating water via the
233711 STB-FB heat exchanger on the heating side. The refrigerant is heated fur-
ther by electrical energy (compressor) and gives off this heat to
the outdoor air via the heat exchanger on the air side.
Specification
WPL 07 ACS classic flex WPL 09 ACS classic flex WPL 17 ACS classic flex
set set set
235984 235987 235990
Heating output
Heating output at A7/W35 (min./max.) kW 1.30/3.50 1.30/4.50 2.60/8.50
Heating output at A2/W35 (min./max.) kW 1.00/3.50 1.00/4.50 2.00/8.50
Heating output at A-7/W35 (min./max.) kW 1.00/3.20 1.00/4.06 3.00/7.80
Heating output at A7/W35 (EN 14511) kW 2.27 2.27 4.86
Heating output at A2/W35 (EN 14511) kW 2.08 2.59 5.73
Heating output at A-7/W35 (EN 14511) kW 3.20 4.06 7.80
Heating output at A-15/W35 (EN 14511) kW 2.90 3.43 7.07
Max. heating output in silent mode at A-7/W35 kW 2.23 2.65 4.96
Max. cooling capacity at A35/W7 kW 2.00 3.00 6.00
Cooling capacity at A35/W7 partial load kW 1.00 1.50 3.00
Max. cooling capacity at A35/W18 kW 2.00 3.00 6.00
Cooling capacity at A35/W18 partial load kW 1.50 1.50 3.00
Power consumption
Max. power consumption, fan heating kW 0.03 0.03 0.1
Power consumption at A7/W35 (EN 14511) kW 0.50 0.50 1.02
Power consumption at A2/W35 (EN 14511) kW 0.55 0.70 1.44
Power consumption at A-7/W35 (EN 14511) kW 1.14 1.49 2.68
Power consumption at A-15/W35 (EN 14511) kW 1.18 1.42 2.84
Coefficient of performance
COP at A7/W35 (EN 14511) 4.54 4.54 4.76
COP at A2/W35 (EN 14511) 3.75 3.72 3.97
COP at A-7/W35 (EN 14511) 2.81 2.72 2.92
COP at A-15/W35 (EN 14511) 2.46 2.41 2.49
Max. cooling capacity factor at A35/W7 2.15 1.62 1.73
Cooling capacity factor at A35/W7 partial load 2.38 2.38 2.40
Max. cooling capacity factor at A35/W18 3.12 3.12 2.88
Cooling capacity factor at A35/W18 partial load 3.56 3.56 3.28
Sound emissions
Sound power level (EN 12102) dB(A) 52 52 57
Sound pressure level at a distance of 5 m in a free field dB(A) 30 30 35
Max. sound power level for outdoor installation dB(A) 58 60 66
Max. sound power level for outdoor installation, silent mode dB(A) 54 56 61
Application limits
Min. application limit on the heating side °C 15 15 15
Max. application limit on the heating side °C 60 60 60
Min. application limit, heat source °C -20 -20 -20
Max. application limit, heat source °C 40 40 40
Energy data
Energy efficiency class A+/A++ A+/A++ A+/A++
Electrical data
Max. power consumption without emergency/booster heater kW 3.0 3.0 4.5
Rated voltage, compressor V 230 230 230
Rated voltage, control unit V 230 230 230
Rated voltage, emergency/booster heater V 400 400 400
Compressor phases 1/N/PE 1/N/PE 1/N/PE
Control unit phases 1/N/PE 1/N/PE 1/N/PE
Emergency/booster heater phases 3/N/PE 3/N/PE 3/N/PE
Compressor fuse/MCB A 1 x B 16 1 x B 16 1 x B 25
Control unit fuse/MCB A 1 x B 16 1 x B 16 1 x B 16
Starting current A 5 5 7
Max. operating current A 9.1 9.1 20.3
WPL 07 ACS classic flex WPL 09 ACS classic flex WPL 17 ACS classic flex
set set set
Versions
Refrigerant R410A R410A R410A
Refrigerant charge kg 1.1 1.1 2
CO2 equivalent (CO2e) t 2.3 2.3 4.18
Global warming potential of the refrigerant (GWP100) 2088 2088 2088
IP rating IP14B IP14B IP14B
Condenser material 1.4401/Cu 1.4401/Cu 1.4401/Cu
Dimensions
Height mm 740 740 812
Width mm 1022 1022 1152
Depth mm 524 524 524
Weight
Weight kg 62 62 91
Connections
Connection, heating flow/return 22 mm 22 mm 22 mm
Water quality requirements
Water hardness °dH ≤3 ≤3 ≤3
pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 8.0-8.5
pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 8.0-10.0
Conductivity (softening) μS/cm <1000 <1000 <1000
Conductivity (desalination) μS/cm 20-100 20-100 20-100
Chloride mg/l <30 <30 <30
Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 <0.02
Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 <0.1
Values
Heating flow rate (EN 14511) at A7/W35, B0/W35 and 5 k m³/h 0.4 0.4 0.8
Nominal heating flow rate at A-7/W35 and 5 k m³/h 0.55 0.70 1.34
Min. heating flow rate m³/h 0.4 0.4 0.6
Nominal internal pressure drop, heating hPa 75 122 149
Flow rate on heat source side m³/h 1300 1300 2200
Permissible operating pressure, heating circuit MPa 0.3 0.3 0.3
HM Trend
232805
Power consumption
Power consumption, emergency/booster heater kW 8.8
Application limits
Max. permissible pressure MPa 0.3
Min. application limit on the heating side °C 7
Max. cooling application limit on the heating side °C 70
Water quality requirements
Water hardness °dH ≤3
pH value (with aluminium fittings) 8.0-8.5
pH value (without aluminium fittings) 8.0-10.0
Conductivity (softening) μS/cm <1000
Conductivity (desalination) μS/cm 20-100
Chloride mg/l <30
Oxygen 8-12 weeks after filling (softening) mg/l <0.02
Oxygen 8-12 weeks after filling (desalination) mg/l <0.1
Hydraulic data
External available pressure differential at 1.5 m³/h hPa 661
External available pressure differential at 2.5 m³/h hPa 300
External available pressure differential at 2 m³/h hPa 468
Weight
Weight kg 27
Electrical data
Frequency Hz 50
Rated voltage, control unit V 230
Rated voltage, emergency/booster heater V 400
Control unit phases 1/N/PE
Emergency/booster heater phases 3/N/PE
Control unit fuse/MCB A 1 x B 16
MCB/fuse protection, emergency/booster heater A 3 x B 16
Power consumption, circulation pump W 3-76
Versions
Circulation pump type Yonos PARA 25/7.5, highly efficient circulation pump
IP rating IP20
Suitable for WPL 10 AC(S), WPL 13/18 E, WPL 19/24, WPL 15/20/25 AC(S), WPL classic, WPL Trend, WPL 33 HT(S)
Dimensions
Height mm 896
Height incl. connector block mm 1131
Width mm 590
Depth mm 405
Connections
Connection G1
Values
Expansion vessel volume l 24
2a
3
6 m/h
5
23
22 HK1
3a 2
2t
D0000068780
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Mischerkreispumpe
Heizpatrone DHC
Heizkreispumpe
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
Warmwasser
WP-Rücklauf
Mischer auf
Mischer zu
Schütz
KUE/Solar
KUE/Solar
EVU-
Mischer
BUS H
Außen
BUS +
BUS L
Fern 3
Fern 1
Netz L
2. WE
BUS -
Freigabe
2.WE
2.WE
EVU
Netz
WW
K PE
PE N L1 L2 L3 L1 N PE 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a
N
PE
L N PE L N PE 1 2 3
WP
BUS H
BUS L
BUS –
D0000068789
Pos. 1
Wärmepumpe
Heat is extracted from the outdoor air via the heat exchanger
(evaporator) on the air side across its entire operating range.
The heating water is heated to the flow temperature in the heat
exchanger on the water side (condenser) using electrical ener-
gy (compressor). At low air temperatures, the humidity in the air
precipitates as hoarfrost on the evaporator fins. This hoarfrost is
Required accessories automatically defrosted. The accumulating water flows out of the
238686 WK 1.1 appliance via the condensate drain in the floor of the appliance
and seeps away into the gravel bed. The energy required for de-
236693 SK 2 frosting is drawn from the heating system. The heat pump auto-
matically reverts to heating mode at the end of the defrost cycle.
Additional accessories The heat pump manager and output control function match the
185579 FE 7 heat pump heating output variably to the actual heat demand.
220193 FEK In cooling mode, heat is extracted from the heating water via the
heat exchanger on the heating side. The refrigerant is heated fur-
233711 STB-FB ther by electrical energy (compressor) and gives off this heat to
the outdoor air via the heat exchanger on the air side.
Specification
WPL 07 ACS classic com- WPL 09 ACS classic com- WPL 17 ACS classic com-
pact set pact set pact set
235985 235988 235991
Heating output
Heating output at A7/W35 (min./max.) kW 1.30/3.50 1.30/4.50 2.60/8.50
Heating output at A2/W35 (min./max.) kW 1.00/3.50 1.00/4.50 2.00/8.50
Heating output at A-7/W35 (min./max.) kW 1.00/3.20 1.00/4.06 3.00/7.80
Heating output at A7/W35 (EN 14511) kW 2.27 2.27 4.86
Heating output at A2/W35 (EN 14511) kW 2.08 2.59 5.73
Heating output at A-7/W35 (EN 14511) kW 3.20 4.06 7.80
Heating output at A-15/W35 (EN 14511) kW 2.90 3.43 7.07
Max. heating output in silent mode at A-7/W35 kW 2.23 2.65 4.96
Max. cooling capacity at A35/W7 kW 2.00 3.00 6.00
Cooling capacity at A35/W7 partial load kW 1.00 1.50 3.00
Max. cooling capacity at A35/W18 kW 2.00 3.00 6.00
Cooling capacity at A35/W18 partial load kW 1.50 1.50 3.00
Power consumption
Max. power consumption, fan heating kW 0.03 0.03 0.1
Power consumption at A7/W35 (EN 14511) kW 0.50 0.50 1.02
Power consumption at A2/W35 (EN 14511) kW 0.55 0.70 1.44
Power consumption at A-7/W35 (EN 14511) kW 1.14 1.49 2.68
Power consumption at A-15/W35 (EN 14511) kW 1.18 1.42 2.84
Coefficient of performance
COP at A7/W35 (EN 14511) 4.54 4.54 4.76
COP at A2/W35 (EN 14511) 3.75 3.72 3.97
COP at A-7/W35 (EN 14511) 2.81 2.72 2.92
COP at A-15/W35 (EN 14511) 2.46 2.41 2.49
Max. cooling capacity factor at A35/W7 2.15 1.62 1.73
Cooling capacity factor at A35/W7 partial load 2.38 2.38 2.40
Max. cooling capacity factor at A35/W18 3.12 3.12 2.88
Cooling capacity factor at A35/W18 partial load 3.56 3.56 3.28
Sound emissions
Sound power level (EN 12102) dB(A) 52 52 57
Sound pressure level at a distance of 5 m in a free field dB(A) 30 30 35
Max. sound power level for outdoor installation dB(A) 58 60 66
Max. sound power level for outdoor installation, silent mode dB(A) 54 56 61
Application limits
Min. application limit on the heating side °C 15 15 15
Max. application limit on the heating side °C 60 60 60
Min. application limit, heat source °C -20 -20 -20
Max. application limit, heat source °C 40 40 40
Energy data
Energy efficiency class A+/A++ A+/A++ A+/A++
Electrical data
Max. power consumption without emergency/booster heater kW 3.0 3.0 4.5
Rated voltage, compressor V 230 230 230
Rated voltage, control unit V 230 230 230
Rated voltage, emergency/booster heater V 400 400 400
Compressor phases 1/N/PE 1/N/PE 1/N/PE
Control unit phases 1/N/PE 1/N/PE 1/N/PE
Emergency/booster heater phases 3/N/PE 3/N/PE 3/N/PE
Compressor fuse/MCB A 1 x B 16 1 x B 16 1 x B 25
Control unit fuse/MCB A 1 x B 16 1 x B 16 1 x B 16
Starting current A 5 5 7
Max. operating current A 9.1 9.1 20.3
WPL 07 ACS classic com- WPL 09 ACS classic com- WPL 17 ACS classic com-
pact set pact set pact set
Versions
Refrigerant R410A R410A R410A
Refrigerant charge kg 1.1 1.1 2
CO2 equivalent (CO2e) t 2.3 2.3 4.18
Global warming potential of the refrigerant (GWP100) 2088 2088 2088
IP rating IP14B IP14B IP14B
Condenser material 1.4401/Cu 1.4401/Cu 1.4401/Cu
Dimensions
Height mm 740 740 812
Width mm 1022 1022 1152
Depth mm 524 524 524
Weight
Weight kg 62 62 91
Connections
Connection, heating flow/return 22 mm 22 mm 22 mm
Water quality requirements
Water hardness °dH ≤3 ≤3 ≤3
pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 8.0-8.5
pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 8.0-10.0
Conductivity (softening) μS/cm <1000 <1000 <1000
Conductivity (desalination) μS/cm 20-100 20-100 20-100
Chloride mg/l <30 <30 <30
Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 <0.02
Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 <0.1
Values
Heating flow rate (EN 14511) at A7/W35, B0/W35 and 5 k m³/h 0.4 0.4 0.8
Nominal heating flow rate at A-7/W35 and 5 k m³/h 0.55 0.70 1.34
Min. heating flow rate m³/h 0.4 0.4 0.6
Nominal internal pressure drop, heating hPa 75 122 149
Flow rate on heat source side m³/h 1300 1300 2200
Permissible operating pressure, heating circuit MPa 0.3 0.3 0.3
Hydraulic data
Nominal capacity, DHW cylinder l 181
Surface area, indirect coil m² 1.6
Capacity, indirect coil l 10
External available pressure differential at 1.0 m³/h hPa 666
External available pressure differential at 1.5 m³/h hPa 560
External available pressure differential at 2 m³/h hPa 274
Application limits
Max. permissible pressure, DHW cylinder MPa 1.0
Test pressure, DHW cylinder MPa 1.5
Max. flow rate l/min 25
Max. permissible temperature °C 95
Water quality requirements
Water hardness °dH ≤3
pH value (with aluminium fittings) 8.0-8.5
pH value (without aluminium fittings) 8.0-10.0
Conductivity (softening) μS/cm <1000
Conductivity (desalination) μS/cm 20-100
Chloride mg/l <30
Oxygen 8-12 weeks after filling (softening) mg/l <0.02
Oxygen 8-12 weeks after filling (desalination) mg/l <0.1
Values
Expansion vessel volume l 12
Expansion vessel pre-charge pressure MPa 0.15
Power consumption
Power consumption, emergency/booster heater kW 8.8
Max. power consumption, circulation pump on the heating side W 72
Energy data
Standby energy consumption/24 h at 65 °C kWh 1.8
Energy efficiency class C
Electrical data
Rated voltage, control unit V 230
Control unit phases 1/N/PE
Control unit fuse/MCB A 1 x B 16
Rated voltage, emergency/booster heater V 400
Emergency/booster heater phases 3/N/PE
MCB/fuse protection, emergency/booster heater A 3 x B 16
Frequency Hz 50
Versions
IP rating IP20
Suitable for Heat pump
Suitable for Component in WPL 07/09/17 ACS classic compact sets
Dimensions
Height mm 1328
Width mm 694
Depth mm 875
Height when tilted mm 1483
Weight
Weight, full kg 341
Weight, empty kg 150
3
m/h
HK1
28
2a
5 3a
6
1 22
D0000068756
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Heizpatrone DHC
Zirk./2.WE WW
Zirk./2.WE WW
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
WP-Rücklauf
Warmwasser
Schütz
KUE/Solar
KUE/SOL
KUE/SOL
KUE/SOL
EVU-
Mischer
EVU L‘
BUS H
Außen
Fern 1
Fern 3
BUS +
BUS L
2. WE
BUS -
Freigabe
2.WE
2.WE
Netz
K PE
PE N L3 L2 L1 L1 N PE 1 2 3 L N PE L N PE 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a
N
PE
L N PE L N PE 1 2 3
WP
BUS H
BUS L
BUS –
D0000068765
Pos. 1
Wärmepumpe
Heat is extracted from the outdoor air via the heat exchanger
(evaporator) on the air side across its entire operating range.
The heating water is heated to the flow temperature in the heat
exchanger on the water side (condenser) using electrical ener-
gy (compressor). At low air temperatures, the humidity in the air
precipitates as hoarfrost on the evaporator fins. This hoarfrost is
Required accessories automatically defrosted. The accumulating water flows out of the
238686 WK 1.1 appliance via the condensate drain in the floor of the appliance
and seeps away into the gravel bed. The energy required for de-
236693 SK 2 frosting is drawn from the heating system. The heat pump auto-
matically reverts to heating mode at the end of the defrost cycle.
Additional accessories The heat pump manager and output control function match the
185579 FE 7 heat pump heating output variably to the actual heat demand.
220193 FEK In cooling mode, heat is extracted from the heating water via the
heat exchanger on the heating side. The refrigerant is heated fur-
233711 STB-FB ther by electrical energy (compressor) and gives off this heat to
the outdoor air via the heat exchanger on the air side.
Specification
WPL 07 ACS classic com- WPL 09 ACS classic com- WPL 17 ACS classic com-
pact plus set pact plus set pact plus set
235986 235989 235992
Heating output
Heating output at A7/W35 (min./max.) kW 1.30/3.50 1.30/4.50 2.60/8.50
Heating output at A2/W35 (min./max.) kW 1.00/3.50 1.00/4.50 2.00/8.50
Heating output at A-7/W35 (min./max.) kW 1.00/3.20 1.00/4.06 3.00/7.80
Heating output at A7/W35 (EN 14511) kW 2.27 2.27 4.86
Heating output at A2/W35 (EN 14511) kW 2.08 2.59 5.73
Heating output at A-7/W35 (EN 14511) kW 3.20 4.06 7.80
Heating output at A-15/W35 (EN 14511) kW 2.90 3.43 7.07
Max. heating output in silent mode at A-7/W35 kW 2.23 2.65 4.96
Max. cooling capacity at A35/W7 kW 2.00 3.00 6.00
Cooling capacity at A35/W7 partial load kW 1.00 1.50 3.00
Max. cooling capacity at A35/W18 kW 2.00 3.00 6.00
Cooling capacity at A35/W18 partial load kW 1.50 1.50 3.00
Power consumption
Max. power consumption, fan heating kW 0.03 0.03 0.1
Power consumption at A7/W35 (EN 14511) kW 0.50 0.50 1.02
Power consumption at A2/W35 (EN 14511) kW 0.55 0.70 1.44
Power consumption at A-7/W35 (EN 14511) kW 1.14 1.49 2.68
Power consumption at A-15/W35 (EN 14511) kW 1.18 1.42 2.84
Coefficient of performance
COP at A7/W35 (EN 14511) 4.54 4.54 4.76
COP at A2/W35 (EN 14511) 3.75 3.72 3.97
COP at A-7/W35 (EN 14511) 2.81 2.72 2.92
COP at A-15/W35 (EN 14511) 2.46 2.41 2.49
Max. cooling capacity factor at A35/W7 2.15 1.62 1.73
Cooling capacity factor at A35/W7 partial load 2.38 2.38 2.40
Max. cooling capacity factor at A35/W18 3.12 3.12 2.88
Cooling capacity factor at A35/W18 partial load 3.56 3.56 3.28
Sound emissions
Sound power level (EN 12102) dB(A) 52 52 57
Sound pressure level at a distance of 5 m in a free field dB(A) 30 30 35
Max. sound power level for outdoor installation dB(A) 58 60 66
Max. sound power level for outdoor installation, silent mode dB(A) 54 56 61
Application limits
Min. application limit on the heating side °C 15 15 15
Max. application limit on the heating side °C 60 60 60
Min. application limit, heat source °C -20 -20 -20
Max. application limit, heat source °C 40 40 40
Energy data
Energy efficiency class A+/A++ A+/A++ A+/A++
Electrical data
Max. power consumption without emergency/booster heater kW 3.0 3.0 4.5
Rated voltage, compressor V 230 230 230
Rated voltage, control unit V 230 230 230
Rated voltage, emergency/booster heater V 400 400 400
Compressor phases 1/N/PE 1/N/PE 1/N/PE
Control unit phases 1/N/PE 1/N/PE 1/N/PE
Emergency/booster heater phases 3/N/PE 3/N/PE 3/N/PE
Compressor fuse/MCB A 1 x B 16 1 x B 16 1 x B 25
Control unit fuse/MCB A 1 x B 16 1 x B 16 1 x B 16
Starting current A 5 5 7
Max. operating current A 9.1 9.1 20.3
WPL 07 ACS classic com- WPL 09 ACS classic com- WPL 17 ACS classic com-
pact plus set pact plus set pact plus set
Versions
Refrigerant R410A R410A R410A
Refrigerant charge kg 1.1 1.1 2
CO2 equivalent (CO2e) t 2.3 2.3 4.18
Global warming potential of the refrigerant (GWP100) 2088 2088 2088
IP rating IP14B IP14B IP14B
Condenser material 1.4401/Cu 1.4401/Cu 1.4401/Cu
Dimensions
Height mm 740 740 812
Width mm 1022 1022 1152
Depth mm 524 524 524
Weight
Weight kg 62 62 91
Connections
Connection, heating flow/return 22 mm 22 mm 22 mm
Water quality requirements
Water hardness °dH ≤3 ≤3 ≤3
pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 8.0-8.5
pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 8.0-10.0
Conductivity (softening) μS/cm <1000 <1000 <1000
Conductivity (desalination) μS/cm 20-100 20-100 20-100
Chloride mg/l <30 <30 <30
Oxygen 8-12 weeks after filling (softening) mg/l <0.02 <0.02 <0.02
Oxygen 8-12 weeks after filling (desalination) mg/l <0.1 <0.1 <0.1
Values
Heating flow rate (EN 14511) at A7/W35, B0/W35 and 5 k m³/h 0.4 0.4 0.8
Nominal heating flow rate at A-7/W35 and 5 k m³/h 0.55 0.70 1.34
Min. heating flow rate m³/h 0.4 0.4 0.6
Nominal internal pressure drop, heating hPa 75 122 149
Flow rate on heat source side m³/h 1300 1300 2200
Permissible operating pressure, heating circuit MPa 0.3 0.3 0.3
HSBC 200
233510
Hydraulic data
Nominal capacity, DHW cylinder l 168
Nominal capacity, buffer cylinder l 100
Surface area, indirect coil m² 3.3
Capacity, indirect coil l 21
External available pressure differential, circulation pump/heat pump at 1.0 m³/h hPa 656
External available pressure differential, circulation pump/heat pump at 1.5 m³/h hPa 527
External available pressure differential, circulation pump/heat pump at 2.0 m³/h hPa 210
External available pressure differential, circulation pump/heating circuit 1 at 1.0 m³/h hPa 725
External available pressure differential, circulation pump/heating circuit 1 at 1.5 m³/h hPa 663
External available pressure differential, circulation pump/heating circuit 1 at 2.0 m³/h hPa 444
External available pressure differential, circulation pump/heating circuit 2 (optional) at 1.0 m³/h hPa 665
External available pressure differential, circulation pump/heating circuit 2 (optional) at 1.5 m³/h hPa 518
External available pressure differential, circulation pump/heating circuit 2 (optional) at 2.0 m³/h hPa 189
Application limits
Max. permissible pressure, DHW cylinder MPa 1.0
Test pressure, DHW cylinder MPa 1.5
Max. flow rate l/min 25
Max. permissible pressure, buffer cylinder MPa 0.3
Test pressure, buffer cylinder MPa 0.45
Max. permissible temperature °C 95
Water quality requirements
Water hardness °dH ≤3
pH value (with aluminium fittings) 8.0-8.5
pH value (without aluminium fittings) 8.0-10.0
Conductivity (softening) μS/cm <1000
Conductivity (desalination) μS/cm 20-100
Chloride mg/l <30
Oxygen 8-12 weeks after filling (softening) mg/l <0.02
Oxygen 8-12 weeks after filling (desalination) mg/l <0.1
Power consumption
Power consumption, emergency/booster heater kW 8.8
Max. power consumption, charging pump W 72
Max. power consumption, circulation pump on the heating side W 72
Energy data
Standby energy consumption/24 h at 65 °C kWh 1.6
Energy efficiency class C
Electrical data
Rated voltage, control unit V 230
Control unit phases 1/N/PE
Control unit fuse/MCB A 1 x B 16
Rated voltage, emergency/booster heater V 400
Emergency/booster heater phases 3/N/PE
MCB/fuse protection, emergency/booster heater A 3 x B 16
Frequency Hz 50
Versions
IP rating IP20
Dimensions
Height mm 1896
Width mm 680
Depth mm 871
Height when tilted mm 2035
Weight
Weight, full kg 471
Weight, empty kg 203
HK1
ww z 28
2a
2
3a 3c
23
5
22
1
6
D0000068762
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Heizpatrone DHC
Zirk./2.WE WW
Zirk./2.WE WW
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
WP-Rücklauf
Warmwasser
Schütz
KUE/Solar
KUE/SOL
KUE/SOL
KUE/SOL
EVU-
Mischer
EVU L‘
BUS H
Außen
Fern 1
Fern 3
BUS +
BUS L
2. WE
BUS -
Freigabe
2.WE
2.WE
Netz
K PE
PE N L3 L2 L1 L1 N PE 1 2 3 L N PE L N PE 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a
N
PE
L N PE L N PE 1 2 3
WP
BUS H
BUS L
BUS –
D0000068757
Pos. 1
Wärmepumpe
Output data
Heating output
10
1
2
5 3
4
5
6
D0000068470
-20 -15 -10 -5 0 5 10 15 20
Cooling capacity
2 1
0
D0000068474
7 9 11 13 15 17 19 21 23
Output data
Heating output
10
1
2
5 3
4
5
6
D0000068471
-20 -15 -10 -5 0 5 10 15 20
Cooling capacity
2 1
2
1
0
D0000068474
7 9 11 13 15 17 19 21 23
Output data
Heating output
10
1
2
5 3
4
5
6
D0000068473
-20 -15 -10 -5 0 5 10 15 20
Cooling capacity
4 1
2
2
0
D0000068474
7 9 11 13 15 17 19 21 23
Sizing the underfloor heating system in the lead room with individual room control
WPL 07 ACS classic WPL 09 ACS classic WPL 17 ACS classic
Minimum flow rate l/h 400 400 600
Buffer cylinder always required no no no
Lead room floor area (composite pipework 16x2 mm, installation spacing 10 cm) m² 21 21 21
Number of circuits (composite pipework 16x2 mm, installation spacing 10 cm) nxm 3x70 3x70 3x70
Lead room floor area (composite pipework 20x2.25 mm, installation spacing 15 cm) m² 21 21 21
Number of circuits (composite pipework 20x2.25 mm, installation spacing 15 cm) nxm 2x70 2x70 2x70
Activate the integral emergency/booster heater yes yes yes
Minimum water content of the buffer cylinder or the open circuits l 16 16 16
Recommended buffer cylinder volume, underfloor heating system l 100 100 100
Recommended buffer cylinder volume, radiators l 100 100 100
≥800
»» The heat pump module must be level (horizontal).
»» The main wind direction must not be towards the fan.
»» When selecting the installation site, remember that the appli-
ance generates noise during operation.
»» Maintain as small a clearance as possible between the heat
pump module and the hydraulic module in order to keep line
losses to a minimum.
»» In winter, the heat pump module must not be covered with
≥300
snow or be submerged if there is heavy rainfall.
»» Ensure access to the wiring chamber under the plastic cover.
»» Condensate must be able to freely drain underneath the appli-
ance, even during frosty weather.
≥200
»» The appliance must be firmly attached to the mounting rail,
which in turn must be secured to the foundation/kerbstones.
≥1000 ≥500
!
D0000060163
≥2000
D0000057581
The appliance is designed for installation on a T-support or wall
mounting bracket. Observe the minimum clearances. If the appli-
ance is installed in an open space, protect the air intake side. Do
this by erecting a wall to shield it against the wind.
91_00_00_0036
! Material losses
The foundations of the building must have a damp proof
membrane.
Note
ffNever use grit for the gravel bed.
≥300
b
a
>800
D0000065666
300
2 Drainage pipe
a
100
Heat pump a b
WPL 07 ACS classic 900 865
WPL 09 ACS classic 900 865
WPL 17 ACS classic 1000 995
>800
ff
Lay a drainage pipe under the appliance to drain moisture
away from the building.
ff
Create a gravel bed below the condensate drain of the appli-
ance.
1
D0000063484
1 Drainage pipe
Heat pump a
WPL 07 ACS classic 700
WPL 09 ACS classic 700
WPL 17 ACS classic 830
ff
Lay a drainage pipe under the appliance to drain moisture
away from the building.
ff
Create a gravel bed below the condensate drain of the appli-
ance.
1
Note
To prevent disturbance due to structure-borne noise
transmission, never install the wall mounting bracket on
3 the external walls of living areas or bedrooms.
A ff Install the wall mounting bracket on a garage wall,
for example.
Note
Condensate drips from the appliance onto the floor.
ffObserve the minimum free space below the
appliance.
B
≥200
D0000063486
150 150
2
Heat pump A B
D0000057582
WPL 07 ACS classic 865 500
WPL 09 ACS classic 865 500
WPL 17 ACS classic 995 500 1 Heating flow
2 Heating return
3 Wall mounting bracket
ff
Observe the structural limits of the wall mounting bracket used.
D0000065624
418
ff
Observe the structural limits of the T-support used.
Siting
b01
410
334
d45
524
a20 504
a10
g01 g02
192
112
109
e02
189
e01
D0000057580
WPL 07 ACS classic WPL 09 ACS classic WPL 17 ACS classic
a10 Appliance Height mm 740 740 812
a20 Appliance Width mm 1022 1022 1152
b01 Entry electrical cables
d45 Condensate drain
e01 Heating flow Diameter mm 22 22 22
e02 Heating return Diameter mm 22 22 22
g01 Air intake
g02 Air discharge
Heating connection
Connect the heat pump into the water side of heating systems in
accordance with the standard circuit diagram.
Prior to connecting the heat pump, thoroughly flush the heating
system, check for tightness and carefully vent it.
Observe the correct connection of heating flow and return as well
as the correct pipework cross-section.
Anti-vibration mounts are built into the appliance to reduce the
transmission of structure-borne noise on the water side.
Fit thermal insulation in accordance with the Energy Saving Ordi-
nance [Germany].
Note
For operation without a buffer cylinder, we recommend
installing an electric emergency/booster heater (DHC).
This kind of emergency/booster heater is installed in
some of the products required as accessories.
ff If you do not install an emergency/booster heater,
activate parameter WW PAIRING FUNCTION in the
WPM heat pump manager.
Electrical connection
Notify the local power supply utility of the heat pump connection.
All electrical installation work, particularly earthing measures,
must be carried out in accordance with VDE regulations and the
requirements of the local power supply utility.
The connection must comply with the electrical connection dia-
gram. For this, also observe the installation instructions for the
heat pump manager and any further accessories used.
Note
Observe the standards and regulations applicable in your
country.
3 X2 X26 X1 X3 X4
Zirk./2.WE WW
T(KUE)/T(WW)
KUE/Solar
T(Aussen)
T(Puffer)
L(Netz)
T(2.WE)
N L1 L2 L3
Fernb.3
Fernb.1
T(WW)
2.WE
2.WE
T(Koll)
MKP
M(A)
T(MK)
M(Z)
HKP
EVU
WW
+ L H
T
GND
2
A
L
N
PE
L1
L2
L3
N
PE
L´
L
N
PE
T
N L1 L N nc H L
X3 X4 X2 PE N L
D0000068365
1 Heat pump
2 HM Trend
3 Fuse box
A Power-OFF contact
X2.1 X2.2 X5 X3 X7 X4
3
+ T(KUE)/T(WW)
PE Zirk./2.WE WW
- T(KUE)/T(WW)
N Zirk./2.WE WW
L Zirk./2.WE WW
PE KUE/Solar
EVU / Netz L´
N KUE/Solar
L KUE/Solar
+ T(2.WE)
- T(2.WE)
+ T(WW)
- T(WW)
+ T(Koll)
+ T(MK)
+ T(Puf)
Fernb.1
Fernb.3
- T(Koll)
- T(MK)
- T(Puf)
Fernb.-
+ T(A)
- T(A)
2.WE
2.WE
+ L H
T
N L1 L2 L3 N L
2
A
L
N
PE
L1
L2
L3
N
PE
L´
L
N
PE
PE N L
T
N L1 L N nc H L
X3 X4 X2
D0000068366
1
1 Heat pump
2 HSBB 200 classic, HSBC 200
3 Fuse box
A Power-OFF contact
2a
6
5
23
22
3
3a 2 m/h
HK1
WW
26 28
2t
2d
D0000068782
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Mischerkreispumpe
Heizpatrone DHC
Heizkreispumpe
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
Warmwasser
WP-Rücklauf
Mischer auf
Mischer zu
Schütz
KUE/Solar
KUE/Solar
EVU-
Mischer
BUS H
Außen
BUS +
BUS L
Fern 3
Fern 1
Netz L
2. WE
BUS -
Freigabe
2.WE
2.WE
EVU
Netz
WW
K PE
PE N L1 L2 L3 L1 N PE 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a 2d
N
PE
L N PE L N PE 1 2 3
WP
BUS H
BUS L
BUS –
D0000068790
Pos. 1
Wärmepumpe
2a
6
5
23
22 36 HK1
3a 2
9
3c
19
2t
5
1
7
10
2b
6
D0000068784
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Mischerkreispumpe
Heizpatrone DHC
Heizkreispumpe
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
Warmwasser
WP-Rücklauf
Mischer auf
Mischer zu
Schütz
KUE/Solar
KUE/Solar
EVU-
Mischer
BUS H
Außen
BUS +
BUS L
Fern 3
Fern 1
Netz L
2. WE
BUS -
Freigabe
2.WE
2.WE
EVU
Netz
WW
K PE
PE N L1 L2 L3 L1 N PE 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a 2b
N
PE
L N PE L N PE 1 2 3
WP
BUS H
BUS L
BUS –
D0000068791
Pos. 1
Wärmepumpe
2a
6
5
23
22 36 HK1
3a 2
9
3c
19 WW
2t 26 28
2d
5
7
1 10
2b
6
D0000068787
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Mischerkreispumpe
Heizpatrone DHC
Heizkreispumpe
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
Warmwasser
WP-Rücklauf
Mischer auf
Mischer zu
Schütz
KUE/Solar
KUE/Solar
EVU-
Mischer
BUS H
Außen
BUS +
BUS L
Fern 3
Fern 1
Netz L
2. WE
BUS -
Freigabe
2.WE
2.WE
EVU
Netz
WW
K PE
PE N L1 L2 L3 L1 N PE 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a 2d 2b
N
PE
L N PE L N PE 1 2 3
WP
BUS H
BUS L
BUS –
D0000068792
Pos. 1
Wärmepumpe
2a
6
5
23
22 36 HK 1
3a 2
9
3c
2t WW
28
2d
22 AB
B
A
5
1 10
6 2b
D0000068788
Busleitung j-Y (St)2x2x08
Hauptanschlusskasten Hydraulik-Modul
L1 N PE L1 L2 L3 N PE L N PE
Mischerkreispumpe
Heizpatrone DHC
Heizkreispumpe
Zirk./2.WE WW
Netz Anschluß
Kollektorfühler
Warmwasser
WP-Rücklauf
Mischer auf
Mischer zu
Schütz
KUE/Solar
KUE/Solar
EVU-
Mischer
BUS H
Außen
BUS +
BUS L
Fern 3
Fern 1
Netz L
2. WE
BUS -
Freigabe
2.WE
2.WE
EVU
Netz
WW
K PE
PE N L1 L2 L3 L1 N PE 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 1 2 3 4
L´
36 ϑ
2a 2d 2b
K1
N
PE
K1
L N PE L N PE 1 2 3 1 2 N PE
WP
AB-A
AB-B
BUS H
BUS L
BUS –
D0000068793
Pos. 1 Pos. 22
Wärmepumpe Umschaltventil