SCHEDULE OF LOADS

Single Phase 2- Wires +

Circuit No. of Rating of Load Size of Conductor (mm²)


Description
No. Outlets HP Ф Volts Watt Amp THHN + THHN (G)
1 9 Lighting Outlet 1 230 900 3.91 2 - 2.0
2 6 Lighting Outlet 1 230 600 2.61 2 - 2.0
3 7 Lighting Outlet 1 230 700 3.04 2 - 2.0
4 10 Lighting Outlet 1 230 1000 4.35 2 - 2.0
5 9 Lighting Outlet 1 230 900 3.91 2 - 2.0
6 9 Lighting Outlet 1 230 900 3.91
7 10 Lighting Outlet 1 230 1000 4.35
8 8 ACU 1.5 1 230 1500 6.52 2 - 3.5
12 7 Convinience Outlet 1 230 1400 6.09 2 - 3.5
14 7 Convinience Outlet 1 230 1400 6.09 2 - 3.5
20 8 Convinience Outlet 1 230 1600 6.96 2 - 3.5
24 7 Convinience Outlet 1 230 1400 6.09 2 - 3.5
27 1 Refrigerator Outlet 1 230 1000 4.35 2 - 3.5
1 230 0 0.00 2 - 3.5
1 230 0 0.00 2 - 3.5
1 230 0 0.00 2 - 3.5
1 230 0 0.00 2 - 3.5
1 230
TOTAL 1 230 14300 62.17 2 - 30.0 THW + 1 -8.0 THW

FEEDER and CURRENT PROTECTION COMPUTATION:

[21850 + (0.25 x 1500)] DF


IFL = = 52.35
230
USE:
MAIN: 100AT, 100AF, 240V, 2P CB with Solid Neutral
FEEDER: 2 - 30.0 mm² THW + 1 - 8.0 THW mm² (G) in 50mm ø RSC
DS
Single Phase 2- Wires + Ground 230V Surface Mounted

ø Conduit Circuit Protection


(mm²) AT AF POLE Type
20 15 100 2 B - On
20 15 100 2 B - On
20 15 100 2 B - On
20 15 100 2 B - On
20 15 100 2 B - On

20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
20 20 100 2 B - On
50 100 100 2 B - On