Sei sulla pagina 1di 57

Power Quality: A Detailed

Understanding of Harmonics
Sanket Bolar
Substation Application Engineer
April 20, 2018

1
Moderator

n Sarah Baumann
• Marketing Programs Manager

2
Q&A
n Send us your questions and
comments during the presentation

3
Today’s Presenter

n Sanket Bolar
• Megger Substation Application Engineer

4
Agenda

n Harmonics – Theory
n Sources of Harmonics
n Current and Voltage Harmonics
n Harmonic Measurement
n Harmonic Indices
n Harmonic Power
n Effects of Harmonics
n Harmonic Evaluation Procedure
n Harmonic Mitigation

5
Harmonics - Theory

6
What are harmonics?

n A pure sinusoidal waveform only has the fundamental


frequency component but a distorted waveform is composed
of various frequency components in addition to the
fundamental frequency
n Harmonics are components of a signal that have frequencies
which are integer multiples of the fundamental frequency of
the signal

7
What are harmonics?
Fundamental 20% 3rd Harmonics
1.5 Resultant 0.3
1 1.5 0.2
0.5 0.1
0 1 0
-0.50.00 4.17 8.33 12.50 16.66 -0.10.00 4.17 8.33 12.50 16.66
0.5
-1 -0.2
-1.5 -0.3
0
0.00 4.17 8.33 12.50 16.66
-0.5 20% 5th Harmonics
0.3
-1 0.2
0.1
-1.5
0
-0.10.00 4.17 8.33 12.50 16.66

-0.2
-0.3
8
Harmonic orders

n Harmonic order is the ratio of the harmonic frequency to the


fundamental frequency

n For example, in a 60Hz system, a harmonic with a frequency


of 120Hz would be a 2nd order harmonic

n Harmonics with odd orders are called odd harmonics,


whereas harmonics with even orders are called even
harmonics

9
Harmonic phase sequences

n Harmonics can be classified on the basis of their phase


sequence
Positive Negative Zero
sequence sequence sequence
Harmonic 1,4,7,10,… 2,5,8,11,… 3,6,9,12,…
orders
A A AB C

C B B C

10
Triple-n harmonics

n Triple-n harmonics are odd multiples of the third harmonic


n h = 3,9,15,…
n Triple-n harmonics, being zero sequence, add at the neutral of
a wye connected system
n If the neutral conductor is not sufficiently sized, triple-n
harmonics can cause overheating at the neutral
n Triple-n harmonics can be “trapped” in the delta winding of a
transformer

11
Sources of harmonics

12
How are harmonics generated?

n Harmonics arise out of non-linear loads


n Non-linear loads are loads whose impedance changes with
voltage
n A common example is a transformer on no-load
n The excitation current of a transformer becomes more
distorted as the excitation voltage is increased and the core
approaches saturation
n This is because of the non-linear characteristics of the
transformer core

13
CT saturation curve

130V

50V

14
Harmonics in transformer no load current

V and Iexc at 50V V and Iexc at 130V

15
Switch-Mode Power Supplies

n Loads which draw current for a portion of the voltage


waveform are also prominent sources of harmonics

n Common loads like computers, printers, copiers use switch-


mode power supplies

n Switch-mode power supplies have rectifier circuits, the


capacitor draws current in short pulses as is shown in the next
slide

16
Full wave rectifier circuit

Input current

17
SMPS waveform - computers

05/12/17 03:57:52.670 PM Time

3.6

1.8
Ia (Amps)

-1.8

-3.6
0.00 24.98 49.97 74.95 99.93
Time (ms)

18
1.8
04/13/18 03:42:01.416 PM Time
Fluorescent lighting
0.9
Ia (Amps)

Magnetic ballasts
-0.9

-1.8
0.00 24.99 49.98 74.97 99.96 04/13/18 04:12:02.826 PM Time
Time (ms)
2.4

1.2

Electronic ballasts
Ia (Amps)

-1.2

-2.4
0.00 24.97 49.95 74.92 99.89
Time (ms)
19
Adjustable Speed Drives
VSI AC Drive

05/31/17 12:22:46.368 PM Time

240

120
Ia (Amps)

-120

-240
0.00 24.98 49.96 74.93 99.91
Time (ms)

20
Current and voltage harmonics

21
Current and voltage harmonics

n Harmonic sources (loads) give rise to distorted current


n When the distorted current passes through the system
impedance, it causes distortion in voltage at the load bus
n The distortion in voltage is higher closer to the load
n So, voltage harmonics are caused by current harmonics
n The current distortion depends on the load
n The voltage distortion depends on the current and the system
impedance

22
Current and voltage harmonics

23
Harmonics measurement

24
Harmonics measurement

n IEC 61000-4-7 deals with harmonics measurement


techniques
n The measurement interval is 200 ms.
n The 200 ms values can be aggregated over 3 additional
intervals – 3 secs, 10 min, 2 hr (Class A as per IEC 61000-4-
30)
n At least up to 50th order harmonics to be measured

25
Harmonics measurement

Owens Corning
2nd Harmonic 3rd Harmonic
05/31/17 10:37:46.368 AM Time 60
600

50
300 DFT/FFT 40
30
0

20
-300

10

-600
0.00 24.97 49.94 74.92 99.89
0
Time (ms)
100 110 120 130 140 150 160 170 180 190 200 210 220
Frequency, Hz

Time Domain Frequency Domain

26
Harmonic Indices

27
Total Harmonic Distortion

n Total Harmonic Distortion is a single parameter used to


quantify the harmonic content in the system
n It is obtained by using the following formula

)* (
+&
!"# = %
+,
&'(

n As per EN50160, the acceptable limit for voltage THD for LV


power supply is 8%

28
Total Harmonic Distortion
Volt THD

4.2 4.2

3.6 3.6
Va TH D (%)

Vb TH D (%)
3.0 3.0

2.4 2.4

1.8 1.8
05/24/16 - 09:45:46 A M 05/26/16 - 03:45:46 P M 05/28/16 - 09:45:46 P M 05/31/16 - 03:45:46 A M 06/02/16 - 09:45:46 A M
Time

29
Total Demand Distortion

n There isn’t much fluctuation in voltage but the current can


change drastically in a short span of time
n A harmonic current of 1A would be 10% if the fundamental is
10A, and 1% if the fundamental is 100A
n Hence, Total Demand Distortion is used to quantify harmonics
in current
n For TDD calculation, the maximum current recorded over a
demand interval is used as the fundamental

30
Total Demand Distortion
Current THD

15.9 15.9

Ib THD (%)
13.2 13.2

10.5 10.5
Ia THD (%)

7.8 7.8

5.1 5.1
05/24/16 - 09:45:4605/26/16
AM - 03:45:4605/28/16
PM - 09:45:4605/31/16
PM - 03:45:4606/02/16
AM - 09:45:46 AM
C urrent
Time TD D

1.19 1.19

0.92 0.92

Ib TDD (%)
0.65 0.65
Ia TDD (%)

0.38 0.38

0.11 0.11
05/24/16 - 09:45:46 AM 05/26/16 - 03:45:46 PM 05/28/16 - 09:45:46 PM 05/31/16 - 03:45:46 AM 06/02/16 - 09:45:46 AM
Time

31
Harmonic power

32
Harmonic Power Flows

n True measurements of voltage and current done to measure


actual power
n The direction of harmonic power flows obtained from the
phase angle relationship with the fundamental
Load to source 270° Source to load

180° 0°

90°

33
Harmonic Power Flows

34
Power factor

n Displacement power factor is the cosine of the phase angle


between voltage and current. It depends only on the
fundamental components
!"# = cos ∅
n True power factor is the ratio of the active power to the
apparent power
*+
)"# =
*,-
n Harmonics results in higher RMS values causing the apparent
power to be higher resulting in a lower true power factor
35
Power factor

36
Power relationships

Without harmonics With harmonics


Q S

D
P
S

Q
P

!= #$ + &$ != #$ + &$ + '$

37
Effects of harmonics

38
Effects of harmonics on transformers

n As mentioned earlier, zero sequence harmonics can cause


overheating of the neutral
n Harmonics can cause increased copper losses in the winding
n Harmonics can cause higher eddy current losses in the core
and winding and other metal parts in the transformer
n Zero sequence flux returns through the metal parts in the
transformer, if the core is 3 legged, resulting in heating and
losses

39
K-factor

n If the transformer is not sufficiently sized to handle the


harmonic content during normal operation, then it needs to be
derated

n K- factor computed using

n Derating is estimated using C57.110

40
Effects of harmonics on motors

n Harmonic voltage distortion results in harmonic fluxes which


rotate at a frequency different than the rotor frequency
n This results in rotor currents.
n This currents cause heating and losses.
n Reduced efficiency and torsional oscillations of the shaft
n Resonance conditions can result in damage to the shaft

41
Resonance

n Resonance occurs when the inductive reactance, XL of a


circuit matches with the capacitive reactance, XC of the circuit

n The resultant reactance of the circuit becomes zero and the


current is only impeded by the resistance in the circuit.

n Resonance can occur in 2 ways – series and parallel

42
Resonance

n The condition can be expressed mathematically as XL = XC

#
n Or, f = $% &'

n If the L and C of the system are such that resonance results at


a particular harmonic frequency f, then it can result in high
harmonic current flow amplifying the voltage distortion that’d
exist in non-resonance conditions

43
Resonance

Parallel resonance Series resonance

44
Harmonics Evaluation Procedure

45
Harmonics Evaluation Procedure

n Harmonics arise from the load and travel to the system source
n The customer is responsible for the current harmonic injection
n The voltage distortion is caused by the current and the system
impedance
n If the current harmonics are within limits, it’s the utility’s
responsibility to ensure voltage distortion is within limits
n Evaluation is done at the Point of Common Coupling (PCC)
n PCC is the point at which multiple customers are served by
the utility
n Duration should be at least 1 week to cover the plant cycle
46
Harmonics Evaluation Procedure

PCC

47
Harmonic Mitigation

48
Controlling harmonics

n Reducing harmonics on the load

n Using filters (shunt or series)

n Changing system response characteristics

49
Megger’s Solution – MPQ2000

n Class A measurement
n Auto CT ID
n Powered off Phase A
n Supports SD cards of up to 32 GB
n Configuration verification
n IP54 with closed lid
n Onboard data analysis

50
Megger’s Solution – MPQ2000

51
Megger’s Solution – MPQ2000

52
References

n Electrical Power Systems Quality


- Roger C. Dugan, Mark F. McGranaghan,
Surya Santoso, H. Wayne Beaty

53
Survey & Contact Info

n Contact Information
• Presenter
– Sanket Bolar
– Sanket.Bolar@megger.com

• USA and Mexico Sales


– sales@megger.com
– +1 800 723 2861
• Canada Sales
– caenquiries@megger.com Please help us improve by filling out
the survey after the webinar ends
– +1 800 297 9688
"Corona discharge 1" by Nitromethane - Own work. Licensed under CC BY-SA 3.0 via Wikimedia Commons -
54 http://commons.wikimedia.org/wiki/File:Corona_discharge_1.JPG#/media/File:Corona_discharge_1.JPG
Join us for our next Webinar

n Title: Test Data Management for NERC Compliance Reporting


n Date: May 18 from 10 am to 11:30 am CST
n Presented by Mark Meyer, Product Manager for PowerDB
n Visit us.megger.com/webinars to register, view our upcoming
schedule and watch video recordings of previous webinars

55
Power Quality & Harmonics

Course: 4.5 Days - 3.6 CEUs

www.avotraining.com
Click for Course
Power Quality & Catalog Download

Harmonics Course

56
Questions?
Power on
At Megger, we understand that keeping the power on is essential for the success
of your business. That is why we are dedicated to creating, designing and
manufacturing safe, reliable, easy-to-use portable test equipment backed by world-
leading support and expertise.

We can assist your acceptance, commissioning and maintenance testing for


predictive, diagnostic or routine purposes. By working closely with electrical
utilities, standards bodies and technical institutions, we contribute to the
dependability and advancement of the electrical supply industry.

57

Potrebbero piacerti anche