INGENIERÍA ELÉCTRICA
MATERIA:
INSTALACIONES ELÉCTRICAS INDUSTRIALES
TRABAJO A REALIZAR:
RESOLVER EJERCICIO
ALUMNA:
SEMESTRE: 6 GRUPO: B
DOCENTE:
ING. ELIGIO MAZA LÓPEZ
DATOS:
a) Temperatura= 38.1 °C
b) F.P.= 0.9
c) F.C.=10%
d) F.D.=100%
e) F.T.=0.38
CALCULAR:
1. Corriente nominal de cada circuito devanado
2. Calcular alimentadores
3. Corriente corregida por temperatura
4. Corriente de protección
5. Caída de tensión
6. Alimentador principal
7. Protección principal
8. Tipo de medidor
9. Caída de tensión de alimentadores
10. Transformador
13,200 VCA
CARACT. DE SISTEMA:
1-14AMP @ F
1-14AMP @ N
1-14AMP @ PTE
L=15 1P-15AMP
L=1.5m 30 PZ
30 WATTS
127VCA
1F-2H
CARACT. DE SISTEMA:
3F-4H--AWG3/0
CARACT. DE SISTEMA:
AWG 6 @ PTE
1-10AMP @ F
3P-200AMP
M
1-10AMP @ N
L=25M 1-10AMP @ PTE
1P-60AMP
10PZAS
162W
127VEA
1F-2H
CARACT. DE SISTEMA:
L=3.0M M 3-6AMP @ F
3-6AMP @ N
CARACT. DE SISTEMA:
2-12AMP @ F
2-12AMP @ N
2-12AMP @ PTE
L=7M 2P-20AMP
2F-2H
24000 BTU
22Vca
CARACT. DE SISTEMA:
1-10AMP @ F
1-10AMP @ N
Datos:
L= 15M -> 0.015KM
30PZAS
30WATTS
127 VEA
1F-2H
(30𝑊)(30𝑃𝑍𝐴𝑆)
1. 𝐼𝑁 = (127)(0.9)
= 7.87𝑎𝑚𝑝
(7.87)
2. 𝐼𝐶𝑇 = = 9.59𝑎𝑚𝑝
(0.82)(1)
3. 𝐼𝑃 = (9.59)(1.25) = 11.9875𝑎𝑚𝑝
(200)(9.59)(8.9)(0.015)
5. 𝑒% = = 2.016%𝑎𝑚𝑝
(127)
2. CONTACTO
Datos:
L=25M -> 0.025KM
10 PZAS
162 WATTS
127 VEA
1F-2H
(162)(10)
1. 𝐼𝑁 = = 14.17𝑎𝑚𝑝
(127)(0.91)
(14.17)
2. 𝐼𝐶𝑇 = = 17.28𝑎𝑚𝑝
(0.82)(1)
3. 𝐼𝑃 = (17.28)(1.25) = 21.6𝑎𝑚𝑝
4. 𝐼𝑃 = (14.17)(1.25) = 17.7125𝑎𝑚𝑝
(200)(17.28)(3.6)(0.025)
5. 𝑒% = = 2.414𝑎𝑚𝑝
(127)
3. MOTOR 1
Datos:
L=10M -> 0.010KM
10HP=28AMP
220A
3F-3H
1. 𝐼𝑁 = 28𝑎𝑚𝑝
(28)
2. 𝐼𝐶𝑇 = = 34.14𝑎𝑚𝑝
(0.82)(1)
3. 𝐼𝑃 = (34.14)(1.25) = 42.67𝑎𝑚𝑝
4. 𝐼𝑃 = (28)(1.25) = 35𝑎𝑚𝑝
(173)(34.14)(1.48)(0.010)
4. 𝑒% = = 0.39
(220)
5. MOTOR 2
Datos:
L=12.5
15HP=42AMP
3F-3H
220VEA
1. 𝐼𝑁 = 42amp
(42)
2. 𝐼𝐶𝑇 = = 51.21𝑎𝑚𝑝
(0.82)
3. 𝐼𝑃 = (51.21)(1.25) = 64.01𝑎𝑚𝑝
6. AIRE ACONDICIONADO
Datos:
L=15M->.015KM
24,000BTU->2,600WATTS
220VEA
2F-2H
(2400)(1)
1. 𝐼𝑁 = = 12.12𝑎𝑚𝑝
(220)(0.9)
(12.12)
2. 𝐼𝐶𝑇 = = 14.78𝑎𝑚𝑝
(0.82)
(100)(18.475)(5.6)(0.007)
4. 𝑒% = = 0.32𝑎𝑚𝑝
(220)
7. CONTACTO
Datos:
L=9M->.009KM
15PZAS
162WATTS
127VEA
1F-2H
(162)(15) 2430
1. 𝐼𝑁 = = = 21.259𝑎𝑚𝑝
(127)(0.9) 114.3
(21.259)
2. 𝐼𝐶𝑇 = = 25.92𝑎𝑚𝑝
(0.82)(1)
3. 𝐼𝑃 = (25.91)(1.25) = 32.39𝑎𝑚𝑝
(200)(25.91)(2.30)(0.009)
5. 𝑒% = = 0.84%
(127)
8. TRANSFORMADOR
𝑷𝑻 = 𝟐𝟔𝟎𝟎𝟎𝑾
(𝐶.𝐼𝑁𝑆𝑇𝐴𝐿𝐴𝐷𝐴)(𝐹.𝐷)(𝐹.𝐶)
FORMULA:
𝐹.𝑃
(26000)(1)(1.1)
𝑇= = 31777.77𝑣𝑎 ∴ 31.77𝑘𝑣𝑎
0.9
9. PARA ALIMENTADOR
1. 𝐼𝑁 = (9.59 + 17.28 + 34.14 + 51.21 + 14.28 + 25.91 = 152.91 Amp
(173)(152.91)(0.308)(0.0015)
4. 𝑒%1 = = 0.06%
220
(173)(152.91)(0.308)(0.003)
5. 𝑒%2 = = 0.13%
220
(173)(152.91)(0.308)(0.005)
6. 𝑒%3 = = 0.23%
220
10. MEDIDOR
DATOS:
Es un medidor de 7 TERMINALES las cuales son:
3 FASES DE ENTRADA
3F-7T-200amp
3 FASES DE SALIDA
1 HILO DE NEUTRO
200 AMP
7T- 200AMP