TECNOLÓGICO NACIONAL DE MÉXICO

INSTITUTO TECNOLÓGICO DE TUXTLA GUTIÉRREZ

INGENIERÍA ELÉCTRICA

MATERIA:
INSTALACIONES ELÉCTRICAS INDUSTRIALES

TRABAJO A REALIZAR:
RESOLVER EJERCICIO

ALUMNA:

MORENO GUZMAN LINDSEY KYLEE

SEMESTRE: 6 GRUPO: B

DOCENTE:
ING. ELIGIO MAZA LÓPEZ

TUXTLA GUTIÉRREZ, CHIAPAS, A 11 DE MARZO DEL 2019


EJERCICIO

DATOS:
a) Temperatura= 38.1 °C
b) F.P.= 0.9
c) F.C.=10%
d) F.D.=100%
e) F.T.=0.38

CALCULAR:
1. Corriente nominal de cada circuito devanado
2. Calcular alimentadores
3. Corriente corregida por temperatura
4. Corriente de protección
5. Caída de tensión
6. Alimentador principal
7. Protección principal
8. Tipo de medidor
9. Caída de tensión de alimentadores
10. Transformador

13,200 VCA

CARACT. DE SISTEMA:
1-14AMP @ F
1-14AMP @ N
1-14AMP @ PTE
L=15 1P-15AMP

L=1.5m 30 PZ
30 WATTS
127VCA
1F-2H
CARACT. DE SISTEMA:
3F-4H--AWG3/0
CARACT. DE SISTEMA:
AWG 6 @ PTE
1-10AMP @ F
3P-200AMP

M
1-10AMP @ N
L=25M 1-10AMP @ PTE
1P-60AMP
10PZAS
162W
127VEA
1F-2H
CARACT. DE SISTEMA:
L=3.0M M 3-6AMP @ F
3-6AMP @ N

L=5.0M 3-6AMP @ PTE


3P-200AMP
L=10M
10 HP
3F-3H
220 VCA
CARACT. DE SISTEMA:
3-1AMP @ F
M 3-1AMP @ N
3-1@ PTE
3P-600AMP
L=12.5M
15 HP
3F-3H
220 Vca

CARACT. DE SISTEMA:
2-12AMP @ F
2-12AMP @ N
2-12AMP @ PTE
L=7M 2P-20AMP

2F-2H
24000 BTU
22Vca

CARACT. DE SISTEMA:
1-10AMP @ F
1-10AMP @ N

L=9M 1-10AMP @ PTE


1P-60AMP
15 PZ
162WATTS
127VCA
1F-2H
1. LAMPARA

Datos:
L= 15M -> 0.015KM
30PZAS
30WATTS
127 VEA
1F-2H

(30𝑊)(30𝑃𝑍𝐴𝑆)
1. 𝐼𝑁 = (127)(0.9)
= 7.87𝑎𝑚𝑝

(7.87)
2. 𝐼𝐶𝑇 = = 9.59𝑎𝑚𝑝
(0.82)(1)

3. 𝐼𝑃 = (9.59)(1.25) = 11.9875𝑎𝑚𝑝

4. 𝐼𝑃 𝑇𝑒𝑟𝑚𝑜𝑚𝑎𝑔𝑛𝑒𝑡𝑖𝑐𝑜 = (7.87)(1.25) = 9.8375𝑎𝑚𝑝

(200)(9.59)(8.9)(0.015)
5. 𝑒% = = 2.016%𝑎𝑚𝑝
(127)

2. CONTACTO

Datos:
L=25M -> 0.025KM
10 PZAS
162 WATTS
127 VEA
1F-2H

(162)(10)
1. 𝐼𝑁 = = 14.17𝑎𝑚𝑝
(127)(0.91)

(14.17)
2. 𝐼𝐶𝑇 = = 17.28𝑎𝑚𝑝
(0.82)(1)

3. 𝐼𝑃 = (17.28)(1.25) = 21.6𝑎𝑚𝑝

4. 𝐼𝑃 = (14.17)(1.25) = 17.7125𝑎𝑚𝑝
(200)(17.28)(3.6)(0.025)
5. 𝑒% = = 2.414𝑎𝑚𝑝
(127)

3. MOTOR 1
Datos:
L=10M -> 0.010KM
10HP=28AMP
220A
3F-3H
1. 𝐼𝑁 = 28𝑎𝑚𝑝

(28)
2. 𝐼𝐶𝑇 = = 34.14𝑎𝑚𝑝
(0.82)(1)

3. 𝐼𝑃 = (34.14)(1.25) = 42.67𝑎𝑚𝑝

4. 𝐼𝑃 = (28)(1.25) = 35𝑎𝑚𝑝

(173)(34.14)(1.48)(0.010)
4. 𝑒% = = 0.39
(220)

5. MOTOR 2

Datos:
L=12.5
15HP=42AMP
3F-3H
220VEA

1. 𝐼𝑁 = 42amp

(42)
2. 𝐼𝐶𝑇 = = 51.21𝑎𝑚𝑝
(0.82)
3. 𝐼𝑃 = (51.21)(1.25) = 64.01𝑎𝑚𝑝

4. 𝐼𝑃𝑡𝑒𝑟𝑚𝑜𝑚𝑎𝑔𝑛𝑒𝑡𝑖𝑐𝑜 = (42)(1.25) = 52.5𝑎𝑚𝑝


(173)(51.21)(0.52)(0.0125)
5. e% = = 𝟤. 𝟨𝟣
(220)

6. AIRE ACONDICIONADO

Datos:
L=15M->.015KM
24,000BTU->2,600WATTS
220VEA
2F-2H

(2400)(1)
1. 𝐼𝑁 = = 12.12𝑎𝑚𝑝
(220)(0.9)

(12.12)
2. 𝐼𝐶𝑇 = = 14.78𝑎𝑚𝑝
(0.82)

3. 𝐼𝑃 = (14.78)(1.25) = 18.475 𝑎𝑚𝑝

(100)(18.475)(5.6)(0.007)
4. 𝑒% = = 0.32𝑎𝑚𝑝
(220)

7. CONTACTO

Datos:
L=9M->.009KM
15PZAS
162WATTS
127VEA
1F-2H

(162)(15) 2430
1. 𝐼𝑁 = = = 21.259𝑎𝑚𝑝
(127)(0.9) 114.3

(21.259)
2. 𝐼𝐶𝑇 = = 25.92𝑎𝑚𝑝
(0.82)(1)
3. 𝐼𝑃 = (25.91)(1.25) = 32.39𝑎𝑚𝑝

4. 𝐼𝑃𝑡𝑒𝑟𝑚𝑜𝑚𝑎𝑔𝑛𝑒𝑡𝑖𝑐𝑜 = (21.259)(1.25) = 26.573𝑎𝑚𝑝

(200)(25.91)(2.30)(0.009)
5. 𝑒% = = 0.84%
(127)

8. TRANSFORMADOR
𝑷𝑻 = 𝟐𝟔𝟎𝟎𝟎𝑾
(𝐶.𝐼𝑁𝑆𝑇𝐴𝐿𝐴𝐷𝐴)(𝐹.𝐷)(𝐹.𝐶)
FORMULA:
𝐹.𝑃
(26000)(1)(1.1)
𝑇= = 31777.77𝑣𝑎 ∴ 31.77𝑘𝑣𝑎
0.9

𝑈𝑆𝑂 = (45000)(0.9) = 40.500𝑤 ∴ 𝑇𝑟𝑎𝑛𝑠𝑓. 45 𝑘𝑣𝑎.


(40.500)(100)
𝑃𝑂𝑅𝐶𝐸𝑁𝑇𝐴𝐽𝐸 𝐷𝐸 𝐷𝐸𝑀𝐴𝑁𝐷𝐴 = = 64.19%
26,000

9. PARA ALIMENTADOR
1. 𝐼𝑁 = (9.59 + 17.28 + 34.14 + 51.21 + 14.28 + 25.91 = 152.91 Amp

2. 𝑰𝒂𝒍𝒊𝒎𝒆𝒏𝒕𝒂𝒅𝒐𝒓 = (51.21x1.25) + 14.78 + 34.14 + (9.59x1.25) + (17.28x1.25) +


(25.91x1.25) = 178.92𝑎𝑚𝑝

3. 𝐼𝑃𝑡𝑒𝑟𝑚𝑜𝑚𝑎𝑔𝑛𝑒𝑡𝑖𝑐𝑜 = (60 + 9.59 + 17.76 + 34.14 + 14.78 + 25.91) =


162.18amp

(173)(152.91)(0.308)(0.0015)
4. 𝑒%1 = = 0.06%
220

(173)(152.91)(0.308)(0.003)
5. 𝑒%2 = = 0.13%
220

(173)(152.91)(0.308)(0.005)
6. 𝑒%3 = = 0.23%
220
10. MEDIDOR
DATOS:
Es un medidor de 7 TERMINALES las cuales son:
3 FASES DE ENTRADA
3F-7T-200amp
3 FASES DE SALIDA
1 HILO DE NEUTRO
200 AMP