Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Building 039
1. Introduction
The resistance to earth of a given electrode depends upon the electrical resistivity of the soil in
which it is installed.
Where:
a is the spacing between electrodes, in metres (m);
R is the resistance measured between the middle electrodes, in ohms ( Ω).
ρ assumed to be 500 Ohm.m for silty sand soil which as per Soil report.
Page 1 of 8
KAP 2 – SITE 6 – EDUCATIONAL BUILDING Saudi Oger Ltd.
Doc: Grounding Calculations
Electrical Engineering
TSSD
1-Rods
The resistance to earth of a rod or pipe electrode R,
in ohms (Ω), is given by the following equation:
EQ.#01
L is the length of the electrode, in meters (m);
d is the diameter, in meters (m);
ρ is the resistivity of the soil, in ohm meters
(Ω ·m) (assumed uniform).
Page 2 of 8
KAP 2 – SITE 6 – EDUCATIONAL BUILDING Saudi Oger Ltd.
Doc: Grounding Calculations
Electrical Engineering
TSSD
(EQ.#02)
R1 is the resistance of one rod in isolation, in Ω;
s is the distance between adjacent rods, in m;(15 M)
ρ is the resistivity of soil, Ω·m;
λ is a factor given in Table 2 or Table 3;
n is the number of electrodes (as given in Table 3).
For Building 039 the no. of rods per side is 10 approximately giving λ to be 7.9
a= 500/(2π*200*15)=0.0265
R tot. rods= 200(1+7.9*0.0265)/40=6.05 Ω
Page 3 of 8
KAP 2 – SITE 6 – EDUCATIONAL BUILDING Saudi Oger Ltd.
Doc: Grounding Calculations
Electrical Engineering
TSSD
For a strip or round conductor electrode the resistance R, in ohms (Ω) is given by
EQ.#03
Page 4 of 8
KAP 2 – SITE 6 – EDUCATIONAL BUILDING Saudi Oger Ltd.
Doc: Grounding Calculations
Electrical Engineering
TSSD
a :Where two or more straight lengths, each of length L in meters (m) and of separation s in meters (m),
are laid parallel to each other and connected together the combined resistance can be calculated from the
following equation:
Rn = FR1
Where,
Rn is the resistance of n straight conductors in parallel, in Ω;
R1 is the resistance of one straight conductor in isolation
calculated from the equation and coefficients given above, in Ω.
F has the following value:
For two lengths, F = 0.5 + 0.078(s/L) –0.307
For three lengths, F = 0.33 + 0.071(s/L) –0.408
For four lengths, F = 0.25 + 0.067(s/L)–0.451 provided that 0.02 ≤ (s/L) ≤ 0.3.
Page 5 of 8
KAP 2 – SITE 6 – EDUCATIONAL BUILDING Saudi Oger Ltd.
Doc: Grounding Calculations
Electrical Engineering
TSSD
= + +
750 0.6
R elbow= 4∗𝛑∗𝟎.𝟔 { log 𝑒 (2 ∗ 0.6 ∗ 0.025∗0.8) + 0.5}
= 406 Ω
750 0.6
R Star= 8∗𝛑∗𝟎.𝟔 { log 𝑒 (2 ∗ 0.6 ∗ 0.025∗0.8) + 3.6}
=357 Ω
1/R Lattice1=1/ R elbow+1/ R Star + 1/ R elbow
yields,
Rlattice1= 129 Ω
For simplified solution we can use table 2 for rods to get the total R for Lattice
Page 6 of 8
KAP 2 – SITE 6 – EDUCATIONAL BUILDING Saudi Oger Ltd.
Doc: Grounding Calculations
Electrical Engineering
TSSD
a= 750/(2π*129*11)=0.0841
Taking n=10 & λ=3.81
R tot Lat. (for Lattice) = 129 *(1+3.81*0.0841)/10=17.03 Ω
As the grounding loop bare copper conductors forms a rectangle with dimensions
of (115 m * 120m) ,It would considered as two pair of parallel conductors.
Using eq. #03, for bare copper conductor w=13 mm (for 120 mm2)
For 2 parallel conductors 115 m in length and spaced 120 m apart, we have,
Conclusion:
The current design is suitable to obtain a value of Ground resistance as required by
specs. 16060-Article 2.2 B ,further tests will be carried out to check this
requirement.
-----------------------------------
Page 8 of 8