DIANZON - VENTANILLA DESIGN OF A 600 MW PULVERIZED COAL-FIRED POWER PLANT

 Calculation of Outlet Temperature of Cooling Tower


𝟏 𝒕𝒊 − 𝒕𝒐
=
𝑭𝒔 𝒕𝒊 − 𝒕𝒘𝒃
𝑺𝒆𝒓𝒗𝒊𝒄𝒆 𝑭𝒂𝒄𝒕𝒐𝒓, 𝑭𝒔 = 𝟏. 𝟐𝟓 𝒇𝒓𝒐𝒎 𝑨𝒎𝒆𝒓𝒊𝒄𝒂𝒏 𝑪𝒐𝒐𝒍𝒊𝒏𝒈 𝑻𝒐𝒘𝒆𝒓 𝑰𝒏𝒄.
1 42 − 𝑡𝑜
=
1.25 42 − 27.8
𝑡𝑜 = 30.64 °C
Thus, the outlet temperature of the cooling tower is 30.64 °C

 Comparison of Selected Condenser and Cooling Tower


The table 6.12 shows the comparison of the selected Condenser and Cooling
Tower.
Table 6.12 Comparison of Selected Condenser and Cooling Tower
Surface Condenser Induced Draft Cooling Tower
Steam Flow Rate 691 TPH - -
Steam Exhaust Flow 661 TPH - -
Cooling Water Hot Water
33 °C 42°C
Temperature Inlet Temperature
Cooling water Cold Water
40 °C 33°C
Temperature Outlet Temperature
Cooling Water Flow Cooling water
51618 t/h 51618 t/h
Rate Flow Rate
Condenser Cooling
17000 m2 - -
Surface Area

Based from the recommended cooling water temperature given by Harbin Electric
Power Equipment Company Ltd., 2015, condenser with cooling water of 33°C will be
selected. For the selection of the cooling tower specification, condenser’s cooling water
inlet and outlet temperature as well as the cooling water flow are considered. Given that
the condenser’s cooling water inlet temperature and outlet temperature are 33°C and
40°C respectively, cooling tower with the same or larger temperature range is selected.