Axis i j
Beam ID:
SECTION T/L/R? B? H? tl? tr? T/L/R? B? H? tl? tr? 120
DIMENSION [cm] T 60 100 13 13 T 60 100 13 13 57.5
Area, Ac [cm2] 8,704 8,704
N_Axis, Yt [cm] 36.5 36.5
N_Axis, Yb [cm] 63.5 63.5
Inertia, Ix [cm4] 8,565,180 8,565,180
Wt [cm3] 234,751 234,751
Wb [cm3] 134,855 134,855
Moment:
SW, [Kg-m] -101,404.00 72,651.00 -101,404.00
SDL, [Kg-m] -53,518.00 38,344.00 -53,518.00
LL, [Kg-m] -102,873.00 73,705.00 -102,873.00
Pre-stress:
Y1, [cm] 70.0 12.0 70.0
Span L, [m] 10.89 10.89
Total Mo, [Ton-m] 350.633 350.633
Bal. Factor, [%] 55% 55%
Drape, [m] 0.580 0.580
Pe-segment, [Ton] 332.497 332.497
Tendon 2PC-1516
Pe-design, [Ton] 320.000 320.000
Inflection Point: 0.10 Lspan 0.10 Lspan
Equivalent Load, [Ton & m]
15,650 15,650
20,756 20,756
Pe Pe
3,913 3,913
Stresses Calculation
Moment:
SW, [Kg-m] -101,404.00 72,651.00 -101,404.00
SDL, [Kg-m] -53,518.00 38,344.00 -53,518.00
LL, [Kg-m] -102,873.00 73,705.00 -102,873.00
Pre-stress: PE Factor = 100%
PTf, [Kg] 320,000 320,000 320,000
PTm, [Kg-m] 109,389.00 -75,939.00 109,389.00
PTm, [Kg-m]
Earthquake:
EQx, [Kg-m]
EQy, [Kg-m]
Beam ID:
SECTION T/L/R? B? H? tl? tr? T/L/R? B? H? tl? tr?
DIMENSION [cm] T 40 75 12 12 T 40 75 12 12
Area, Ac [cm2] 4,704 4,704
N_Axis, Yt [cm] 26.1 26.1
N_Axis, Yb [cm] 48.9 48.9
Inertia, Ix [cm4] 2,505,010 2,505,010
Wt [cm3] 96,017 96,017
Wb [cm3] 51,216 51,216
Moment:
SW, [Kg-m] -35,146.00 18,404.00 -35,146.00
SDL, [Kg-m] -6,207.00 3,071.00 -6,207.00
LL, [Kg-m] -16,551.00 8,190.00 -16,551.00
Pre-stress:
Y1, [cm] 52.0 12.0 52.0
Span L, [m] 7.50 7.50
Total Mo, [Ton-m] 78.291 78.291
Bal. Factor, [%] 55% 55%
Drape, [m] 0.400 0.400
Pe-segment, [Ton] 107.650 107.650
Tendon 1PC-15 8
Pe-design, [Ton] 80.000 80.000
Inflection Point: 0.10 Lspan 0.10 Lspan
Equivalent Load, [Ton & m]
5,689 5,689
2,471 2,471
Pe Pe
1,422 1,422
Stresses Calculation
Moment:
SW, [Kg-m] -35,146.00 18,404.00 -35,146.00
SDL, [Kg-m] -6,207.00 3,071.00 -6,207.00
LL, [Kg-m] -16,551.00 8,190.00 -16,551.00
Pre-stress: PE Factor = 100%
PTf, [Kg] 80,000 80,000 80,000
PTm, [Kg-m] 18,408.00 -9,488.00 18,408.00
PTm, [Kg-m]
Earthquake:
EQx, [Kg-m]
EQy, [Kg-m]
Beam ID:
SECTION T/L/R? B? H? tl? tr? T/L/R? B? H? tl? tr?
DIMENSION [cm] T 40 75 12 12 T 40 75 12 12
Area, Ac [cm2] 4,704 4,704
N_Axis, Yt [cm] 26.1 26.1
N_Axis, Yb [cm] 48.9 48.9
Inertia, Ix [cm4] 2,505,010 2,505,010
Wt [cm3] 96,017 96,017
Wb [cm3] 51,216 51,216
Moment:
SW, [Kg-m] -35,146.00 18,404.00 -35,146.00
SDL, [Kg-m] -6,207.00 3,071.00 -6,207.00
LL, [Kg-m] -16,551.00 8,190.00 -16,551.00
Pre-stress:
Y1, [cm] 52.0 12.0 52.0
Span L, [m] 7.50 7.50
Total Mo, [Ton-m] 78.291 78.291
Bal. Factor, [%] 55% 55%
Drape, [m] 0.400 0.400
Pe-segment, [Ton] 107.650 107.650
Tendon 1PC-15 8
Pe-design, [Ton] 80.000 80.000
Inflection Point: 0.10 Lspan 0.10 Lspan
Equivalent Load, [Ton & m]
5,689 5,689
2,471 2,471
Pe Pe
1,422 1,422
Stresses Calculation
Moment:
SW, [Kg-m] -35,146.00 18,404.00 -35,146.00
SDL, [Kg-m] -6,207.00 3,071.00 -6,207.00
LL, [Kg-m] -16,551.00 8,190.00 -16,551.00
Pre-stress: PE Factor = 100%
PTf, [Kg] 80,000 80,000 80,000
PTm, [Kg-m] 18,408.00 -9,488.00 18,408.00
PTm, [Kg-m]
Earthquake:
EQx, [Kg-m]
EQy, [Kg-m]