2506C-E15TAG4
Type of operation and application
Designation Units Emergency Standby Power only
60 Hz @ 1800 rev/min
Gross engine power kWb 623
Fan power kWm 15,5
Restriction losses kWm 10,5
ElectropaK nett engine power kWm 597
Gross brake mean effective pressure kPa 2769
Combustion air flow m³/min 42
Exhaust gas temperature (max) °C 550
Exhaust gas flow m³/min 120
Boost pressure ratio - 3,5
Overall thermal efficiency (nett) % 40
Friction and pumping power losses kWm 62
Mean piston speed m/s 10
Engine coolant flow l/sec 7,2
Cooling fan air flow (zero duct allowance) m³/min 866
kWe 550
Typical Gen Set electrical output (0.8 pf)
kVA 687
Assumed alternator efficiency % 92
Note: Emergency Standby Power only - power available in the event of a main power network failure, up to a maximum of 200 hours per
year which may by run continuously. Load factor may be up to 100% of the Emergency Standby Power rating. No overload is permitted.
Rating definitions
Prime power
Variable load. Unlimited hours usage with an average load factor of 80% of the published Prime Power rating over each 24 hour period.
A 10% overload is available for 1 hour in every 12 hours operation.
Standby power
Variable load. Limited to 500 hours annual usage up to 300 hours of which may be continuous running. No overload is permitted.
Emissions capability
Certified against the requirements of Tier 2 legislation for non-road mobile machinery, powered by constant speed engines (EPA 40 CFR
Part 89 Tier 2). These engines also comply with the 1/2 TA Luft (1986) NOx limits of 2000 mg/nm³
Energy balance
2506C-E15TAG3
Type of operation and application
Designation Units Prime Standby
60 Hz @ 1800 rev/min
Energy in fuel kWt 1260 1380
Energy in power output (gross) kWb 519 568
Energy to cooling fan and restrictions kWm 24.4 25
Energy in power output (nett) kWm 495 543
Energy to exhaust kWt 395 450
Energy to coolant and oil kWt 186 190
Energy to radiation kWt 38,5 32,5
Energy to charge cooler kWt 106 124
2506C-E15TAG4
Type of operation and application
Designation Units Emergency Standby Power only
60 Hz @ 1800 rev/min
Energy in fuel kWt 1540
Energy in power output (gross) kWb 623
Energy to cooling fan and restrictions kWm 26
Energy in power output (nett) kWm 597
Energy to exhaust kWt 540
Energy to coolant and oil kWt 195
Energy to radiation kWt 26,5
Energy to charge cooler kWt 140
CRANKCASE BREATHER
FAN GUARDS REMOVED CONNECTION SIZE: Ø 44.45 (1.75")
FOR CLARITY
AIR INLET ELBOW
MANIFOLD INCORPORATED INTO HEAD.
TAPPING SIZE IN ELBOW: 1/4-18 NPTF
AIR CLEANER
FAN
2506C-E15TAG3 and 2506C-E15TAG4 - left side view
HAND PRIMING
PUMP
FUEL RETURN
NO. 6 PORT - 9/16-18-2B THD
FUEL INLET
NO. 8 PORT - 3/4-16-2B THD
Note: This drawing is for reference only. For installation purposes, please refer to the relevant General Installation drawing (Z13579).
2506C-E15TAG3 and 2506C-E15TAG4 - front view
1064
532
10 - M8 X 1.25
WELD NUTS
1718 4 PITCHES
@ 277.5
= 1110
483
283
8 THK 560
1120
Note: This drawing is for reference only. For installation purposes, please refer to the relevant General Installation drawing (Z13579).
EXHAUST MANIFOLD
TURBOCHARGER
648
10 FRONT LIFTING
BRACKET
REAR FACE
OF BLOCK
763
15°
Ø 203
TEMPERATURE SENDER
TAPPING SIZE:
1/2-14-NPTF THD
885
699
2506C-E15TAG3 and 2506C-E15TAG4 - right side view
WATER PUMP
CRANKSHAFT
392
417
448
DIPSTICK
12
OIL SAMPLE VALVE OIL PRESSURE TAPPING
SIZE: NO.6 PORT ( 51)
OIL COOLER OIL FILTER 9/16-18-2B 12.7 DEEP
Note: This drawing is for reference only. For installation purposes, please refer to the relevant General Installation drawing (Z13579).
2506C-E15TAG3 and 2506C-E15TAG4 - rear view
12 HOLES
M12 X 1.75 X 21.5 DP
ON 619.12 PCD
165.1
431.8
375 375
8 HOLES
1/2"-13-UNC X 24 DP
ON 438.17 PCD B
Note: This drawing is for reference only. For installation purposes, please refer to the relevant General Installation drawing (Z13579).
1126 FRONT
32 REAR LIFTING BRACKET
499.4 REQUIRED FOR LIFTING BRACKET ENGINE ONLY
ELEMENT REMOVAL ENGINE ONLY
CRANKSHAFT
23 232
324
45° Ø 200
8 HOLES Ø 13 THRU.
674 759 136.5
EQUI SPACED ON
170 P.C.D
2657
Note: This drawing is for reference only. For installation purposes, please refer to the relevant General Installation drawing (Z13579).
2506C-E15TAG3 and 2506C-E15TAG4 - miscellaneous views
R21 31
54 TO
CRANKSHAFT
625
TO
CRANKSHAFT
BATTERY (POS)
SCRAP VIEW SHOWING M6 X 1
DETAILS OF REAR LIFTING INDICATOR LIGHT TIGHTEN TO
EYE M4 X 0.7 11.3 Nm NOM
TIGHTEN TO
2.25 Nm NOM
RELAY
M4 X 0.7 GROUND (NEG)
TIGHTEN TO 1/4" UNC X 20 TPI
2.25 Nm NOM TIGHTEN TO 6 Nm.
R20 62
TO SCRAP VIEW SHOWING ALTERNATOR CONNECTIONS.
53 FAN GUARDS & THERMOSTAT REMOVED FOR CLARITY.
CRANKSHAFT SCALE 1:3
674
TO
CRANKSHAFT
SOLENOID (POS)
No 10 X 32 TPI
BATTERY (POS) TIGHTEN TO 2.5 Nm.
1/2" X 13 TPI
TIGHTEN TO 24 Nm.
SCRAP VIEW SHOWING GROUND (NEG)
DETAILS OF FRONT LIFTING 1/2" X 13 TPI
EYE TIGHTEN TO 24 Nm.
25.4
24 SCRAP VIEW SHOWING
STARTER MOTOR CONNECTIONS
SCALE 1:3
9.3
8.7
SECTION B-B
DETAILS OF SAE 1 / 2 FLYWHEEL HOUSING
AND SAE J620 SIZE 14 FLYWHEEL
Note: This drawing is for reference only. For installation purposes, please refer to the relevant General Installation drawing (Z13579).
Cooling system Cooling clearance
Ambient cooling clearance (standby power) based on air
Recommended coolant: temperature at fan of 6 °C above the ambient
50% inhibited ethylene glycol or 50% inhibited propylene glycol and
2506C-E15TAG3 maximum additional restriction (duct
50% clean fresh water. Where there is no likelihood of ambient
allowance) to cooling airflow and resultant minimum airflow
temperatures below 10 °C, clean ‘soft’ water may be used, treated
with 1% by volume of Perkins inhibitor in the cooling system. The Duct allowance with inhibited coolant at 50 °C
inhibitor is available from all Perkins Distributors. Description rev/min Units Standby
Total system coolant capacity ... ... ... ... ... ... ... ... ... ... 58,0 litres
Duct allowance 1800 kPa 0·125
Maximum pressure:
-in crankcase water jacket . ... ... ... ... ... ... ... ... ... ... ... ... 276 kPa Minimum airflow 1800 m³/min 822
Maximum top tank temperature . ... ... ... ... ... ... ... ... ... ... . 107 °C Duct allowance with 50% glycol at 43 °C
Maximum static pressure on pump ... ... ... ... ... ... ... ... .. 170 kPa Duct allowance 1800 kPa 0·200
Maximum permissible restriction:
Minimum airflow 1800 m³/min 792
-to coolant pump flow . ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 30 kPa
Temperature rise across engine with inhibited coolant:
2506C-E15TAG4 maximum additional restriction (duct
-standby power .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... 10 °C
allowance) to cooling airflow and resultant minimum airflow
-prime power .. ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 9 °C
Thermostat operation range... ... ... ... ... ... ... ... ... ... .. 88 to 98 °C Duct allowance with inhibited coolant at 50 °C
Description rev/min Units Standby
Radiator
Duct allowance 1800 kPa 0·125
-face area... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... .. 1·238 m²
-weight (dry) ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 132 kg Minimum airflow 1800 m³/min 822
-rows and materials ... ... ... ... ... ... ... ... ... ... ...2 rows, Aluminium Duct allowance with 50% glycol at 43 °C
-matrix density and material ... ... ... ... . 12 fins per inch, Aluminium
Duct allowance 1800 kPa 0·200
-width of matrix... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1048 mm
-height of matrix . ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... . 1100 mm Minimum airflow 1800 m³/min 792
-pressure cap setting (minimum) ... ... ... ... ... ... ... ... ... ... . 69 kPa
15W-40
10W-40
10W-30
5W-40
5W-30
0W-40
0W-30
0W-20
Mountings
Maximum static bending moment at
rear face of block ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ..1356 Nm
2506C-E15TAG4
2nd Load Application
Initial Load Acceptance
Immediately after engine has recovered to rated
When engine reaches rated speed
speed
(15 seconds maximum after engine starts to crank)
(5 seconds after initial load application)
Transient Frequency Transient Frequency
Prime Load kWm Frequency recovery Prime Load kWm Frequency recovery
Engine speed
Power % (kWe) Nett Deviation time Power % (kWe) Nett Deviation time
% seconds % seconds
1800 rev/min 55 275 ≤ 10 5 50 250 ≤ 10 5
All tests were conducted using an engine installed and serviced to Perkins Engines Company Limited recommendations.
The applied load is a percentage of generator electrical output, using alternator efficiencies as published in the general installation section
of this Technical Data Sheet.
The information given on this Technical Data Sheet is for standard ratings only. For ratings other than those shown, please
contact Perkins Engines Company Limited, Stafford.
Notes